E401.pdf
PDF 390 KB Posted
- Attached to
- Boiler #3 Replacement
- Solicitation number
- 14-223-SOL-00059
About this file
E401
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Amendment_1.pdf | ||
| M303.pdf | ||
| M200.pdf | ||
| M306.pdf | ||
| M501.pdf | ||
| S102.pdf | ||
| E301.pdf | ||
| M403.pdf | ||
| M402.pdf | ||
| M103.pdf | ||
| Attachment_J-1_Specifications.pdf | ||
| E101.pdf | ||
| M305.pdf | ||
| M601.pdf | ||
| M702.pdf | ||
| G100.pdf | ||
| M307.pdf | ||
| M203.pdf | ||
| E102.pdf | ||
| Attachment_J-2_Drawings.pdf | ||
| M202.pdf | ||
| M302.pdf | ||
| M304.pdf | ||
| Attachment_J-4_FDA_Form_3391.pdf | ||
| M401.pdf | ||
| M701.pdf | ||
| M201.pdf | ||
| S101.pdf | ||
| M301.pdf | ||
| M102.pdf | ||
| E201.pdf | ||
| E202.pdf | ||
| Solicitation_14-223-SOL-00059.pdf | ||
| M204.pdf | ||
| Attachment_J-3_General_Decision_Number_AR140125.pdf | ||
| M100.pdf | ||
| M101.pdf | ||
| M104.pdf |
Show all 38
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FEEDER SCHEDULE (COPPER)
COPPER CONDUCTORS, 90°C RATED INSULATION, TYPE THHN /THWN WITH EQUIPMENT GROUND CONDUCTOR
3 CONDUCTORS & GROUND 4 CONDUCTORS & GROUND
CODE SETS CONDUCTORS RACEWAY
AMPS
RACEWAY CONDUCTORS SETS CODE
NOTES:
1. ALL CONDUCTORS AMPACITY BASED ON THE 2008 NEC TABLE 310-16 FOR CONDUCTORS W/ 75°C INSULATI ON.
2. ALL RACEWAY SIZES (EMT/RMC/PVC 40) BASED ON THE 2008 NEC TABLE 4 (CHAPTER 9), 40% FILL COLUMN.
3. ELECTRICAL CONTRACTOR TO VERIFY ALL EQUIPMENT CONDUCTOR TERMINATION TEMPERATURE RATINGS.
ADJUST CONDUCTOR AND CONDUIT SIZES ACCORDINGLY.
4. ELECTRICAL CONTRACTOR TO VERIFY MAXIMUM NO. OF SETS OF SERVICE ENTRANCE CONDUCTORS W/
UTILITY CO. AND EQUIPMENT PROVIDER.
3-#12, 1-#12G
3-#10, 1-#10G
3-#8, 1-#10G
3-#6, 1-#10G
3-#4, 1-#8G
3-#3, 1-#8G
3-#2, 1-#6G
3-#1, 1-#6G
3-#1/0, 1-#6G
3-#2/0, 1-#6G
3-#3/0, 1-#6G
3-#4/0, 1-#4G
3-#250 KCMIL, 1-#4G
3-#300 KCMIL, 1-#4G
3-#350 KCMIL, 1-#4G
3-#400 KCMIL, 1-#3G
3-#500 KCMIL, 1-#3G
3-#3/0, 1-#3G
3-#4/0, 1-#2G
3-#250 KCMIL, 1-#2G
3-#350 KCMIL, 1-#1G
3-#500 KCMIL, 1-#1/0G
3-#400 KCMIL, 1-#2/0G
3-#350 KCMIL, 1-#3/0G
3-#400 KCMIL, 1-#4/0G
3-#400 KCMIL, 1-#250 KCMIL G
3-#500 KCMIL, 1-#350 KCMIL G
3-#500 KCMIL, 1-#400 KCMIL G
3-#500 KCMIL, 1-#500 KCMIL G
3-#300 KCMIL, 1-#1/0G
CONDUCTORS
