This document is Section 23 11 23 of the specifications for the Camp Nelson National Cemetery Wash Bay/Admin Building project, detailing requirements for Facility Natural-Gas Piping installation.
The specification establishes comprehensive requirements for fuel gas systems, including piping, equipment, and accessories. For fuel gas service connections to the building, black steel pipe (ASTM A53, Schedule 40) with shop-applied coatings is required from the exterior wall to approximately 1.5 meters outside the building, with coating options including coal tar enamel (with fibrous glass mat felt, not asbestos), adhesive-thermoplastic resin, or thermosetting epoxy. Fittings must comply with ANSI standards, including butt weld fittings (ANSI B16.9), socket weld and threaded fittings (ANSI B16.11), and grooved end fittings (ductile iron ASTM A536, malleable iron ASTM A47, or steel ASTM A53). Interior fuel gas piping shall use black steel (ASTM A53, Schedule 40) with steel nipples (ASTM A733) and welded or threaded joints. The specification requires dielectric fittings between ferrous and non-ferrous pipe, flexible gas equipment connectors with Teflon core and AGA certification, and "Y" type strainers with removable brass sleeves on high-pressure sides of reducing valves and equipment inlets. Installation must comply with the International Fuel Gas Code and NFPA 54, including support per code requirements, valve placement with horizontal stems, union and shut-off valves at equipment connections, and drip pockets at low points. Pipe hangers and supports require red lead or zinc chromate primer coating, cast iron plates with set screws, height-adjustable clevis hangers, and additional support for vertical runs exceeding 6 meters. Fire stopping and waterproofing are required at wall and floor penetrations, with cast escutcheons at all visible penetrations. Testing must conform to the International Fuel Gas Code upon completion.
View the file
Other files
Show 40 more
Latest 50 of 67 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CAMP NELSON NATIONAL CEMETERY PROJECT NO. 833-CM3-026
WASH BAY / ADMIN BUILDING 05-20-15
FACILITY NATURAL-GAS PIPING
23 11 23 - 1
SECTION 23 11 23
PART 1 - GENERAL
1.1 DESCRIPTION
Fuel gas systems, including piping, equipment and all necessary accessories as designated in this section.
1.2 RELATED WORK
A. Penetrations in rated enclosures: Section 07 84 00, FIRESTOPPING.
B. Preparation and finish painting and identificati on of piping systems:
Section 09 91 00, PAINTING.
C. Section 22 05 11, COMMON WORK RESULTS FOR PLUMBI NG.
1.3 SUBMITTALS
A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT
DATA, AND SAMPLES.
B. Manufacturer's Literature and Data:
1. Piping.
2. Strainers.
3. All items listed in Part 2 - Products.
C. Detailed shop drawing of clamping device and ext ensions when required in connection with the waterproofing membrane or th e floor drain.
1.4 APPLICABLE PUBLICATIONS
A. The publications listed below form a part of thi s specification to the extent referenced. The publications are referenced in the text by the basic designation only.
B. American National Standards Institute (ANSI):
American Society of Mechanical Engineers (ASME): ( Copyrighted Society)
A13.1-07................Scheme for Identification o f Piping Systems
B16.3-06................Malleable Iron Threaded Fit tings ANSI/ASME
B16.9-07................Factory-Made Wrought Steel Buttwelding Fittings
ANSI/ASME
B16.11-05...............Forged Steel Fittings, Sock et-Welding and
Threaded ANSI/ASME
B16.15-06...............Cast Bronze Threaded Fittin gs ANSI/ASME
B31.8-07................Gas Transmission and Distri bution Piping
Systems ANSI/ASME
C. American Society for Testing and Materials (ASTM ):
A47-04..................Ferritic Malleable Iron Cas tings
23 11 23 - 2
A53-07..................Pipe, Steel, Black And Hot- Dipped, Zinc-coated
Welded and Seamless
A183-03.................Carbon Steel Track Bolts an d Nuts
A536- E1-R05............Ductile Iron Castings
A733-03.................Welded and Seamless Carbon Steel and Austenitic
Stainless Steel Pipe Nipples
B687-E1-R05.............Brass, Copper, and Chromium -Plated Pipe Nipples
D. National Fire Protection Association (NFPA):
54-2002.................National Fuel Gas Code
E. Manufacturers Standardization Society of the Val ve and Fittings
Industry, Inc. (MSS):
SP-72-99................Ball Valves With Flanged or Butt Welding For
General Purpose
SP-110-96...............Ball Valve Threaded, Socket Welding, Solder
Joint, Grooved and Flared Ends
F. International Fuel Gas Code.
PART 2 - PRODUCTS
2.1 FUEL GAS SERVICE CONNECTIONS TO BUILDING
A. From inside face of exterior wall to a distance of approximately 1.5 m(5 feet) outside of building, use coated piping.
B. Pipe: Black steel, ASTM A53, Schedule 40. Shop-a pplied pipe coating shall be one of the following types:
1. Coal Tar Enamel Coating: Exterior of pipe and fi ttings shall be cleaned, primed with Type B primer and coated with hot-applied coal tar enamel with bonded layer of felt wrap in accord ance with AWWA
C203. Asbestos felt shall not be used; felt materia l shall be fibrous glass mat as specified in Appendix Section A2.1 of AWWA
C203.
2. Adhesive-thermoplastic Resin Coating: Fed. Spec. L-C-530, Type I.
3. Thermosetting Epoxy Coating: Fed. Spec. L-C-530, Type II.
4. Field-applied plastic tape material used on pipe joints and for repairing damaged areas of shop-applied coatings, F ed. Spec. L-T-
1512, Type I, 10 mils nominal thickness for pipe jo ints, and Type
II, 20 mils nominal thickness for coating repairs.
