This federal solicitation is seeking proposals for the operation and maintenance of the US Navy Medical Research Unit Six facilities in Peru. Requirements include preventative, predictive, demand, and emergency maintenance of systems across medical research laboratories, support structures, and satellite facilities. Limited grounds keeping is also required. Defense Base Act insurance will be applicable. A firm-fixed-price contract with a one year base period and four one-year options is anticipated. The Army Corps of Engineers Mobile District will direct the work. Offerors must check the website for any solicitation changes, as the document will only be posted digitally on SAM.gov and not provided in paper format. The size standard is $41.5M average annual gross revenue for the past three years under NAICS 561210.
View the file
Other files
Show all 45
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Standard Service Order #
Title Request Date Room
Employee reporting the issue Status
Assigned to facilities technician Due Date
20417 IQUITOS, Monthly inspection November to Cummins storage tank. 11/9/2021 Generator area. Davila Pedro Active Acosta Ricardo 11/16/2021
20415 Monthly inspection November to FULTON 100 gallons local diesel storage tank. 11/9/2021 Fulton room, B2 Davila Pedro Active Ugarte Luis 11/9/2021 20414 Monthly inspection November to HVAC 100 gallons local diesel storage tank. 11/9/2021 Container HVAC. Davila Pedro Active Ugarte Luis 11/9/2021 20413 Monthly inspection November to GENERATOR 320 gallons local diesel storage tank. 11/9/2021 Generator room B1. Davila Pedro Active Ugarte Luis 11/9/2021
20412 Monthly inspection November to 8,000 gallons diesel storage tank. 11/9/2021 Diesel tank area. Davila Pedro Active Acosta Ricardo 11/9/2021
20410 replace pictures of officers in repection area 11/8/2021 B10-F1-RECEPCION Rodriguez Jesus Active Rodriguez
Jesus 11/8/2021
20409 pour salt in water softener of animal facilities boiler 11/8/2021 B2-F1-R-118 BOYLER. Rodriguez Jesus Active Rodriguez
Jesus 11/9/2021
20388 Increase the light levels in fume hood room at Iquitos 10/28/2021 Room -fume hood -, Entomologia, Iquitos Flores Carmen Active
20380 Schedule quarterly Preventive Maintenance (PM) two A/Cs of 60kBT each one in the freezer room at B1, F2. 10/26/2021 Freezer room at B1, F2. Davila Pedro Active Ugarte Luis 10/30/2021 20379 Schedule quarterly Preventive Maintenance (PM) two A/Cs of 60kBT each one in the freezer room at B1, F1. 10/26/2021 Freezer room at B1, F1. Davila Pedro Active Ugarte Luis 10/30/2021 20378 Schedule quarterly Preventive Maintenance (PM) to A/C 60KBT in data room B1, F2 10/26/2021 Data room B1, F2 Davila Pedro Active Ugarte Luis 10/28/2021 20377 Schedule quarterly Preventive Maintenance (PM) to A/C 36KBT in data room B1, F2 10/26/2021 Data room B1, F2 Davila Pedro Active Ugarte Luis 10/28/2021 20369 Replace fluorescent led tube in the IT Container. Miguel Ramirez Office. 10/22/2021 IT Container. Davila Pedro Active Davila Pedro 10/22/2021 20368 Replace three fluorescent 3x18Wat in the reception area, close to Rony Sanchez Office. 10/22/2021 Reception, B10,F1 Davila Pedro Active Davila Pedro 10/22/2021
20367 Painting in repection area 10/22/2021 B-10 F1 RECEPCION. Rodriguez Jesus Active Rodriguez
Jesus 10/22/2021
20362 water is on the floor close to toilet, inspect and repair it. 10/19/2021 Men bathroom at B2,F1. Davila Pedro Active Rodriguez Jesus 10/19/2021
20327 MdD-Monthly inspection September to 100 gallons diesel storage tank. 9/21/2021 Generator room Davila Pedro Active Davila Pedro 9/21/2021 20326 MdD-Annual inspection September to 100 gallons diesel storage tank. 9/21/2021 Generator room Davila Pedro Active Davila Pedro 9/21/2021
20325 IQUITOS - Monthly inspection September to GENERATOR CUMMINS diesel storage tank. 9/21/2021 Generator area. Davila Pedro Active Acosta Ricardo 9/27/2021
20324 IQUITOS - Annual inspection September to GENERATOR CUMMINS diesel storage tank. 9/21/2021 Generator area. Davila Pedro Active Acosta Ricardo 9/27/2021
20311 Install chains to fix sharp container 9/8/2021 Room 217 PRNT, Dpto. VEID Huaman Alfredo Active Rodriguez
Jesus 9/20/2021
20301 4 Duplicates of keys for office 215 - Building 2 8/27/2021 Ampuero Julia Active Davila Pedro 9/9/2021
20285 Mantenimiento preventivo A/Cs freezer room B1F2 8/18/2021 Mantenimiento preventivo a los dos aires Acondicionado en el freezer room B1,F2 Davila Pedro Active Ugarte Luis 8/21/2021
20284 Mantenimiento preventivo A/Cs freezer room B1F1 8/18/2021 Mantenimiento preventivo a los dos aires Acondicionado en el freezer room B1,F1 Davila Pedro Active Ugarte Luis 8/21/2021
20283 Quarterly Preventive Maintenance to A/As data center B1, F2 8/18/2021 B1, F2 Davila Pedro Active Ugarte Luis 8/21/2021 20281 EXIT signs on laboratory area - CAP 8/16/2021 B1 and B2 laboratories Rivera Ines Active 20280 Reflective Tapes on Laboratory Areas - CAP 8/16/2021 B1 and B2 Rivera Ines Active
20249 Acomodar Cables eléctricos desordenados 6/16/2021 Rm-218 Castillo Roger Active Quineche Wilver 6/21/2021
20416 MdD, Monthly inspection November to Cummins storage tank. 11/9/2021 Generator area. Davila Pedro Closed Davila Pedro 11/9/2021
20411 Monthly inspection October to 8,000 gallons diesel storage tank. 11/9/2021 Diesel tank area. Davila Pedro Closed Acosta Ricardo 11/9/2021
