M402.pdf

PDF 556 KB Posted

Attached to
Boiler #3 Replacement
Solicitation number
14-223-SOL-00059
Issued by

About this file

M402

View the file

Other files

File Type Posted
Amendment_1.pdf PDF
M303.pdf PDF
M200.pdf PDF
M306.pdf PDF
M501.pdf PDF
S102.pdf PDF
M702.pdf PDF
G100.pdf PDF
M307.pdf PDF
M203.pdf PDF
E102.pdf PDF
Attachment_J-2_Drawings.pdf PDF
M202.pdf PDF
M302.pdf PDF
M304.pdf PDF
Attachment_J-4_FDA_Form_3391.pdf PDF
M401.pdf PDF
M701.pdf PDF
E301.pdf PDF
M403.pdf PDF
M103.pdf PDF
Attachment_J-1_Specifications.pdf PDF
E101.pdf PDF
M305.pdf PDF
M601.pdf PDF
E401.pdf PDF
M201.pdf PDF
S101.pdf PDF
M301.pdf PDF
M102.pdf PDF
E201.pdf PDF
E202.pdf PDF
Solicitation_14-223-SOL-00059.pdf PDF
M204.pdf PDF
Attachment_J-3_General_Decision_Number_AR140125.pdf PDF
M100.pdf PDF
M101.pdf PDF
M104.pdf PDF
Show all 38

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

4" CONC. PAD

3"

(4) 3/8" THREADED ANCHOR

SETS IN BASE PAD

FLOOR

1/4" BASE

PLATE STEEL

6"

36"

27"

3" 6"

TO BACK-PRESSURE

VALVE AND RETURN

TO STORAGE TANK

TYP.: (4) 3/4" EX. HEAVY

WELDED HALF COUPLINGS

4" WELD

CAP

FROM BURNER PUMP

TO BURNER PUMP

FROM STORAGE

CIRC. PUMP

22"x22"x4" H - 16 GA. STEEL CONTAINMENT

TANK. WELD SEAMS AND GASKET SEAL

THRU-BOLTS WITH "LEAK-LOCK" SEALANT.

(1/2) 1/2" THREADED

SCH. 80 COUPLING

INSULATE ANCHOR AS INDICATED FOR COLD PIPING.

NOTE:

STRUCTURE

WELD

ANCHOR

BOLTS, 2 AT

EACH PLATE.

MIN. SIZE 5/8"

STRUCTURAL

CHANNEL OR

ANGLES

(2"x2"x1/4")

3/8" BASE

PLATE

PIPE &

INSULATION

1/2"

U-BOLT

3/8" PLATE

CUT TO

SUIT PIPE

DIA. AND

INSULATION

THICKNESS

PIPE &

INSULATION

STRUCTURAL

CHANNEL OR

ANGLES

(2"x2"x1/4")

3/8" PLATE

CUT TO SUIT

PIPE DIA. AND

INSULATION

THICKNESS

PLAN VIEW

CONCRETE TRENCH

CHANNEL TO BE SET IN

SIDE WALL OF TRENCH.

SIZE OF STEAM

LINE GOVERNS

SIZE OF

CHANNEL.

PROVIDE TWO "U" BOLTS WITH

NUT & LOCK NUT ON STEAM LINE.

SPOT WELD "U" BOLT TO PIPE &

BOLT TO CHANNEL.

STEAM LINE CONDENSATE RETURN LINE

PROVIDE ONE "U" BOLT WITH NUT

& LOCK NUT ON RETURN LINE.

SPOT WELD "U" BOLT TO PIPE &

BOLT TO CHANNEL

2-1/2 - 5

6 - 8

1 - 2

3/4 DIA.

3/8 DIA.

1/2 DIA.

SIZE OF PIPE

INCH

SCHEDULE

SIZE OF "U" BOLT

INCH

10 x 20

6 x 10.5

8 x 13.75

SIZE OF CHANNEL

INCH

SCHEDULE FOR 8 FT. SPAN OR LESS.

HORIZONTAL

VERTICAL

ABOVE 2" DIA. PIPE

2 1/2" DIA.

2" DIA. & SMALLER

ABOVE 2" DIA. PIPE 2" DIA. & SMALLER

2 1/2" DIA.

TACK WELD TACK WELD

TACK

WELDTACK

WELD

36" MINIMUM

STACK

CAP

COUNTER-FLASHING

FLASHING

COLLAR

FLASHING, REFER

TO ARCHITECTURAL

DETAILS

ROOF

SLEEVE

BOILER

FLUE

ANCHOR

GUY

WIRE

PLAN

ELEVATION

NOTES:

PIPE SLEEVE

WHERE SPECIFIED

RISER CLAMP

FIRE-STOPPING MATERIAL

BOLT

RISER CLAMP

PIPE SLEEVE

WHERE

SPECIFIED

PIPE

BOLT

(TYPICAL)

FLOOR SLAB

INSULATIONRISER

RISER CLAMP.

