M601.pdf

PDF 444 KB Posted

Attached to
Boiler #3 Replacement
Solicitation number
14-223-SOL-00059
Issued by

About this file

M601

View the file

Other files

File Type Posted
Amendment_1.pdf PDF
M201.pdf PDF
S101.pdf PDF
M301.pdf PDF
M102.pdf PDF
E201.pdf PDF
E202.pdf PDF
Solicitation_14-223-SOL-00059.pdf PDF
M204.pdf PDF
Attachment_J-3_General_Decision_Number_AR140125.pdf PDF
M100.pdf PDF
M101.pdf PDF
M104.pdf PDF
M702.pdf PDF
G100.pdf PDF
M307.pdf PDF
M203.pdf PDF
E102.pdf PDF
Attachment_J-2_Drawings.pdf PDF
M202.pdf PDF
M302.pdf PDF
M304.pdf PDF
Attachment_J-4_FDA_Form_3391.pdf PDF
M401.pdf PDF
M701.pdf PDF
E301.pdf PDF
M403.pdf PDF
M402.pdf PDF
M103.pdf PDF
Attachment_J-1_Specifications.pdf PDF
E101.pdf PDF
M305.pdf PDF
E401.pdf PDF
M303.pdf PDF
M200.pdf PDF
M306.pdf PDF
M501.pdf PDF
S102.pdf PDF
Show all 38

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

HVAC LEGEND

HVAC DEMOLITION LEGEND

TEE, OUTLET DOWN

CAPPED OUTLET

ELBOW, TURNED DOWN

RISE OR DROP IN PIPE

TEE, SIDE CONNECTION

TEE, OUTLET UP

ELBOW, TURNED UP

FLANGE

RETURN AIR GRILLE

CEILING DIFFUSER

RETURN DUCT DOWN

EXHAUST DUCT DOWN

ACCESS PANEL

EXHAUST AIR GRILLE

ACCESS PANEL IN ROUND

AP

AP

CONTROL VALVE (2-WAY) ELECTRIC OR ELECTRONIC

H

METAL BELLOWS PUMP CONNECTOR

PRESSURE GAUGE W/ SIPHON

AIR VENT (A - AUTO, H - HAND)

PRESSURE AND TEMPERATURE TAP

THERMOMETER W/ INSERTION WELL

PIPE GUIDE

ANCHOR

PRESSURE GAUGE

STRAINER W/ DRAIN VALVE

CONTROL VALVE (2-WAY) PNEUMATIC

FLEXIBLE PIPE CONNECTOR

CHECK VALVE (BUTTERFLY CHECK)

CONTROL VALVE (3-WAY) PNEUMATIC

UNION

12SR

BFW

12S

PCR

D

OF

CW

STEAM RETURN (PRESSURE NOTED)

CHECK VALVE (SWING CHECK)

BUTTERFLY VALVE (GEAR OPERATOR)

BUTTERFLY VALVE (LEVER HANDLE)

GATE VALVE

GLOBE VALVE

BALL VALVE

DOMESTIC COLD WATER

OVERFLOW

CONDENSATE DRAIN

PUMPED CONDENSATE RETURN

BOILER FEEDWATER

STEAM SUPPLY (PRESSURE NOTED)

MOTORIZED VOLUME DAMPER

MANUAL VOLUME DAMPER

ROUND DUCT OFFSET

FIRE DAMPER (FD)

SMOKE DAMPER

CHANGE IN ELEVATION (R - RISE, F - FALL)

RECTANGULAR DUCT (WIDTH/DEPTH)

EXHAUST DUCT UP

SUPPLY DUCT DOWN

FLEXIBLE DUCT

SUPPLY DUCT UP

RETURN DUCT UP

R

20/12

GPM FLUID FLOW METER

SUPPLY AIR DUCT

RETURN AIR DUCT

ROUND DIAMETER

CUBIC FEET PER MINUTE

STREAMLINE TAP (ROUND)

ELL WITH TURNING VANES

EXHAUST AIR DUCT

FLAT OVAL (MAJOR/MINOR)

CONICAL TAP

SA

RA

CFM

EH

F

POINT OF CONNECTION TO EXISTING

DIRECTION OF PITCH

TEMPERATURE SENSOR

PIPE TO FLOOR DRAINTFD

TS

THERMOSTATT

NEW EQUIPMENT

STEAM TRAP

CONCENTRIC REDUCER

STEAM TRAP (DRIP LEG)

ECCENTRIC REDUCER

CAPPED PIPE

CFM DEVICE

CFM AIR DEVICE

TYPE RETURN/EXHAUST

TYPE - THROW SUPPLY AIR

OR OVAL DUCT

S

PRESSURE REDUCING VALVE

VALVE AT RISER

LONG (1.5x) RADIUS ELL

SHORT (1x) RADIUS ELL

STREAMLINE TAP (RECTANGULAR)

M

(RECTANGULAR OR ROUND)

(ROUND OR OVAL)

