This document contains an amendment to a federal contract solicitation and the related solicitation. The amendment extends the proposal due date to October 22nd, 2020 and provides responses to bidder inquiries. The solicitation is for the construction of a Fuels Storage Complex Replacement at the Quonset Point Rhode Island Air National Guard Station. The work includes replacing truck offload and fillstand positions, associated pumping and filtration equipment, constructing a new 600 GPM pumphouse and control room, upgrading the refueler parking area, and reusing existing storage tanks. The NAICS code is 236220 and the estimated value is between $5-10 million. The requirement will be solicited as a small business set-aside using Best Value Tradeoff procedures by the Department of the Army Corps of Engineers New England District.
View the file
Other files
Show 40 more
Latest 50 of 51 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER (Type or print)
30-105-04EXCEPTION TO SF 30
APPROVED BY OIRM 11-84
STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA
FAR (48 CFR) 53.243
This Amendment is issued to provide: 1) Extend the Proposal Due Date from 15 Oct 2020 to 22 Oct 2020; 2) Revised Bidding Schedule; 3) Responses to Bidder Inquiries/Requests for Information and 4) Corresponding revised Specification Sections(s) and/or Draw ings. All other terms and conditions remain unchanged.
1. CONTRACT ID CODE PAGE OF PAGES
1 11
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
16C. DATE SIGNED
BY 09-Oct-2020
16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR
(Signature of Contracting Officer)(Signature of person authorized to sign)
8. NAME AND ADDRESS OF CONTRACTOR (No., Street , County, State and Zip Code) X W912WJ20R0011
X 9B. DATED (SEE ITEM 11)
10-Aug-2020
10B. DATED (SEE ITEM 13)
9A. AMENDMENT OF SOLICITATION NO.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer X is extended, is not extended.
Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:
(a) By completing Items 8 and 15, and returning 1 copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN
REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE
CONTRACT ORDER NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
10A. MOD. OF CONTRACT/ORDER NO.
2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)
6. ISSUED BY
3. EFFECTIVE DATE
09-Oct-2020
CODE
US ARMY ENGR DISTRICT, NEW ENGLAND
696 VIRGINIA ROAD
CONCORD MA 01742-2751
W912WJ 7. ADMINISTERED BY (If other than item 6)
4. REQUISITION/PURCHASE REQ. NO.
CODE
See Item 6
FACILITY CODECODE
EMAIL:TEL:
W912WJ20R0011
SECTION SF 30 BLOCK 14 CONTINUATION PAGE
SUMMARY OF CHANGES
SECTION 00010 - SOLICITATION CONTRACT FORM
The required response date/time has changed from 15-Oct-2020 02:00 PM to 22-Oct-2020
02:00 PM.
The following have been added by full text:
BIDDER INQUIRIES/REQUEST FOR INFORMATION:
1. Information:
Section 26 32 15.00 10 DIESEL-GENERATOR SET STATIONARY 100-2500 KW, WITH AUXILIARIES paragraph
3.11 PERMITS states, "The Contractor shall assist the Contracting Officer in obtaining Federal, State of Rhode Island and local permits for the generator set. The Contractor shall provide all documentation necessary to be submitted with permit applications."
Section 01 57 19 TEMPORARY ENVIRONMENTAL CONTROLS, paragraph 1.6.8.2 Pollution Generating Equipment states, "Identify air pollution generating equipment or processes that may require federal, state, or local permits under the Clean Air Act. Determine requirements based on any current installation permits and the impacts of the project. Provide a list of all fixed or mobile equipment, machinery or operations that could generate air emissions during the project to the Installation Environmental Office (Air Program Manager). Note that permits for air emission sources can take more than 8 months to be issued/approved."
Section 01 57 19 indicates that requirements are to be determined based on any current installation permits and the impacts of the project and section 26 32 15.00 10 indicates that the contractor is to assist the Contracting Officer in obtaining Federal, State of Rhode Island and local permits for the generator set and provide documentation necessary to be submitted with permit applications.
Questions:
1) Is the contractor to pay permitting costs associated with the generator?