4-#12, 1-#12EG
4-#10, 1-#10EG
4-#8, 1-#10EG
4-#6, 1-#10EG
4-#4, 1-#8EG
4-#3, 1-#8EG
4-#2, 1-#6EG
4-#1, 1-#6EG
4-#1/0, 1-#6EG
4-#2/0, 1-#6EG
4-#3/0, 1-#6EG
4-#4/0, 1-#4EG
4-#250 KCMIL, 1-#4EG
4-#300 KCMIL, 1-#4EG
4-#350 KCMIL, 1-#4EG
4-#400 KCMIL, 1-#3EG
4-#500 KCMIL, 1-#3EG
4-#3/0, 1-#2EG
4-#4/0, 1-#2EG
4-#250 KCMIL, 1-#2EG
4-#350 KCMIL, 1-#2/0EG
4-#500 KCMIL, 1-#1/0EG
4-#400 KCMIL, 1-#2/0EG
4-#350 KCMIL, 1-#4/0EG
4-#400 KCMIL, 1-#250 KCMIL EG
4-#400 KCMIL, 1-#250 KCMIL EG
4-#500 KCMIL, 1-#350 KCMIL EG
4-#500 KCMIL, 1-#400 KCMIL EG
4-#500 KCMIL, 1-#500 KCMIL EG
4-#300 KCMIL, 1-#2/0EG
3/4" 3/4"
3/4" 3/4"
3/4" 3/4"
3/4" 1"
1" 1 1/4"
1 1/4" 1 1/4"
1 1/4" 1 1/4"
1 1/2"
1 1/2"
1 1/2"
2"
2" 2"
2" 2"
2" 2 1/2"
2 1/2"
2 1/2"
3"
3"
3" 3"
3" 3"
3 1/2" 4"
2" 2"
2" 2 1/2"
2 1/2" 3"
3" 3"
3 1/2" 4"
2 1/2" 3"
3" 3"
3 1/2"
3 1/2"
3 1/2"
3 1/2"
3 1/2"
3 1/2"
3"
3"
3"
4"
4"
4"
AMERICAN NATIONAL STANDARDS
INSTITUTE
A
A, AMPS
A/C
AC
ADJ
AF
AFC
AFF
AFG
AHU
AIC
AL
ANSI
ARCH
AUX
AWG
B
BFC
BFG
BFS
BKR
BLDG
C C
CATV
CCTV
C.I.
CKT
CL
CLG
COORD
CSA
CU, C/U
D
DC
DDC
DEMO,
DIA
DISC. SW.,
DN
DWG
E
EA
EC
EF, EXH-
ELEC
EM
ENCL
EPO
EQUIP
ETR
EWC
F
FA
FACP
FD
FEP
FLA
FLEX
FM
AMPERES
AIR CONDITIONING
ALTERNATING CURRENT
ADJUSTABLE
AMPERE FUSE
ABOVE FINISHED CEILING
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AIR HANDLING UNIT
AMPERE INTERRUPTING CURRENT
ALUMINUM
ARCHITECT, ARCHITECTURAL
AUXILIARY
AMERICAN WIRE GAUGE
BELOW FINISHED CEILING
BELOW FINISHED GRADE (EARTH)
BELOW FLOOR SLAB
BREAKER
BUILDING
CONDUIT
CABLE TELEVISION SYSTEM
CLOSED CIRCUIT TELEVISION
CUBIC INCHES
CIRCUIT
CENTERLINE
CEILING
COORDINATE
COLOR SELECTED BY ARCHITECT
COPPER, CONDENSING UNIT
DIRECT CURRENT
HVAC DIGITAL CONTROL PANEL
DEMOLISH, DEMOLISHED
DIAMETER
DISCONNECT SWITCH
DOWN
DRAWING
EACH
ELECTRICAL CONTRACTOR
EXHAUST FAN
ELECTRICAL
EMERGENCY FIXTURE
ENCLOSURE
EMERGENCY POWER OFF
EQUIPMENT
EXISTING EQUIPMENT TO REMAIN
ELECTRICAL WATER COOLER
FIRE ALARM
FIRE ALARM CONTROL PANEL
FIRE DAMPER
HVAC FIELD EQUIP RELAY PANEL
FULL LOAD AMPS
FLEXIBLE
FACTORY MUTUAL
ABBREVIATIONS
G
G, GND, GRD
GA
GALV
GENSET
GFCI
GFI
H
HP
HR, HRS
HSD
HTR
HVAC
HZ
I
ID
IEEE
IES
IG
J
J-BOX
K
KAIC
KCML
KV
KVA
KW
KWH
L
LF
LRA
LV
M
MAX
MCA
MCB
MD
MDP
MECH
MFGR,
MLO
MIN
MOCP,
MTD
N N.
