This document is a structural engineering general notes sheet for a California Department of Corrections and Rehabilitation (CDCR) roofing project located at California State Prison, Los Angeles County in Lancaster, California. The project, identified as Phase 1 with job number 21-040, involves place roof replacement at the facility located at 44750 60th Street West. The drawings are dated August 31, 2023, and have been reviewed and approved by multiple state agencies, including the Office of the State Fire Marshal (approval dated 10/10/23) and a Certified Access Specialist (CASp certificate #1317).
The general notes sheet provides comprehensive technical specifications for structural construction, including detailed requirements for concrete, structural steel, concrete masonry units, and cold-formed metal framing. The document outlines specific standards for materials, fabrication, welding, reinforcement, and construction practices, referencing multiple building codes and standards such as the 2022 California Building Code, ASCE 7-16, ACI 318-19, and AISC standards. The project appears to be funded through state infrastructure funding, with strict adherence to California state building and safety regulations, and includes provisions for special inspections, material testing, and compliance with seismic design category D requirements.
View the file
Other files
Show 40 more
Latest 50 of 55 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERAL NOTES
100SN001
1. INTERPRETATION OF DRAWINGS & SPECIFICATIONS
A. WHERE SPECIFICATIONS HAVE BEEN PREPARED FOR THIS PROJECT, THEY ARE ARRANGED
IN SEVERAL SECTIONS, BUT SUCH SEPARATION SHALL NOT BE CONSIDERED AS THE LIMITS
OF THE WORK REQUIRED OF ANY SEPARATE TRADE. THE TERMS AND CONDITIONS OF
SUCH LIMITATIONS ARE WHOLLY BETWEEN THE CONTRACTOR AND THEIR
SUBCONTRACTORS.
B. IN GENERAL, THE WORKING DETAILS WILL INDICATE DIMENSIONS, POSITION AND KIND OF
CONSTRUCTION, AND THE SPECIFICATIONS, QUALITIES AND METHODS. ANY WORK
INDICATED ON THE WORKING DETAILS AND NOT MENTIONED IN THE SPECIFICATIONS, OR
VICE VERSA, SHALL BE FURNISHED AS THOUGH FULLY SET FORTH IN BOTH. WORK NOT
PARTICULARLY DETAILED, MARKED OR SPECIFIED, SHALL BE IDENTICAL OR SIMILAR TO LIKE
CASES OF CONSTRUCTION THAT ARE DETAILED, MARKED OR SPECIFIED. IF CONFLICTS
OCCUR ON DRAWINGS AND/OR SPECIFICATIONS, THE MOST EXPENSIVE MATERIALS OR
METHODS WILL PREVAIL.
C. SHOULD AN ERROR APPEAR IN THE WORKING DETAILS OR SPECIFICATIONS OR IN WORK
DONE BY OTHERS AFFECTING THIS WORK, THE CONTRACTOR SHALL NOTIFY THE
ARCHITECT AT ONCE AND IN WRITING. IF THE CONTRACTOR PROCEEDS WITH THE WORK
SO AFFECTED WITHOUT HAVING GIVEN SUCH WRITTEN NOTICE AND WITHOUT RECEIVING
THE NECESSARY APPROVAL, DECISION OR INSTRUCTIONS IN WRITING FROM THE OWNER,
THEN THE CONTRACTOR SHALL HAVE NO VALID CLAIM AGAINST THE OWNER, FOR THE
COST OF SO PROCEEDING AND SHALL MAKE GOOD ANY RESULTING DAMAGE OR DEFECT.
NO VERBAL APPROVAL, DECISION, OR INSTRUCTION SHALL BE VALID OR BE THE BASIS FOR
ANY CLAIM AGAINST THE OWNER, ITS OFFICERS, EMPLOYEES OR AGENTS. THE
FOREGOING INCLUDES TYPICAL ERRORS IN THE SPECIFICATIONS OR NOTATIONAL ERRORS
IN THE WORKING DETAILS WHERE THE INTERPRETATION IS DOUBTFUL OR WHERE THE
ERROR IS SUFFICIENTLY APPARENT AS TO PLACE A REASONABLY PRUDENT CONTRACTOR
ON NOTICE THAT, SHOULD THE CONTRACTOR ELECT TO PROCEED, THEY ARE DOING SO AT
THEIR OWN RISK.
2. CONSTRUCTION SHALL CONFORM TO ALL APPLICABLE CODES AND REGULATIONS.
3. SHOP DRAWING NOTE:
A. WHEN NOT ADDRESSED BY DIVISION 1 OF THE SPECIFICATIONS, SUBMITTALS SHALL BE
ELECTRONIC PDF FORMAT.
B. THE PURPOSE OF SHOP DRAWING SUBMITTALS BY THE CONTRACTOR IS TO DEMONSTRATE
TO THE STRUCTURAL ENGINEER THAT THE CONTRACTOR UNDERSTANDS THE DESIGN
CONCEPT BY INDICATING WHICH MATERIAL THE CONTRACTOR INTENDS TO FURNISH AND
INSTALL, AND BY DETAILING THE FABRICATION AND INSTALLATION METHODS THE
CONTRACTOR INTENDS TO USE ON A STAND ALONE SET OF DOCUMENTS. DUPLICATION OF
DESIGN DOCUMENTS FOR THE PURPOSE OF SHOP DRAWINGS IS NOT ACCEPTABLE.
C. PRIOR TO FABRICATION, SHOP DRAWINGS SHALL BE SUBMITTED FOR REVIEW BY THE
STRUCTURAL ENGINEER. SHOP DRAWING SUBMITTALS SHALL INCLUDE, BUT ARE NOT
NECESSARILY LIMITED TO, STRUCTURAL STEEL, REINFORCING STEEL, & GLUE-LAMINATED
BEAMS.
D. PRIOR TO SUBMISSION THE CONTRACTOR SHALL REVIEW ALL SUBMITTALS FOR
CONFORMANCE WITH THE CONTRACT DOCUMENTS AND SHALL STAMP SUBMITTALS AS
BEING "REVIEWED FOR CONFORMANCE".
E. SHOP DRAWING SUBMITTALS PROCESSED BY THE STRUCTURAL ENGINEER ARE NOT
CHANGE ORDERS.
F. ANY DETAIL ON THE SHOP DRAWINGS THAT DEVIATES FROM THE CONTRACT DOCUMENTS
SHALL CLEARLY BE MARKED WITH THE NOTE "THIS IS A CHANGE".
G. SHOP DRAWINGS OR CALCULATIONS SUBMITTED FOR REVIEW THAT REQUIRE
RESUBMITTAL FOR RE-REVIEW SHALL BE BILLED HOURLY FOR SUCH TIME TO THE GENERAL
CONTRACTOR. RE-REVIEW WILL NOT PROCEED WITHOUT WRITTEN APPROVAL FROM THE
GENERAL CONTRACTOR FOR ADDITIONAL ENGINEERING REVIEW SERVICES.
4. SAFETY NOTE:
A. IT IS THE CONTRACTORS RESPONSIBILITY TO COMPLY WITH THE PERTINENT SECTIONS, AS
THEY APPLY TO THIS PROJECT, OF THE "CONSTRUCTION SAFETY ORDERS" ISSUED BY THE
STATE OF CALIFORNIA LATEST EDITION, AND ALL OSHA REQUIREMENTS.
B. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ADEQUATE DESIGN AND CONSTRUCTION
OF ALL FORMS AND SHORING REQUIRED. SHORING INDICATIONS (LOCATION, DIRECTION,
DURATION, ETC.) ARE ONLY SHOWN ON THE STRUCTURAL DWGS WHEN REQUIRED TO
IMPLEMENT THE DESIGN INTENT OF THE FINAL WORK PRODUCT. DETERMINATION
WHETHER SHORING IS REQUIRED FOR TEMPORARY OR INTERMEDIATE CONDITIONS
DURING CONSTRUCTION IS WHOLLY THE RESPONSIBILITY OF THE CONTRACTOR.
C. THE OWNER AND THE STRUCTURAL ENGINEER DO NOT ACCEPT ANY RESPONSIBILITY FOR
THE CONTRACTOR'S FAILURE TO COMPLY WITH THESE REQUIREMENTS.
5. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT AND STRUCTURAL ENGINEER WHERE A
CONFLICT OR DISCREPANCY OCCURS BETWEEN THE STRUCTURAL DRAWINGS AND ANY
OTHER PORTION OF THE CONTRACT DOCUMENTS OR EXISTING FIELD CONDITIONS. SUCH
NOTIFICATION SHALL BE GIVEN IN DUE TIME SO AS NOT TO AFFECT THE CONSTRUCTION
SCHEDULE. IN CASE OF A CONFLICT BETWEEN STRUCTURAL DRAWINGS AND SPECIFICATIONS
THE MORE RESTRICTIVE CONDITION SHALL TAKE PRECEDENCE UNLESS WRITTEN APPROVAL
HAS BEEN GIVEN FOR THE LEAST RESTRICTIVE. CONTRACTOR SHALL VERIFY ALL DIMENSIONS
WITH ARCHITECTURAL PRIOR TO COMMENCING ANY WORK.
6. WHEN CONSTRUCTION ATTACHES TO OR IS WITHIN AN EXISTING BUILDING, A COMPLETE SET OF DRAWINGS OF THE EXISTING BUILDING SHALL BE KEPT ON THE JOB SITE. CONTRACTOR TO
OBTAIN THESE DRAWINGS FROM THE OWNER (IF THEY ARE AVAILABLE).
7. CONTRACTOR SHALL PROVIDE AN ALLOWANCE EQUAL TO 2% OF THE BID FOR STRUCTURAL
STEEL, MISC. IRON AND REINFORCING STEEL TO BE USED AT THE DISCRETION OF THE
STRUCTURAL ENGINEER. UNUSED AMOUNT TO REVERT TO THE OWNER UPON COMPLETION
OF THE JOB.
8. ANY SUBSTITUTIONS FOR STRUCTURAL MEMBERS, HARDWARE OR DETAILS SHALL BE
REVIEWED BY THE ARCHITECT AND STRUCTURAL ENGINEER. SUCH REVIEW WILL BE BILLED
ON A TIME AND MATERIALS BASIS TO THE GENERAL CONTRACTOR WITH NO GUARANTEE THAT
THE SUBSTITUTION WILL BE ALLOWED.
9. DO NOT SCALE DRAWINGS. CONTACT THE ARCHITECT OR STRUCTURAL ENGINEER FOR ANY
DIMENSIONS NOT SHOWN.
10. THESE DRAWINGS ARE NOT COMPLETE UNTIL REVIEWED AND ACCEPTED BY LOCAL BUILDING
OFFICIALS AND THE OWNER AND SIGNED BY THE STRUCTURAL ENGINEER.
CMU SPLICE & DEVELOPMENT LENGTHS (f'm = 2000 PSI)
BAR
SIZE
fy
(KSI)
6" CMU
CENTER
60#3
60#4
#5
#6
#7
EF
8" CMU 10" CMU 12" CMU
12" 12"
21"
33"
12"
22"
37"
54"
12"
15"
24"
48"
63"
14"
24"
45"
12"
12"
19"
36"
50"
13"
22"
35"
CONCRETE MASONRY UNITS (CMU)
410SN001
1. ALL MASONRY SHALL BE MANUFACTURED AND PLACED IN ACCORDANCE WITH TMS 402,
"BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES", AND TMS 602 "SPECIFICATION
FOR MASONRY STRUCTURES".
2. MASONRY UNITS AND COMPONENTS THAT ARE DAMAGED ARE NOT TO BE INSTALLED IN THIS
PROJECT. REINFORCEMENTS AND ACCESSORIES ARE NOT TO BE STORED ON THE GROUND
AND ARE TO BE PROTECTED FROM PERMANENT DISTORTIONS.
3. WHEN THE AMBIENT AIR TEMPERATURE IS BELOW 40°F, THE COLD WEATHER PROCEDURES
FROM TMS 602, ARTICLE 1.8C ARE TO BE IMPLEMENTED. WHEN THE AMBIENT AIR
TEMPERATURE IS ABOVE 90°F, THE HOT WEATHER PROCEDURES FROM TMS 602, ARTICLE 1.8D
ARE TO BE IMPLEMENTED.
4. CONCRETE BLOCK UNITS SHALL CONFORM TO ASTM C90 . f'm = 2000 PSI. f'm SHALL BE VERIFIED IN ACCORDANCE WITH TMS 602, ARTICLE 1.4 B.2. CONCRETE BLOCK UNITS SHALL BE
MEDIUM WEIGHT. ALL MASONRY CONSTRUCTION IS TO BE GROUTED SOLID.
5. MORTAR SHALL BE TYPE S PER ASTM C270.
6. GROUT SHALL CONFORM TO ASTM C476. THE CONTRACTOR IS TO DETERMINE THE PROPER
APPLICATION OF FINE GROUT OR COARSE GROUT BASED ON THE GROUT POUR HEIGHT USED
AND THE CLEAR GROUT SPACE WIDTH (FOR MULTI-WYTHE CONSTRUCTION) OR CLEAR GROUT
SPACE DIMENSIONS IN ACCORDANCE WITH TMS 402 TABLE 3.2.1. GROUT SHALL BE
PROPORTIONED TO ATTAIN A 28 DAY COMPRESSIVE STRENGTH EQUAL TO THE SPECIFIED f'm
VALUE NOTED ABOVE. NOT MORE THAN 5% OF THE PEA GRAVEL SHALL PASS THE NO. 8 SIEVE
AND 100% SHALL PASS THE 3/8" SIEVE. WHEN REQUIRED, GROUT STRENGTH SHALL BE
VERIFIED IN ACCORDANCE WITH ASTM C1019. GROUT MIX SHALL HAVE APPROXIMATELY 1 LB
OF SIKAGROUT AID, OR APPROVED EQUAL, PER 100 LBS OF CEMENTITIOUSMATERIAL.
7. REINFORCING STEEL SHALL CONFORM TO ASTM A615 GRADE 60 UNO. REINFORCING STEEL TO
BE WELDED SHALL CONFORM TO ASTM A706 GRADE 60. CONTRACTOR SHALL SUBMIT REBAR
MILL CERTIFICATES.
8. VERTICAL REINFORCING SHALL CONSIST OF #5 BARS AT 8" ON CENTER, LOCATED AT CENTER
OF MASONRY WALL, UNO. LOCATE BARS AT ALL CORNERS, WALL ENDS, INTERSECTIONS,
JAMBS AND AT EACH SIDE OF A WALL JOINT. LOCATE BARS OR ADD ADDITIONAL BARS
DIRECTLY UNDER FRAMING MEMBERS SUCH AS BEAMS, JOISTS, GIRDERS, AND TRUSSES
WHERE CENTER TO CENTER SPACING OF FRAMING MEMBERS EXCEED 48"CC. DOWELS WITH
STANDARD 90° HOOKS INTO THE FOUNDATION TO WITHIN 3" CLR OF BOTTOM OF FOUNDATION
SHALL MATCH AND LAP VERTICAL REINFORCING PER TABLE BELOW, TYPICAL, UNLESS NOTED
OTHERWISE.
9. INTERMEDIATE HORIZONTAL REINFORCING SHALL CONSIST OF #5 BARS AT 24" ON CENTER, LOCATED AT THE CENTER OF THE MASONRY WALL, UNO. ASSEMBLIES, SUCH AS ROOFS, FLOORS, AND STAIRS. ALSO, LOCATE ONE #5 HORIZONTAL BAR AT TOPS OF PARAPETS, TOPS
OF FREE-STANDING WALLS, AT THE BOTTOM OF ALL WALLS, AND ALIGNED WITH THE SLAB-ON-
GRADE. PLACE A #5 BAR AT EACH FACE OF THE MASONRY WALL ABOVE AND BELOW ALL WALL
OPENINGS, UNO. EXTEND THESE BARS A MINIMUM OF A LAP LENGTH PAST THE EDGE OF THE
OPENING. WHERE EXTENSION CAN NOT BE ACHIEVED, BEND BARS UP OR DOWN FOR A
DISTANCE EQUAL TO THE SPECIFIED LAP LENGTH.
10. PLACE ALL HORIZONTAL BARS IN BOND BEAM UNITS. WHEN 2 BARS ARE USED, STAGGER LAPS
MINIMUM OF 5'-0".