2) Please confirm that the Contracting Officer is effecting the determination of the requirements for permitting and type of permit, or otherwise clarify and further direct.
3) Please confirm that the Contracting Officer is completing and then filing the permit, or otherwise clarify and further direct.
4) Please confirm the 8 month duration and additionally advise as to when the generator cab be released for fabrication, in regards to the status of the permit. (ProjNet ID 8802929)
GOVERNMENT RESPONSE:
The Installation Environmental Office Air Program Manager will apply for the air permit for the generator.
The Contractor must provide the Air Program Manager with the generator specifications needed to complete the permit application.
There is no statutory time frame for RIDEM to issue air permits, therefore, we cannot determine how long the review/approval of a permit application takes. The permit is required prior to operation of the generator. Contractor should provide the generator information to the Environmental Office Air Program Manager as soon as possible.
2. Drawing G-013 Phase 2 Demolition Note #1 and C-407 / C-407A Note #2 both indicate that a gravel surface layer will be provided for all unpaved surfaces inside the new permanent fence line. Per the above drawings, it is acceptable to stockpile the existing gravel surface layer and respread it, but if there is not enough material available then new material will be required.
Only Boring Log #3 indicates a top layer of crushed stone on drawing G-015, and this top layer is only shown as
0.25". No specification specifically relating to this gravel surface layer is available, and there are no cross sections in the civil construction plans illustrating this new gravel surface layer.
Please clarify/confirm the following:
a) Please confirm for bidding purposes the assumed thickness of the existing gravel surface layer around the existing fuel facility.
b) What is the desired thickness of the new gravel surface layer? Please provide a corresponding detail.
c) Please confirm for bidding purposes the gradation of the gravel surface layer.
d) Please provide a specification that specifically addresses this gravel surface layer. (ProjNet ID 8778606)
GOVERNMENT RESPONSE: See Revised G-009
a) The 0.25 inches should read 0.25 feet. (3 inches)
b) Provide 3-inches of gravel on all unpaved surfaces as indicated in the bid.
c) For bidding purpose assume the gravel will be similar to a #57 stone gradation
d) Follow instruction in Note on Drawing G-013
3. Specification 01 45 35 paragraph 1.2 states "Perform Special Inspections in accordance with the Statement of Special Inspections, Schedule of Special Inspections... The Statement of Special Inspections and Schedule of Special Inspections are included as an attachment to this specification." There is not Schedule of Special Inspections attached to specification 01 45 35, please provide the Schedule. (ProjNet ID8787174)
GOVERNMENT RESPONSE: See Attachment Schedule of Special Inspections.
4. Information - Existing equipment on fuel tanks Reference: Drawings ES404 and ES508 Drawing ES404 states that the equipment on the fuel tanks is existing. Drawing ES508 shows new equipment on the fuel tanks.
Questions:
A. What equipment is existing?
B. What equipment is new?
C. What equipment is being replaced?
D. Is any of the equipment being relocated or extended?
(ProjNet ID 8802512)
GOVERNMENT RESPONSE:
A. All equipment shown on the tanks on drawing ES508 is existing. The note pointing at the high level alarm (HLA) and high-high level alarm (HHLA) should read "Typical level alarm."
B. Refer to the Mechanical Fueling drawings to determine whether any equipment on the tanks is new.
C. Refer to the Mechanical Fueling drawings to determine whether any equipment on the tanks is being replaced.
D. Refer to Mechanical Fueling drawings to determine whether any equipment on the tanks is being relocated or extended.
5. Drawing G004, Note #4 provides a description of the Phase 1 temporary R11 vehicle parking area. The area is to be constructed by removing the existing curb and gravel surfacing, placement of a temporary fuel resistant liner system.
There is not requirement for temporary asphalt pavement. Please confirm that no temporary asphalt pavement is needed in this temporary parking area. (No ID#)
GOVERNMENT RESPONSE: Please provide temporary asphalt in area indicates as “Temporary Refueler Parking” on Drawing G-009. Follow detail 13/C-502.
6. The following questions have been posed by several electrical equipment manufacturers (GE, Seimens, SquareD and Eaton) due to these specification and drawing questions these gear suppliers indicate that they could not provide a conforming quotation for the equipment, as discussed below.