20408 Repair one leg wheel of the office chairB2, Basement. 11/5/2021 B2, Basement. Davila Pedro Closed Rodriguez Jesus 11/5/2021
20407 Dirt coming from vents 11/5/2021 Bldg 2, Rm 203 Graf Paul Closed Acosta Ricardo 11/5/2021
20406 Replace broken shelve of the bookcase in office 104, B1,F1. 11/5/2021 office 104, B1,F1. Davila Pedro Closed Rodriguez Jesus 11/5/2021
20405 Repair broken drain pipe PVC 2" of the UPS Air conditioners. 11/4/2021 roof electrical room B1. Davila Pedro Closed Rodriguez Jesus 11/5/2021
20404 Coser toldo azul todo lado puerta biomedical. 11/4/2021 Picnic B11. Davila Pedro Closed Acosta Ricardo 11/5/2021
20403 Turn on for 30minutes or one hour the power generator, without load. 11/4/2021 Power generator room. Davila Pedro Closed Quineche Wilver 11/5/2021
20402 Cambio de florescente 11/4/2021 Container # 1 Bedoya Edgar Closed Quineche Wilver 11/4/2021
20401 Activar Badge 11/4/2021 Namru-6 Quineche Wilver Closed Quineche
Wilver 11/4/2021
20400 Activar Badge 11/4/2021 Namru6 Quineche Wilver Closed Quineche
Wilver 11/4/2021
20399 Replace 2 fluorescent bulbs in office 11/3/2021 Building 2, 2nd floor, Room 203 Gonzales Cecilia Closed Quineche
Wilver 11/3/2021
20398 Escort contractor to install concrete stoppers in the parking lot A. 11/3/2021 parking lot A. Davila Pedro Closed Rodriguez Jesus 11/3/2021
20397 Luz pasadizo 11/2/2021 B2, F1 hall 106 Quineche Wilver Closed Quineche
Wilver 11/2/2021
20396 Camara 110 11/2/2021 Anfac rm 110 Cedamanos Diana Closed Quineche
Wilver 11/3/2021
20395 Refri de Frutas 11/2/2021 Anfac al frente del cuarto 115 Cedamanos Diana Closed Acosta
Ricardo 11/3/2021
20394 Replace light bulb in hallway at B10. 11/2/2021 hallway at B10. Davila Pedro Closed Quineche Wilver 11/2/2021
20393 Clean up electrical room at B2 11/2/2021 electrical room at B2 Davila Pedro Closed Quineche Wilver 11/2/2021
20392 Clean up the SE 10kV, and the electrical room and UPS B1. 11/2/2021 Electrical room B1. Davila Pedro Closed Quineche Wilver 11/3/2021
NAMRU-6 STANDARD SERVICE CALL IN 2020 & 2021
Section J - Exhibit 11.2.4
20391 Install a nail to hang up map, Office 102, B1F1. 10/29/2021 Office 102, B1F1. Davila Pedro Closed Rodriguez Jesus 10/29/2021
20390 Monthly inspection (October) to fire extinguishers at N6 10/29/2021 N6 Buildings LIMA Davila Pedro Closed Ugarte Luis 10/29/2021 20389 Monthly inspection (October) to jockey and fire pumps. 10/29/2021 Pit B1 Davila Pedro Closed Ugarte Luis 10/29/2021
20387 Secure cabinet to wall 10/28/2021 Hallway, 2nd floor, Building #2 Gonzales Cecilia Closed Rodriguez
Jesus 10/29/2021
20386 Chairs in hallway 10/28/2021 2nd floor hallway, Building #2 Gonzales Cecilia Closed Villanueva
Edgar 10/29/2021
20385 Maintenance to refrigerator at Occ. Heath Office, B10, F2. 10/27/2021 Heath Office, B10, F2. Davila Pedro Closed Ugarte Luis 11/2/2021
20384 ESCOLTA ALA EMPRESA INOFUENTE PARA LA INSTALACION DE ACRILICO ALAS MESAS DEL PICNIC. 10/27/2021 AREA DEL PICNIC. Rodriguez Jesus Closed Rodriguez
Jesus 10/27/2021
20383 instalar calendario 2022. 10/27/2021 B2-F2-R-207-R-204B.B12 F1 OFICINA. Rodriguez Jesus Closed Rodriguez
Jesus 10/27/2021
20382 lavador de ojo lab 105 10/26/2021 Lab 105 Flores Carmen Closed Rodriguez
Jesus 10/27/2021
20381 Repair soap dispenser, despite it has liquid soap does not work. 10/26/2021 women bathroom, 2nd floor B2. Davila Pedro Closed Rodriguez Jesus 10/26/2021
20376 Schedule quarterly Preventive Maintenance (PM) to A/Cs UPS room. 10/26/2021 UPS room B1, F1 Davila Pedro Closed Ugarte Luis 10/27/2021
20375 Mantenimiento a las duchas de emergencias. 10/25/2021 B1-F2-R-CORREDORB2-F1-R-114
ANFAC.
Rodriguez Jesus Closed Rodriguez
Jesus 10/26/2021
20374 hechar sal industrial al ablandador general 10/25/2021 B1-F1 R- ABLANDADOR GENERAL. Rodriguez Jesus Closed Rodriguez
Jesus 10/26/2021
20373 Pagar sócalo lado impresora B11,F2. 10/25/2021 B11,F2. Davila Pedro Closed Rodriguez Jesus 10/26/2021
20372 FRONT DOOR BUILDING #2 2ND FLOOR 10/25/2021 2nd Floor Building #2 Gonzales Cecilia Closed Rodriguez
Jesus 10/25/2021
20371 ARMAR 3 PANELES INFORMATIVO. 10/22/2021 NAMRU-6 Rodriguez Jesus Closed Rodriguez
Jesus 10/22/2021
20370 ESCOLTA ALA EMPRESA MULTIAGUA 10/22/2021 B2-F1-R BOYLER. Rodriguez Jesus Closed Rodriguez
Jesus 10/22/2021
20366 electrical extension 10/22/2021 buidling 11 second floor Orellana Milagros Closed Quineche
Wilver 10/26/2021
20365 Repair and paint drivers' office 10/22/2021 building 11 second floor Orellana Milagros Closed Rodriguez
Jesus 10/26/2021
20364 Install wall clock Safety office B10,F2. 10/19/2021 safety office B10,F2. Davila Pedro Closed Rodriguez Jesus 10/20/2021
20363 Install wall clok container IT (M.Ramirez) 10/19/2021 container IT (M.Ramirez) Davila Pedro Closed Rodriguez Jesus 10/20/2021
20361 Colocar con cadena un envase de bioseguridad 10/18/2021 lab 105 Flores Carmen Closed Rodriguez
Jesus 10/22/2021
20360 colocar jebe al contorno del marco para amortiguar. 10/15/2021 B10-F2- PUERTA DE INGRESO. Rodriguez Jesus Closed Rodriguez
Jesus 10/15/2021
20359 FUGA DE AGUA LAVADERO DE ENTOMOLOGIA. 10/14/2021 B2-F1-R-105 ENTOMOLOGIA. Rodriguez Jesus Closed Rodriguez
Jesus 10/4/2021
20358 REPARAR FUGA DE AGUA TALLER 10/14/2021 ZONA TALLER DE FACILITIES. JARDIN. Rodriguez Jesus Closed Rodriguez
Jesus 10/14/2021
20357 ESCOLTA A LA EMPRESA SERMECO (MANTENIMIENTO TANQUE DE PETROLIO). 10/14/2021 JARDIN .ZONA TANQUE DE PETROLIO
NAMRU-6.