11. MINIMUM REBAR CLEARANCE TO FACE SHELL IS ONE BAR DIAMETER OR 1/2", WHICHEVER IS
GREATER. WHERE WALLS ARE EXPOSED TO EARTH OR WEATHER, A MINIMUM COVER FOR THE
REINFORCING BARS OF 2" SHALL BE MAINTAINED.
12. BEFORE BLOCK IS PLACED ON CONCRETE, THOROUGHLY CLEAN CONCRETE OF ALL LAITANCE
AND ALL LOOSE MATERIAL. ROUGHEN AS IN A CONCRETE CONSTRUCTION JOINT.
13. CONCRETE BLOCK MASONRY SHALL BE BUILT TO PRESERVE THE UNOBSTRUCTED VERTICAL
CONTINUITY OF THE CELLS. ALL HEAD AND END JOINTS SHALL BE SOLIDLY FILLED WITH
MORTAR FOR A DISTANCE IN FROM THE FACE OF THE WALL OR UNIT NOT LESS THAN THE
THICKNESS OF THE LONGITUDINAL FACE SHELLS. BOND SHALL BE PROVIDED BY LAPPING
SUCCESSIVE COURSES OR BY EQUIVALENT MECHANICAL ANCHORAGE.
14. GROUT PLACEMENT SHALL CONFORM TO TMS 602 SECTION 3.5.
15. CLEAN OUT OPENINGS SHALL BE PROVIDED AT THE BOTTOMS OF ALL CELLSTO BE FILLED AT
EACH LIFT OR POUR OF GROUT WHERE SUCH LIFT OR POUR OF GROUT IS IN EXCESS OF 4'-0" IN HEIGHT OR 5'-4" FOR 10" NOMINAL OR LARGER, IN ACCORDANCE WITH CBC SECTION 2104.2.4.
ANY OVERHANGING MORTAR OR OTHER OBSTRUCTION GREATER THAN 1/4" SHALL BE
REMOVED FROM INSIDE OF SUCH CELLS. THE CLEAN OUTS SHALL BE SEALED AFTER
INSPECTION AND BEFORE GROUTING. MECHANICALLY VIBRATE ALL GROUT POURS.
16. REINFORCEMENT IS TO BE SUPPORTED IN PLACE TO PREVENT DISPLACEMENT CAUSED BY
PLACEMENT OF GROUT AND MORTAR OR BY CONSTRUCTION LOADS.
17. THOROUGHLY CLEAN ALL CELLS AND BOND BEAMS OF MORTAR BEFORE GROUTING.
18. ALL CELLS SHALL BE FILLED SOLIDLY WITH GROUT. ALL GROUTING SHALL BE DONE UNDER
THE OBSERVATION OF A QUALIFIED INSPECTOR. REFER TO SPECIAL STRUCTURAL INSPECTION
SECTION OF THESE NOTES FOR FREQUENCY OF GROUTING INSPECTION.
19. WHEN GROUTING IS STOPPED FOR ONE HOUR OR LONGER, HORIZONTAL CONSTRUCTION
JOINTS, OR KEYS, SHALL BE FORMED BY STOPPING THE POUR OF GROUT 1-1/2" BELOW THE
TOP OF THE UPPERMOST UNIT.
20. ALL EMBEDDED ITEMS (BOLTS, STRAPS, ETC.) SHALL BE SECURED IN PLACE PRIOR TO
GROUTING. CUT A HOLE IN THE FACE SHELL TO ATTAIN A MINIMUM OF 1/2" GROUT ALL AROUND
EMBEDDED ITEMS AT THE FACE SHELL. WITHIN THE CELL OF THE UNIT, PROVIDE A MINIMUM
OF 8" OF GROUT AROUND EMBEDDED ITEMS. AT HORIZONTAL ANCHOR INSTALLATIONS,
MAINTAIN A MINIMUM CLEAR DISTANCE OF 1/2" BETWEEN END OF ANCHOR AND FACE SHELL OF
UNIT.
21. SINGLE CONDUITS (3/4" MAX) MAY BE PLACED IN VERTICAL CELLS NOT CONTAINING VERTICAL.
REBAR. NO HORIZONTAL CONDUITS ALLOWED IN WALL CONSTRUCTION.
22. ANCHOR BOLTS CAST IN MASONRY SHALL BE HEADED BOLTS WITH CUT THREADS
CONFORMING TO ASTM F1554 GRADE 36, UNO. BENT BAR ANCHOR BOLTS ARE NOT
PERMITTED.
23. USE OPEN END BLOCK FOR ALL CONSTRUCTION NOT LAID IN RUNNING BOND.
24. ALL REBAR SHALL BE LAP SPLICED AND DEVELOPED AS FOLLOWS (UNO). WHERE EPOXY
COATED REBAR IS USED, MULTIPLY LAP LENGTHS BY 1.5. BARS LARGER THAN #8 ARE TO BE
LAPPED WITH MECHANICAL SPLICES THAT DEVELOP AT LEAST 125 PERCENT OF THE YIELD
STRENGTH OF THE BAR.
CENTER EF CENTER EF CENTER EF
12"
19"
36"
49"
POST-INSTALLED ANCHORS
305SN001
1. FOR CONCRETE CONSTRUCTION, POST-INSTALLED ANCHORS SHALL BE ONE OF THE
FOLLOWING:
A. ADHESIVE ANCHORS FOR THRD ROD & REBAR:
a. HILTI HIT-HY 200 PER ESR-3187
b. HILTI HIT-RE500 V3 PER ESR-3814
c. SIMPSON SET-XP PER ESR-2508
d. SIMPSON SET-3G PER ESR-4057
e. DEWALT/PURE ESR-3298
B. EXPANSION ANCHORS:
a. HILTI KB-TZ2 PER ESR-4266
b. SIMPSON STRONG BOLT 2 PER ESR-3037
c. DEWALT/POWER-STUD+ SD2 ESR-2502
C. SCREW ANCHORS:
a. HILTI KWIK HUS-EZ (KH-EZ) PER ESR-3027
b. SIMPSON TITEN HD PER ESR-2713
c. DEWALT/SCREWBOLT+ PER ESR-3889
2. FOR GROUT-FILLED MASONRY CONSTRUCTION, POST-INSTALLED ANCHORS SHALL BE ONE OF
THE FOLLOWING:
A. ADHESIVE ANCHORS FOR THRD ROD & REBAR:
a. HILTI HIT-HY 270 PER ESR-4143
b. SIMPSON SET-XP IAPMO UES ER-265
c. DEWALT/AC 100+ GOLD ESR-3200
B. EXPANSION ANCHORS:
a. HILTI KB-TZ2 PER ESR-4561
b. SIMPSON WEDGE-ALL PER ESR-1396
c. DEWALT/POWER-STUD+ SD1 ESR-2966
C. SCREW ANCHORS:
a. HILTI KWIK HUS-EZ (KH-EZ) PER ESR-3056
b. SIMPSON TITEN HD PER ESR-1056
c. DEWALT/SCREWBOLT+ PER ESR-4042
3. FOR UNREINFORCED MASONRY CONSTRUCTION, ADHESIVE ANCHORS SHALL BE ONE OF THE
FOLLOWING:
a. HILTI HY-270 PER ESR-4144
b. DEWALT AC100+ GOLD PER ESR-4105
4. PLASTIC MESH SCREEN TUBES SHALL BE PROVIDED AND EXISTING WALL THICKNESS AND
MORTAR SHEAR STRENGTH SHALL MEET THE REQUIREMENTS OF THE EVALUATION REPORT.
5. ANCHOR TYPE, SIZE & EMBEDMENT SHALL BE AS INDICATED IN DRAWINGS. POST-INSTALLED
ANCHORS FOR REPAIR SHALL BE EVALUATED ON A CASE BY CASE BASIS. NOTIFY STRUCTURAL
ENGINEER FOR REPAIRS.
6. ALL EMBEDMENT DEPTHS CALLED OUT IN DRAWINGS REFER TO EFFECTIVE EMBEDMENT
UNLESS OTHERWISE NOTED. SEE DIAGRAM BELOW AND ICC REPORTS.
7. ANCHORS SHALL BE INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS GIVEN IN THE
EVALUATION REPORT. PROVIDE MINIMUM EMBEDMENT PROVIDED IN ICC ESR REPORT UNLESS
NOTED OTHERWISE.
