CAMP NELSON NATIONAL CEMETERY, KY 833CM3030 – CORRECT FCA DEFICIENCIES
Solicitation number
36C78626R0058
Issued by

About this file

This is an NFPA 780 Lightning Risk Assessment report prepared by Astute Engineering PLLC for the Camps Nelson National Cemetery project (Project No. 833CM3030) dated July 24, 2024, addressing correctable Facility Condition Assessment (FCA) deficiencies related to lightning protection.

The assessment evaluates six buildings at the facility: Public Restroom Building (18'-3" height), Wash Bay Building (19'-8"), Historic Maintenance Building (19'-3"), Maintenance Storage Building (22'-11"), Horse Stall Building (20'-11"), and Equipment Storage Building (29'-3"). All structures feature masonry construction with concrete slab foundations and gable asphalt shingle roofs. Using the 2023 version of NFPA 780 Annex L simplified risk assessment methodology, the report compares the annual threat occurrence (ND) against tolerable lightning frequency (NC) for each building. The assessment incorporates Lightning Flash Density data from the Vaisala National Lightning Detection Network (NG = 34.43 flashes per square kilometer annually) and applies location factors, construction coefficients, contents coefficients, occupancy coefficients, and consequence coefficients from NFPA 780 tables. Risk calculations for each building demonstrate that the expected annual threat occurrence exceeds the tolerable lightning frequency for all structures, with ND values ranging from 0.00990 to 0.0591 events per year against NC values ranging from 0.0003 to 0.0030 events per year. Based on this analysis, the assessment concludes that installation of new Lightning Protection Systems is recommended for all six buildings at Camps Nelson National Cemetery to mitigate the identified lightning strike risk.

View the file

Other files

File Type Posted
Amendment 4-833CM3030 - CD1 - Historic Hardware.pdf PDF
Amendment 4-833CM3030 - BID - HA-001 from 20260422 - 833CM3030 - BID - SET.pdf PDF
Amendment 4-833CM3030 - BID - CU-105 from 20260107 - 833CM3030 - BID - SET.pdf PDF
Amendment 4-833CM3030 - BID - 23 11 13 Fuel Storage Tanks.pdf PDF
Amendment 4-833CM3030 - BID - 037 - CU-105 UTILITY PLAN (R2).pdf PDF
Amendment 4-833CM3030 - BID - 26 29 23 Engine Control and Monitoring.pdf PDF
Amendment 4-833CM3030 - BID - 028 - CP-105 PAVING PLAN (R2).pdf PDF
Amendment 4-833CM3030 - BID - SN-104 105 and X-series from 20260107 - 833CM3030 - BID - SET.pdf PDF
Amendment 4-833CM3030 - BID - Historic Pages from 20260422 - 833CM3030 - BID - SET A-004 005 132 133 154 155.pdf PDF
Amendment 4-ConVault Specification with UL 752 Level 8.pdf PDF
Amendment 4-Convault Storage tank 500 GL-telford.pdf PDF
Amendment 4-Convault Brochure 2019 (003).pdf PDF
Amendment 4-833CM3030 - BID - 020 - CG-201 POND AND CRYPT FIELD SECTIONS (R1).pdf PDF
Amendment 4-AE-113 from 20260422 - 833CM3030 - BID - SET.pdf PDF
Amendment 4-AE-113 833CM3030 - BID - SET.pdf PDF
S02 36C78626R0058 Amendment 0004.docx DOCX document
Amendment 4-833CM3030 - CD1 - Historic Preservation.pdf PDF
Amendment 4-SED FCA - 04212022_Camp Nelson.pdf PDF
Amendment 4-833CM3030 - BID - AE-110 from 20260422 - 833CM3030 - BID - SET.pdf PDF
Amendment 4-833CM3030 - BID - 328400 Plant Irrigation_10-31-24.pdf PDF
Amendment 4- 36C78626R0058 FuelForce 814 Advanced Fuel Controller Brochure.pdf PDF
Amendment 4-240524-Camp Nelson National Cemetery - KY- SUE Field Report Deliverable.pdf PDF
Amendment 4-833CM3030 - BID - AE-150 from 20260422 - 833CM3030 - BID - SET.pdf PDF
Amendment 4-833CM3030 - BID - 07 42 43 Plastic Panel.pdf PDF
Amendment 4-833CM3030 - BID- EQUIPMENT STORAGE GARAGE-AE-141.pdf PDF
Amendment 4-GI-104 from 20260107 - 833CM3030 - BID - SET.pdf PDF
Amendment 4-833CM3030 - BID - 231123 NatGas.pdf PDF
Amendment 4- 833CM3030 - BID - 072727 - BARRIER VAPOR.pdf PDF
Amendment 4-3189 ECS Geotechnical Engineering Report - Expansion Area.pdf PDF
Amendment 4-833CM3030 - BID - 329000 Planting.pdf PDF
Amendment 4-3189 ECS Geotechnical Engineering Report - Camp Nelson Cemetery.pdf PDF
Amendment 4-833CM3030 - BID - 050 - S-101 STRUCTURAL PLAN (R2).pdf PDF
Amendment 4-Dispensing System Controller-SafeSite DSC with specs.pdf PDF
Amendment 4-833CM3030 - BID - CD-102 from 20260107 - 833CM3030 - BID - SET.pdf PDF
Amendment 4-AD-150 from 20260107 - 833CM3030 - BID - SET.pdf PDF
Amendment 4-833CM3030 - BID - 33 56 10 Temporary Fuel Storage Tanks.pdf PDF
Amendment 4-833CM3030 - BID - 052 - S-202 MATERIALS STORAGE BLDG. FRAMING (R2).pdf PDF
Amendment 4-3189 ECS Geotechnical Engineering Report - Maintenance Area.pdf PDF
S06_36C78626R0058 Amend. 0003.pdf PDF
S02 Amendement 36C78626R0058 0002.pdf PDF
S02 amendment 2.pdf PDF
S02 Fire Alarm Panel.pdf PDF
S02 Liquidated Damages 833CM3030_CNNC FCA Corrections CONS.pdf PDF
S02 12 from 833CM3030_CNNC FCA Corrections_CONS_BD DRAWINGS_VOL 1_addendum01.pdf PDF
S02 Amendment 36C78626R0058 0001.pdf PDF
P07 Jessamine Camp Nelson Building.pdf PDF
S02_Price Proposal Breakdown.docx DOCX document
S02_Attachment - Past Performance Questionnaire.docx DOCX document
P07 Jessamine Camp Nelson Highway.pdf PDF
S02_Attachment - DOL Payroll Form.pdf PDF
Show 40 more

