21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_44.pdf

PDF 748 KB Posted

Attached to
FPCM-LAC-I001104-M035-RS
Solicitation number
0000036277
Issued by
Los Angeles County, California

About this file

This document is a detailed architectural drawing set (Sheet A905) for a roof replacement project by the California Department of Corrections and Rehabilitation (CDCR) at California State Prison, Los Angeles County, located in Lancaster, CA. The project, labeled "Replace Roofs - Phase 1", involves comprehensive roofing modifications including installing new PVC roofing assemblies, replacing drains, and implementing various flashing and waterproofing details. The drawings are dated August 31, 2023, with final approval from the Office of the State Fire Marshal on 10/10/23, and include specific technical specifications for roof drain installations, scuppers, pitch pockets, and termination strips.

The technical drawings provide precise engineering details for roof system components, specifying materials like 22 GA galvanized sheet metal coping, PVC roofing membranes, cast iron drains (Zurn Z121 or equivalent), and specific installation techniques such as heat welding, fastening methods, and sealant applications. The project appears to be a state-funded infrastructure improvement focusing on maintaining and upgrading the roofing systems at the California State Prison facility, with meticulous attention to waterproofing, drainage, and long-term durability of the roof assemblies. The drawings include multiple scaled sections and detailed views to guide precise implementation of the roofing replacement project.

View the file

Other files

File Type Posted
21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_14.pdf PDF
21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_30.pdf PDF
21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_36.pdf PDF
I-001104_-_21-040_-_002_-_Roof_Penetrations.pdf PDF
21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_10.pdf PDF
21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_37.pdf PDF
21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_9.pdf PDF
21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_13.pdf PDF
21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_32.pdf PDF
21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_48.pdf PDF
21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_26.pdf PDF
21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_21.pdf PDF
21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_51.pdf PDF
21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_6.pdf PDF
21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_31.pdf PDF
21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_25.pdf PDF
21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_38.pdf PDF
21-039_LAC_Replace_Roofs_Volume_1.pdf PDF
21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_34.pdf PDF
21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_27.pdf PDF
21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_40.pdf PDF
21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_7.pdf PDF
21-039_LAC_Replace_Roofs_Volume_2.pdf PDF
21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_23.pdf PDF
12_-_FPCM-LAC-I001104-M035-RS.pdf PDF
21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_47.pdf PDF
21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_42.pdf PDF
21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_33.pdf PDF
21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_12.pdf PDF
21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_16.pdf PDF
21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_3.pdf PDF
21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_20.pdf PDF
21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_18.pdf PDF
21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_46.pdf PDF
21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_39.pdf PDF
21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_35.pdf PDF
21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_22.pdf PDF
21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_5.pdf PDF
21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_24.pdf PDF
21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_28.pdf PDF
21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_43.pdf PDF
21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_15.pdf PDF
21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_50.pdf PDF
21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_4.pdf PDF
21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_19.pdf PDF
21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_49.pdf PDF
21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_8.pdf PDF
21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_29.pdf PDF
21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_17.pdf PDF
21-040-LAC_Replace-Roofs-Phase1_Final-Drawings_41.pdf PDF
Show 40 more

Latest 50 of 55 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MAIN ROOF AND OVERFLOW DRAIN

SCALE: 3" = 1'-0"

MATCH (E) VERIFY IN FIELD

(N) PVC ROOFING

ASSEMBLY, SEE DETAIL

A900

(E) LIGHT WEIGHT CONCRETE DECK

(N) 12" Ø PRIMARY ROOF DRAIN,

COATED CAST IRON (ZURN Z121 OR

EQ.)

SECURE (N) PVC ROOF MEMBRANE

REINSTALLED (E) DRAIN

(E) RAIN WATER LEADER

(N) 12" Ø ROOF

OVERFLOW DRAIN W/ 2"

DAM, COATED CAST IRON

(ZURN Z121 OR EQ.)

1'-6"

M

IN

6"

SLOPE DN

1/2":1'-0"

NOTES:

1. (N) 22 GA. GALV. S.M. COPING & REGLETS TO

BE PAINTED. COLORS TO MATCH EXISTING.

3. SOLDER ALL JOINTS.

SCUPPER AT LOWER ROOF-EXISTING

SCALE: 3" = 1'-0"

SLOPE DN

1/2":1'-0"

(N) HEAT WELDED LAPS

PER MANUFACTURER

REQUIREMENTS

(N) PVC ROOFING

ASSEMBLY, SEE DETAIL

A900(N) HEXAGON HEAD,

SLOTTED DRIVE, SELF-TAPPING

CONCRETE SCREW

W/ 1-1/2" MIN EMBED.,

@ 24" O.C., TYP.