8. PROVIDE SPECIAL INSPECTION AS INDICATED IN THE STATEMENT OF STRUCTURAL SPECIAL
INSPECTIONS AND TESTING AND THE EVALUATION REPORT.
9. WHEN INSTALLING POST-INSTALLED ANCHORS IN EXISTING CONCRETE OR MASONRY, USE
CARE AND CAUTION TO AVOID CUTTING OR DAMAGING EXISTING REINFORCING BARS. DO NOT
INSTALL ANCHORS WITHIN 1 1/2" OF CMU HEAD JOINTS. DO NOT INSTALL ANCHORS IN
PRESTRESSED CONCRETE ELEMENTS.
10. ANCHORS INSTALLED FROM THE BOTTOM INTO METAL DECK WITH CONCRETE SHALL BE
INSTALLED IN THE CENTER OF THE LOW FLUTE OF THE DECKING UNLESS NOTED OTHERWISE
IN EVALUATION REPORT. THE DECKING SHALL HAVE A MINIMUM THICKNESS OF 20 GAUGE.
THE MINIMUM THICKNESS OF THE CONCRETE ABOVE THE HIGH FLUTE OF THE METAL DECK
SHALL BE AS INDICATED IN THE EVALUATION REPORT. SEE EVALUATION REPORT FOR
ADDITIONAL REQUIREMENTS, INCLUDING MINIMUM DIMENSIONS FOR FLUTE WIDTH AND DEPTH.
11. THE CONCRETE SHALL HAVE ATTAINED ITS MINIMUM DESIGN STRENGTH PRIOR TO
INSTALLATION OF THE ANCHORS.
12. ADHESIVE ANCHORS SHALL BE INSTALLED IN CONCRETE HAVING A MINIMUM AGE OF 21 DAYS
AT THE TIME OF ANCHOR INSTALLATION PER ACI 318, CHAPTER 17.
13. INSTALLER CERTIFICATION AND INSPECTION IS REQUIRED FOR HORIZONTAL AND UPWARDLY
INCLINED ADHESIVE ANCHORS SUBJECTED TO SUSTAINED TENSION LOADING IN ACCORDANCE
WITH ACI 318, CHAPTER 17.
14. IF TEMPERATURE OF BASE MATERIAL AT TIME OF ADHESIVE ANCHOR INSTALLATION IS 45
DEGREES FARENHEIT OR LOWER, AN "ACRYLIC" OR COLD WEATHER ADHESIVE IS REQUIRED.
USE DEWALT AC200+, SIMPSON AT-XP, OR HILTI HIT-HY200 WHEN THIS OCCURS.
15. THE INSPECTION OF THE ANCHORS SHALL BE DONE BY A QUALIFIED INSPECTION AGENCY AND
A REPORT OF THE INSPECTION RESULTS SHALL BE SUBMITTED TO THE GOVERNING AGENCY
AND ARCHITECT/STRUCTURAL ENGINEER.
INSTALLED ANCHOR DIAGRAMS
E M
B E D
E F F E C T
IV
E
E M
B E D
N O
M
IN
A L
P E R R
E P O
R T
H O
L E D
E P T H
E M
B E D
E F F E C T
IV
E
E M
B E D
N O
M
IN
A L
P E R R
E P O
R T
H O
L E D
E P T H
EXPANSION ANCHOR SCREW ANCHOR
(A) -
AB -
ABV -
ADDL -
AHU -
ALT -
APPROX -
ARCH -
(B) -
BLDG -
BLKG -
BLW -
BM -
B.O. -
BOF -
BOTT -
BRCG -
BRG -
BTWN -
BYND -
CC -
CG -
CJ -
CJP -
CL -
CLG -
CLR -
CMU -
COL -
CONC -
CONN -
CONT -
CONTR -
COORD -
CSK -
DBL -
DF -
DIAG -
DL -
DWG -
(E) -
EA -
EF -
EJ -
ELEV -
EN -
EOS -
EQ -
EW -
FB -
FC -
FDN -
FF -
FRMG -
FRT -
FS -
FTG -
GA -
GALV -
GLB -
GR -
GYP -
HD -
HDR -
HGR -
HK -
HORIZ -
HSB -
HSS -
HT -
OCCURS ABOVE
ANCHOR BOLT
ABOVE
ADDITIONAL
AIR HANDLING UNIT
ALTERNATE
APPROXIMATE
ARCHITECTURAL
OCCURS BELOW
BUILDING
BLOCKING
BELOW
BEAM
BOTTOM OF
BOTTOM OF FOOTING
BOTTOM
BRACING
BEARING
BETWEEN
BEYOND
CENTER TO CENTER
CENTER OF GRAVITY
CONSTRUCTION JOINT
COMPLETE JOINT PENETRATION
CENTERLINE
CEILING
CLEAR
CONCRETE MASONRY UNIT
COLUMN
CONCRETE
CONNECTION
CONTINUOUS
CONTRACTOR
COORDINATE
COUNTERSINK
DOUBLE
DOUGLAS FIR
DIAGONAL
DEAD LOAD
DRAWING
EXISTING
EACH
EACH FACE OR EDGE FASTENER
EXPANSION JOINT
ELEVATION
EDGE NAILING
EDGE OF SLAB
EQUAL
EACH WAY
FACE OF BLOCK/BRICK OR FLAT BAR
FACE OF CONCRETE
FOUNDATION
FINISH FLOOR
FRAMING
FIRE RETARDANT TREATED
FACE OF STUD OR FAR SIDE
FOOTING
GAUGE OR GAGE
GALVANIZED
GLUED LAMINATED BEAM
GRADE
GYPSUM
HOLDOWN
HEADER
HANGER
HOOK
HORIZONTAL
HIGH STRENGTH BOLT
HOLLOW STRUCTURAL SECTION
HEIGHT
JH -
LL -
LLH -
LLV -
LONGIT -
LS -
LW -
MECH -
MFR -
MI -
MTL -
(N) -
NIC -
NS -
NTS -
NW -
O/ -
OH -
OPNG -
OSB -
PC -
PERP -
PJP -
PL -
PT -
PW -
REINF -
REQD -
RWD -
SC -
SCH -
SEOR -
SHTG -
SIM -
SJ -
SMS -
SOG -
SP -
SPCG -
SQ -
STD -
STFNR -
STGRD -
STL -
STRUCT -
SW -
T&B - T&G -
THRD -
TN -
T.O. -
TOC -
TOF -
TOS -
TOW -
TRANS -
TYP -
UNO -
VERT -
VIF -
WF -
WHS -
WP -
WS -
WWF -
XS -
XXS -
Ø -
JOIST HANGER
LIVE LOAD
LONG LEG HORIZONTAL
LONG LEG VERTICAL
LONGITUDINAL
LAG SCREW
LIGHTWEIGHT
MECHANICAL
MANUFACTURER
MALLEABLE IRON
MARK
METAL
NEW
NOT IN CONTRACT
NEAR SIDE
NOT TO SCALE
NORMAL WEIGHT
OVER
OPPOSITE HAND
OPENING
ORIENTED STRAND BOARD
PIECE
PERPENDICULAR
PARTIAL JOINT PENETRATION
PLATE
PRESSURE TREATED
PUDDLE WELD
REINFORCING OR REINFORCEMENT
REQUIRED
REDWOOD
SLIP CRITICAL
SCHEDULE
STRUCTURAL ENGINEER OF RECORD
SHEATHING
SIMILAR
SLAB CONTROL JOINT
SHEET METAL SCREW
SLAB-ON-GRADE
STRUCTURAL PANEL
SPACING
SQUARE
STANDARD
STIFFENER
STAGGERED
STEEL
STRUCTURAL
SHEAR WALL
TOP & BOTTOM
TONGUE & GROOVE
THREADED
TOE NAIL
TOP OF
TOP OF CONCRETE (SLAB UNO)
TOP OF FOOTING OR TOP OF FRAMING
TOP OF STEEL
TOP OF WALL
TRANSVERSE
TYPICAL
UNLESS NOTED OTHERWISE
VERTICAL
VERIFY IN FIELD
WIDE FLANGE
WELDED HEADED STUD
WORK POINT
WOOD SCREW
WELDED WIRE FABRIC
EXTRA STRONG
DOUBLE EXTRA STRONG
ROUND OR DIAMETER
ABBREVIATIONS
100SN003
CONCRETE
300SN001
1. CONCRETE SHALL ATTAIN 28 DAY COMPRESSIVE STRENGTH AS REQUIRED IN NOTE #28.
MAXIMUM SLUMP SHALL NOT EXCEED 4 INCHES.
