39-39 - PL1.3.pdf

PDF 391 KB Posted

Attached to
Surplus Real Property Sale For Economic Development; 438 Scott Boulevard
Solicitation number
RFP260305
Issued by
Hart County, Kentucky

About this file

This is a plumbing design document prepared by the Commonwealth of Kentucky Finance and Administration Cabinet, Department for Facilities & Support Services, Division of Engineering, in collaboration with KLH Engineers, PSC for the Gateway Urban Campus project located at 438-440 Scott Street, Covington, Kentucky. The document presents detailed plumbing plans for the third floor of a classroom center facility, including sanitary and vent piping systems, water supply distribution, and fixture connections. The design accommodates multiple functional spaces including a clinical massage lab, client massage rooms, office, storage areas, restrooms, lobby, and HVAC mechanical rooms. The plumbing scope encompasses new underground piping installation, water piping routing through wall cavities to serve multiple fixtures, vent piping with roof penetrations, gas piping, and floor drain installations with trap seal primers. The plans indicate coordination requirements with HVAC and electrical subcontractors, with specifications for concealed piping runs where feasible and mandatory site verification of existing conditions prior to bidding.

The plumbing specifications establish that all piping work must comply with applicable local and state codes, with particular emphasis on water piping prohibitions in areas subject to freezing temperatures. The contractor is required to furnish and install carriers, P-traps, and shutoff valves at each fixture, seal all penetrations to maintain fire resistance and watertight integrity, and perform saw cutting and core drilling for all slab penetrations. Multi-trade coordination is mandated prior to installation, with the mechanical contractor bearing responsibility for field verification of existing stub-ins and taps, and immediate notification of any discrepancies to the engineer to prevent unknown additional costs. The design was approved for program concept purposes and dated December 18, 2015, with preparation completed on January 12, 2016.

View the file

Other files

File Type Posted
66-67 - CT0.0.pdf PDF
51-49 - HV1.3.pdf PDF
8-13 - A1-1 - FIRST FLOOR DEMOLITION AND NEW WORK PLANS.pdf PDF
34-35 - PD1.1.pdf PDF
30-30 - A8-2 - Basement - FINISHES.pdf PDF
29-29 - A8-1 - ROOM FINISH PLANS (N-I-C- FURNITURE LAYOUT).pdf PDF
12-11 - S4-2 - FRAMING DETAILS.pdf PDF
15-8 - S2-5 - ROOF FRAMING PLAN.pdf PDF
73-19 - A3-0 - BUILDING ELEVATIONS.pdf PDF
49-51 - HV2.0.pdf PDF
72-72 - CT5.2.pdf PDF
67-69 - CT1.2.pdf PDF
62-63 - EP4.0.pdf PDF
3-6 - S2-3 - SECOND FLOOR FRAMING PLAN.pdf PDF
23-24 - A5-2 - MISCELLANEOUS DETAILS.pdf PDF
43-46 - HV1.0.pdf PDF
17-3 - S1-1 - GENERAL NOTES.pdf PDF
13-18 - A2-1 - 2ND 3RD FLR REFLECTED CLG PLANS.pdf PDF
28-31 - A8-3 - 1st FLOOR - FINISHES.pdf PDF
21-23 - A5-1 - MISCELLANEOUS STAIR DETAILS.pdf PDF
70-71 - CT5.1.pdf PDF
36-37 - PL1.1.pdf PDF
42-44 - FP1.1.pdf PDF
31-32 - A8-4 - 2nd Floor - FINISHES.pdf PDF
32-33 - A8-5 - 3rd Floor - FINISHES.pdf PDF
50-52 - HV2.1.pdf PDF
38-40 - PL1.4.pdf PDF
35-34 - PD1.0.pdf PDF
69-70 - CT4.1.pdf PDF
11-12 - A1-0 - BASEMENT DEMOLITION AND NEW WORK PLANS.pdf PDF
68-68 - CT1.0.pdf PDF
25-26 - A6-1 - ENLARGED PLANS AND INTERIOR ELEVATIONS.pdf PDF
63-64 - EL1.0.pdf PDF
19-10 - S4-1 - FRAMING DETAILS.pdf PDF
65-66 - EL2.0.pdf PDF
2-2 - A0-1 - CODE INFO AND WALL TYPES.pdf PDF
9-14 - A1-2 - SECOND FLOOR DEMOLITION AND NEW WORK PLANS.pdf PDF
76-Elevator Inspection 2026-03-25-12-13-48.pdf PDF
58-59 - EP1.3.pdf PDF
46-47 - HV1.1.pdf PDF
57-58 - EP1.2.pdf PDF
61-62 - EP3.0.pdf PDF
80-438 Scott Full Inspection Report (PDF).pdf PDF
7-5 - S2-2 - FIRST FLOOR FRAMING PLAN.pdf PDF
53-54 - HV3.1.pdf PDF
4-9 - S3-1 - TYPICAL DETAILS.pdf PDF
1-4 - S2-1 - FOUNDATION PLAN.pdf PDF
24-25 - A6-0 - ENLARGED PLANS AND INTERIOR ELEVATIONS.pdf PDF
48-50 - HV1.4.pdf PDF
20-21 - A4-1 - BUILDING SECTIONS.pdf PDF
Show 40 more