Rodriguez Jesus Closed Rodriguez
Jesus 10/14/2021
20356 ESCOLTAR EMPRESA MULTI AGUA.( MANTENIMIENTO CLORINADOR ANFAC 10/14/2021 B2-F1-R-117 LIMPIO ANFAC. Rodriguez Jesus Closed Rodriguez
Jesus 10/14/2021
20355 RESIVAR LAS BISAGRAS DE LAS PUERTAS DE LOS CONTAINER. 10/14/2021 JARDIN AL COSTADO DEL B-10. Rodriguez Jesus Closed Rodriguez
Jesus 10/14/2021
20354 ENGRASAR PUERTA DE EMERGENCIA DE SAFE HAVEN. 10/14/2021 B12 -F1- SAFE HAVEN Rodriguez Jesus Closed Rodriguez
Jesus 10/14/2021
20353 Smoke detector fell off on the table, 10/13/2021 container conference room. Davila Pedro Closed Ugarte Luis 10/13/2021
20352 Inspect the emergency door, it makes a noise every times it opens. 10/13/2021 B12, emergency door Davila Pedro Closed Rodriguez Jesus 10/13/2021
20351 Cambiar de enchufe de 220V 10/13/2021 Entomology - R105 (Lab) Flores Carmen Closed Quineche
Wilver 10/15/2021
20350 REVISAR LAVADERO CON SENSOR NOFUNCIONA. 10/12/2021 B11-F2-R- BAÑO DE MUJERES. Rodriguez Jesus Closed Rodriguez
Jesus 10/13/2021
20349 Partial reception of 2000 gallons of diesel. 10/11/2021 Main diesel tank Davila Pedro Closed Ugarte Luis 10/12/2021
20348 Escolta ala empresa Cerper 10/6/2021 namru-6 Rodriguez Jesus Closed Rodriguez
Jesus 10/7/2021
20347 Install alchol gel dispenser on wall Occ Heath Office. 10/6/2021 Occ Heath Office B10,F2. Davila Pedro Closed Rodriguez Jesus 10/6/2021
20346 Revisar el lavador de ojos esta goteando. 10/6/2021 B2-F1-R-105 ENT. Rodriguez Jesus Closed Rodriguez
Jesus 10/6/2021
20345 Repair eye washer in Lab 105 at B2,F1. 10/6/2021 Lab 105 at B2,F1. Davila Pedro Closed Rodriguez Jesus 10/6/2021
20344 REMPLAZAR CERRADURA CON LLAVE PROPIO 10/6/2021 B2-F2-R-204 B OF.DFA. Rodriguez Jesus Closed Rodriguez
Jesus 10/6/2021
20343 desconectar freezer -30 para que entre en mantenimiento 10/5/2021 Edificio 2, primer piso, corridorECN 103411
Flores Carmen Closed Ugarte Luis 10/7/2021
20342 Replace photoelectric cell of the outdoor reflectors lights at B2. 10/5/2021 Replace photoelectric cell of the outdoor reflectors lights at B2. Davila Pedro Closed Quineche
Wilver 10/5/2021
20341 Remove broken 50 litters water heater. 10/4/2021 Lactation room Basement B2. Davila Pedro Closed Rodriguez Jesus 10/4/2021
20340 Change Fluorescent in IM/IT Container #2 10/1/2021 IM/IT Container #2 Ramirez Miguel Closed Quineche
Wilver 10/1/2021
20339 Mantenimiento de Freezer 9/30/2021 Room 120 1er piso Edificio 1 Zamora Jennifher Closed Ugarte Luis 9/30/2021
20338 Fluorescentes quemados 9/30/2021 Room 215, Dept VEID Gamero Maria Closed Quineche Wilver 9/30/2021
20337 Luces Warehouse 9/29/2021 Warehouse Azul Quineche Wilver Closed Quineche
Wilver 9/29/2021
20336 CAMBIAR GRIFO DE JARDIN 9/29/2021 JARDIN DE NAMRU-6 Rodriguez Jesus Closed Rodriguez
Jesus 9/29/2021
20335 TANQUE DE QUIMICO DEL BOYLER MANTENIMIENTO. 9/29/2021 B2-F1-R-CUARTO DEL BOYLER ANF. Rodriguez Jesus Closed Rodriguez
Jesus 9/29/2021
20334 retirar estructura metalica en lab 218 edificio 1 9/28/2021 lab 218 del edificion 1 Cruz Cristhopher Closed Acosta
Ricardo 9/29/2021
20333 PUERTA PRINCIPAL NO CIERRA 9/27/2021 B2-F1 Rodriguez Jesus Closed Rodriguez
Jesus 9/29/2021
20332 urinario de baño de hombres no pasa el agua del desague .y tampoco cierra su plush 9/27/2021 B2-F2-R-BAÑO DE HOMBRES Rodriguez Jesus Closed Rodriguez
Jesus 9/29/2021
20331 Instalar equipos en las paredes 9/27/2021 anfac room 110 Cedamanos Diana Closed Rodriguez
Jesus 9/29/2021
20330 hechar sal industrial al ablandador 9/22/2021 B1-F1-R-ABLANDADOR Rodriguez Jesus Closed Rodriguez
Jesus 9/29/2021
20329 Key for SGT Sickler 9/22/2021 103 Cedamanos Diana Closed Quineche
Wilver 9/29/2021
20328 Mover centrifuga 9/21/2021 Animal Facilities Tapia Laura Closed Acosta Ricardo 10/1/2021
20323 Monthly inspection September to GENERATOR 320 gallons local diesel storage tank. 9/21/2021 Generator room B1. Davila Pedro Closed Ugarte Luis 9/24/2021 20322 Monthly inspection September to HVAC 100 gallons local diesel storage tank. 9/21/2021 Container HVAC. Davila Pedro Closed Ugarte Luis 9/23/2021 20321 Monthly inspection September to FULTON 100 gallons local diesel storage tank. 9/21/2021 Fulton room, B2 Davila Pedro Closed Ugarte Luis 9/23/2021
20320 Monthly inspection September to 8,000 gallons diesel storage tank. 9/21/2021 Diesel tank area. Davila Pedro Closed Acosta Ricardo 9/27/2021
20319 Annual inspection September to 8,000 gallons diesel storage tank. 9/21/2021 Diesel tank area. Davila Pedro Closed Acosta Ricardo 9/27/2021
20318 Cambiar fluorescente 9/20/2021 IM/IT Trailer Mendoza Victor Closed Quineche
Wilver 9/20/2021
20317 Replace ligh bulb on hallway at B10, F2. 9/20/2021 hallway at B10, F2. Davila Pedro Closed Quineche Wilver 9/21/2021
20316 mantenimiento de congeladora VIR058 9/16/2021 216 Popuche Dina Closed Ugarte Luis 9/20/2021
20315 Reemplazar tres fluorescentes PRNT 217, B1,F2. 9/13/2021 PRNT 217, B1,F2. Davila Pedro Closed Quineche Wilver 9/14/2021
20314 Add desk (or tables) for HM2 Jessica Becht 9/13/2021 Bldg 11, Room 101 Ramirez Miguel Closed Quineche
Wilver 9/13/2021
20313 Focos Rojos 9/8/2021 Room 110, 111, 112, 113. Quineche Wilver Closed Quineche
Wilver 9/9/2021
20312 Camara no funciona 9/8/2021 B2 room 110 Quineche Wilver Closed Quineche
Wilver 9/9/2021
20310 Cadenas para Biohazard Sharp Containers 9/2/2021 Mobile lab A, Mobile Lab B Nieto Monica Closed Rodriguez Jesus 9/22/2021
20309 MANTENIMIENTO ALAS DUCHAS DE EMERGENCIAS. 9/1/2021 B1-F2 B2-F1-R-114 ANFAC. Rodriguez Jesus Closed Rodriguez
Jesus 9/2/2021
20308 cambiar resividor del cerrojo del montacarga 9/1/2021 B1-MONTACARGA. Rodriguez Jesus Closed Rodriguez
Jesus 9/2/2021
20307 PUERTA DEL BAÑO NO CIERRA CHOCA CON EL MARCO METALICO. 9/1/2021 B12-FBAÑO DE HOMBRES Rodriguez Jesus Closed Rodriguez
Jesus 9/1/2021
20306 TAPA DE INODORO ROTO REMPLAZAR. 9/1/2021 B2-F1-BAÑO DE HOMBRES. Rodriguez Jesus Closed Rodriguez
Jesus 9/1/2021
20305 MANIJA DE PUERTA SUELTA REVISAR. 9/1/2021 B12-F1-PUERTA INTERNA DIENDO AL
BAÑO.