2. CONCRETE MIX DESIGNS SHALL BE PREPARED ACCORDING TO ACI 318-14 CHAPTER 26.4 AND ACI 301-10 SECTION 4, REVIEWED BY OWNER'S TESTING LABORATORY AND SUBMITTED TO THE
STRUCTURAL ENGINEER FOR REVIEW.
3. CEMENTITIOUS MATERIALS:
CEMENT SHALL CONFORM TO ASTM C-150 TYPE II OR V.
FLY ASH SHALL CONFORM TO ASTM C-618. MAX. QUANTITY OF FLY ASH SHALL BE 25% OR AS
GIVEN IN SPECS.
4. CONCRETE AGGREGATES SHALL CONFORM TO ASTM C-33 FOR NORMAL WEIGHT CONCRETE
AND ASTM C-330 FOR LIGHTWEIGHT CONCRETE.
5. NON-SHRINK GROUT OR DRYPACK SHALL CONSIST OF A PREMIXED NONMETALLIC FORMULA.
6. REINFORCING STEEL SHALL CONFORM TO ASTM A-615 GRADE 60 UNO. REINFORCING STEEL
TO BE WELDED SHALL CONFORM TO ASTM A-706 GRADE 60. CONTRACTOR SHALL SUBMIT
REBAR MILL CERTIFICATES. REINFORCING STEEL IN SPECIAL REINFORCED SHEAR WALLS OR
MOMENT FRAMES, EXCEPT TIES AND HOOPS, SHALL CONFORM TO ASTM A-706.
7. ALL PREHEATING AND WELDING OF REINFORCING BARS SHALL BE DONE IN ACCORDANCE WITH
AWS D1.4 LATEST EDITION AND SHALL BE CONTINUOUSLY INSPECTED BY A QUALIFIED
LABORATORY. CONTRACTOR SHALL FURNISH WPS FOR ALL REBAR WELDING TO THE
LABORATORY.
8. REINFORCING STEEL SHALL BE FABRICATED ACCORDING TO "MANUAL OF STANDARD
PRACTICE FOR REINFORCED CONCRETE CONSTRUCTION".
9. WIRE FABRIC SHALL CONFORM TO ASTM A1064.
10. DIMENSIONS SHOWN FOR LOCATION OF REINFORCING ARE TO THE FACE OF BARS LISTED AND
DENOTE CLEAR COVERAGE. NON-PRESTRESSED, CAST-IN-PLACE CONCRETE COVERAGE
SHALL BE AS FOLLOWS, UNO:
CONCRETE DEPOSITED DIRECTLY AGAINST GROUND (EXCEPT SLABS)--------- 3"
CONCRETE EXPOSED TO GROUND OR WEATHER BUT PLACED IN FORMS:
#5 AND SMALLER-------------------------------------------------------------------------- 1-1/2" #6 AND LARGER--------------------------------------------------------------------------- 2"
BEAMS & COLUMNS (TIES)------------------------------------------------------------------------- 1-1/2" BEAMS & COLUMNS (MAIN REINFORCING)-------------------------------------------------- 2" CAST-IN-PLACE WALLS (EXTERIOR FACE & SOIL SIDE)-------------------------------- SEE ABOVE CAST-IN-PLACE WALLS (INTERIOR FACE-#11 & SMALLER)--------------------------- 3/4" TILT-UP WALLS--------------------------------------------------------------------------------------- SEE DETAILS SLABS (ON FORMS)--------------------------------------------------------------------------------- 3/4" SLABS (ON GROUND)------------------------------------------------------------------------------- 2" CLEAR FROM
TOP
11. SPLICES IN CONTINUOUS REINFORCEMENT SHALL BE LAPPED UNO, SEE SCHEDULE THIS
SHEET. SPLICES IN ADJACENT BARS SHALL BE GREATER THAN 5'-0" APART. SPLICE
CONTINUOUS BARS IN SOIL-BEARING GRADE BEAMS, STRUCTURAL SLABS ON GRADE AND MAT
FOUNDATIONS AS FOLLOWS UNO: TOP BARS AT CENTERLINE OF SUPPORT; BOTTOM BARS AT
MID-SPAN. SPLICE CONTINUOUS BARS IN ELEVATED SLABS AND BEAMS, ETC. AS FOLLOWS
UNO: TOP BARS AT MID-SPAN; BOTTOM BARS AT CENTERLINE OF SUPPORT. ALL BARS SIZE #14
AND LARGER SHALL BE CONTINUOUS FOR FULL LENGTH SHOWN OR SPLICED WITH
MECHANICAL COUPLERS AS NOTED IN DETAILS. SPLICES IN WWF SHALL BE 1-1/2 MESHES WIDE.
12. THE MINIMUM CLEAR SPACING BETWEEN PARALLEL BARS IN A LAYER SHALL NOT BE LESS
THAN THE LARGER OF BAR DIAMETER, 1", OR 33% GREATER THAN THE MAXIMUM AGGREGATE
SIZE (NOMINAL), WHICHEVER IS GREATEST. THIS REQUIREMENT ALSO APPLIES TO THE CLEAR
SPACING BETWEEN DIFFERENT LAYERS OF PARALLEL BARS AND TO THE CLEAR DISTANCE
BETWEEN A CONTACT LAP SPLICE AND ADJACENT SPLICES OR BARS.
13. ALL HOOKS SHALL BE STANDARD HOOKS UNLESS OTHERWISE SHOWN OR NOTED. AT WALLS,
PROVIDE HOOKS AT ENDS OF ALL REINFORCING AT ENDS, CORNERS AND INTERSECTIONS,
UNO.
14. CONSTRUCTION JOINTS SHALL BE MADE ROUGH AND ALL LAITANCE REMOVED FROM THE
SURFACE. CONCRETE MAY BE ROUGHENED BY CHIPPING THE ENTIRE SURFACE, SAND
BLASTING, OR RAKING THE SURFACE TO PROVIDE 1/4" DEEP DEFORMATIONS.
15. REMOVE ALL DEBRIS FROM FORMS BEFORE CASTING ANY CONCRETE.
16. REINFORCING, DOWELS, BOLTS, ANCHORS, SLEEVES, ETC. TO BE EMBEDDED IN CONCRETE
SHALL BE SECURELY POSITIONED BEFORE PLACING CONCRETE.
17. ANCHOR BOLTS (AB'S) CAST IN CONCRETE FOR WALL SILL AND LEDGER APPLICATIONS SHALL
BE HEADED BOLTS WITH CUT THREADS CONFORMING TO ASTM F1554, UNO. REFER TO "WOOD"
NOTES FOR ADDITIONAL REQUIREMENTS FOR BOLTS IN CONTACT WITH PRESSURE TREATED
OR FIRE RETARDANT MATERIAL. REFER TO 'STRUCTURAL STEEL' NOTE FOR REQUIREMENTS
FOR ANCHOR RODS (AR'S) CAST IN CONCRETE FOR COLUMN BASE PLATE AND STEEL EMBED
APPLICATIONS.
18. WALLS SHALL BE CAST IN HORIZONTAL LAYERS OF 2'-0" MAXIMUM DEPTH.
19. CONCRETE IN WALLS, PIERS OR COLUMNS SHALL SET AT LEAST 2 HOURS BEFORE PLACING
CONCRETE IN BEAMS, SPANDRELS, OR SLABS SUPPORTED THEREON.
20. HORIZONTAL WALL BARS IN MULTI-CURTAIN CAST IN PLACE WALLS SHALL BE STAGGERED.
21. DOWEL ALL VERTICAL REINFORCING IN WALLS AND COLUMNS FROM FOUNDATION WITH SAME
SIZE BAR.