Latest 50 of 80 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

B C D EA G

F

CORRIDOR

CLIENT MASSAGE

301D

CLIENT MASSAGE

301E

CLIENT MASSAGE

301C

CLIENT MASSAGE

301A

OFFICE

302C

STORAGE

MEN

STAIR

D3

EXISTING STAIR

C3

MASSAGE CLINICAL

LAB

WOMEN

LOBBY

CLIENT MASSAGE

301B

LINENS

301F

CORRIDOR

300A

CLOSET

HVAC

302A ROOF ACCESS

302B

V

V V

V V

V

V

V

V

V

V

V

FD1

FD1

4"STORM DOWN

4"STORM UP TO RD1

1-1/2"VENT DOWN

1-1/2"VENT

DOWN

1-1/2"VENT

DOWN

2"VENT

DOWN

3"VENT DOWN

3"VENT UP TO 4"VTR

1-1/2"VENT

DOWN

1-1/2"VENT DOWN

2"VENT DOWN

2"VENT DOWN

1-1/2"VENT DOWN

1-1/2"VENT DOWN

1-1/2"VENT DOWN

1-1/2"VENT DOWN

1-1/2"VENT DOWN

1-1/2"VENT DOWN

WC1

WC1LV1

LV1

UR1

DF1

SK3

MS1

SK3

SK3SK3

SK3

SK3

1-1/2"VENT

DOWN

WB1

1-1/2"VENT DOWN

4" UP TO

ADDED

ROOF

DRAIN

B C D EA G

F

CORRIDOR

CLIENT MASSAGE

301D

CLIENT MASSAGE

301E

CLIENT MASSAGE

301C

CLIENT MASSAGE

301A

OFFICE

302C

STORAGE

MEN

STAIR

D3

EXISTING STAIR

C3

MASSAGE CLINICAL

LAB

WOMEN

LOBBY

CLIENT MASSAGE

301B

LINENS

301F

CORRIDOR

300A

CLOSET

HVAC

302A ROOF ACCESS

302B

HB

HB

WC1

WC1

LV1

LV1

UR1

DF1

SK3

MS1

SK3

SK3SK3

SK3

SK3

3/4"CW FROM BELOW TO SERVE

FIXTURES ON THIS WALL

3/4"CW

TO UR1 FROM

BELOW

1/2"H&CW

TO LV1

FROM BELOW

1/2"H&CW

TO LV1 FROM

BELOW

1/2"H&CW

TO MS1

FROM

BELOW

1/2"H&CW TO SK3 FROM BELOW

1/2"H&CW TO SK3 FROM BELOW

1/2"H&CW TO SK3

FROM BELOW

1/2"H&CW TO SK3 FROM BELOW

1/2"H&CW TO SK3

FROM BELOW

1/2"CW TO DF1

FROM BELOW

1/2"H&CW TO

SK3 FROM

BELOW

2" G

2"GAS DOWN

2"GAS UP TO ROOF

INSTALL TP1 TO SERVE

FLOOR DRAINS IN

3RD FLOOR RESTROOMS

WB1

1/2"H&CW

TO WB1

FROM

BELOW

HB

S.C. SPRINKLER CONTRACTOR

P.C. PLUMBING CONTRACTOR

HUB DRAINHD

PRV PRESSURE REDUCING VALVE

RD ROOF DRAIN

INVERT ELEVATIONI.E.

VTR VENT THRU ROOF

FLOOR DRAIN, F.D.

HOSE BIBB (INTERIOR)

BALANCING VALVE

CHECK VALVE

CONTROL/SHUT-OFF VALVE

G GAS PIPE, G

ST STORM PIPING, ST

HOT WATER RETURN PIPING, HWRHWR

HOT WATER PIPING, HWHW

COLD WATER PIPING, CWCW

V VENT PIPING, V

S SANITARY/WASTE PIPING, S, W

SYMBOL DESCRIPTION

PLUMBING LEGEND

CO CLEANOUT

APPROVED FOR PROGRAM CONCEPT ONLY

APPROVED FOR PROGRAM CONCEPT ONLY

DATE

DATE

ENGINEERING

DIVISION OF

AGENCY

AUTHORIZED AGENT

FOR INTENT ONLY

DIV. OF ENGR.

REVIEWED

ENGR. ACCT NO.

DRAWING NO.

DATE

A&E FILE NO.