Latest 50 of 67 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

WALKER FEDERAL SERVICES

7820B Wormans Mill Road, Suite 162, Frederick, Maryland 21701

Project: Camps Nelson National Cemetery Correct FCA Deficiencies

Project No.: 833CM3030

Date: 07/24/2024

NFPA 780 Lightning Risk Assessment

1. Introduction Astute Engineering PLLC (Astute), the electrical engineers on the subject project, performed an NFPA 780 lightning risk assessment for the public restroom/ wash bay building, Historic maintenance Building, Maintenance storage building, Horse stall Building, and Maintenance storage building.

The buildings are surrounded by tall trees and structures. The buildings included in the assessment currently do not have a lightning protection system.

Using the data available for the building structures a simplified risk assessment was performed to determine the necessity of the lightning protection system for both the buildings, per the 2023 version of NFPA 780 Annex L.

This report presents the data used, the assessment/evaluation, and the recommended action based on the analysis. The tolerable lightning frequency (NC) is compared with the annual threat occurrence (ND).

The result of this comparison is used to decide if a lightning protection system is needed. The conclusion is provided based on a two-level system of “recommended” and “optional”, per NFPA 780.

2. Building structure description:

2.1. Public Restroom Building Description:

Foundation Concrete slab on grade Structure Masonry Roof Gable and Asphalt shingles Number of stories 1 Height 18’-3”

2.2. Wash Bay Building Description:

Foundation Concrete slab on grade Structure Masonry Roof Gable and Asphalt shingles

Height 19’-8”

2.3. Historic Maintenance Building Description:

Structure Masonry Roof Gable and Asphalt shingles

Height 19’-3”

2.4. Maintenance Storage Building Description:

Structure Masonry Roof Gable and Asphalt shingles

Height 22’-11”

2.5. Horse Stall Building Description:

Structure Masonry Roof Gable and Asphalt shingles

Height 20’-11”

2.6. Equipment Storage Building Description:

Structure Masonry Roof Gable and Asphalt shingles

Height 29’-3” ft.

3. Data utilized in the analysis

The focus of the analysis was to assess the risk of a lightning strike occurring near or at the structures on the site. Parameter values used in the assessment & calculation are obtained from Tables L.4.2, L.5.1.2(a), L.5.1.2(b), L.5.1.2(c), L.5.1.2(d), and Figure L.2 of NFPA 780 based on statistical lighting density, lightning risk, environmental conditions, and structure construction. Building dimensions obtained from “Google Earth” are verified with available records and field measurements. The following sections include the selections and descriptions of the parameter values used to perform the risk assessment calculations for the structures in question.

3.1. Terms & Definitions

Lightning Protection Systems (LPS) Lightning Flash Density (NG) = Yearly number of flashes to ground per square kilometer.

Refer to Vaisala National Lightning Detection Network (2021)

Annual threat of occurrence (ND) = Yearly annual threat of occurrence (lightning strike frequency) (ND) to a structure is determined by the following equation:

ND = (NG) (AE) (C1) Potential events/year

Equivalent ground collection area (AE) = Area having equivalent lightning flash vulnerability (km2) as the structure.

(AE) = LW + 6H (L+ W) + 9𝜋𝐻ଶ

Where L= length, W = width, H= height of the structure

Tolerable lightning frequency (NC) = Calculated tolerable lightning events per year.