Rodriguez Jesus Closed Rodriguez
Jesus 9/1/2021
20304 ENGRASAR PUERTA DEL CUARTO FRIO CONTAINER. 9/1/2021 CONTAINER CUARTO FRIO. Rodriguez Jesus Closed Rodriguez
Jesus 9/1/2021
20303 puerta del B12 golpea el brazo hidraulico con el marco 9/1/2021 B12-F1 PUERTA DE EMERGENCIA. Rodriguez Jesus Closed Rodriguez
Jesus 9/1/2021
20302 Reemplazar fluorescentes en cuarto sucio 115 Autoclave. 8/29/2021 ANFAC 115 B2. Davila Pedro Closed Quineche Wilver 8/31/2021
20300 Flourecentes quemados 8/27/2021 B1 F2 hall Quineche Wilver Closed Quineche
Wilver 8/27/2021
20299 Copia de llave de gabinete de acidos 8/27/2021 pasadiso del Segundo piso, edificio 1 Sulca Juan Closed Rodriguez Jesus 8/27/2021
20297 Limpieza tanque de reserva de agua clorinada ANFAC. 8/23/2021 B2-F1-R-117 CUARTO LIMPIO ANFAC. Rodriguez Jesus Closed Rodriguez
Jesus 8/23/2021
20296 remplazar cabezal de ducha 8/23/2021 B2-F2-R-Baño de mujeres. Rodriguez Jesus Closed Rodriguez
Jesus 8/23/2021
20295 Cable de extención de 110v para lavadora de placas de Elisa 8/23/2021 Room 217 Popuche Dina Closed Quineche Wilver 8/24/2021
20294 REMPLAZAR LOS DESAGUE DEL LAVATORIO. 8/23/2021 B12-F1-R-baño de hombres Rodriguez Jesus Closed Rodriguez
Jesus 8/24/2021
20293 cambiar desague del lavadero de la cocina. 8/23/2021 B12-F1-R-COCINA. Rodriguez Jesus Closed Rodriguez
Jesus 8/23/2021
20292 remplazar mezcladora de los lavatorios 8/23/2021 B12- F1- R-Baño de hombres. Rodriguez Jesus Closed Rodriguez
Jesus 8/23/2021
20291 Cambiar tanque de mezcla de gases 8/19/2021 Laboratorio Parasitologia , 2 piso , Room
Barazorda Keare Closed Acosta
Ricardo 8/24/2021
20290 Move cabinet 8/19/2021 IMIT storage trailer Mendoza Victor Closed Grados Edwin 8/23/2021
20289 PM trimestral A/Cs safe haven B12. 8/18/2021 Save Heaven B12. Davila Pedro Closed Ugarte Luis 8/24/2021 20288 PM trimestral A/Cs cuarto data y eléctrico B12. 8/18/2021 Cuartos de data y eléctrico en B12. Davila Pedro Closed Ugarte Luis 8/25/2021
20287 PM trimestral A/Cs cuarto eléctrico B2. 8/18/2021 B2 Davila Pedro Closed Acosta Ricardo 8/20/2021
20286 MP 3 A/Cs York en GyM B2, Sótano. 8/18/2021 GyM B2 Sótano Davila Pedro Closed Acosta Ricardo 8/20/2021
20282 Colocar bandeja que se desmonto congelador VIR59 8/16/2021 Rm: 120, Dept: VEID Gamero Maria Closed Acosta Ricardo 8/20/2021
20279 Pick up of two chairs 8/16/2021 IM/IT trailer Mendoza Victor Closed Gutierrez Jose 8/16/2021
20278 Nueva ubicacion para Freezer P-006 y Refrigeradora P-010 8/11/2021
P-006 ECN: 11068 ubicado en Farm Rm B1,F2P-010 ECN 103273 ubicado en Hallway, frente al Lab de Parasitologia
RM220.
Lucas Carmen Closed Acosta
Ricardo 8/12/2021
20277 NUEVA UBICACION PARA DOS EQUIPOS: P-010 Y P-007 8/10/2021 P-007 LOCATED IN FARM 224 B1,F2P-
010 LOCATED IN HALLWAY B1-F2
Lucas Carmen Closed Acosta
Ricardo 8/12/2021
20275 Retiro de Refrigeradora P-11 para Descarte 8/10/2021 B1-F2, inside RM 214 Lucas Carmen Closed Acosta
Ricardo 8/10/2021
20274 AIRE ACONDICIONADO MUY CALIENTE LAB 114C 8/6/2021 Building 2, Lab 114C, dept VEID Galvan Patricia Closed Ugarte Luis 8/9/2021
20273 ALARM IN THE FREEZER 8/5/2021 217 Sulca Juan Closed Davila Pedro 8/13/2021
20272 Mantenimiento de Congeladora VIR013 8/1/2021 Area de Congeladoras (Room 217-A), Edificio 1, segundo piso. Rivera Cecilia Closed Ugarte Luis 8/11/2021
20271 Poner cadenas a los sharp containers que se encuentran en el piso. 7/31/2021 218. 215, 118 B2,114-C B2 Caceda Edna Closed Acosta Ricardo 8/10/2021
20270 Ordenar los cables de las computadoras y lectoras 7/31/2021 215 Caceda Edna Closed Quineche Wilver 8/10/2021
20269 Proteger la cabian de flujo laminar del lab 217 7/27/2021 edificio 1 lab 217 (Segundo piso), VEID Cruz Cristhopher Closed Acosta
Ricardo 7/27/2021
20268 Trasladar equipos del Lab 215 y 218 al frente de BIOMED 7/26/2021 215, 218 Caceda Edna Closed Acosta Ricardo 7/27/2021
20267 Reparar el eye washer lab 114-C 7/26/2021 Building 2, Room 114-C, VEID Galvan Patricia Closed Rodriguez
Jesus 8/12/2021
20266 Cabina de Flujo no tiene corriente electrica 7/23/2021 Building 1, Room 215, VEID Galvan Patricia Closed Quineche
Wilver 7/23/2021
20265 Freezer maintenance 7/23/2021 Room 120 Felices Vidal Closed Acosta Ricardo 8/13/2021
20264 Colocar pilas a reloj lab 217 7/22/2021 Building 1, room 217 (veid) Galvan Patricia Closed Cedillo Jose 7/22/2021
20263 Cambiar reloj de laboratorio 216 a laboratorio 114-C 7/22/2021 Building 1, Room 216 Galvan Patricia Closed Acosta
Ricardo 7/23/2021
20262 Solicito mantenimiento freezer Frigidaire 7/22/2021 Clean room 214, seconf floor, building 1 De Los Santos Maxy Closed Acosta
Ricardo 7/23/2021
20261 Set up new office for MAC 7/19/2021 MAC's office Rubio Lucy Closed Acosta Ricardo 7/19/2021
20260 Moving furniture 7/19/2021 CO's container Rubio Lucy Closed Acosta Ricardo 7/19/2021
20259 Cambiar Baterias de Reloj lab 218 7/16/2021 building 1, floor 2, room 218 Galvan Patricia Closed Cedillo Jose 7/21/2021
20258 Re-activacaion tarjeta de accesos a instalaciones 7/15/2021 Felices Vidal Closed Quineche Wilver 7/22/2021
20257 Goteo Maquina de Hielo Lab 218 7/14/2021 Building 1 Floor 2 Room 218 Galvan Patricia Closed Acosta
Ricardo 7/21/2021
20256 Mantenimiento Freezer 7/9/2021 Room 214 Felices Vidal Closed Acosta Ricardo 7/21/2021
20255 Reparar Refrigeradora 7/8/2021 Room 217-B Cultivo Celular Rivera Cecilia Closed Acosta Ricardo 7/21/2021
20254 Dispensadores Portatiles de gel 7/7/2021 Cosio Roberto Closed Grados Edwin 7/7/2021
20253 Cmbiar de ubicación los letreros de EXIT B1 2do piso 6/30/2021 B1, 2do piso Caceda Edna Closed Quineche Wilver 7/9/2021
20252 Install a Defiblillator box (AED) 6/24/2021 B1 Floor 2 Cosio Roberto Closed Acosta Ricardo 7/15/2021
20251 ANTI SLIPPERY TAPE NEEDED AT STAIRWELLS 6/24/2021 B2 y B10 Stairs Cosio Roberto Closed Rodriguez Jesus 7/23/2021
20250 Sellar Ventana 6/16/2021 Rm-218 Castillo Roger Closed Rodriguez Jesus 6/25/2021
20248 Refrigerator Maintenance 6/10/2021 Lab216, building01 Felices Vidal Closed Acosta Ricardo 6/10/2021
20247 Limpieza de sillas con hongos 6/4/2021 214 - B2 Caceda Edna Closed Villanueva Edgar 6/11/2021
20246 Mantenimiento a la estación de lavado de ojos 6/4/2021 118-B2 / VEID Caceda Edna Closed Rodriguez Jesus 6/11/2021
