18-20 - A4-0 - BUILDING SECTIONS AND ROOF DETAILS.pdf
PDF 527 KB Posted
- Solicitation number
- RFP260305
- Issued by
- Hart County, Kentucky
About this file
This file comprises architectural building sections and roof details prepared by the Commonwealth of Kentucky Finance and Administration Cabinet, Department for Facilities Management, Division of Engineering for the Gateway Urban Campus project located at 438-440 Scott Street, Covington, Kentucky. The drawings illustrate schematic representations of the building structure across multiple floors, including basement level at -10'-8", first floor at 0'-0", second floor at 16'-2", third floor at 29'-5", and roof at 42'-3". The document provides detailed specifications for roof construction, including SBS modified bitumen roofing over polyisocyanurate insulation and structural wood sheathing, as well as supplementary architectural elements such as roof hatches, ship's ladder access systems with aluminum components, gravel stop edge details with pre-finished aluminum trim, and chimney cap and reglet details. The building contains multiple functional spaces across its floors, including classrooms, offices, reception areas, corridors, restrooms, storage areas, and specialized rooms such as a cosmetology salon and massage therapy facilities.
The drawings are record documents dated December 18, 2015, prepared on the basis of information compiled by others, with the architect/engineer disclaiming responsibility for errors or omissions resulting from erroneous information provided by third parties. The document references structural drawings, reflected ceiling plans, and previous schematic sheets (A2.1) for additional specifications regarding acoustical batt insulation placement and other construction details. The project drawing number is 470-C5N5-NC11-01, with A&E file number 201114.02, and includes multiple detail scales ranging from 1/4" = 1'-0" to 3" = 1'-0" for clarity in construction specification.
View the file
Other files
Show 40 more
Latest 50 of 80 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A4.0
A4.0
B C D EA G
A4.1
A4.1
CLIENT MASSAGE
301E
CORRIDOR
HVAC
302A
ROOF ACCESS
302B
LOBBY
CORRIDOR
300A MEN
MEN
CORRIDOR
200A
OFFICE 1
CLASSROOM
RECEPTION
100A
COSMETOLOGY
SALON
CORRIDOR
100B
CORRIDOR
100E
MEN
EXISTING STORAGE
STUDENT LOUNGE
F
BUILDING SECTIONS ARE FOR
SCHEMATIC REPRESENTATION ONLY
ACOUSTICAL BATT INSULATION,
REFER TO NOTE #8 ON SHEET A2.1
A2.1
A2.1
1ST FLOOR
0' - 0"
2ND FLOOR
16' - 2"
0 basement -10' - 8"
3RD FLOOR
29' - 5" roof 42' - 3"
1ST FLOOR REAR
0' - 10"
A4.1
A4.1
A4.0
A4.0
1 3
STORAGE
WOMEN
MEN
STAIR
D3
STAIR
D2
CUSTODIAL
STAIR
D1
MEN
WOMEN
105STORAGE
FACIAL / COUPLE
MASSAGE
MEN
A5.0
ACOUSTICAL BATT INSULATION,
REFER TO NOTE # 8 ON SHEET A2.1
EXISTING HARDWOOD FLOORING OVER WOOD
FLOOR JOISTS
60" X 36" ROOF HATCH
1 1/4" DIA. SCHED.
40 ALUM. PIPE HANDRAIL
5" x 2" x 3/16" ALUM.
CHANNEL STRINGER
M A
X
M
IN
INTERNAL ALUM.
FITTINGS
1' - 0"
MOUNTING BRACKET
(6005-T5)
ALUMINUM TREAD
(6005-T5)
A
5"
4-3/4" 2"
2-1/2"
3/8" DIA.
1/4"
B
BRACKET WELDED TO
INSIDE OF STRINGER
1-1/4" x 1-1/4" x 1/4"
ANGLE WELDED TO TREAD
TREAD WELDED AND BOLTED
TO STRINGER W/ 1/4"
ROUND HEAD BOLTS
1/4" x 2" x 3"
FLOOR CLIPS
2' - 2 3/256"
3/8" DIA.
5 3/16" TREAD
/8
D
4" ANGLEB
NOTE: ALL BOLTS / FASTENERS
NECESSARY TO ANCHOR
LADDER ARE BY OTHERS
A
2' - 6"
1' - 11 3/4"
A P
P R
O X
H
E
IG
H T
F
IE
L D
V E
R
IF
Y
A S
R E
Q 'D
FIBER CANT
SBS MODIFIED BITUMEN
ROOFING OVER 1/2"
HIGH DENSITY
POLYISOCYANURATE
COVERBOARD OVER 3"
MIN. POLYISOCYANRATE
INSULATION OVER NEW
STRUCTURAL SHEATHING
OVER EXISTING ROOF
SHEATHING
2x12 F.P.T. WOOD FRAMING
REFER TO STRUCTURAL
DRAWINGS
P.T. WOOD BLOCKING
68 DEGREES
MULTIPLE-PLY MEMBRANE
BASE FLASHING
SBS MODIFIED BITUMEN
ROOFING OVER 1/2" HIGH
DENSITY POLYISOCYANURATE
COVERBOARD OVER 3" MIN
POLYISOCYANURATE
INSULATION OVER NEW WOOD
SHEATHING (REFER TO
STRUCTURAL DRAWINGS)
OVER EXISTING WOOD ROOF
SHEATHING AND RAFTERS
WOOD NAILERS
LIGHTTRACKER REFLECTOR
LIGHT TUBE - BASIS OF
DESIGN: SOLATUBE 160DS
W/ EXTENSION TUBE WITH
ELECTRONIC MOTORIZED
DIMMING CAPABILITY
TOP 0-30 DEGREES
ADAPTER TUBE
BOTTOM 0-30 DEGREES
ADAPTER TUBE
FIELD VERIFY
24" O.C.