Specification 26 24 19.00 40** paragraph 2.2.2.1 requires a Type 1B arc resistant motor control center enclosure in accordance with IEEE C37.20.7
The design currently requires drawout mains (Main-Gen application). These are not available with arc resistant construction.
An alternative would be to provide the mains in QED construction (would not be arc resistant and have a larger footprint than allowed) these could not be bus connected to the arc resistant MCC sections.
Another alternate would be to provide PZ4 mains. These would be too deep, would require front access only and is not available in arc resistant construction and could not be bus connected to the arc resistant MCC sections.
If ArcBlock technology on the mains is used in lieu of arc resistant construction, drawout mains would be too large and alternatives for drawout QED or PZ4 mains would be too large
Comment from one gear supplier:
The design should have utilized an arc resistant switchgear lineup with a feeder breaker to a separate arc resistant MCC Draw-out insulated-case breakers in MCC construction can’t be provided in arc resistant or non-arc resistant construction
Additional issues that may be problematic and should be addressed with the items discussed above:
The specification requires severe duty RVAT’s and are only available in IEC not NEMA. These IEC controllers are not available in arc resistant MCC’s
The MCC schedule requires all breakers 100A and above to be ground fault. The feeder for panel HP will be in an 18” bucket and the 100A breakers will be in 12” buckets. The front elevation drawing shows 6” breaker buckets. This requirement will likely cause issues meeting the footprint requirements.
The EFSO system is shown to be mounted in the MCC. Is not the EFSO system a series of stand-alone switches throughout the facility with wiring daisy chained back to the MCC? (No ID#)
GOVERNMENT RESPONSE:
1. Type 1B arc-resistant MCC construction is not required because of the relatively low fault current available at the MCC for this project, 20,200A RMS Symmetrical. Paragraph 2.2.2.1 of Specification Section 26 24 19.00 40** has been deleted.
2. The EFSO terminal cabinet in the MCC can be reduced to a 6” bucket and relocated to the bottom of section 5.
Panel HP can move to section 6, bottom (where EFSO terminal formerly located). Section 1: Delete spare buckets, relocate Offload 1 & 2 to section 1. Water heater bucket to remain in section 5. The MCC elevation, sheet EP601, has been modified.
3. The requirement for “Severe Duty RVAT’s” has been changed to “RVSS” (Reduced Voltage Solid State) per the latest UFGS specifications. Paragraph 2.4.1.2 has been revised. Per notes on EI601 and EI602, components are located in the EFSO panel unless indicated otherwise. Per note on EI602, only the starters are located in the MCC with wiring from the EFSO panel to FP-1, FP-2, FP-3 and FTP-1. The EFSO terminal shown on the MCC elevation, sheet EP601, is for wiring connections only.
7. See attached drawings ES507, the circuits noted (EFSO panel, ATG power/controls, float switches, overfill valve, FTP- 1, WP-1, leak detection, PP2-16) are not shown on the conduit schedule. Please clarify the conduit and wire sizes. (No
ID#)
Government Response: See Amendment 0008 Response to #9 (ProjNet ID 8802701).
8. See attached drawing, Note 6 the power and control circuits for the personnel gate lock and control stations are not shown on the conduit schedule. Please clarify wire size requirements. (No ID#)
GOVERNMENT RESPONSE: The Contractor shall assume 2#12&1#12G for power to the gate lock from Panel P1 in Building 14 and 8#14&1#14G to the control stations (4 to each). This wiring will fit in a 1" conduit. The actual wiring required shall be confirmed with the approved shop drawings for the gate operator and control equipment. Provide a new 20A, 1 pole bolt-on circuit breaker to be installed in Panel P1 which is a Square D Type NQOB panelboard. See Drawings ES403 and ES404.
9. Specs call for Arc Resistant MCC construction Drawings show drawout mains, (Main-Gen application) which are not available with AR construction.
Alt to provide the mains in QED construction would not be AR, would have larger footprint than allowed, and could not be bus connected to the AR MCC sections.
Alt to provide PZ4 mains would be too deep, would require front access only, which isn’t available in AR construction, and could not be bus connected to the AR MCC sections.