NC =

ଵ.ହ୶ଵషయ

𝐂 events/year

Where C = (C2) (C3) (C4) (C5)

(C1) = Location factor - Table L.4.2, NFPA 780 (C2) = Determination of construction coefficient - Table L.5.1.2(a), NFPA 780 (C3) = Determination of structure contents coefficient - Table L.5.1.2(b), NFPA 780 (C4) = Determination of structure occupancy coefficient - Table L.5.1.2(c), NFPA 780 (C5) = Determination of Lightning consequence coefficient - Table L.5.1.2(d), NFPA 780

4. Risk evaluation Tables 4.1 to 4.6 below present the Simplified Risk Calculations (Per NFPA 780, Table L.5.2.2) for the assessment/analysis of the public restroom/ wash bay building, Historic maintenance Building, Maintenance storage building, Horse stall Building, and Maintenance storage building.

Table 4.1: Public Restroom Building Data Input Equations Data Input Results

(AE) = LW + 6H (L+W) + 9𝜋𝐻ଶ L = 15 ft W = 13 ft H = 18 ft, H2 = 324 Sqft

AE =12379.88 Sqft AE =0.001150 Km2

Expected annual threat occurrence

ND = (NG) (AE) (C1)

NG = 34.43

AE = 0.001150

C1 = 0.25

ND = 0.00990

Tolerable lightning frequency to the structure

NC = (1.5×10-3) /C

Where C = (C2) (C3) (C4) (C5)

C2 = 1

C3 = 1

C4 = 1

C5 = 5

C = 5

NC = 0.0003

Table 4.2: Wash Bay Building Data Input Equations Data Input Results

(AE) = LW + 6H (L+W) + 9𝜋𝐻ଶ L = 9 ft W = 11 ft H = 20 ft, H2 = 400 Sqft

AE =13808.73 Sqft AE =0.001283 Km2

NG = 34.43

AE = 0.001283

C1 = 0.5

ND = 0.0221

Tolerable lightning frequency to the structure

NC = (1.5×10-3) /C

Where C = (C2) (C3) (C4) (C5)

C2 = 1

C3 = 1

C4 = 0.5

C5 = 1

C = 0.5

NC = 0.0030

Table 4.3: Historic Maintenance Building

(AE) = LW + 6H (L+W) + 9𝜋𝐻ଶ L = 58 ft W = 19 ft H = 19 ft, H2 = 361 Sqft

AE =20087.03 Sqft AE =0.001866 Km2

NG = 34.43

AE = 0.001866

C1 = 0.25

ND = 0.0161

Tolerable lightning frequency to the structure

NC = (1.5×10-3) /C

Where C = (C2) (C3) (C4) (C5)

C2 = 1

C3 = 1

C4 = 1

C5 = 1

C = 1

NC = 0.0015

Table 4.4: Maintenance Storage Building

(AE) = LW + 6H (L+W) + 9𝜋𝐻ଶ L = 26 ft W = 30 ft H = 23 ft, H2 = 529 Sqft

AE =23465.12 Sqft AE =0.002180 Km2

NG = 34.43

AE = 0.002180

C1 = 0.5

ND = 0.0375

Tolerable lightning frequency to the structure

NC = (1.5×10-3) /C

Where C = (C2) (C3) (C4) (C5)

C2 = 1

C3 = 1

C4 =0.5

C5 = 1

Table 4.5: Horse Stall Building

(AE) = LW + 6H (L+W) + 9𝜋𝐻ଶ L = 59 ft W = 36 ft H = 21 ft, H2 = 441 Sqft

AE =26562.98 Sqft AE =0.002468 Km2

NG = 34.43

AE = 0.002468

C1 = 0.5

ND = 0.0425

Tolerable lightning frequency to the structure

NC = (1.5×10-3) /C

Where C = (C2) (C3) (C4) (C5)

C2 = 1

C3 = 1

C4 = 0.5

C5 = 1

Table 4.6: Equipment Storage Building

(AE) = LW + 6H (L+W) + 9𝜋𝐻ଶ L = 38 ft W = 31 ft H = 29 ft, H2 = 841 Sqft

AE =36962.71 Sqft AE =0.003434 Km2

NG = 34.43

AE = 0.003434

C1 = 0.5

ND = 0.0591

Tolerable lightning frequency to the structure

NC = (1.5×10-3) /C

Where C = (C2) (C3) (C4) (C5)

C2 = 1

C3 = 1

C4 = 0.5

C5 = 1

5. Results According to NFPA 780 guidelines:

If (ND) ≤ (NC), then LPS is optional, If (ND) > (NC), then LPS is recommended

As assessed in Tables 4.1, 4.2, 4.3, 4.4, 4.5 and 4.6 above, calculated value of “ND” > “NC”, suggesting that Lightning Protection System is recommended for all buildings.

6. Conclusion & Recommendation:

Based on the above assessment, Astute concludes and recommends providing new Lightning Protection Systems at the Public restroom, Wash Bay building, Historic maintenance Building, Maintenance storage building, Horse stall Building, and Maintenance storage building.