FUEL OIL RETURN

FUEL OIL SUPPLYFOS

FOR

CONTROL VALVE (3-WAY) ELECTRIC OR ELECTRONIC

FLOW LIMITING VALVE

EXISTING EQUIPMENT

HUMIDISTATH

THERMOSTAT WIRING

SYMBOL DESCRIPTION

EXISTING PIPING TO REMAIN

EXISTING EQUIPMENT TO REMAIN

PIPING TO BE REMOVED

EQUIPMENT TO BE REMOVED

TERMINATION OF DEMOLITION

SYMBOL DESCRIPTIONDESCRIPTIONSYMBOL

OS & Y GATE VALVE

AIR TERMINAL / FAN COIL UNIT/HOT WATER RETURN

AIR TERMINAL / FAN COIL UNIT

CONTROL VALVE (2-WAY) ELECTRIC OR ELECTRONIC

CONTROL VALVE (3-WAY) ELECTRIC OR ELECTRONIC

CALIBRATED BALANCING VALVE/ PLUG VALVE

CENTERLINE RADIUS = 1d

CENTERLINE RADIUS = 1.5d

ENERGY MANAGEMENT SYSTEM

AUTOMATIC TEMP CONTROLS

PARTS PER MILLION

CARBON DIOXIDE

EMS

ATC

PPM

CO2

BD BLOW DOWN

BLOW DOWN SEPARATORBS

SCW SOFTEN WATER

X X

X X

FIRE TUBE BOILER

DESIGNATION

MANUFACTURER/MODEL

MAXIMUM UNIT LENGTH

MAXIMUM UNIT WIDTH

MAXIMUM UNIT HEIGHT (INCLUDES BASE RAIL)

MAXIMUM OPERATING WEIGHT (LBS.)

EMISSION

GENERAL DATA

AIRFLOW LENGTH (INCHES)

GAS (NATURAL)

OIL (NO.2)

HORSEPOWER

GAS INPUT (NMHP)

OPERATING PRESSURE (PSIG)

OUTPUT (#/HR) / (FROM AND AT °F.)

DESIGN PRESSURE (PSIG)

OIL INPUT (GPH)

UNIT CONFIGURATION

NOX EMISSION (MAXIMUM):

ELECTRICAL

REMARKS:

B-3

STEAM DISENGAGING AREA (MINIMUM SQ. INCHES)

STEAM STORAGE AREA (MINIMUM CU. FEET)

HEATING SURFACE (MINIMUM SQ. FEET FIRESIDE)

BURNER TURNDOWN RATION NATURAL GAS

NATURAL GAS (%)

NO. 2 OIL (%)

ELECTRICAL FAN MOTOR

AIR COMPRESSOR MOTOR

OIL PUMP MOTOR

NOISE LEVEL (3'-0" FROM BURNER)

ELECTRICAL (V / H / P)

AVAILABLE GAS SUPPLY PRESSURE (PSIG)

BOILER SHALL BE FURNISHED WITH SINGLE POINT POWER CONNECTION.

CODE REQUIREMENTS: ASME / NATION AL BOARD - CSD-1 NFPA 8501 -

STATE OF ARKANSAS CODE REQUIREMENTS.

CLEAVER BROOKS 4WI-200-750-150ST

151.5"

119"

75,500

80"

218.7

750 H.P.

28,875 / 212

4-PASS / WET BACK / WITH INTERNAL BURNER

30.61

15,826

115.6

3,500

10:1

30- PPM (CORRECTED TO 3% O2)

90- PPM (CORRECTED TO 3% O2)

75 HP

7.5 HP

1 HP

460 / 60 / 3

88 dBA NORMAL - 90 dBA MAXIMUM

4.6 - 6.8

OVERALL

EFFICIENCY

(FUEL TO STEAM)

BOILER SHALL BE TESTED FOR GUARANTEED EFFICIENCY.

REFER TO SHEETS M703 FOR CONTROLS REQUIREMENTS.

REFER TO SPECIFICATION

REFER TO SPECIFICATION

TOTAL PACKAGE SHALL BE LISTED BY UNDERWRITER'S LAB (UL).

HEAT EXCHANGERS (STACK ECONOMIZER)

DESIGNATION LOCATION PRODUCT

REFERENCE SERVES

FLOW

UNIT

WEIGHT

( LBS )

SHELL SIDE

PRESSURE

( IN. W.C.)

REMARKS

FIRST STAGE

FLOW

SECOND STAGE

HEAT RECOVERED

SENSIBLE ( MBH )

EXHAUST

ENTERING

TEMP. ( °F. )

DESIGN PRESSURE

(PSIG)

ENTERING/ LEAVING

WATER ( °F. )

HEAT RECOVERED

LATENT ( MBH )

TOTAL EFF. HTG.

SURFACE (SQ. FT.)