20245 ALCOHOL GEL DISPENSERS INSTALLATION 4/22/2021 ALL BUILDINGS ENTRANCE Cosio Roberto Closed Rodriguez Jesus 6/9/2021
20244 FLORESCENTES QUEMADOS 4/7/2021 WH. BLUE Buendia Tirso Closed Quineche Wilver 7/23/2021
20243 FLORECENTE QUEMADO 2/26/2021 WH. PLOMO Buendia Tirso Closed Quineche Wilver 7/23/2021
20242 SELLAR TANQUE DE AGUA 2/26/2021 WH.PLOMO PARTE EXTERENA Buendia Tirso Closed Rodriguez Jesus 7/23/2021
20241 Refrigerator NOT WORKING 2/3/2021 Main Building - Second floor - Freezer Room - Lab 214 Pinto Luis Closed Acosta
Ricardo 7/21/2021
20240 Revisar transformador de 110v a 220v 1/26/2021 Blue Warehouse Monzon Hernan Closed Davila Pedro 1/26/2021
20239 Transformadores 110-220v 1/11/2021 Building 2 Basement & Warehouse Monzon Hernan Closed Davila Pedro 1/11/2021
20238 Bano de damas 12/10/2020 Procurement De La Torre Elsa Closed Villanueva
Edgar 12/10/2020
20237 temperatura 3/13/2020 Anfac rm 112 Cedamanos Diana Closed Acosta
Ricardo 3/14/2020
20236 Cambio tanque CO2 3/13/2020 Room 217-B Cell Culture Lab (dentro de PRNT) VEID Rivera Cecilia Closed Acosta
Ricardo 3/14/2020 https://namru6-ap-03.med.ds.osd.mil/eticketISD/nFacility/frm_Status.aspx?_uDoD=280&_cDoD=1&_nDoD=4&_iDoD=0&_yDoD=0&_sDoD=0
20235 Baño Mujeres 2do Edificio Piso 2 3/13/2020 Zea Mariella Closed Rodriguez Jesus 3/13/2020
20234 LN2 Tank surfaces cleaning and surrounding areas 3/12/2020 Receiving Area Pinto Luis Closed Chileno Victor 3/13/2020
20233 Cambio anua de filtros deshidratadores de Chiller. 3/12/2020 Chiller. Davila Pedro Closed Acosta Ricardo 3/14/2020
20232 Mantenimiento de aire acondicionado en Puerto Maldonado. 3/12/2020 MdD Davila Pedro Closed Davila Pedro 3/12/2020
20231 Recibir parcial y final de 2,000 gallones de diesel. 3/12/2020 Tanque Diesel. Davila Pedro Closed Acosta Ricardo 3/13/2020
20230 Cage Washer 3/12/2020 ANFAC Loza Christian Closed Quineche Wilver 3/13/2020
20229 TRANSLADO DE FREEZER 3/12/2020 Mobil Lab A2 Bernal Manuela Closed Acosta
Ricardo 3/16/2020
20228 Resistencia no funciona 3/12/2020 b10-f2 Acosta Ricardo Closed Acosta
Ricardo 3/13/2020
20227 cambio de termostato 3/12/2020 b10-f1 Acosta Ricardo Closed Acosta
Ricardo 3/13/2020
20226 Reparacion de aire acondiconado B10 3/12/2020 b10-f1 Acosta Ricardo Closed Acosta
Ricardo 3/13/2020
20225 Traslado de equipos al Warehouse Azul 3/11/2020 BIOMED SHOP Rengifo Ana Closed Villanueva Edgar 3/12/2020
20224 Porgrama camaras 3/11/2020 Rm 103 Cedamanos Diana Closed Quineche
Wilver 3/11/2020
20223 Instalar tomas adosables 220 Voltios de microondas, TV y Refri (A6). 3/11/2020 B2, Bsmnt. Davila Pedro Closed Quineche Wilver 3/11/2020
20222 Recibir parcial de 2,000 gallones de diesel. 3/11/2020 Tanque diesel. Davila Pedro Closed Acosta Ricardo 3/11/2020
20221 Mudar colgadores en zona de receiving B1F1. 3/11/2020 Receiving B1F1. Davila Pedro Closed Acosta Ricardo 3/11/2020
20220 Eye washer 3/10/2020 Anfac rm 115 114C 114D Cedamanos Diana Closed Rodriguez
Jesus 3/10/2020
20219 revisar chapa rm 111 3/10/2020 Anfac rm 111 Cedamanos Diana Closed Rodriguez
Jesus 3/10/2020
20218 Tubos de metal 3/9/2020 Receiving room Flores Carmen Closed Acosta
Ricardo 3/10/2020
20217 Reemplazar fluorescente en cocinilla B2F2. 3/9/2020 cocinilla B2F2. Davila Pedro Closed Quineche Wilver 3/10/2020
20216 Install the gases mix tank in the MLB 3/9/2020 Nuñez Gladys Closed Acosta Ricardo 3/10/2020
20215 lavador de ojos 3/9/2020 R-114 (Vet) Flores Carmen Closed Rodriguez
Jesus 3/9/2020
20214 Tomacorriente en B11 3/7/2020 B11 area de Picnic nuevo Quineche Wilver Closed Quineche
Wilver 3/7/2020
20213 mantenimiento alas duchas de emergencia 3/6/2020 B1-F2-CORREDOR.B2-F1-R-114 ANFAC. Rodriguez Jesus Closed Rodriguez
Jesus 3/6/2020
20212 Poner tapon plastico 1/2" a bandeja lado llenado de combustible. 3/6/2020 Tanque diesel Davila Pedro Closed Acosta Ricardo 3/7/2020
20211 Botar agua y limpiar tanque colector lado tanque diesel. 3/6/2020 Tanque diesel. Davila Pedro Closed Acosta Ricardo 3/7/2020
20210 Reemplazar fluorescente en baño de damas. 3/6/2020 B2,F1. Davila Pedro Closed Quineche Wilver 3/7/2020
20209 Retiro de accesorios 3/6/2020 218, VEID Loyola Steev Closed Rodriguez Jesus 3/9/2020
20208 Reubicar 5 cilindros de gas propano de 45 kg c/u. 3/6/2020 Exterior B1 Davila Pedro Closed Acosta Ricardo 3/6/2020
20207 Reparar llave francesa 12" 3/5/2020 Receiving B1,F1 Davila Pedro Closed Rodriguez Jesus 3/5/2020
20206 MEZCLADORA CON GOTEO. 3/5/2020 B12-F1-R-COCINA Rodriguez Jesus Closed Rodriguez
Jesus 3/5/2020
20205 Fuga de agua(goteo de las mezcladora de los lavaderos). 3/5/2020 B12-F1-R-BAÑO DE HOMBRES Rodriguez Jesus Closed Rodriguez
Jesus 3/5/2020
20204 Apoyo para transportar tanques de nitrogeno al warehouse azul y a DRMO 3/5/2020 Receiving area Rengifo Ana Closed Davila Pedro 3/6/2020
20203 INSTALACION DE TOMA DE ENERGIA ELECTRICA 3/5/2020 WH. Plomo Buendia Tirso Closed Quineche Wilver 3/5/2020
20202 hechar sal industrial al ablandador de agua 3/5/2020 B1-F1-R-126-nuevo ubicacion Rodriguez Jesus Closed Rodriguez
Jesus 3/5/2020
20201 Revisar chapa de cuarto de Drivers B10,F2. 3/4/2020 Davila Pedro Closed Davila Pedro 3/4/2020
20200 REPAIR DOOR HANDLE 3/4/2020 BUILDING 10 2ND FLOOR DRIVERS'
OFFICE
Orellana Milagros Closed Rodriguez
Jesus 3/5/2020
20199 Solicito reparacion de caños agua potable lab 220 3/4/2020 Edificio 1, 2do piso, lab 220. De Los Santos Maxy Closed Rodriguez
Jesus 3/5/2020
20198 Fijar Tomar corriente a la pared 3/4/2020 VEID Offices, Building 2, 2nd floor Rengifo Ana Closed Quineche Wilver 3/5/2020
20197 tapa blanca sin sellar 3/4/2020 Anfac 115 Cedamanos Diana Closed Rodriguez
Jesus 3/4/2020
20196 pantalla llena de bichos 3/4/2020 Anfac rm 115 Cedamanos Diana Closed Quineche
Wilver 3/5/2020
20195 foco quemado 3/4/2020 Anfac corredor Cedamanos Diana Closed Quineche
Wilver 3/5/2020
20194 Bano Damas 3/3/2020 BLD 11 Galicia Nathalie Closed Rodriguez
Jesus 3/3/2020
20193 Install power and data point in BLDG 11 Chief's desk 3/3/2020 BLDG 11, BioMed Robinson Claudia Closed Quineche
Wilver 3/5/2020
20192 Apoyo de mover una caja con equipo 3/3/2020 2do piso, 2do edificio, VEID Admin Office Rengifo Ana Closed Villanueva Edgar 3/4/2020