BOTTOM CLAMP

REQUIRED AT

ANCHOR POINTS

ONLY.

1. PROVIDE ANCHORS

ONLY WHERE

SHOWN ON

DRAWINGS.

2. EXTEND SLEEVE

ABOVE FLOOR

WHERE SPECIFIED.

1/2"

ORIFICE PLATE FLOW METER

EQUALIZING

VALVE

BLOWDOWN

VALVE

1/2"

1/2"

TAPPED FLANGE

1/2"

BLOWDOWN

VALVE

STEAM

FLOW

H L

KEYED NOTES:

SLOPE ALL HORIZONTAL PIPING TOWARDS

TRANSMITTER.

DIFFERENTIAL PRESSURE TRANSMITTER IS

SPECIFIED IN SECTION 15900.

ORIFICE PLATE FLOW METER IS SPECIFIED IN

SECTION 15900.

FILL LINES W/ DISTILLED WATER.

INSTALL TEES AT SAME ELEVATION.

SECURE DEVICE TO ADJACENT WALL.

1 1

SUPPORT FROM BUILDING STRUCTURE

DRIP PAN ELBOW

PIPE NIPPLE

DRAIN TO FLOOR DRAIN

UNION

RELIEF VALVE

6" MIN.

TERMINATE MINIMUM 6'-0" ABOVE ROOF

UNION

DISCHARGE RISER

TO CONDENSATE RETURN SYSTEM

3/4"

3/4" SERVICE BYPASS

6" DIRT TRAP

3/4"

6" MINIMUM

BRANCH STEAM DROP STEAM MAIN RISER

TFD

STEAM

RETURN

ST-3 (HIGH PRESSURE)

ST-3A(LOW PRESSURE)

3/4" SERVICE BYPASS

LAST STEAM RUNOUT

6" DIRT TRAP

3/4" 3/4"

6" MINIMUM

(HIGH PRESSURE)

(LOW PRESSURE)

STEAM

RETURN

STEAM

SUPPLY

TFD

6" LONG DIRT TRAP

1-1/4"

GATE

VALVE

STRAINER

UNION

ECCENTRIC REDUCER

CONCENTRIC

REDUCER

MODULATING CONTROL

VALVE

VACUUM RELIEF

JOHNSON VB8-1/2"

(DO NOT USE

CHECK VALVE)

STEAMRETURN

CHECK

VALVE

STRAINER

WITH HOSE

ADAPTER GATE

VALVE

1"

PIPE SIZE SAME

AS COIL

CONNECTION

1"

RVAC

AIR

FLOW

S15

1-1/4"

F & T

STEAM

ST-3

ISSUE DATE:

SHEET NUMBER:

PROJECT NUMBER:

5800 EVERGREEN DRIVE

LITTLE ROCK,

ARKANSAS

72205-1757

Phone: (501) 666-6776 Fax: (501) 663-8888 tme@tmecorp.com

SHEET TITLE:

ENGINEER SEAL

CORPORATE SEAL

MARK DATE DESCRIPTION

M402

DETAILS - MECHANICAL

03-24-14

01-13-0018

B ui ld in g

B oi le r #3

R ep la ce m en t Je ffe rs on L ab or at or ie s

F oo d an d D ru g

A dm in is tr at io n

N C

T R

R d

Je ffe rs on

, A R

CONSTRUCTION

DOCUMENT

NOT TO SCALE

CIRCULATING OIL TANK DETAIL

NOT TO SCALE

HORIZONTAL PIPE ANCHOR DETAIL

NOT TO SCALE

DETAIL OF ANCHOR IN TRENCH FOR STEAM AND CONDENSATE LINES

NOT TO SCALE

INSTALLATION OF THERMOMETER WELLS

NOT TO SCALE

BOILER STACK DETAIL

NOT TO SCALE

SUPPORT/ANCHOR FOR PIPE RISERS

NOT TO SCALE

STEAM FLOW AND PRESSURE TRANSMITTER PIPING DETAIL

NOT TO SCALE

STEAM RELIEF VALVE W/ DRIP PAN ELBOW DETAIL

NOT TO SCALE

DRIP LEG TRAP PIPING DETAIL

NOT TO SCALE

END OF MAIN PIPING DETAIL

NOT TO SCALE

STEAM UNIT HEATER PIPING DETAIL