Amendment 4-833CM3030 - BID - 07 42 43 Plastic Panel.pdf

PDF 160 KB Posted

Attached to
CAMP NELSON NATIONAL CEMETERY, KY 833CM3030 – CORRECT FCA DEFICIENCIES
Solicitation number
36C78626R0058
Issued by

About this file

This is a specification section for composite wall panels required for the Camp Nelson National Cemetery project (VA Project No. 833CM3030) in Kentucky, part of a 100% Construction Document phase dated July 8, 2025.

The specification requires the installation of corrugated polycarbonate wall cladding panels as the primary product, with Palram "SUNTUF" Corrugated Polycarbonate Panels designated as the basis-of-design. Panels must be 0.8 mm nominal thickness, 26 inches in nominal width, sea green in color, with 60–90% light transmission and a Class B fire rating per ASTM E84. The panels shall feature a co-extruded UV-resistant layer on the outer face, provide 200 times greater impact resistance than glass, and operate within a temperature range of -40°F to 240°F. A 10-year manufacturer's warranty against UV degradation and loss of impact strength is required. Accessory components include corrosion-resistant self-drilling screws with Neoprene or EPDM-sealed washers, UV-stable closure strips matching panel profile, matching ridge caps, corner caps, J-channel and U-channel trim, and UV-resistant neutral-cure silicone sealants compatible with polycarbonate. Installation must include vertical or horizontal panel orientation with at least one corrugation overlap, fastening through the crown of corrugation with oversize holes drilled for thermal expansion (minimum 1/8" larger than screw shank), and a minimum 1/8" end gap at trim for thermal movement. The manufacturer must have a minimum five years of polycarbonate panel production experience, and the installer must demonstrate experience with corrugated panel system installation. Panels shall be stored flat, out of sunlight, and covered with opaque material. Compliance with ASTM standards D635, D1929, E84, D638, D696, D790, and D1003 is required.

View the file

Other files

File Type Posted
Amendment 4-833CM3030 - CD1 - Historic Hardware.pdf PDF
Amendment 4-833CM3030 - BID - HA-001 from 20260422 - 833CM3030 - BID - SET.pdf PDF
Amendment 4-833CM3030 - BID - CU-105 from 20260107 - 833CM3030 - BID - SET.pdf PDF
Amendment 4-833CM3030 - BID - 23 11 13 Fuel Storage Tanks.pdf PDF
Amendment 4-833CM3030 - BID - 037 - CU-105 UTILITY PLAN (R2).pdf PDF
Amendment 4-833CM3030 - BID - 26 29 23 Engine Control and Monitoring.pdf PDF
Amendment 4-833CM3030 - BID - 028 - CP-105 PAVING PLAN (R2).pdf PDF
Amendment 4-833CM3030 - BID - SN-104 105 and X-series from 20260107 - 833CM3030 - BID - SET.pdf PDF
Amendment 4-833CM3030 - BID - Historic Pages from 20260422 - 833CM3030 - BID - SET A-004 005 132 133 154 155.pdf PDF
Amendment 4-ConVault Specification with UL 752 Level 8.pdf PDF
Amendment 4-Convault Storage tank 500 GL-telford.pdf PDF
Amendment 4-Convault Brochure 2019 (003).pdf PDF
Amendment 4-833CM3030 - BID - 020 - CG-201 POND AND CRYPT FIELD SECTIONS (R1).pdf PDF
Amendment 4-AE-113 from 20260422 - 833CM3030 - BID - SET.pdf PDF
Amendment 4-AE-113 833CM3030 - BID - SET.pdf PDF
S02 36C78626R0058 Amendment 0004.docx DOCX document
Amendment 4-833CM3030 - CD1 - Historic Preservation.pdf PDF
Amendment 4-SED FCA - 04212022_Camp Nelson.pdf PDF
Amendment 4-833CM3030 - BID - AE-110 from 20260422 - 833CM3030 - BID - SET.pdf PDF
Amendment 4-833CM3030 - BID - 328400 Plant Irrigation_10-31-24.pdf PDF
Amendment 4- 36C78626R0058 FuelForce 814 Advanced Fuel Controller Brochure.pdf PDF
Amendment 4-240524-Camp Nelson National Cemetery - KY- SUE Field Report Deliverable.pdf PDF
Amendment 4-833CM3030 - BID - AE-150 from 20260422 - 833CM3030 - BID - SET.pdf PDF
Amendment 4-833CM3030 - BID- EQUIPMENT STORAGE GARAGE-AE-141.pdf PDF
Amendment 4-GI-104 from 20260107 - 833CM3030 - BID - SET.pdf PDF
Amendment 4-833CM3030 - BID - 231123 NatGas.pdf PDF
Amendment 4- 833CM3030 - BID - 072727 - BARRIER VAPOR.pdf PDF
Amendment 4-3189 ECS Geotechnical Engineering Report - Expansion Area.pdf PDF
Amendment 4-833CM3030 - BID - 329000 Planting.pdf PDF
Amendment 4-3189 ECS Geotechnical Engineering Report - Camp Nelson Cemetery.pdf PDF
Amendment 4-833CM3030 - BID - 050 - S-101 STRUCTURAL PLAN (R2).pdf PDF
Amendment 4-Lightning Protection Asmnt Report_Camps Nelson Cemetery.pdf PDF
Amendment 4-Dispensing System Controller-SafeSite DSC with specs.pdf PDF
Amendment 4-833CM3030 - BID - CD-102 from 20260107 - 833CM3030 - BID - SET.pdf PDF
Amendment 4-AD-150 from 20260107 - 833CM3030 - BID - SET.pdf PDF
Amendment 4-833CM3030 - BID - 33 56 10 Temporary Fuel Storage Tanks.pdf PDF
Amendment 4-833CM3030 - BID - 052 - S-202 MATERIALS STORAGE BLDG. FRAMING (R2).pdf PDF
Amendment 4-3189 ECS Geotechnical Engineering Report - Maintenance Area.pdf PDF
S06_36C78626R0058 Amend. 0003.pdf PDF
S02 Amendement 36C78626R0058 0002.pdf PDF
S02 amendment 2.pdf PDF
S02 Fire Alarm Panel.pdf PDF
S02 Liquidated Damages 833CM3030_CNNC FCA Corrections CONS.pdf PDF
S02 12 from 833CM3030_CNNC FCA Corrections_CONS_BD DRAWINGS_VOL 1_addendum01.pdf PDF
S02 Amendment 36C78626R0058 0001.pdf PDF
P07 Jessamine Camp Nelson Building.pdf PDF
S02_Price Proposal Breakdown.docx DOCX document
S02_Attachment - Past Performance Questionnaire.docx DOCX document
P07 Jessamine Camp Nelson Highway.pdf PDF
S02_Attachment - DOL Payroll Form.pdf PDF
Show 40 more