20191 Apoyo mover caja con documentos 3/3/2020 Receiving area. Rengifo Ana Closed Villanueva Edgar 3/3/2020
20190 Pegar plastico antideslizante 3/2/2020 Entrada 2do piso, Edificio #2 Gonzales Cecilia Closed Rodriguez
Jesus 3/2/2020
20189 Solicito mantenimiento Freezer 3/2/2020 Building 1, second floor, room 214, Clean Room.
De Los Santos Maxy Closed Acosta
Ricardo 3/5/2020
20188 Revisar montacargas, cabina quedó 2do piso, no baja. 3/2/2020 Receiving B1,F1. Davila Pedro Closed Ugarte Luis 3/2/2020 20187 Reemplazar un fluorescente en Lab 218. 3/2/2020 Lab 218. B1,F2. Davila Pedro Closed Davila Pedro 3/2/2020 20186 Reemplazar fos fluorescentes en Lab 214. 3/2/2020 Lab 214, B1,F2. Davila Pedro Closed Davila Pedro 3/2/2020 20185 Reemplazar 2 fluorescentes en pasaizo de B1,F2. 3/2/2020 Davila Pedro Closed Davila Pedro 3/2/2020
20184 Mudar freezer -80 y reemplazarlo por el VIR029 (-80). 2/28/2020 Freezer Room B1,F1. Davila Pedro Closed Acosta Ricardo 2/28/2020
20183 Mudar freezer -80 a zona de todo azul lado whse azul. 2/28/2020 Freezer room B1,F1. Davila Pedro Closed Ugarte Luis 2/28/2020 20182 Poner 4 soportes de metal a tablero (mesa). 2/28/2020 Freezer room B1F1. Davila Pedro Closed Ugarte Luis 2/28/2020
20181 Fluorescentes quemados 2/28/2020 Room 220, B1, F2 Lucas Carmen Closed Davila Pedro 2/28/2020
20180 Autoclave goteando 2/28/2020 Anfac rm 115 Cedamanos Diana Closed Quineche
Wilver 2/28/2020
20179 Trabajos con el Rees 2/28/2020 B2, Veterinaria. Quineche Wilver Closed Quineche
Wilver 2/28/2020
20178 Tablero Electrico Azotea 2/28/2020 B1, roof. Quineche Wilver Closed Quineche
Wilver 2/28/2020
20177 Cambio de lavador de ojos laboratorio 218 2/28/2020 Lavadero laboratorio Room 218 VEID Edificio 1
Espejo Victoria Closed Rodriguez
Jesus 3/3/2020
20176 Instalar ventiladores en picnic. 2/28/2020 Picnic. Davila Pedro Closed Acosta Ricardo 2/28/2020
20175 Fijar baldosas de aluminio. 2/28/2020 ANFAC B2,F1. Davila Pedro Closed Acosta Ricardo 3/4/2020
20174 Poner tapon a drenaje tanque inferior de cage washer. 2/28/2020 Dirty Room ANFAC. Davila Pedro Closed Ugarte Luis 3/1/2020
20173 Sellar puertas de contenedores de IT. 2/28/2020 3 Containers IT. Davila Pedro Closed Rodriguez Jesus 3/3/2020
20172 Puerta de sala 114 (animal facilities no cierra bien) 2/27/2020 Edificio 2, primer piso, Sala 114 - Veterinaria
Flores Carmen Closed Rodriguez
Jesus 2/29/2020
20171 Clorinador no funciona 2/27/2020 Anfac rm 116 Cedamanos Diana Closed Quineche
Wilver 2/28/2020
20170 Puerta cuarto 111 2/27/2020 Anfac rm 111 Cedamanos Diana Closed Rodriguez
Jesus 2/29/2020
20169 Puerta de salida de emergencia 2/27/2020 Anfac rm 116 Cedamanos Diana Closed Rodriguez
Jesus 2/29/2020
20168 instalar una mesa en la sala pequena de reuniones 2/27/2020 Cruz Cristhopher Closed Davila Pedro 2/29/2020
20167 Ducha gotea 2/27/2020 Building 2, Ladies Bathroom first floor Galvan Patricia Closed Rodriguez
Jesus 2/29/2020
20166 Freezer -20 C maintenance ECN 44852105567 2/26/2020 Freezer farm Nuñez Gladys Closed Acosta Ricardo 2/29/2020
20165 Cable UPS 2/26/2020 B2- room105 Flores Carmen Closed Quineche
Wilver 2/29/2020
20164 tubos sueltos 2/26/2020 Anfac rom112 Cedamanos Diana Closed Rodriguez
Jesus 2/29/2020
20163 retoque pintura 115 2/26/2020 Anfac rm 115 Cedamanos Diana Closed Rodriguez
Jesus 2/29/2020
20162 instalar colgador de escobas 2/26/2020 Anfac Rm 114 C Cedamanos Diana Closed Rodriguez
Jesus 2/28/2020
20161 Limpieza de pizarra blanca 2/26/2020 Building 2, 201 BID Tsuha Augusto Closed Villanueva
Edgar 2/28/2020
20160 Pintar caja sugerencias y installar en B10, F1. 2/26/2020 B10,F1. Davila Pedro Closed Rodriguez Jesus 3/5/2020
20159 Instalar valvulas de vacuum breakers todos los caños exteriores. 2/26/2020 Exteriores N6. Davila Pedro Closed Rodriguez Jesus 2/26/2020
20158 instalar Tanque de Co2 2/25/2020 Anfac rm 112 Cedamanos Diana Closed Ugarte Luis 2/26/2020
20157 Dispensador del Alcohol gel 2/25/2020 Anfac Cedamanos Diana Closed Rodriguez
Jesus 2/27/2020
20156 Goteo de manguera 2/25/2020 Anfac rm 112 Cedamanos Diana Closed Rodriguez
Jesus 2/27/2020
20155 Tape amarilla con negro 2/25/2020 Anfac rm 112 Cedamanos Diana Closed Rodriguez
Jesus 2/27/2020
20154 liquid soap dispenser is not working 2/25/2020 building 2, second floor, ladies room Reategui Miryam Closed Rodriguez
Jesus 2/26/2020
20153 Reubicación de contenedores de toners vacios 2/25/2020 Building 2 Monzon Hernan Closed Zevallos
Mauricio 3/2/2020
20152 NO CIERRA PUERTA LAB 215 2/24/2020 Rm 215 Dept VEID Gamero Maria Closed Ugarte Luis 2/25/2020
20151 Fijar transformador de refrigeradora en freezer room B1F2. 2/22/2020 Freezer room B1,F2. Davila Pedro Closed Davila Pedro 2/22/2020 20150 Fijar transformador de balanza en freezer room lado montacargas B1F2. 2/22/2020 B1F2. Davila Pedro Closed Davila Pedro 2/22/2020 20149 Cambiar fluorescente quemado en pasadizo de B2,F1. 2/22/2020 B2,F1. Davila Pedro Closed Davila Pedro 2/22/2020 20148 Instalar 12 detectores de humo en containers. 2/22/2020 Containers. Davila Pedro Closed Ugarte Luis 2/25/2020
20147 Filtros de aire acondiconado en bolsas amarillas 2/21/2020 contenedores Acosta Ricardo Closed Acosta
Ricardo 2/21/2020
20146 Instalacion de Tomacorriente 2/21/2020 B2, F1, room 112 Quineche Wilver Closed Quineche