DESIGN

PRESSURE

( PSIG )

ENTERING/

LEAVING

WATER ( °F. )

5,000 +/- 10"CLEAVER BROOKS

C2X-S3CF6AL

BOILER

PLANTBSE-3 B-3 453 373 300 / 150 227 / 24452 GPM 222526 GPM997.0 300 / 150 80 / 157 ·INNER CASING JOINTS TO BE SEAL WELDED. ALUMINUM PAINT ON ALL

EXTERIOR SURFACES, GALVANIZED OUTER CASING. FURNISH WITH STACK

ADAPTER PLATES. VERIFY BOILER STACK CONNECTION SIZE PRIOR TO

ORDERING.

·BOILER EFFICIENCY WITH ECONOMIZER = 87.9%

·TOTAL HEAT RECOVERED: 1,450,000 BTUH

PRESSURE SAFETY RELIEF VALVES

DESIGNATION SERVES CAPACITY

( LBS/HR )

PRESSURE RELIEF

SETTING ( PSIG )

REMARKS

SRV-1,2,3 1 1

1 FURNISHED WITH BOILERS, CAPACITY AND SIZE PER BOILER'S MANUFACTURER. 3 EACH PER BOILER.

B-3

STEAM TRAPS

REMARKS

MIN. DIFF.

PRESSURE

(PSIG )

MAX. INLET

PRESSURE

(PSIG )

CAPACITY

(LBS/HR)

CONDENSATE

LOAD

(LBS/HR)

SERVESTYPEDESIGNATION

ST-1 302400 110800INVERTED

BUCKET

HIGH PRESSURE MAIN FOR HIGH PRESSURE MAIN - DRIP LEG

ST-2 2400 15200INVERTED

BUCKET

LOW PRESSURE MAIN FOR LOW PRESSURE - DRIP LEG

ST-3 2300 15110F & T UNIT HEATERS FOR STEAM RETURN FROM UNIT HEATERS

UNIT HEATERS - STEAM

DESIGNATION REFERENCE

PRODUCT

AIR FLOW

RATE

(CFM)

AIR

EDB / LDB

(ºF) VOLTS/PHASE

STEAM

FLOW RATE

(LBS/HR)

STEAM

PRESSURE

(PSIG)

ROTATION

(RPM)

MOTOR

SIZE

(MHP)

ELECTRICAL

REMARKSSERVES

HEATING

CAPACITY

(MBH)

UH-1 TRANE P-102 1180 123 106 15 850 1/8 FURNISH WITH THERMOSTAT AND CONTROL VALVE PACKAGE.277 / 1Ø101.8BOILER

ROOM

MODEL

WATER SOFTNER SYSTEM

DESIGNATION

VALVE

SIZE

(IN)

TOTAL

GRAIN

EXCHANGED

LEAVING WTR

HARDNESS

(MG/L)

BACKWASH

FLOW

(GPM)

BRINE TANK AND

SALT CAPACITY (LBS)

DXH(IN)

PRE-REVERSE

OSMOSIS FLOW

(GPM)

MIN/PEAK FLOW

(GPM) REMARKS

NALCO#011-

SLDFVLEX.88WS-1 3"67

(4500 LBS)

(50" X 60")401115 / 270 1,800,00,000 THE WATER SOFTENER SHALL BE ULTRA SOFT DUPLEX ALTERNATING UNIT. CONTRACTOR

SHALL PROVIDE A COMPLETE SYSTEM, INSTALLED AND PIPED WITH PACKAGED CONTROLS.

UNIT WILL HAVE TWO(2) INDIVIDUAL FRP PRESSURE VESSEL SHARING ONE BRINE SYSTEM.

THE SYSTEM SHALL PROVIDE CONTINUOUS 24-HOUR SOFTENED WATER TO BOILERS.

RESIN VOL.

PER TANK

(FT )

REFERENCE

PRODUCT

LOUVERS

DESIGNATION

PRESSURE

DROP

(IN. WATER)

FINISH

WIDTH

(IN.)

HEIGHT

( IN. )

DEPTH

( IN. )

MAXIMUM

AIR FLOW

( CFM )

TYPE REMARKS

AMERICAN WARMING

& VENTILATINGL-1 0.0515,0006"156"144"DRAINABLE

BLADE

MATCH

EXISTING

BUILDING

EXTERIOR

WINDOW COLOR

FURNISH WITH BIRD SCREEN, WIND DRIVEN RAIN LOUVER.

ISSUE DATE:

SHEET NUMBER:

PROJECT NUMBER:

5800 EVERGREEN DRIVE

LITTLE ROCK,

ARKANSAS

72205-1757

Phone: (501) 666-6776 Fax: (501) 663-8888 tme@tmecorp.com

SHEET TITLE:

ENGINEER SEAL

CORPORATE SEAL

MARK DATE DESCRIPTION

M601

SCHEDULES AND LEGEND -

MECHANICAL

03-24-14

01-13-0018

B ui ld in g

B oi le r #3

R ep la ce m en t Je ffe rs on L ab or at or ie s

F oo d an d D ru g

A dm in is tr at io n

N C

T R

R d

Je ffe rs on

, A R

CONSTRUCTION

DOCUMENT

File details come from the government source that posted it. Updated .