40-41 - PL1.5.pdf

PDF 592 KB Posted

Attached to
Surplus Real Property Sale For Economic Development; 438 Scott Boulevard
Solicitation number
RFP260305
Issued by
Hart County, Kentucky

About this file

This is a mechanical and plumbing design document prepared by the Commonwealth of Kentucky's Department for Facilities & Support Services, Division of Engineering, in conjunction with KLH Engineers for the Gateway Urban Campus project located at 438-440 Scott Street in Covington, Kentucky. The document contains detailed plumbing and mechanical specifications and schedules for the facility's infrastructure systems, including natural gas input requirements, water heating equipment, drainage systems, and backflow prevention devices. The gas input schedule specifies a total equivalent pipe length of 250 feet with a required delivery pressure of 7 inches of water column to support equipment loads totaling 698 cubic feet per hour, distributed among two gas water heaters (199 CFH each) and a dedicated outdoor air system unit (300 CFH). The specifications include detailed installation requirements for two 100-gallon natural gas-fired water heaters, roof-top unit gas connections, floor drain systems with trap primer valves, and reduced pressure backflow preventers sized and installed in accordance with state and local plumbing codes.

The document emphasizes compliance with building specification section 22 13 00 for approved piping materials and references the plumbing plan for specific locations and sizing of all drains and piping throughout the facility. Installation requirements address slope configurations for floor drains, vertical trap primer valve mounting at prescribed intervals, condensate drain sizing (preferably 1.5 inches if permitted by the local plumbing inspector), and proper air gap provisions for pressure relief valves. The plumbing contractor is designated as responsible for furnishing and installing all reduced pressure backflow preventers to meet all applicable state and local codes and regulations. All specifications are drawn from a professional services classification document dated December 18, 2015, with project number 11369.04 and drawing number 470-C5N5-NC11-01 prepared by KLH Engineers, PSC.

View the file

Other files

File Type Posted
66-67 - CT0.0.pdf PDF
51-49 - HV1.3.pdf PDF
8-13 - A1-1 - FIRST FLOOR DEMOLITION AND NEW WORK PLANS.pdf PDF
34-35 - PD1.1.pdf PDF
30-30 - A8-2 - Basement - FINISHES.pdf PDF
29-29 - A8-1 - ROOM FINISH PLANS (N-I-C- FURNITURE LAYOUT).pdf PDF
12-11 - S4-2 - FRAMING DETAILS.pdf PDF
15-8 - S2-5 - ROOF FRAMING PLAN.pdf PDF
73-19 - A3-0 - BUILDING ELEVATIONS.pdf PDF
49-51 - HV2.0.pdf PDF
72-72 - CT5.2.pdf PDF
67-69 - CT1.2.pdf PDF
62-63 - EP4.0.pdf PDF
3-6 - S2-3 - SECOND FLOOR FRAMING PLAN.pdf PDF
23-24 - A5-2 - MISCELLANEOUS DETAILS.pdf PDF
43-46 - HV1.0.pdf PDF
17-3 - S1-1 - GENERAL NOTES.pdf PDF
13-18 - A2-1 - 2ND 3RD FLR REFLECTED CLG PLANS.pdf PDF
28-31 - A8-3 - 1st FLOOR - FINISHES.pdf PDF
21-23 - A5-1 - MISCELLANEOUS STAIR DETAILS.pdf PDF
70-71 - CT5.1.pdf PDF
36-37 - PL1.1.pdf PDF
42-44 - FP1.1.pdf PDF
31-32 - A8-4 - 2nd Floor - FINISHES.pdf PDF
32-33 - A8-5 - 3rd Floor - FINISHES.pdf PDF
50-52 - HV2.1.pdf PDF
38-40 - PL1.4.pdf PDF
35-34 - PD1.0.pdf PDF
69-70 - CT4.1.pdf PDF
39-39 - PL1.3.pdf PDF
11-12 - A1-0 - BASEMENT DEMOLITION AND NEW WORK PLANS.pdf PDF
68-68 - CT1.0.pdf PDF
25-26 - A6-1 - ENLARGED PLANS AND INTERIOR ELEVATIONS.pdf PDF
63-64 - EL1.0.pdf PDF
19-10 - S4-1 - FRAMING DETAILS.pdf PDF
65-66 - EL2.0.pdf PDF
2-2 - A0-1 - CODE INFO AND WALL TYPES.pdf PDF
9-14 - A1-2 - SECOND FLOOR DEMOLITION AND NEW WORK PLANS.pdf PDF
76-Elevator Inspection 2026-03-25-12-13-48.pdf PDF
58-59 - EP1.3.pdf PDF
46-47 - HV1.1.pdf PDF
57-58 - EP1.2.pdf PDF
61-62 - EP3.0.pdf PDF
80-438 Scott Full Inspection Report (PDF).pdf PDF
7-5 - S2-2 - FIRST FLOOR FRAMING PLAN.pdf PDF
53-54 - HV3.1.pdf PDF
4-9 - S3-1 - TYPICAL DETAILS.pdf PDF
1-4 - S2-1 - FOUNDATION PLAN.pdf PDF
24-25 - A6-0 - ENLARGED PLANS AND INTERIOR ELEVATIONS.pdf PDF
48-50 - HV1.4.pdf PDF
Show 40 more