Wilver 2/21/2020
20145 Mantto anual al sistema de tableros y controles y valvulas, SCI. B12, empresa: TICO 2/21/2020 B12 Ugarte Luis Closed Ugarte Luis 2/21/2020 20144 Cotizacion de programacion del VSD, del las AHU 102 y 202 2/21/2020 Namru 6 Ugarte Luis Closed Ugarte Luis 2/21/2020 20143 Cotizacion de pintado de extintores 2/21/2020 Namru 6 Ugarte Luis Closed Ugarte Luis 2/21/2020
20142 Pasar e instalar, RACK de bacty Walking freezer a Freezer room container 2/21/2020 B1 Ugarte Luis Closed Ugarte Luis 2/21/2020 20141 Compra e instalacion, de ventiladores para VSD de AHU 103 2/21/2020 B1 Ugarte Luis Closed Ugarte Luis 2/21/2020 20140 Training varios de seguridad ESAMS, SWAN, etc 2/21/2020 B2 Ugarte Luis Closed Ugarte Luis 2/21/2020 20139 Verificacion de HVAC Luz Borja 2/21/2020 B10 Ugarte Luis Closed Ugarte Luis 2/21/2020 20138 Escolta a Praxair recepcion de CO2 2/21/2020 Namru 6 Ugarte Luis Closed Ugarte Luis 2/21/2020 20137 Distribucion de extintores de reemplazo en namru 6 2/21/2020 Namru 6 Ugarte Luis Closed Ugarte Luis 2/21/2020 20136 Alistar documentos de Training para extintores 2/21/2020 Namru 6 Ugarte Luis Closed Ugarte Luis 2/21/2020 20135 Escolta a Jtech Control, trabajos de actualizacion de tarjeta de tablero SCI. B2 2/21/2020 B2 Ugarte Luis Closed Ugarte Luis 2/21/2020 20134 Escolta a JCI. cambio de filtros a AHUs B1 y B2 2/21/2020 B1 y B2 Ugarte Luis Closed Ugarte Luis 2/21/2020 20133 Subir filtros a la asotea, para AHU 201 enero 2/21/2020 B2 Ugarte Luis Closed Ugarte Luis 2/21/2020 20132 Escolta a Control Tech, barras antipanico del B12 2/21/2020 B12 Ugarte Luis Closed Ugarte Luis 2/21/2020 20131 Hacer pedidos de almacen para facilities 2/21/2020 B 2 Ugarte Luis Closed Ugarte Luis 2/21/2020 20130 Entrega del segundo grupo de extintores febrero 2/21/2020 Namru 6 Ugarte Luis Closed Ugarte Luis 2/21/2020 20129 Poner residuos peligrosos de petroleo en bolza amarillas. 2/21/2020 Namru 6 Ugarte Luis Closed Ugarte Luis 2/21/2020 20128 Ordenar cosas para el entrenamiento de extintores 2/21/2020 Namru 6 Ugarte Luis Closed Ugarte Luis 2/21/2020 20127 Poner filtros en bolsas negras para la basura 2/21/2020 B 6 Ugarte Luis Closed Ugarte Luis 2/21/2020 20126 Recarga del primero grupo de extintores 2/21/2020 Namru 6 Ugarte Luis Closed Ugarte Luis 2/21/2020
20125 verificar voltaje y mover 2/21/2020 Edificio 2 primer piso, corredor Flores Carmen Closed Quineche
Wilver 2/24/2020
20124 Mantto. anual de tanque de petroleo por EMpresa externa 2/21/2020 tanque de petroleo Ugarte Luis Closed Ugarte Luis 2/21/2020 20123 Chequeo y arreglo de AHU 201,. 23 enero 2/21/2020 B 2 Ugarte Luis Closed Ugarte Luis 2/21/2020 20122 Chequeo de HVAC Luz Borja 2/21/2020 B 10 Ugarte Luis Closed Ugarte Luis 2/21/2020 20121 Mantto de variadores JCI: 2/21/2020 B 1 Ugarte Luis Closed Ugarte Luis 2/21/2020 20120 Cotizacion de parlantes para Lab. Portatiles 2/21/2020 Lab. portatil Ay B Ugarte Luis Closed Ugarte Luis 2/21/2020 20119 Mantto. bombas 3FP. periodico enero 2/21/2020 Picnic Ugarte Luis Closed Ugarte Luis 2/21/2020 20118 Asistir a Curso de extintores en la Embajada A. 2/21/2020 Embajada Americana Ugarte Luis Closed Ugarte Luis 2/21/2020 20117 Mantto. tanque de petroleo general 2/21/2020 Tanque de petroleo Ugarte Luis Closed Ugarte Luis 2/21/2020 20116 Training para facilities tema proteccion electrica 2/21/2020 Namru 6 Ugarte Luis Closed Ugarte Luis 2/21/2020 20115 Realizar entrenamiento anual de extintores 2 dias enero 2/21/2020 Namru 6 Ugarte Luis Closed Ugarte Luis 2/21/2020 20114 Subir filtros para AHUs del B1 2/21/2020 B1 Ugarte Luis Closed Ugarte Luis 2/21/2020 20113 Escolta a Empresa Clicoe, garanria de HVAC 2/21/2020 Freezer room B1 F1 Ugarte Luis Closed Ugarte Luis 2/21/2020 20112 Escolta a empresa Jtech Control Conexionado de puertas Lab. portatil a, b 2/21/2020 Lab. portatil A y B Ugarte Luis Closed Ugarte Luis 2/21/2020 20111 Realizar documentacion de viaje a Iquitos 2/21/2020 Namru Iquitos Ugarte Luis Closed Ugarte Luis 2/21/2020 20110 Llamadas de emergencia HVAC 19 febrero, temp ANFAC 2/21/2020 B 2 Ugarte Luis Closed Ugarte Luis 2/21/2020 20109 Llamadas de emergencia HVAC 20 enero, temp ANFAC 2/21/2020 Namru 6 Ugarte Luis Closed Ugarte Luis 2/21/2020 20108 Llamadas de emergencia HVAC 12 enero, temp ANFAC 2/21/2020 Namru 6 Ugarte Luis Closed Ugarte Luis 2/21/2020
20107 PUERTA DE INSECTARIO 2/21/2020 EDIFICIO 2, SEGUNDO PISO Flores Carmen Closed Ugarte Luis 2/21/2020
20106 Apoyo para mover tanque de nitrogeno con jaba hacia warehouse azul 2/21/2020 Receiving area Rengifo Ana Closed Acosta Ricardo 2/21/2020
20105 Inadequate compressed gas storage 2/21/2020 Iquitos, Clinica Naval Cosio Roberto Closed Davila Pedro 2/25/2020
20104 Preventive maintenance two UPS Lima. 2/21/2020 Electrical Room B1 & B12 Davila Pedro Closed Davila Pedro 2/22/2020
20103 ucaracha - insectario 2/20/2020 Edificio 2 - primer piso Flores Carmen Closed Acosta
Ricardo 2/21/2020