N.C.
N.L.
N.T.S N/A
NEC
NEMA
N/F
NFPA
NIC
O O.C.
OD
GROUND
GAUGE
GALVANIZED
GENERATOR SET
GROUND FAULT CIRCUIT INTERRUPTER
GROUND FAULT INTERRUPTER
HORSEPOWER
HOUR, HOURS
HOUSE SIDE OPTICS
HEATER
HEATING, VENTILATION, AND
HERTZ
INSIDE DIAMETER
INSTITUTE OF ELECTRICAL & ELECTRONICS
ILLUMINATING ENGINEERING SOCIETY
ISOLATED GROUND
JUNCTION BOX
1000 AMPS INTERUPTING CURRENT
1000 CIRCULAR MILS
KILOVOLT
KILOVOLT-AMPERE
KILOWATT
KILOWATT-HOUR
LINEAR FEET
LOCKED ROTOR AMPS
LOW VOLTAGE
MAXIMUM
MINUMUM CIRCUIT AMPACITY
MAIN CIRCUIT BREAKER
MOTORIZED DAMPER
MAIN DISTRIBUTION PANEL
MECHANICAL
MANUFACTURER
MAIN LUGS ONLY
MINUTE, MINIMUM
MAX. OVERCURRENT PROTECTIVE DEVICE
MOUNTED
NEUTRAL
NORMALLY CLOSED
NIGHT LIGHT (FIXTURE ON 24 HRS)
NOT TO SCALE
NOT APPLICABLE
NATIONAL ELECTRIC CODE
NATIONAL ELECTRIC MANUFACTURER'S
NON-FUSED
NATIONAL FIRE PROTECTION ASSOCIATION
NOT IN CONTRACT
ON CENTER
P
PF
PH, �
PLBG
PNL
PVC
Q
QTY
R
RCP
RE:, REF
REQD
REV
RGS
RLA
RM
RTU
S
SDBC
SE
SECT
SHT
SIM
SPEC
SQ. FT., S.F.
SS
STD
SURF
SUSP
SW
T
TELECOM
TGB
TGMB
THD
THRU
TYP
U U/F U/G
UGE
UH
UL
UON, UNO
UPS
V V
VA
VFD
W W W/ W/O
WH
WP
X
XFMR
XSTG
POWER FACTOR
PHASE
PLUMBING
PANEL
POLYVINYL CHLORIDE
QUANTITY
REFLECTED CEILING PLAN
REFERENCE, REFER
REQUIRED
REVISED, REVISION, REVISE
RIGID GALVANIZED STEEL
RUNNING LOAD AMPS
ROOM
ROOF TOP UNIT
SOFT-DRAWN BARE COPPER
SERVICE ENTRANCE
SECTION
SHEET
SIMILAR
SPECIFICATIONS
SQUARE FEET
STAINLESS STEEL
STANDARD
SURFACE
SUSPEND
SWITCH
TELECOMMUNICATIONS
TELECOM GROUNDING BUSBAR
TELECOM GROUNDING MAIN
TOTAL HARMONIC DISTORTION
THROUGH
TYPICAL
UNDERFLOOR
UNDERGROUND
UNDERGROUND ELECTRIC
UNIT HEATER
UNDERWRITERS LABORATORIES,
UNLESS OTHERWISE NOTED
UNINTERRUPTIBLE POWER
VOLT
VOLT-AMPERE
VARIABLE FREQUENCY DRIVE
WATT, WIDTH
WITH
WITHOUT
WATER HEATER
WEATHER-PROOF
TRANSFORMER
EXISTING
NOTE: REFER TO INDUSTRY STANDARDS,
APPLICABLE CODES, AND PLAN DOCUMENTS OF
ALL DISCIPLINES FOR MORE INFORMATION ON
ABBREVIATIONS AND NOMENCLATURE.