EQ EQ
OPENING
1' - 0"
DRESS RING
12 7/8" DIA.
FLASHING
5/8" GYPSUM CEILING
BOARD, REFER TO
REFLECTED CEILING
PLANS
SBS MODIFIED BITUMEN
ROOFING OVER 1/2" HIGH
DENSITY POLYISOCYANURATE
COVER BOARD OVER 3" MIN.
POLYISOCYANURATE INSUL.
STRUCTUAL WOOD
SHEATHING, REFER TO
STRUCT. DRAWINGS
TAPER INSULATION AS
REQUIRED TO PROVIDE
POSITIVE DRAINAGE
1/4" TO 1'-0" MIN.
PRE-FINISHED ALUMINUM
GRAVEL STOP EDGE WITH
WITH CONTINUOUS GALV.
METAL CLEAT SECURE
TO EXISTING CORNICE
CONTINUE ONE LAYER
OF ROOFING MEMBRANE
OVER CORNICE EDGE
4"4"
F .V
REMOVE AND REPLACE
ANY EXISTING WATER
DAMAGE BLOCKING
WHEN EXPOSED AFTER
EXISTING ROOFING IS
DEMOLISHED
EXISTING WOOD ROOF
RAFTER OR OUTRIGGER
2x P.T. WOOD BLOCKING
/2
SBS MODIFIED BITUMEN
ROOFING OVER 1/2" HIGH
DENSITY POLYISOCYANURATE
COVER BOARD OVER 3" MIN.
POLYISOCYANURATE INSUL.
8"
CONT. SEALANT
FIBER CANT
PRE-FINISHED SHEET METAL FLASHING
WITH 2 PIECE SPRING CLIP
BACKER ROD &
SEALANT, CONT.
EXISTING ABANDONED CHIMNEY
RE-EMBED AND TUCKPOINT ALL LOOSE
MASONRY, TYPICAL
CONT.
SEALANT
PRE-FINISHED ALUMINUM CHIMNEY
CAP WITH CONTINUOUS CLEAT AND
DRIP EDGE
3/4" EXT. GRADE PLYWOOD
SUBSTRATE SECURED
TO EXISTING BRICK
2x P.T. WOOD NAILERS
CONT., ATTACHED TO
PLYWOOD SUBSTRATE
EXTERIOR GRADE PLYWOOD
SECURED TO WOOD NAILERS
TERMINATION BAR
SELF-ADHERED MEMBRANE FLASHING, EXTEND
OVER SIDES
C
COMMONWEALTH
T
R E
R
A
HC
I
N
KE
UT
OF
B
3 87
I
R
EG
No.
TS E
NT U
C E
YK T
N E R
D
ER
RB
APPROVED FOR PROGRAM CONCEPT ONLY
APPROVED FOR PROGRAM CONCEPT ONLY
DATE
DATE
ENGINEERING
DIVISION OF
AGENCY
AUTHORIZED AGENT
FOR INTENT ONLY
DIV. OF ENGR.
REVIEWED
ENGR. ACCT. NO.
DRAWING NO.
DATE
A&E FILE NO.
CHECKED BY
SHEET DRAWN BY
RECORD DATE
DATEREVISIONS
COMMONWEALTH OF KENTUCKY
FINANCE AND ADMINISTRATION CABINET
DEPARTMENT FOR FACILITIES MANAGEMENT
DIVISION OF ENGINEERING
FRANKFORT, KENTUCKY
/5
/2
:5 :0
P
M C
U s e rs
\R H in s o n \D o c u m e n ts
\1
G
C T
C
A b o d e B u il d in g R e n o v a ti o n rh in s o n .r v t
A4.0
BUILDING SECTIONS AND ROOF
DETAILS
470-C5N5-NC11-01
GATEWAY URBAN CAMPUS
09/25/14
201114.02
BB
REH
PROFESSIONAL SERVICES CLASSROOM CENTER
438-440 Scott St., Covington, KY 41011
SCALE: 1/4" = 1'-0"A4.0
1 BUILDING SECTION 1
SCALE: 1/4" = 1'-0"A4.0
2 BUILDING SECTION 2
SCALE: 3/4" = 1'-0"A4.0
3 ROOF HATCH & ACCESS SHIP'S LADDER
SCALE: 1" = 1'-0"A4.0
4 ENLARGED DETAIL
SCALE: 3" = 1'-0"A4.0
5 GRAVEL STOP EDGE DETAIL
SCALE: 3" = 1'-0"A4.0
6 CHIMNEY CAP & REGLET DETAIL
AS-BUILT
12-18-15
RECORD DRAWINGS
THESE RECORD DRAWINGS HAVE BEEN PREPARED IN PART, ON THE BASIS OF INFORMATION COMPILED BY OTHERS. THE ARCHITECT/ENGINEER HAS NOT VERIFIED THE ACCURACY OR COMPLETENESS OF THE INFORMATION, AND SHALL NOT BE RESPONSIBLE FOR ANY ERRORS OR OMISSIONS THAT MAY BE
INCORPORATED AS A RESULT OF ERRONEOUS INFORMATION PROVIDED BY OTHERS.