If we take exception to the AR requirement and quote ArcBlock technology, on the mains:
Drawout MCC mains would still be too large Alts for Drawout QED or PZ4 mains would still be too large
Additional issues that may cause problems once we decide which way to go:
They spec severe duty RVATs and those are only available in IEC, not NEMA, and IEC controllers are not available in AR MCC’s.
The MCC schedule asks for all breakers 100A and above to have ground fault. The feeder for panel HP will be in an 18” bucket and the 100A feeders would be in 12” buckets. Their front elevation drawing shows 6” breaker buckets. This will likely cause issues with meeting the footprint requirements.
The larger overarching concern is that there is not enough room in the currently designed Control Room to install the MCC. If the specifications remain as is with the Arc Resistant requirement, there is additional space required behind the MCC to meet the specification that is not presently available in the Control Room.
If the specifications are to be maintained, the Control Room layout and construction needs to be reconsidered (re-designed).
Also caution, that we cannot utilize IEC code equipment on this project. UL is the typical guidance from our experience working with USACE Omaha MCX. (No ID#)
GOVERNMENT RESPONSE:
1. Type 1B arc-resistant MCC construction is not required because of the relatively low fault current available at the MCC for this project, 20,200A RMS symmetrical. Paragraph 2.2.2.1 of Specification Section 26 24 19.00 40** has been deleted.
2. The requirement for “Severe Duty RVAT’s” has been revised to “RVSS” (Reduced Voltage Solid State) per the latest UFGS specifications. See Paragraph 2.4.1.2 has been revised.
3. The EFSO terminal cabinet in the MCC can be reduced to a 6” bucket and relocated to the bottom of section 5.
Panel HP can move to section 6, bottom (where EFSO terminal formerly located). Section 1: Delete spare buckets, relocate Offload 1 & 2 to section 1. Water heater bucket to remain in section 5. The MCC elevation, sheet EP601, has been modified.
**REVISED SPEC 26 24 19.00 40 IS ANNOTATED WITH AMENDMENT 0007, ALL REVISIONS APPLY TO
RESPONSES FROM AMENDMENT 0009
LIST OF REVISED DOCUMENTS
As a result of revisions, other documents required revision. This list shows which amenemdnent and question revised documents are associated with.
Amendment 0002 Question 8 – ProjNet ID 8762399
ES507
Question 9 – ProjNet ID 8762540
EP101, EP601, EP602
Amendment 0004 Question 1 – ProjNet ID 8763069 M-302, M-403, M-603 Question 4 – ProjNet ID 8773881 A-101, A-002, A-103, A-202, A-302 Question 8 – ProjNet ID 8802520
ES401, EP602
Question 9 – ProjNet ID 8802556
ES401, EP604
Question 10 – ProjNet ID 8802578
ES401
Question 12 - ProjNet ID 8802658
E001, EP101
Question 13 – ProjNet ID 8802663
EP101
Question 16 – ProjNet ID 8802685
A-101, EP101
Amendment 0006 Question 3 – ProjNet ID 8774040
A-101, A-002, A-103, A-202, A-302, MH-101
Question 4 – ProjNet ID 8789104 A-101, A-002, A-103, A-202, A-302, A-501 Question 5 – ProjNet ID 8789108 A-101, A-002, A-103, A-202, A-302 Question 6 – ProjNet ID 8773802 A-202, A-302
Amendment 0008 Question 1 – ProjNet ID 8802506
ES404
Question 2 – ProjNet ID 8802493
ES101, ES401
Question 5 – ProjNet ID 8776321 G-013, C-407 Question 7 – ProjNet ID 8802582
ES401
Question 8 – ProjNet ID 8802588
ES401, EP603, EP603
Question 9 – ProjNet ID 8802701
ES507
Question 10 – ProjNet ID 8762504 Spec 33 52 43.11 Question 11 – ProjNet ID 8778658 Spec 03 30 00 Question 12 – ProjNet ID 8778658 Spec 32 13 13.06
Amendment 0009
Question 2 – ProjNet ID 8778606 G-009 Question 3 – ProjNet ID 8787174 Schedule of Special Inspections Question 4 – ProjNet ID 8802512
ES508
Question 5 – No ID# G-009 Question 6 – No ID# Spec 26 24 19.00 40 par 2.2.2.1 and 2.4.1.2 Question 8 – No ID#
ES403, ES404, EP601
Question 9 – No ID# Spec 26 24 19.00 40, EP601, The following have been modified:
BID SCHEDULE
REVISED
BIDDING SCHEDULE
Refer to Section 01 22 00 MEASUREMENT AND PAYMENT for additional information concerning each price item and description of each price item and form of measure.