KO KNOCKOUT
CWA COORDINATE WITH ARCHITECT
NS NOT SWITCHED
OUTSIDE DIAMETER
OCCUPANCY SENSOROC, OS
GC GENERAL CONTRACTOR
DEMO'D
D/S
FAN
AIR CONDITIONING
ENGINEERS
MANUF.
MOCPD
ASSOCIATION
BUSBAR
INC.
SUPPLY
SYMBOLS SCHEDULE
* AC
AFF
ER NS
AFG
SYMBOL DESCRIPTION SYMBOL DESCRIPTION
FLUORESCENT STRIP
FIXTURE
FLUORESCENT STRIP FIXTURE -
EMERGENCY
EXIT SIGN
EXIT SIGN - WALL MOUNTED
BATTERY-POWERED EMERGENCY
LIGHT
SINGLE-POLE
SWITCH
THREE-WAY
SWITCH
FOUR-WAY
SWITCH
MANUAL MOTOR STARTER WITH OVERLOADS,
TOGGLE OPERATED
BRANCH CIRCUIT IN CONDUIT - HOT LEG, SWITCH
LEG, NEUTRAL, AND EQUIPMENT GROUND
BRANCH CIRCUIT HOMERUN - PANEL & CIRCUIT
NUMBER INDICATED
DASHED INDICATES
EXISTING EXISTING
RELOCATED
DUPLEX
RECEPTACLE
DUPLEX RECEPTACLE - GROUND FAULT
INTERRUPTING AND WEATHER-PROOF TYPES
AS INDICATED ON PLANS
DUPLEX RECEPTACLE MOUNTED ABOVE COUNTER
TOP - VERIFY MOUNTING HEIGHT WITH
ARCHITECTURAL DRAWINGS
QUADRAPLEX RECEPTACLE
SPECIAL PURPOSE OUTLET - NEMA
CONFIGURATION (VOLTAGE, AMPACITY)
INDICATED
JUNCTION BOX
NONFUSED DISCONNECT SWITCH - SIZE
NOTED ON PLAN
FUSED
DISCONNECT
ELECTRIC MOTOR
SURFACE MOUNTED PANEL BOARD
FLUSH MOUNTED PANEL
BOARD
ABOVE COUNTER
NON-SWITCHED
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
GFI/WP
GENERAL NOTES
13. COORDINATE ROUTING OF CONDUIT WITH OTHER DISCIPLINES FOR A NEAT
AND PROFESSIONAL INSTALLATION.
14. ALL HORIZONTAL RUNS OF CONDUIT INTERIOR TO BUILDING SHALL BE
INSTALLED AS HIGH AS POSSIBLE TO BOTTOM OF STRUCTURE.
15. MINIMUM CONDUIT SIZE SHALL BE 3/4" FOR POWER CIRCUITS AND 1" FOR LOW
VOLTAGE SYSTEMS UNLESS OTHERWISE NOTED.
16. ALL PENETRATIONS OF SMOKE/FIRE RATED FLOORS OR PARTITIONS DUE TO
THE INSTALLATION OF ELECTRICAL SYSTEMS SHALL BE SEALED WITH A U.L.
LISTED AND FACTORY MUTUAL (FM) APPROVED ASSEMBLY AND SHALL
MAINTAIN THE FIRE RATING OF THE PARTITION.
17. PROVIDE SIMILAR LOOKING ENGRAVED NAMEPLATES FOR ALL FOLLOWING
ELECTRICAL DISTRIBUTION EQUIPMENT WHETHER OR NOT PROVIDED
DIRECTLY BY THE E.C.; E.G. SWITCHBOARDS, DISTRIBUTION BOARDS,
PANELBOARDS, TRANSFER SWITCHES, DISCONNECT SWITCHES, MANUAL &
AUTOMATIC STARTERS, COMBINATION STARTER/DISCONNECTS, AND TRANSFORMERS.
18. PANEL SCHDULE DIRECTORIES SHALL BE TYPEWRITTEN AND KEPT CURRENT
TO AS-BUILT CONDITIONS.
19. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR MARKING ALL
SWITCHES, RECEPTACLES, AND FIXED EQUIPMENT WITH THE BRANCH CIRCUIT
PANEL NAME AND NUMBER SERVING EACH DEVICE.