Latest 50 of 67 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

VA Project No. 833CM3030 Camp Nelson National Cemetery, KY Correct FCA Deficiencies 100% CD2

7-8-2025

COMPOSITE WALL PANELS

SECTION 07 46 33 - 1

SECTION 07 46 33

COMPOSITE WALL PANELS

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Corrugated polycarbonate wall cladding panels.

2. Accessories including fasteners, closure strips, trim, and sealants.

B. Related Sections:

1. Section 06 10 00 – Rough Carpentry

2. Section 07 60 00 – Flashing and Sheet Metal

3. Section 07 92 00 – Joint Sealants

1.2 REFERENCES

Comply with the following standards:

• ASTM D635 – Standard Test Method for Rate of Burning of Plastics

• ASTM D1929 – Ignition Temperature

• ASTM E84 – Surface Burning Characteristics

• ASTM D638 – Tensile Properties of Plastics

• ASTM D696 – Coefficient of Linear Thermal Expansion

• ASTM D790 – Flexural Properties of Plastics

• ASTM D1003 – Haze and Luminous Transmittance

1.3 SUBMITTALS

A. Product Data: Manufacturer’s data sheets on panels and accessories

B. Samples: One 12" x 12" panel sample, showing color and profile

C. Warranty: Manufacturer’s standard 10-year limited warranty

1.4 QUALITY ASSURANCE

A. Manufacturer Qualifications: Minimum 5 years of polycarbonate panel production

B. Installer Qualifications: Experience with installation of corrugated panel systems

1.5 DELIVERY, STORAGE, AND HANDLING

A. Store panels flat, out of sunlight, and covered with opaque material

B. Handle to prevent scratching and edge damage

1.6 WARRANTY

A. Provide 10-year manufacturer’s warranty against UV degradation and loss of impact strength

PART 2 – PRODUCTS

2.1 MANUFACTURERS

A. Basis-of-Design: Palram “SUNTUF” Corrugated Polycarbonate Panels

1. Profile: Greca Square Wave, or Arc Wave

2. Substitutions: Permitted with prior approval

VA Project No. 833CM3030 Camp Nelson National Cemetery, KY Correct FCA Deficiencies 100% CD2

7-8-2025

COMPOSITE WALL PANELS

SECTION 07 46 33 - 2

2.2 CORRUGATED POLYCARBONATE PANELS

A. Material: UV-resistant extruded polycarbonate

B. Thickness: 0.8 mm (nominal)

C. Panel Width: 26 inches nominal

D. Panel Length: [As required – typically 8', 10', or 12']

E. Color: Sea Green

F. Light Transmission: 60–90%

G. UV Protection: Co-extruded UV-resistant layer on outer face

H. Fire Rating: Class B per ASTM E84

I. Impact Resistance: 200 times greater than glass

J. Temperature Range: -40°F to 240°F (-40°C to 115°C)

2.3 ACCESSORIES

A. Fasteners: Corrosion-resistant self-drilling screws with Neoprene or EPDM-sealed washers

B. Closure Strips: UV-stable foam wood, or plastic to match panel profile

C. Trims: Matching ridge caps, corner caps, J-channel, and U-channel as needed

D. Sealants: UV-resistant, neutral-cure silicone, compatible with polycarbonate

E. Venting Tape (optional): To prevent condensation in enclosed cavities

PART 3 – EXECUTION

3.1 EXAMINATION

A. Confirm wood or metal framing is plumb and secure

B. Do not begin installation until substrate conditions are corrected

3.2 INSTALLATION

A. Install panels vertically (or horizontally as specified), overlapping by at least one corrugation

B. Fasten through crown of corrugation using specified fasteners with washers

C. Drill oversize holes for thermal expansion (minimum 1/8” larger than screw shank)

D. Allow minimum 1/8” end gap at trim and terminations for thermal movement

E. Install closure strips at panel ends and penetrations

F. Trim all edges with matching finish accessories

G. Do not over-tighten screws—snug fit only

H. Utilize all accessories including vertical and horizontal closure strips

3.3 CLEANING AND PROTECTION

A. Clean panels with mild soap and water—no abrasives or solvents

B. Protect panels from scratching and damage until project completion.

- - - END - - -