Latest 50 of 80 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GAS INPUT SCHEDULE FOR JOB# 11369.04

TOTAL EQUIVALENT LENGTH OF PIPE:250'

REQUIRED DELIVERY PRESSURE: 7"W.C.

EQUIPMENT

LOAD (CFH)

GWH-1 199

GWH-2 199

DOAS-1 300

TOTAL 698

FD2

140°F

140°F

OPEN WEBBED BAR

JOIST

AMTROL ST-42V EXPANSION TANK

STRAINER

(TYP.)

CHECK VALVE (TYP.)

HOT WATER

RETURN

SHUT-OFF VALVE (TYP.)

CW

A

DIRT LEG (TYP.)

GAS COCK (TYP.)

NOTES

3/4" (TYP.)

UNION (TYP.)

G

G

3/4" (TYP.)

110° F.

THERMOMETER

(TYP.)

G G

BAR JOIST AND BOLTED (2 REQUIRED)

SCALE:

WATER HEATER DETAIL

NONE

224000.00-35

4" PVC

INTAKE/EXHAUST BY

P.C.

AQUASTAT (STRAP ON

TYPE) FOR PUMP

CONTROL

CP1

100 GAL. NATURAL GAS FIRED WATER

ASME TEMPERATURE & PRESSURE

RELIEF VALVE HARD PIPED FULL

SIZE TO FLOOR DRAIN WITH 3" AIR

GAP (TYP.)

100 GAL. NATURAL GAS FIRED

WATER HEATER

4'' BLOCK

AIR GAP

(TYP)

140° F.

CONNECT TO UNIT GAS

CONTROLS. PROVIDE GROMMET

FOR WATER-TIGHT SEAL

S/S CLAMPING RING

LAP SEALANT

ROOFTOP UNIT

DRIP/DIRT POCKET

GAS COCK

GROUND JOINT UNION

GAS PIPE SUPPORT

SCALE:

RTU NATURAL GAS CONNECTION DETAIL

NONE

220700.00-07

ROOF

SLOPE PIPING

BELOW SLAB TO

FLOOR DRAIN.

VALVE

1/2"

DOMESTIC COLD

WATER LINE

TRAP PRIMER VALVE WITH BACKFLOW

PREVENTER AND VACUUM BREAK EQUAL

TO BASIS OF DESIGN: SIOUX CHIEF

MANUFACTURING COMPANY, INC.; TP

695-01. INSTALL VERTICALLY ON 1/2" TO 3"

COLD WATER LINE NEAREST TRAP

SERVED, AT LEAST 12" A.F.F. TO INSURE

PRESSURE DROP FOR ACTIVATION,

INSTALL NEAR PLUMBING FIXTURES.

INSTALL WITH VERTICAL LOOP TO HELP

PREVENT SEDIMENT BUILDUP. INSTALL IN

LOCATION HIDDEN FROM PUBLIC VIEW.

MOUNT 12" ABOVE LOWEST CEILING IN

AREA. PROVIDE ACCESS PANEL IF

INSTALLED ABOVE HARD CEILING.