20. PROVIDE DEDICATED NEUTRALS FOR ALL BRANCH CIRCUITS, NEUTRAL SHALL
NOT BE SHARED.
21.
22.
COORDINATE WITH THE GENERAL CONTRACTOR FOR THE SEQUENCE OF
WORK AT EACH AREA.
21.
EXISTING BRANCH CIRCUITS NO LONGER USED SHALL BE REMOVED BACK TO
THE SERVING PANEL. CONDUIT SHALL REMAIN TO ACCESSIBLE CEILING SPACE
ABOVE PANEL. PANEL SCHEDULE DIRECTORIES SHALL BE UPDATED AND TYPEWRITTEN.
22.
ALL EQUIPMENT, FIXTURES AND DEVICES REMOVED SHALL BE STORED AS
DIRECTED BY THE OWNER OR RELOCATED AS INDICATED. PROVIDE FOR
CONTINUITY OF EXISTING CIRCUITS TO REMAIN.
OUTAGES SHALL BE COORDINATED WITH THE OWNER AND GENERAL
CONTRACTOR A MINIMUM OF 5 WORKING DAYS PRIOR TO COMMENCEMENT OF WORK.
1. WHERE PLANS AND SPECIFICATIONS MAY BE CONSTRUED TO BE IN CONFLICT,
THE MORE STRINGENT REQUIREMENT SHALL BE COMPLIED WITH.
2. ALL WORK SHALL COMPLY WITH THE EDITION OF THE 2011 NATIONAL ELECTRIC
CODE (N.E.C.).
3. THE SPECIFICATIONS ARE AS BINDING ON THE CONTRACTOR AS THE
DRAWINGS. THE CONTRACTOR SHALL READ THE SPECIFICATIONS AND SHALL
INCLUDE ALL ITEMS REQUIRED BY THE SPECIFICATIONS BEFORE SUBMITTING A
BID.
4. MINIMUM WIRE SIZE SHALL BE #12 AWG UNLESS OTHERWISE NOTED.
5. EACH CIRCUIT SHALL HAVE AN EQUIPMENT GROUNDING CONDUCTOR, AND
MULTI-WIRE CIRCUITS OF DIFFERENT PHASES MAY SHARE THE EQUIPMENT
GROUND. EQUIPMENT GROUND CONDUCTOR SIZE SHALL NOT BE LESS THAN
#12 AWG OR AS INDICATED ON THE DRAWINGS.
6. ALL CONDUCTORS #10 AND SMALLER SHALL BE SOLID COPPER, EXCEPT
WHERE FLEXIBILITY IS REQUIRED, AND ALL CONDUCTORS #8 AND LARGER
SHALL BE STRANDED COPPER USING BOLTED LUGS AT TERMINALS.
7. ALL EQUIPMENT AND DEVICES SHALL BE INSTALL PLUMB, SQUARE AND TRUE.
ALIGN EQUIPMENT HORIZONTALLY OR VERTICALLY FOR A NEAT AND
PROFESSIONAL INSTALLATION.
8. ALL ELECTRICAL EQUIPMENT AND DEVICES SHALL BE LABELED WITH THE
PANEL NAME AND CIRCUIT NUMBER(S).
9. JUNCTION BOXES SHALL BE LABELED WITH THE LIST OF CIRCUITS BY PANEL
NAME AND CIRCUIT NUMBER.
10. VERIFY EXACT LOCATION, ELEVATION AND REQUIREMENTS OF ALL
MECHANICAL EQUIPMENT WITH MECHANICAL CONTRACTOR.
11. VERIFY EXACT LOCATION, ELEVATION AND REQUIREMENTS OF ALL PLUMBING
EQUIPMENT WITH PLUMBING CONTRACTOR.
12. ALL LOW VOLTAGE INTERLOCKING OF HVAC EQUIPMENT SHALL BE BY
THECONTROLS CONTRACTOR. ALL "LINE VOLTAGE" CONTROLS SHALL BE BY THE
ELECTRICAL CONTRACTOR AND SHALL BE IN CONDUIT.