Item No. Description Quantity Unit Price Amount
BASE ITEMS
0001 Fuel Storage Complex One Job
Replacement
Furnishing and Delivering Prestressed Concrete Piles
LF
Driving Prestressed Concrete Piles
Prestressed Concrete Pile Compressive Load Tests
EA
Base Items Total
OPTIONAL ITEMS
0005 Canopy Foundation One Job $
Canopy Superstructure
One
Job
Item No.
Description
Est Lo/Hi Qty. Limit
Unit
Unit Price
Estimated Amount
Contaminated Soil:
Cost of testing and stockpiling of contaminated soil
0007A First 20 CY 20 CY $ $
0007B Over 20 CY 40
CY
Contaminated Soil:
Cost of transporting and disposal of contaminated soil
0008A First 20 CY 20 CY $ $
0008B Over 20 CY 40
CY
Asbestos Containing Gasket
0009A First 10 gaskets 10
0009B Over 10 gaskets 20
Transite Pipe
0010A First 10 linear feet 10 encountered
0010B Over 10 linear feet 20
Item No.
Description
Est Lo/Hi Qty. Limit
Unit Unit Price
Estimated Amount
Lead Contaminated Material
0011A Provide cost per ton 03 Ton $ $ This unit cost will be applied for the first 3 tons are encountered
0011B
Provide cost per ton
Ton $
This unit cost will be applied when more than 3 tons are encountered
ATG Related Work
One
Job
0013 Additional year of
Overall Warranty of Construction
Optional Items Total
One Job $
Total for Base and Optional Items $
Note 1: "CY" = Cubic Yard; "LF" = Linear Foot
Note 2: Offerors must price all items. The work will be awarded as a whole to one offeror. Offers will be evaluated and the low offer will be determined by the Total Estimated Amount for Line Items 0001 through 0013. The minimum work awarded will be for the Base Price items.
Note 3: Line Item Numbers 0005 and 0006 above are Optional Price Items that may, at the option of the Government, be exercised at any time up to 60 calendar days from the receipt by the Contractor of the Notice to Proceed. If these Optional Items are awarded, no additional calendar days will be added to the project duration.
Note 4: Line Item Number 0012 above is an Optional Price Item that may, at the option of the Government, be exercised at any time up to 180 calendar days from the receipt by the Contractor of the Notice to Proceed. If this Optional Item is awarded, no additional calendar days will be added to the project duration.
Note 5: Line Item Numbers 0007, 0008, 0009, 0010 and 0011 are Optional Price items that may, at the option of the Government, be exercised at any time if this work is encountered through the end of the period of performance of this contract and are subdivided into estimated quantities and shall be separately priced. The Government will evaluate this item on the basis of the total price of its sub-items. See SPECIAL CONTRACT REQUIREMENTS, Clause, "VARIATION IN ESTIMATED QUANTITIES - SUBDIVIDED
ITEMS" (52.211-5001)
Note 6: All work shall be completed within the time period specified in Section 00 80 00 SPECIAL CONTRACT REQUIREMENTS, Subpart COMMENCEMENT, PROSECUTION AND COMPLETION OF WORK (APR 1984) FAR 52.211-10 document.
Note 7: In the event there is a difference between a unit price and the extended total, the unit price will be held to be the intended price.
If the offeror shows only the total price but fails to enter a unit price, the total divided by the estimated quantity will be held to be the intended unit price.
Note 8: Line Item Number 0013 is an Optional Price Item that must be exercised at the time of contract award.
POC NAME___________________________________
POC EMAIL__________________________________