22. CONSOLIDATE CONCRETE PLACED IN FORMS BY MECHANICAL VIBRATING EQUIPMENT
SUPPLEMENTED BY HAND-SPADING, RODDING OR TAMPING. USE EQUIPMENT AND
PROCEDURES FOR CONSOLIDATION OF CONCRETE IN ACCORDANCE WITH THE
RECOMMENDED PRACTICES OF ACI 309 TO SUIT THE TYPE OF CONCRETE AND PROJECT
CONDITIONS. CONCRETE SHALL NOT BE DROPPED THROUGH REINFORCING STEEL (AS IN
WALLS) SO AS TO CAUSE SEGREGATION OF AGGREGATES. IN SUCH CASES HOPPERS AND
CHUTES OR TRUNKS OF VARIABLE LENGTHS SHALL BE USED SO THAT THE FREE UNCONFINED
FALL OF CONCRETE SHALL NOT EXCEED 6 FEET.
23. NO WOOD SPREADERS ALLOWED. NO WOOD STAKES ALLOWED IN AREAS TO BE CONCRETED.
24. ADDITIONAL REINFORCING IN PRECAST OR TILT-UP PANELS REQUIRED FOR LIFTING STRESSES
SHALL BE SUPPLIED BY CONTRACTOR.
25. PROVIDE #4x4'-0" DIAGONAL REINFORCING AT EACH REINFORCING LAYER OF SLAB AT ALL RE-
ENTRANT CORNERS TYPICAL UNO. THIS APPLIES TO SLAB ON GRADE, CONCRETE OVER METAL
DECK, AND ELEVATED STRUCTURAL SLAB CONDITIONS.
26. ALL SAW CUTTING SHALL BE DONE AFTER INITIAL SET HAS OCCURRED TO AVOID TEARING OR
DAMAGE BY THE SAW BLADE, BUT BEFORE INITIAL SHRINKAGE HAS OCCURRED.
27. NOTIFY STRUCTURAL ENGINEER A MINIMUM OF 48 HOURS BEFORE PLACING ANY CONCRETE.
28. CONCRETE STRENGTHS & MIX PROPERTIES:
F'C @ MAX AGGR MAX W/CM*
ITEM 28 DAYS SIZE WEIGHT RATIO
A. FOUNDATIONS, ELEVATOR PITS, 4000 PSI 1-1/2" NW 0.58
TIE BEAMS
B. SLAB ON GRADE 4000 PSI 1" NW 0.45
C. COLUMNS, BEAMS, WALLS, 4000 PSI 1" NW 0.50
ELEVATED SLABS, PILE CAPS
D. NW CONC FILL OVER DECK 3500 PSI 3/4" NW 0.52
E. LW CONC FILL OVER DECK 3000 PSI 3/4" LW 0.52
SITE & MISCELLANEOUS - SEE CIVIL OR ARCH DRAWINGS
* W/CM = WATER : CEMENTITIOUS MATERIAL RATIO
DESIGN CRITERIA
100SN002-19
1. CODES AND STANDARDS
2022 CALIFORNIA BUILDING CODE (CBC)
ASCE 7-16
ACI 318-19
AISC 360-16, 341-16, 358-16
AISI S100-16 w/ S2-20, S240-20, S400-20
TMS 402/602-16
2018 NDS, 2021 SDPWS
SEISMIC:
SITE CLASS D
SS = 1.5 ; SDS = 1.2
S1 = 0.608 ; SD1 = N/A
IP = 1.0 TYPICAL
IP = 1.5 PER ASCE 7-16 SECT 13.1.3
RISK CATEGORY: IV
SEISMIC DESIGN CATEGORY: D
WIND:
V = 106 MPH
RISK CATEGORY: IV
EXPOSURE CATEGORY: C
GCPI = +/- 0.18
2. LATERAL LOADS
#3
B
#4 #5 #6 #7 #8 #9 #10 #11
#3 #4
#7#6 #5 #8 #9 #10 #11
ACI 318
CBC/IBC
#11#10#9 #8 #5 #6 #7
#4#3
#11#10#9 #8 #5 #6 #7#4
#3 f'c= 3000 PSI CONC f'c = 4000 PSI CONC
LAP SPLICE LENGTHS FOR GRADE 60 REINFORCING BARS IN TENSION (Lst)
300SN002
(ALL LENGTHS SHOWN ARE IN INCHES)
f'c = 3500 PSI CONC f'c = 5000 PSI CONC
DEFINITIONS:
LD = DEVELOPMENT LENGTH OF DEFORMED BARS IN TENSION
LST = TENSION LAP SPLICE LENGTH
TOP = HORIZONTAL REINFORCEMENT LOCATED SUCH THAT MORE THAN 12 INCHES OF FRESH
CONCRETE IS CAST IN THE MEMBER BELOW THE SPLICE.
NOTES:
1. SCHEDULE APPLIES TO NORMAL WEIGHT CONCRETE WITH UNCOATED, GRADE 60 REINFORCING
STEEL FOR #3 BARS AND LARGER.
2. ROUND UP TO THE NEAREST WHOLE NUMBER FOR ALL LENGTH CALCULATIONS.
3. Lst SHALL BE 12 INCHES MINIMUM.
4. WHERE EPOXY-COATED BARS ARE USED, MULTIPLY LAP LENGTHS BY 1.2, BUT WHERE EPOXY-
COATED BARS HAVE CLEAR COVER LESS THAN 3 BAR DIA. OR CLEAR SPACING LESS THAN 6 BAR
DIA., MULTIPLY LAP LENGTHS BY 1.31 FOR TOP REBAR AND 1.5 FOR OTHER REBAR.
5. WHEN LIGHTWEIGHT CONCRETE IS USED, MULTIPLY LAP LENGTHS BY 1.33.
6. WHERE CLEAR SPACING OF BARS BEING SPLICED IS LESS THAN 2 BAR DIA. OR WHERE CLEAR
COVER OF BARS BEING SPLICED IS LESS THAN 1 BAR DIA., MULTIPLY LAP LENGTHS BY 1.50, UNO.
7. WHERE CLASS A LAP SPLICE IS NOTED IN DETAIL, DIVIDE LENGTHS ABOVE BY 1.30.
8. DEVELOPMENT LENGTH OF DEFORMED BARS, Ld, SHALL BE CALCULATED BY DIVIDING THE
LENGTH ABOVE BY 1.30. Ld SHALL BE 12 INCHES MINIMUM.
9. WHEN SPLICING DIFFERENT SIZE BARS, Lst SHALL BE THE GREATER OF Ld OF THE LARGER BAR
AND Lst OF THE SMALLER BAR.
10. INDIVIDUAL BAR SPLICES WITHIN A BUNDLE SHALL NOT OVERLAP. INCREASE LAP LENGTHS BY
20 PERCENT FOR A THREE-BAR BUNDLE AND 33 PERCENT FOR A FOUR-BAR BUNDLE
11. THE LENGTHS SHOWN IN THE SCHEDULE SHALL BE INCREASED BY ALL APPLICABLE
MULTIPLIERS LISTED IN THE NOTES ABOVE.
REINF
LOCATION
SPLICE
CLASS
TOP
OTHER
B
REINF
LOCATION
SPLICE
CLASS
TOP
OTHER
B
REINF
LOCATION
SPLICE
CLASS
TOP
OTHER
B
REINF
LOCATION
SPLICE
CLASS
TOP
OTHER
STRUCTURAL STEEL
500SN001
1. FABRICATION, ERECTION AND MATERIALS SHALL CONFORM WITH THE AISC SPECIFICATION FOR
STRUCTURAL STEEL BUILDINGS, THE AISC SEISMIC PROVISIONS FOR STRUCTURAL STEEL
BUILDINGS AND THE AISC CODE OF STANDARD PRACTICE, LATEST EDITIONS ADOPTED BY THE
BUILDING CODE SPECIFIED IN THE DESIGN CRITERIA NOTES, UNO.