A. THE ELECTRICAL CONTRACTOR SHALL DISCONNECT POWER TO ANY AND ALL LIGHTS, WIRING DEVICES AND HVAC
EQUIPMENT PRIOR TO MOVING, REMOVAL OR INSTALLATION. FOR DEMO'D EQUIPMENT REMOVE ALL RELATED SWITCHES, DISCONNECTS, WIRE AND CONDUIT IN ITS ENTIRETY EXCEPT AS IT WILL SERVE NEW DEVICES OR THE
EXISTING DEVICES AND EQUIPMENT WHICH ARE TO REMAIN.
B. THE ELECTRICAL CONTRACTOR IS ADVISED TO VISIT THE SITE TO FAMILIARIZE HIMSELF WITH ALL EXISTING CONDITIONS PRIOR TO THE BID AND FIELD VERIFY DISTANCES, QUANTITIES AND RELEVANT CONDITIONS. THE
CONTRACTOR SHALL PROVIDE ALL REQUIREMENTS FOR COMPLETED INSTALLATIONS.
C. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL DEMOLITION IN AREAS OF RENOVATION. ALL WIRING DEVICES, LIGHT FIXTURES, WIRE, AND CONDUIT THAT IS TO BE REMOVED SHALL BE EITHER STORED, AS DIRECTED BY THE OWNER, RELOCATED AS SHOWN ON THE NEW FLOOR PLANS, OR ELSE REMOVED FROM THE PREMISES. EXISTING
DEVICES AND EQUIPMENT THAT ARE ABANDONED SHALL BE REMOVED.
D. ALL EXISTING CONDUCTORS THAT ARE NOT USED SHALL BE REMOVED BACK TO THE SERVING PANELBOARD. THE ASSOCIATED CIRCUIT BREAKERS SHALL BE LABELED AS "SPARE", AND EXISTING CONDUIT SHALL REMAIN FROM THE PANEL TO ABOVE ACCESSIBLE CEILING SPACE, WHERE SUCH EXISTS. REMOVE ALL OTHER ABANDONED CONDUIT
WHERE EVER IT IS ACCESSIBLE.
E. APPROPRIATE MEASURES SHALL BE TAKEN TO ASSURE CONTINUITY OF EXISTING CIRCUITS THAT REMAIN. ALL OUTAGES WHICH MAY RESULT SHALL BE COORDINATED WITH THE OWNER PRIOR TO THE COMMENCEMENT OF WORK.
THE ELECTRICAL CONTRACTOR SHALL ONLY SPLICE CONDUCTORS AS PERMITTED AND ENSURE THAT EXISTING CIRCUIT CONTINUITY FOR EVERY DEVICE IS MAINTAINED. INACCESSIBLE CONDUIT MAY BE ABANDONED IN PLACE. ALL JUNCTION BOXES ASSOCIATED WITH THIS SCOPE THAT ARE TO REMAIN MUST BE ACCESSIBLE PER NEC.
F. ALL EXISTING BRANCH LIGHTING CIRCUITS THAT ARE AFFECTED BY DEMOLITION, ADDITION OR RELOCATION SHALL BE FIELD TESTED FOR MAXIMUM LOAD AT THE PANEL BOARD. PROVIDE AS-BUILT MARK-UP DRAWINGS SHOWING RESULTING LOAD VALUES FOR EACH CIRCUIT. IMMEDIATELY NOTIFY ENGINEER OF ANY CIRCUIT EXEEDING 70 PERCENT OF AMPERAGE RATING OF THE OVER-CURRENT PROTECTIVE DEVICE (OCPD). IF THE PEAK CIRCUIT LOAD EXCEEDS 80% OF THE CONDUCTOR RATING OR OCPD RATING FOR THOSE CIRCUITS AFFECTED BY THIS SCOPE OF WORK, SOME PORTION OF THAT CIRCUIT WILL BE REQUIRED TO RECIRCUITED TO A NEW BREAKER AT THE SERVING
PANELBOARD. COORDINATE ALL REQUIREMENTS WITH ENGINEER.
G. PROVIDE NEW PANEL SCHEDULE DIRECTORY WITH UPDATED INFORMATION FOR ALL PANELS AFFECTED BY
DEMOLITION, ADDITION OR RELOCATION OF EQUIPMENT.