C. Fittings:
1. Butt weld fittings, wrought steel, ANSI B16.9.
2. Socket weld and threaded fittings forged steel, ANSI B16.11.
23 11 23 - 3
3. Grooved End: Ductile iron (ASTM A536, Grade 65-4 5-12), malleable iron (ASTM A47, Grade 32510), or steel (ASTM A53, T ype F or Type E or S, Grade B).
D. Joints: Welded, ANSI B31.8.
2.2 FUEL GAS PIPING
A. Pipe: Black steel, ASTM A53, Schedule 40.
B. Nipples: Steel, ASTM A733, Schedule 40.
C. Fittings:
1. Steel Welded: Schedule 40
a. Up to 100 mm (4 inch), ANSI B16.11, Socket welde d.
b. Over 100 mm (4 inch), ANSI B16.9, Butt welded.
2. Malleable Iron, Threaded: ANSI B16.3.
3. Grooved End: Ductile iron (ASTM A536, Grade 65-4 5-12), malleable iron (ASTM A47, Grade 32510), or steel (ASTM A53, T ype F or Type E or S, Grade B).
D. Joints: Provide welded or threaded joints.
2.3 EXPOSED FUEL GAS PIPING
A. Unfinished Rooms and Mechanical Rooms: Chrome-pl ated brass piping is not required. Paint piping systems as specified in Section 09 91 00, PAINTING.
2.4 WATERPROOFING
A. Provide at points where pipes pass through membr ane waterproofed floors or walls in contact with earth.
B. Floors: Provide cast iron stack sleeve with flas hing device and an underdeck clamp. After stack is passed through slee ve, provide a waterproofed caulked joint at top hub.
C. Walls: See detail shown on drawings.
2.5 STRAINERS
A. Provide on high pressure side of pressure reduci ng valves, on suction side of pumps, on inlet side of indicating and cont rol instruments and equipment subject to sediment damage and where show n on drawings.
Strainer element shall be removable without disconn ection of piping.
B. Gas Lines: "Y" type with removable mesh lined br ass strainer sleeve.
C. Body: Smaller than 80 mm (3 inches), brass or br onze; 80 mm (3 inches) and larger, cast iron or semi-steel.
23 11 23 - 4
2.6 DIELECTRIC FITTINGS
A. Provide dielectric couplings or unions between f errous and non-ferrous pipe.
2.7 GAS EQUIPMENT CONNECTORS
A. Flexible connectors with Teflon core, interlocke d galvanized steel protective casing, AGA certified design.
PART 3 - EXECUTION
3.1 INSTALLATION
A. General: Comply with the International Fuel Gas Code and the following:
1. Install branch piping for fuel gas and connect t o all fixtures, valves, cocks, outlets, casework, cabinets and equi pment, including those furnished by the Government or specified in o ther sections.
2. Pipe shall be round and straight. Cutting shall be done with proper tools. Pipe, except for plastic and glass, shall be reamed to full size after cutting.
3. All pipe runs shall be laid out to avoid interfe rence with other work.
4. Install valves with stem in horizontal position whenever possible.
All valves shall be easily accessible.
5. Install union and shut-off valve on pressure pip ing at connections to equipment.
6. Pipe Hangers, Supports and Accessories:
a. All piping shall be supported per International Fuel Gas Code.
b. Shop Painting and Plating: Hangers, supports, ro ds, inserts and accessories used for Pipe supports shall be shop co ated with red lead or zinc Chromate primer paint. Electroplated copper hanger rods, hangers and accessories may be used with copp er tubing.
c. Floor, Wall and Ceiling Plates, Supports, Hanger s:
1) Solid or split unplated cast iron.
2) All plates shall be provided with set screws.
3) Pipe Hangers: Height adjustable clevis type.
4) Adjustable Floor Rests and Base Flanges:Steel.
5) Concrete Inserts: "Universal" or continuous slot ted type.
6) Hanger Rods: Mild, low carbon steel, fully threa ded or
Threaded at each end with two removable nuts at ea ch end for positioning rod and hanger and locking each in plac e.
7) Riser Clamps: Malleable iron or steel.
23 11 23 - 5
8) Rollers: Cast iron.
9) Self-drilling type expansion shields shall be "P hillips" type, with case hardened steel expander plugs.
10)Hangers and supports utilized with insulated pip e and tubing shall have 180 degree (min.) metal protection shiel d Centered on and welded to the hanger and support. The shield shall be 4 inches in length and be 16 gauge steel. The shield shall be sized for the insulation.
11)Miscellaneous Materials: As specified, required, directed or as noted on the drawings for proper installation of hangers, supports and accessories. If the vertical distance exceeds 6 m
(20 feet) for cast iron pipe additional support sha ll be provided in the center of that span. Provide all ne cessary auxiliary steel to provide that support.
7. Install cast escutcheon with set screw at each w all, floor and ceiling penetration in exposed finished locations a nd within cabinets and millwork.
8. Penetrations:
a. Fire Stopping: Where pipes pass through fire par titions, fire walls, smoke partitions, or floors, install a fire stop that provides an effective barrier against the spread of fire, smoke and gases as specified in Section 07 84 00, FIRESTO PPING.
Completely fill and seal clearances between raceway s and openings with the fire stopping materials.
b. Waterproofing: At floor penetrations, completely seal clearances around the pipe and make watertight with sealant as specified in
Section 07 92 00, JOINT SEALANTS.
B. Piping shall conform to the following:
1. Fuel Gas:
a. Entire fuel gas piping installation shall be in accordance with requirements of NFPA 54 and International Fuel Gas Code.
b. Install fuel gas piping with plugged drip pocket s at low points.
3.2 TESTS
A. General: Test system either in its entirety or i n sections in accordance with International Fuel Gas Code.
- - - E N D - - -