2. ALL HOT ROLLED STEEL SHAPES, PLATES AND BARS SHALL BE NEW STEEL CONFORMING TO ASTM
A6, UNO IN THE STRUCTURAL DRAWINGS. STRUCTURAL STEEL SHALL BE AS FOLLOWS:
A. WIDE FLANGE AND WT SHAPES: ASTM A992
B. M- AND S- SHAPES: ASTM A36
C. C- AND MC- SHAPES: ASTM A992
D. L- SHAPES: ASTM A572 GRADE 50
E. ROUND HSS: ASTM A500 GRADE C (Fy = 46 KSI) F. RECTANGULAR HSS: ASTM A500 GRADE C (Fy = 50 KSI) G. PIPE: ASTM A53, GRADE B (Fy = 35 KSI)
H. BASE PLATES UP TO 4�THICK: ASTM A572 GRADE 50
I. ALL OTHER PLATE MATERIAL: ASTM A572 GRADE 50, UNO
J. BUILT UP COLUMNS: ASTM A572 GRADE 50
K. PLATE GIRDERS: ASTM A572 GRADE 50
L. CONNECTION MATERIAL
a. COLUMN CONTINUITY PLATES AND DOUBLER PLATES: ASTM A572 GRADE 50
b. BRACED FRAME GUSSET PLATES: ASTM A572 GRADE 50
3. ALL STRUCTURAL STEEL SHALL RECEIVE A MINIMUM OF ONE SHOP COAT OF RED PRIMER PAINT.
DO NOT PAINT AREAS TO BE FIELD WELDED, FIREPROOFED, GALVANIZED, TO RECEIVE SLIP-
CRITICAL HIGH STRENGTH BOLTS, OR TO BE EMBEDDED IN CONCRETE. PROVIDE ADDITIONAL
PAINTING AS NOTED IN THE SPECIFICATIONS.
4. ALL STRUCTURAL STEEL SHALL BE ERECTED PLUMB AND TRUE TO LINE. TEMPORARY BRACING
SHALL BE INSTALLED AND SHALL BE LEFT IN PLACE UNTIL OTHER MEANS ARE PROVIDED TO
ADEQUATELY BRACE THE STRUCTURE. THE CONTRACTOR IS RESPONSIBLE FOR REVIEWING ALL
BASE PLATE AND SUPPORT CONDITIONS DURING ERECTION AND BRACING AS REQUIRED. SEE
AISC AND OSHA REQUIREMENTS.
5. GROUT BELOW BASE PLATES SHALL BE NON-METALLIC, NON-SHRINK GROUT WITH A MINIMUM
COMPRESSIVE STRENGTH OF 8,000 PSI UNO. COLUMN BASE PLATES SHALL BE PROMPTLY
GROUTED AFTER STEEL FRAME HAS BEEN PLUMBED AND PRIOR TO INSTALLATION OF METAL
DECKING.
6. STRUCTURAL STEEL BELOW GRADE SHALL HAVE 3 INCHES MINIMUM OF CONCRETE COVER.
7. STRUCTURAL BOLTS AND THREADED FASTENERS
A. BOLTED CONNECTIONS SHALL CONSIST OF UNFINISHED BOLTS CONFORMING TO ASTM F3125
GRADE A325 UNO.
B. WHERE HIGH-STRENGTH BOLTS ARE SPECIFIED, BOLTS CONFORMING TO ASTM F3125 GRADE
A325 OR GRADE A490 SHALL BE PROVIDED AS INDICATED. HIGH STRENGTH BOLTS IN SLIP-
CRITICAL AND PRETENSION JOINTS SHALL CONFORM TO THE REQUIREMENTS OF ASTM F1852
FOR TWIST-OFF TYPE TENSION CONTROL BOLT PRETENSIONING OR BE PROVIDED WITH
DIRECT TENSION INDICATOR WASHERS CONFORMING TO THE REQUIREMENTS OF ASTM F959.
C. ANCHOR RODS CAST IN CONCRETE OR MASONRY SHALL BE HEADED BOLTS WITH CUT THREAD, FULL DIAMETER BODY STYLE CONFORMING TO ASTM F1554 GRADE 36, 55 (WELDABLE PER S1
SUPPLEMENTARY REQUIREMENTS), OR GRADE 105 AS INDICATED ON DRAWINGS. IN LIEU OF
HEADED ANCHOR RODS, THREADED ROD CONFORMING TO THE ABOVE SPECIFICATIONS MAY
BE USED WITH A SINGLE NUT WELDED TO THE ROD OR DOUBLE NUTS TIGHTENED TO PREVENT
ROTATION. ANCHOR ROD PROJECTION ABOVE TOP OF FOUNDATION SHALL BE AS NOTED ON
THE DRAWINGS.
D. BOLTED CONNECTIONS SHALL HAVE WASHERS CONFORMING TO ASTM F436 UNO. WASHERS
MAY BE OMITTED AT SNUG-TIGHTENED AND SLIP-CRITICAL CONNECTIONS, EXCEPT WHERE
REQUIRED BY THE RCSC SPECIFICATION FOR STRUCTURAL JOINTS, LATEST EDITION.
E. BASE PLATES SHALL HAVE NUTS AND WASHERS AT TOP AND BOTTOM OF PLATE. WASHERS
FOR BASE PLATES SHALL BE A36 SQUARE OR CIRCULAR PLATE UNLESS ASTM F844 WASHERS
ARE PERMITTED. SEE BASE PLATE DETAILS FOR PLATE WASHER SIZE AND PERMISSIBLE
WASHER TYPE.
F. THREADED RODS SHALL CONFORM TO ASTM A36 UNLESS NOTED OTHERWISE ON THE
DRAWINGS.
G. PINS: ALL PINS IN PIN CONNECTED MEMBERS SHALL CONFORM TO ASTM A36 OR ASTM A108 AS
INDICATED ON THE DRAWINGS.
8. ADDITIONAL REQUIREMENTS FOR "SLIP-CRITICAL" BOLTED CONNECTIONS:
A. "SLIP-CRITICAL" CONNECTIONS (A325-SC DESIGN VALUES WITH SPECIAL INSPECTION) ARE
REQUIRED AT ALL MOMENT FRAME CONNECTIONS, BRACED FRAME CONNECTIONS, AT ALL
CONNECTIONS ALONG CHORD LINES AND DRAG LINES (AS NOTED ON PLANS), AND UNO, AT ALL
BOLTS IN OVERSIZED OR SLOTTED HOLES.
B. THE SPECIAL INSPECTOR MUST BE PRESENT DURING THE INSTALLATION AND TIGHTENING
OPERATION OF "SLIP-CRITICAL" CONNECTIONS.
9. PROVIDE 3/4" DIAMETER STITCH BOLTS AND RING FILLS, SPACED AT NOT MORE THAN 2'-0" ON
CENTER FOR ALL DOUBLE ANGLE MEMBERS UNO.
10. AT WOOD TO STEEL PARALLEL CONTACT, BOLT WITH 1/2" DIAMETER BOLTS AT MAXIMUM 24"CC
UNLESS NOTED OTHERWISE IN THE DRAWINGS.
11. BOLT HOLES SHALL BE AISC STANDARD HOLES UNLESS SPECIFIED OTHERWISE. USE STANDARD
AISC GAGE AND PITCH FOR BOLTS EXCEPT AS NOTED OTHERWISE.
12. WELDING SHALL BE DONE BY THE ELECTRIC ARC PROCESS IN ACCORDANCE WITH AMERICAN
WELDING SOCIETY STANDARDS, USING ONLY CERTIFIED WELDERS. ALL GROOVE WELDS SHALL
HAVE COMPLETE PENETRATION UNLESS NOTED OTHERWISE. ALL ELECTRODES FOR WELDING
SHALL COMPLY WITH AWS D1.1 AND D1.8 AS APPLICABLE, E70 SERIES MINIMUM.
13. WELD LENGTHS SPECIFIED ON PLANS ARE THE NET EFFECTIVE LENGTHS REQUIRED.
14. MINIMUM FILLET WELDS: (T = THICKNESS OF THINNER PART JOINED)
3/16" @ T < 1/2" 1/4" @ T < 3/4" 5/16" @ T > 3/4"
15. WELDING PROCEDURE SPECIFICATIONS (WPS) FOR SHOP AND FIELD PREQUALIFIED WELD JOINTS AND WELD JOINTS QUALIFIED BY TEST SHALL BE SUBMITTED FOR REVIEW BY THE STRUCTURAL
ENGINEER AND THE OWNER�S TESTING LABORATORY PRIOR TO FABRICATION. ALL WELDING
PROCEDURE ITEMS SUCH AS BASE METALS, WELDING PROCESSES, FILLER METALS AND JOINT
DETAILS THAT MEET THE REQUIREMENTS OF AWS D1.1 SECTION 3 SHALL BE CONSIDERED AS
PREQUALIFIED. ANY CHANGE OR SUBSTITUTION THAT IS BEYOND THE RANGE OR TOLERANCE OR REQUIREMENTS FOR PREQUALIFICATION SHALL BE QUALIFIED BY TEST PER AWS D1.1 SECTION 4 PART B. SUBMIT TEST REPORTS SHOWING SUCCESSFUL PASSAGE OF QUALIFICATION TESTS FOR
ALL NON-PREQUALIFIED WELDING PROCEDURE SPECIFICATIONS.