(N) BACKER ROD AIR SEAL

ON ALL FOUR FLANGES

(N) ADHESIVE COLD APPLIED MEMBRANE

(N) 22 GA GALV. S.M. COPING CAP, SEE DETAIL

A902

(E) PRECAST CONCRETE

WALL TO REMAIN

(E) CONCRETE PLANK W/

CONCRETE TOPPING

18'-6"

T.O. (E) PRECAST

CONCRETE WALL

(E) SCUPPER

8"

1'-0"

(N) SCUPPER S.S.D.

ELEVATION - A

(E) CONC. PLANK

(E) CONC.

TOPPING SLAB

TOP OF (E) DECK

/2

4" M

IN

LONG SECTION

S501

(N) OVERFLOW

SCUPPER

SLOPE DN

1/2":1'-0"

10"

4"

A

SLOPE DN

M

IN

(E) STEEL DOWEL

(N) PVC ROOFING

ASSEMBLY,

SEE DETAIL

PITCH POCKET

SCALE: 3" = 1'-0"

FLASHING, HOT-AIR WELDED

16 GA METAL PITCH PAN

FASTENED W/ SMS @ 4" O.C.

PENETRATIONS

INSULATION

SECURELY

FASTENED VAPOR

RETARDER

NON-SHRINK GROUT

2" MIN

SEALANT

POCKET FILLER

(E)CONCRETE

ROOF DECK

LARGE PITCH POCKET

SCALE: 3" = 1'-0"

NOTES:

1. REMOVE ALL EXISTING FLASHING, LEAD, ETC. PIPE SURFACE MUST BE FREE OF ALL RUST, GREASE, INSUALATION, ETC.

2. POURABLE SEALER MOUNTED TO SHED WATER (MINIMUM DEPTH OF 2", REMAINDER OF POCKET MAY BE FILLED W/ NON-SHRINKING GROUT).

3. WHEN OUTSIDE DIAMETER OF PIPE EXCEEDS 18", ADDITIONAL FIELD MEMBRANE SECUREMENT REQUIRED.

4. DO NOT USE WHEN SERVICE TEMP EXCEEDS 180°F. REFER TO DETAIL X/A9.0

4" V.I.F.

(N) PVC ROOFING ASSEMBLY, SEE DETAIL

(N) 18 GA. METAL PENETRATION POCKET,

TYP.

A900

(N) 3/8"Ø EXPANSION ANCHOR W/ 2" MIN.

EMBED., TYP.

(N) POURABLE SEALER PITCH POCKET

(N) SURFACE MOUNTED COUNTER-FLASHING

FASTENED @ 8" O.C., MIN.

(N) NON-SHRINKING GROUT, TYP.

(E) ROOF DECK

(N) TERMINATION BAR FASTENED @ 8" O.C.,

TYP.

(N) BUTYL TAPE

#12 HEX HEAD SCREWS W/ INTEGRAL

NEOPRENE WASHERS, TYP.

(N) BUTYL TAPE

(E) PIPE, TYP.

4" V.I.F.

(N) CONTINUOUS BEAD OF AP OR HIGH GRADE SEALANT

(N) MULTI-PURPOSE PVC TAPE

(N) REGLET FASTENED AT 8" O.C. W/ GROMETTED

FASTENERS

(N) PVC FLASHING,

ADHERED TO (E)

PARAPET. HEAT

WELD TO ROOFING

MEMBRANE.

(N) PVC ROOFING

ASSEMBLY,

SEE DETAIL 4

A900

M

IN

(E) PRECAST CONCRETE WALL

TERMINATION STRIP

SCALE: 3" = 1'-0"

A

METAL COPING CAP

TERMINATION STRIP W/

APPROVED SEALANT

(TOOLED)

A

B

B

(N) REGLET FASTENED AT

8" O.C. W/ GROMETTED

FASTENERS W/

MULTI-PURPOSE PVC TAPE

CONTINUOUS BEAD

(E) PRECAST

CONCRETE

WALL

(N) PVC ROOFING

ASSEMBLY,

SEE DETAIL

A905

D E T A

IL

S

SHEET NUMBER

S

TA

TE

O

F C

A

LI

FO

R

N

IA

D E P A R

TM

E N

T O

F C

O R

R E C

TI

O

N S A

N D

R E H

A B

IL

IT

A

TI

O N

FA

C

IL

IT

Y P

LA

N

N

IN

G , C

O N

S

TR

U C

TI

O

N A

N D

M A N

A G

E M

E N

T D

IV

IS

IO

N

DE

SI

G N

SE

RV

IC

ES

A

ND

S

TA

ND

AR

DS

B

RA

NC

H

DE

SI

G

N

SE

RV

IC

ES

S

EC

TI

O N

APPROVAL

L A C

V1

C A L

IF

O R

N

IA

S T A T E P

R

IS

O N

L O

S A

N G

E L E S C

O U

N T Y

T H

S T R

E E T , W

E S T

LA

N

C A S T E R

, C A

R E P L A C

E R

O O

F S

P H

A S E

A U

G U

S T

F

IN

A L D

R A W

IN

G

S

. 1

V1

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

10/10/23

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

23-0002

11/20/2023 CASp-491 #1317