CHECKED BY

SHEET DRAWN BY

RECORD DATE

DATEREVISIONS

COMMONWEALTH OF KENTUCKY

FINANCE AND ADMINISTRATION CABINET

DEPARTMENT FOR FACILITIES & SUPPORT SERVICES

DIVISION OF ENGINEERING

FRANKFORT, KENTUCKY

WWW.KLHENGRS.COM

ENGINEERS, PSC

MECHANICAL/ELECTRICAL ENGINEERS

KOHRS LONNEMANN HEIL

LEXINGTON, KENTUCKY

COLUMBUS, OHIO

DAYTON, OHIO

NEW YORK, NEW YORK

1538 ALEXANDRIA PIKE, SUITE

11 FT. THOMAS, KENTUCKY

41075 800-354-9783 859-442-8050

859-442-8058 FAX

KLH PRO. NO.

11369.04

PROFESSIONAL SERVICES CLASSROOM CENTER

/1

/2

:3 :5

A

M

PL1.3

PLUMBING - NEW - 3RD FLOOR

C5N5-NC11-01

GATEWAY URBAN CAMPUS

438-440 Scott St., Covington, KY 41011

12/18/15

201114.02

FAC

KPO

SCALE: 1/4" = 1'-0"PL1.3

1 PLUMBING SANITARY AND VENT- NEW - 3RD FLOOR

SCALE: 1/4" = 1'-0"PL1.3

2 PLUMBING SUPPLY - NEW - 3RD FLOOR

GENERAL PLUMBING NEW WORK NOTES

A. BOLD - DASHED LINES INDICATE NEW UNDERGROUND PLUMBING PIPING

AND FADED - DASHED LINES INDICATE EXISTING UNDERGROUND

PLUMBING WORK TO REMAIN.

B. WATER PIPING IN AREAS SUBJECT TO FREEZING TEMPERATURES WILL

NOT BE PERMITTED.

C. WHEREVER POSSIBLE, NEW PIPING AND RELOCATED PIPING SHALL BE

RUN CONCEALED. COORDINATE LOCATION OF ALL PIPING WITH HVAC

AND ELECTRIC SUBCONTRACTOR. COORDINATE CUTTING AND PATCHING

WITH GENERAL CONTRACTOR.

D. WHEREVER FIXTURES REQUIRING PLUMBING CONNECTIONS ARE

FURNISHED BY OWNER OR ARE RELOCATED, PLUMBING

SUBCONTRACTOR SHALL FURNISH AND INSTALL CARRIERS, "P" TRAP

AND STOPS.

E. ALL PIPE DROPS IN SALES AREA FROM ROOF TO LOW WALLS OR

EQUIPMENT SHOULD BE COORDINATED AND GROUP TOGETHER WITH

OTHER MECHANICAL PIPES.

F. NO PIPE ROUTING ALLOWED TO RUN THROUGH ELEVATOR EQUIPMENT

ROOMS.

G. DROP WATER DOWN IN WALL. ROUTE WATER THRU WALL TO SERVE

MULTIPLE FIXTURES ON COMMON WALL. FIXTURE SCHEDULE FOR

FIXTURE REQUIREMENTS.

H. ALL MEP TRADES, INCLUDING SPRINKLER MUST COORDINATE WITH EACH

OTHER PRIOR TO INSTALLATION.

I. PRIOR TO BID, CONTRACTOR SHALL VISIT THE JOB SITE AND FIELD

VERIFY THE EXISTING CONDITIONS. THE MECHANICAL CONTRACTOR

SHALL BE RESPONSIBLE FOR FIELD VERIFYING THE EXISTING STUB-INS,

TAPS, ETC. FOR PLUMBING SYSTEM FOR THE TENANT SPACE. THE

CONTRACTOR SHALL NOTIFY THE ENGINEER IMMEDIATELY OF ANY

DISCREPANCIES FOUND BETWEEN PLANS AND FIELD CONDITIONS IN

ORDER TO PREVENT UNKNOWN ADDITIONAL COSTS TO THE TENANT.

J. PROVIDE SHUTOFF VALVE(S) AT EACH FIXTURE.

K. ALL PLUMBING PIPING DROPS TO PLUMBING FIXTURES SHALL BE

INSTALLED IN WALL SPACE EXCEPT WHERE NOTED.

L. SUSPEND ALL HORIZONTAL WATER AND VENT PIPING AS HIGH AS

POSSIBLE ABOVE CEILING.

M. SAW CUT/CORE DRILL ALL SLAB PENETRATIONS. SEAL AROUND ALL

WALL, FLOOR AND CEILING PIPE PENETRATIONS WITH APPROVED

SEALANT MATERIAL AND ENSURE PENETRATIONS REMAIN FIRE

RESISTANT AND WATERTIGHT.

N. ALL EQUIPMENT, INSTALLATIONS AND MATERIALS SHALL COMPLY WITH

APPLICABLE LOCAL AND STATE CODES.

O. PROVIDE TRAP SEAL PRIMER ON ALL FLOOR DRAINS

File details come from the government source that posted it. Updated .