MINIMUM 3/8" COPPER FLOOR DRAIN TRAP

MAKE-UP WATER LINE. (TYPICAL)

SEWER GASES

WATER TRAP

SCALE:

TRAP PRIMER DETAIL

NONE

221313.00-20

NOTE: TRAP PRIMER VALVE SHALL BE MOUNTED ONE FOOT ABOVE THE

FINISHED FLOOR FOR EVERY 20 FEET OF HORIZONTAL PRIMER LINE.

No. 4

SEE

NOTE

AFTER FLOOR

HAS

No. 3

CUT OFF EXCESS

PIPE

SEE NOTE

BEEN POURED.

FLOOR DRAIN

FLOOR LINE

HUB DRAIN

LIGHT DUTY

FLOOR LINE

GENERAL NOTES:

1. SLOPE FLOOR TO FLOOR DRAIN TO

FLOOR DRAIN AS INDICATED ON

CONCRETE PLACEMENT PLAN.

2. REFER TO BUILDING SPECIFICATION

SECTION 22 13 00 FOR APPROVED

PIPING MATERIAL

3. REFER TO PLUMBING PLAN FOR

LOCATIONS AND SIZES OF DRAINS

AND PIPING

4. TYPICALLY 1" BUT PREFERABLY

" IF

PERMITTED BY LOCAL PLUMBING

INSPECTOR TO FACILITATE

CONDENSATE DRAIN INSTALLATION.

SCALE:

TYPICAL HUB & LIGHT DUTY FLOOR

DRAIN DETAILS

NONE

221313.00-48

LIGHT DUTY FLOOR DRAIN WITH OR WITHOUT

TRAP PRIMER AS REQUIRED, SEE NOTE No. 3.

NICKEL BRONZE GRATE,

SEE NOTE No. 3.

DRAWING NOTES:

1. REDUCED PRESSURE BACKFLOW PREVENTER,

SIZE AS INDICATED ON DRAWINGS.

2. SHUT-OFF VALVES.

3. INLET, SIZE AS INDICATED ON DRAWINGS.

4. OUTLET, SIZE AS INDICATED ON DRAWINGS.

5. PRESSURE RELIEF VALVE, RUN DISCHARGE

PIPE FULL SIZE TO FLOOR DRAIN WITH REQUIRED

AIR GAP & TRAP PRIMER.

6. THE PLUMBING CONTRACTOR SHALL FURNISH

AND INSTALL ALL REDUCED PRESSURE

BACKFLOW PREVENTERS IN THIS SYSTEM AS

REQUIRED TO MEET ALL STATE AND LOCAL

CODES AND REGULATIONS.

7. STRAINER.

FIN. FLOOR

SCALE:

REDUCED PRESSURE BACKFLOW

PREVENTER

NONE

221113.00-14

DATE

DATE

ENGINEERING

DIVISION OF

AGENCY

AUTHORIZED AGENT

DIV. OF ENGR.

REVIEWED

ENGR. ACCT NO.

DRAWING NO.

DATE

A&E FILE NO.

CHECKED BY

SHEET DRAWN BY

RECORD DATE

DATEREVISIONS

COMMONWEALTH OF KENTUCKY

FINANCE AND ADMINISTRATION CABINET

DEPARTMENT FOR FACILITIES & SUPPORT SERVICES

DIVISION OF ENGINEERING

FRANKFORT, KENTUCKY

WWW.KLHENGRS.COM

ENGINEERS, PSC

MECHANICAL/ELECTRICAL ENGINEERS

KOHRS LONNEMANN HEIL

LEXINGTON, KENTUCKY

COLUMBUS, OHIO

DAYTON, OHIO

NEW YORK, NEW YORK

1538 ALEXANDRIA PIKE, SUITE

11 FT. THOMAS, KENTUCKY

41075 800-354-9783

859-442-8050

859-442-8058 FAX

KLH PRO. NO.

11369.04

470-C5N5-NC11-01

GATEWAY URBAN CAMPUS

438-440 Scott St., Covington, KY 41011

12/18/15

201114.02

PROFESSIONAL SERVICES CLASSROOM CENTER

PL1.5

PLUMBING DETAILS

AND SCHEDULE

File details come from the government source that posted it. Updated .