H. PROVIDE FOR FULLY OPERATIONAL MODIFICATIONS AND INSTALLATIONS.
I. E.C. SHALL PROVIDE FOR THE DEMOLITION STIPULATIONS OF THE ENGINEER, UTILITIES AND OTHER DESIGN DISCIPLINES.
J. COORDINATE WITH OWNER A MIN. OF 5 WORKING DAYS IN ADVANCE FOR ALL OUTAGES OF ANY SERVICE UTILITIES. REFER TO SPECIFICATION FOR ADDITIONAL REQUIREMENTS REGARDING ALL OUTAGES OF ANY SERVICE UTILITIES FOR THIS
BUILDING, ANY OTHER BUILDING OR ANY OTHER POINT OF USE.
K. OCCUPIED AREAS SHALL BE KEPT CLEAN OF DEBRIS ON A CONTINUAL BASIS. ALL RUBBISH SHALL BE REMOVED FROM
THE SITE AND TAKEN TO APPROPRIATE DISPOSAL FACILITIES.
GENERAL ELECTRICAL DEMOLITION NOTES
MDP 7-1 (EXISTING)
600A, 480V, 3Ø, 4W
SE RATED, 22KAIC, 600A MCB
ALL BREAKERS SHALL BE LSI ADJUSTABLE TRIP
200A225A 225A200A 200A
B O
IL
E
R
B O
IL
E
R
B O
IL
E
R
D E
A E
R A
T O
R
200A 125A 125A 125A
S P
A R
E
S P
A R
E
TE
M
P O
R A
R Y
B O
IL
E
R
S P
A R
E
125A
S U
R G
E T
A N
K
70A
ATS 7-1 (EXISTING)
SE RATED
600A, 480V, 3P
35KAIC
OPEN TRANSITION
NEW
GENERATOR
350KW
G
600A
NH-7-1 (EXISTING)
225A, 480V, 3Ø, 4W
225A MCB, FEED THRU LUGS
TN-7-1 (EXISTING)
75KVA, 480VY/120-208V
NL-7-1 (EXISTING)
225A, 208V, 3Ø, 4W
225A MCB, FEED THRU LUGS
NH-7-2 (EXISTING)
225A, 480V, 3Ø, 4W
225A MCB, FEED THRU LUGS
TN-7-2 (EXISTING)
75KVA, 480VY/120-208V
NL-7-2 (EXISTING)
225A, 208V, 3Ø, 4W
225A MCB, FEED THRU LUGS
225A
225A
NL-7-1B (EXISTING)
225A, 208V, 3Ø, 4W
225A MCB, FEED THRU LUGS
225A
225A
125A
125A
R V
T R
A N
S F
O R
M E
R
400A
NH-7-E1
(EXISTING)
100A
EXISTING FEEDER FROM SUB 1A.
600A, 480V, 3P FUSED
DISCONNECT. FUSED AT
600A (EXISTING)
300KVA ISOLATION
TRANSFORMER.
480V-DELTA/480V-Y
NEMA 3R (EXISTING)
600A, 480V, 3P, 3R
FUSED DISCONNECT.
FUSED AT 600A
(EXISTING)
1. SPARES CREATED BY DEMO OF DRAFT FANS.
2. NEW BOILER CONNECTED TO EXISTING SPARE BREAKER.
KEYED NOTES:
TO
TEMPORARY
BOILER
PROVIDE
100 AMP
DISCONNECT
AT 50A FUSE
FOR
TEMPORARY
BOILER
ISSUE DATE:
SHEET NUMBER:
PROJECT NUMBER:
5800 EVERGREEN DRIVE
LITTLE ROCK,
ARKANSAS
72205-1757
Phone: (501) 666-6776 Fax: (501) 663-8888 tme@tmecorp.com
SHEET TITLE:
ENGINEER SEAL
CORPORATE SEAL
MARK DATE DESCRIPTION
E401
SCHEDULE, LEGEND, NOTES
AND DETAIL - ELECTRICAL
03-24-14
01-13-0018
B ui ld in g
B oi le r #3
R ep la ce m en t Je ffe rs on L ab or at or ie s
F oo d an d D ru g
A dm in is tr at io n
N C
T R
R d
Je ffe rs on
, A R
CONSTRUCTION
DOCUMENT
1/4" = 1’−0"
ONE−LINE DIAGRAM − BOILER #3 INSTALLATION
File details come from the government source that posted it. Updated .