COLD-FORMED METAL FRAMING
540SN001
1. GALVANIZED SHEET STEEL SHALL CONFORM TO ASTM A653, STRUCTURAL QUALITY, WITH A
MINIMUM YIELD STRENGTH OF 33 KSI FOR 43 MILS (18 GA) AND THINNER AND ASTM A653,
STRUCTURAL QUALITY, WITH A MINIMUM YIELD STRENGTH OF 50 KSI FOR 54 MILS (16 GA) AND THICKER. HOT-ROLLED CARBON SHEET AND STRIP STEEL USED IN THE FABRICATION OF COLD- FORMED MEMBERS SHALL CONFORM TO ASTM A1011 WITH A RUST INHIBITIVE COATING. ALL CFS
MEMBERS ARE TO BE COATED IN ACCORDANCE WITH THE OPTIONS SHOWN IN PARAGRAPH 4.3
AND TABLE 1 OF ASTM C955 AND SHALL HAVE A MINIMUM COATING PROTECTION LEVEL OF CP 60.
2. METAL STUDS AND JOISTS SHALL BE OF SIZE AND THICKNESS SHOWN ON DRAWINGS WITH THE
MINIMUM EFFECTIVE SECTION PROPERTIES SHOWN IN THE TABLE(S).
3. MINIMUM THICKNESS SHOWN IN TABLE FOR THE THICKNESS SPECIFIED REPRESENTS 95% OF
DESIGN THICKNESS PER AISI S240-15
4. METAL FRAMING SHALL BE PER ICC-ES NO. 3064P OR ICC-ES 4205. CONTRACTOR SHALL BE
RESPONSIBLE FOR OBTAINING AGENCY APPROVAL FOR ANY SUBSTITUTIONS.
5. WELDING SHALL BE IN ACCORDANCE WITH AWS D1.3 "STRUCTURAL WELDING CODE-SHEET
STEEL". WELDERS SHALL BE AWS CERTIFIED. WELDING RODS: E60XX MIN (43 MIL AND THINNER), E70XX MIN (54 MIL AND THICKER).
6. SMS SHALL BE PER ONE OF THE FOLLOWING:
A. GRABBER CONSTRUCTION PRODUCTS INC PER ESR-1271
B. PRIMESOUCE BUILDING PRODUCTS PER ESR-1408
C. ITW BUILDEX PER ESR-1976
D. ITW BUILDEX PER ESR-3223
E. HILTI PER ESR-2196
F. PORTEOUS FASTENER PER ESR-3231
G. ELCO CONSTRUCTION PRODUCTS PER ESR-3294
H. SIMPSON STRONG-TIE COMPANY PER ESR-3006
7. SMS MUST BE INSTALLED WITH THE FOLLOWING MINIMUM DIMENSIONAL LIMITATIONS: WHERE
MULTIPLE FASTENERS ARE USED, SCREWS ARE TO HAVE A CENTER-TO-CENTER SPACING OF AT
LEAST 3 TIMES THE NOMINAL DIAMETER (D). SCREWS ARE TO HAVE A CENTER-OF-SCREW TO
EDGE-OF-STEEL DIMENSION OF AT LEAST 1.5 TIMES THE NOMINAL DIAMETER (D) OF THE SCREW.
8. ALL SCREWS ARE TO PROTRUDE A MINIMUM OF THREE FULL THREADS BEYOND THE
CONNECTED PARTS, UNLESS OTHERWISE NOTED. WHERE THE CONNECTED PARTS ARE
DIFFERENT THICKNESS, THE SCREW IS TO FIRST PENETRATE THE THINNER MEMBER, THEN
PENETRATE THICKER PART, MEANING, THE SCREW HEAD IS IN CONTACT WITH THE THINNER
MEMBER, UNLESS OTHERWISE NOTED.
9. TYPICAL METAL TRACK SHALL BE SAME GAUGE AS STUDS WHICH IT SUPPORTS, UNPUNCHED, WITH A FLANGE WIDTH OF 1 1/4 INCHES AND A DEPTH EQUAL TO THE NOMINAL STUD PLUS 2
TIMES THE TRACK THICKNESS PLUS THE RADIUS. NESTED TRACKS SHALL BE FABRICATED TO
FILL THE OUTSIDE OF A TYPICAL METAL TRACK. DEEP LEG TRACKS SHALL HAVE A MINIMUM
FLANGE WIDTH OF 2 INCHES. USE SLOTTED SLIP TRACKS WHERE SPECIFIED. SEE SECTIONS
AND TYPICAL METAL STUD DETAILS.
10. METAL STUDS AND JOISTS SHALL NOT HAVE PUNCH-OUTS CLOSER THAN 10" CLEAR FROM THE
END OF THE MEMBER OR AT INTERMEDIATE LATERAL BEARING POINTS OF THE MEMBER. METAL
STUDS WHICH ARE PART OF BUILT-UP HEADER SECTIONS SHALL BE UNPUNCHED FULL LENGTH.
S
STA TE OF CAL I FOR N I A
STRUCTURAL
R
EFORP
DERETSI
GE
SI N
ENGINEER
O AL
DE
PA
R
TM
EN
T
OF
CO
RRE
CT IONS AND
REHAB
IL
ITA
T
IO
N
S T
A
TE
OF CAL I FORN
I A
A rc h ite ct s, I n c.
H
IB
SE
R Y
A M
A U C
H I n d S tr ee t, S u ite
D a vi s, C
A
.7
.1 o ff ic e
.7
.4 fa x
600 Q STREET, SUITE 200
SACRAMENTO, CA 95811
916 443 0303
CALIFORNIA DEPARTMENT OF
CORRECTIONS AND REHABILITATION
ACCESS COMPLIANCE REVIEW
APPROVAL OF THIS PLAN DOES NOT
AUTHORIZE OR APPROVE ANY OMISSION OR
DEVIATION FROM THE APPLICABLE REGULATIONS.
TRACKING NUMBER:___________________
DATE:____________________________
REVIEWER:_________________________
APPROVAL
F
IN
A L
D R
A W
IN
G
S
SHEET NUMBER
ST
AT
E O
F C
AL
IF
O R
N
IA
D
EP
AR
TM
EN
T
O F
C O
R R
EC
TI
O
N S
AN
D
R
EH
AB
IL
IT
AT
IO
N
FA
C
IL
IT
Y
PL
AN
N
IN
G , C
O N
ST
R
U C
TI
O N A
N D M
AN
AG
EM
EN
T D
IV
IS
IO
N
DE
SI
GN
S
ER
VI
CE
S
AN
D
ST
AN
DA
RD
S
BR
AN
CH
DE
SI
GN
S
ER
VI
CE
S
SE
CT
IO
N
R E V
D A T E
S C R
IP
T
IO
N
L A C
V1
C A
LI
F O
R N
IA
S T A T E P
R
IS
O N , L
O S A
N G
E
LE
S C
O U N
T Y
TH
S
TR
E E T, W E S T
LA
N
C A S
TE
R , C
A
R E P
LA
C E R
O O
F
P H A S
C
C R
P H A S E
J O B
N U M B E R
A T E A
U G
U S T
1, P ro je c t N o
.1
P ro je c t
P h a s e
S H E E T
T
IT
L
M. TODD
THORP
No. 2990
/9
/2
:3 :1
P
M c re v it \2
-0
.0
C D
C R
L A P
H R C
E N
T R
A L d d ir e .r v t
G E N E R
A L N
O T E S
SSSS111100001 111
APPLICABLE TO ALL DRAWINGS UNLESS NOTED OR SHOWN OTHERWISE
GENERAL NOTES
08/24/2023
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
10/10/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-0002
11/20/2023 CASp 491 #1317