20102 Chequeo de temp/pres. ene. 28 - 31 2/20/2020 Namru 6 Ugarte Luis Closed Ugarte Luis 2/20/2020 20101 Chequeo de temp/pres. ene. 21 - 24 2/20/2020 Namru 6 Ugarte Luis Closed Ugarte Luis 2/20/2020 20100 Chequeo de extintores febrero 20 2/20/2020 Namru 6 Ugarte Luis Closed Ugarte Luis 2/20/2020 20099 Chequeo de extintores ene. 24 2/20/2020 Namru 6 Ugarte Luis Closed Ugarte Luis 2/20/2020 20098 Medicion de petroleo, ene. 28 - 31 2/20/2020 Tanque de petroleo Ugarte Luis Closed Ugarte Luis 2/20/2020 20097 Medicion de petroleo, ene. 21 - 24 2/20/2020 Tanque de petroleo Ugarte Luis Closed Ugarte Luis 2/20/2020 20096 BMS Chequeo semanal, ene. 28 - 31 2/20/2020 Namru 6 Ugarte Luis Closed Ugarte Luis 2/20/2020 20095 BMS Chequeo semanal, ene. 21 - 24 2/20/2020 Namru 6 Ugarte Luis Closed Ugarte Luis 2/20/2020 20094 Formato de Safety tanque petroleo (Jimena), ene. 31 2/20/2020 Tanque de petroleo Ugarte Luis Closed Ugarte Luis 2/20/2020 20093 Formato de Safety tanque petroleo (Jimena), ene. 24 2/20/2020 Tanque de petroleo Ugarte Luis Closed Ugarte Luis 2/20/2020 20092 Formato de Safety tanque petroleo (Jimena), ene. 17 2/20/2020 Tanque de petroleo Ugarte Luis Closed Ugarte Luis 2/20/2020 20091 Formato de Safety representative, febrero 20 2/20/2020 Namru 6 Ugarte Luis Closed Ugarte Luis 2/21/2020 20090 Formato de Safety representative, febrero 14 2/20/2020 Namru 6 Ugarte Luis Closed Ugarte Luis 2/20/2020 20089 Formato de Safety representative, febrero 07 2/20/2020 Namru 6 Ugarte Luis Closed Ugarte Luis 2/20/2020 20088 Formato de Safety representative, ene. 31 2/20/2020 Namru 6 Ugarte Luis Closed Ugarte Luis 2/20/2020 20087 Formato de Safety representative, ene. 24 2/20/2020 Namru 6 Ugarte Luis Closed Ugarte Luis 2/20/2020 20086 Reubicar termostato aprox 10 cm a la derecha. 2/20/2020 Occ. Heath Office. Davila Pedro Closed Ugarte Luis 2/25/2020 20085 CAmbio balon de CO2 2/20/2020 Lab 216 Felices Vidal Closed Ugarte Luis 2/20/2020
20084 Cambio de filtros HEPA ENC:103286 2/20/2020 vet-room 112 Acosta Ricardo Closed Acosta
Ricardo 2/20/2020
20083 Apoyo para mover equipo a Recepcion 2/19/2020 Of. 211, VEID ADMIN, building 2, 2nd floor Rengifo Ana Closed Villanueva Edgar 2/19/2020
20082 Sillas para el conference room el Miercoles 26 de febrero 2/19/2020 Conference room - Miercoles 26 febrero Angulo Noelia Closed Davila Pedro 2/26/2020
20081 fijacion de cables 2/19/2020 Rm # 211 Guevara Carolina Closed Quineche
Wilver 2/25/2020
20080 trampa de luz 2/19/2020 sala 114- Veterinaria Flores Carmen Closed Quineche
Wilver 2/20/2020
20079 trampa Shannon 2/19/2020 Insectario mosquitos, edificio 2- primer piso
Flores Carmen Closed Davila Pedro 2/20/2020
20078 Install an exit sign (emergency exit door seond floor) as required by 29 CFR 1910.37 & Rearrange the exit signs location to guide clearly to the exit door. 2/19/2020 B1, second floor Caceda Edna Closed Davila Pedro 3/5/2020
20077 Fix transformer to the wall as required by NFPA. 2/19/2020 Freezer area, B1 second floor, close to forklift Caceda Edna Closed Quineche
Wilver 2/20/2020
20076 Repair the freezer insulation 2/19/2020 Room 214 Caceda Edna Closed Davila Pedro 2/20/2020
20075 Retirar jaba de madera - tanque nitrogeno 2/18/2020 Receiving area Rengifo Ana Closed Rodriguez Jesus 2/19/2020
20074 four light fluorescents in Iquitos 2/18/2020 Rm # 115 Guevara Carolina Closed Quineche
Wilver 2/20/2020
20073 Mantenimiento de congelador 2/18/2020 Rm 218 Castillo Roger Closed Acosta Ricardo 2/20/2020
20072 Arreglar el cajón del escritorio de Roxana Lescano 2/18/2020 Nueva oficina de RAP Zuloeta Toane Closed Rodriguez
Jesus 2/20/2020
20071 Foco quemado en hall del B11 2/18/2020 B11 stairs 200 Quineche Wilver Closed Quineche
Wilver 2/18/2020
20070 Temperatura alta y falta de aire en el lab 215 2/18/2020 LAb 215, VEID Serologia. Sulca Juan Closed Acosta Ricardo 2/18/2020
20069 Evaluar cargas y disponibilidad de tomas 110 y 220 Voltios. 2/14/2020 Labs 215 y 216 at B1,F2. Davila Pedro Closed Quineche Wilver 2/18/2020
20068 Mover equipos de laboratorio 2/14/2020 215 y 216 Felices Vidal Closed Quineche Wilver 2/21/2020
20067 Colgar acrilico transparente porta papeles. 2/14/2020 New walking freezer. Davila Pedro Closed Quineche Wilver 2/14/2020
20066 Electrical door to SE 10kV does not open at all. 2/14/2020 SE 10 kV. Davila Pedro Closed Davila Pedro 2/14/2020
20065 Install electrical extension for food truck. 2/14/2020 Davila Pedro Closed Quineche Wilver 2/18/2020
20064 Annual replacement of hepa filter to EF-103, BSL3 at B1 2/14/2020 B1 Roof Davila Pedro Closed Ugarte Luis 2/22/2020 20063 Mover y instalar anaqueles de walking freezer B1 a nuevo walking freezer. 2/14/2020 New walking freezer Davila Pedro Closed Ugarte Luis 2/13/2020 20062 Mover temporal baranda de receiving. 2/13/2020 Vereda B1 Receiving. Davila Pedro Closed Davila Pedro 2/13/2020 20061 Replace burned fluorescente on hall at B2,F1. 2/13/2020 hall at B2,F1. Davila Pedro Closed Davila Pedro 2/13/2020
20060 Telefono del Lab 118 no funciona 2/13/2020 Lab 118 - Segundo Edificio Troncos Gilda Closed Davila Pedro 2/13/2020
20059 Certification of biosafety cabinets ECN: 092434 & 091675 in lab 216 at B1,F2. 2/13/2020 lab 216 at B1,F2. Davila Pedro Closed Acosta Ricardo 2/13/2020
20058 Apoyo para trasladar equipo y ubicarlo en el Warehouse azul 2/13/2020 Warehouse plomo Rengifo Ana Closed Villanueva Edgar 2/13/2020
20057 NCH monthly water inspection and final to both boiler Fulton and Bryan. 2/13/2020 Fulton & Bryan Boilers. Davila Pedro Closed Acosta Ricardo 2/12/2020
20056 Schedule PM to air conditioner UPS Room at B1. 2/13/2020 Electrical Room B1. Davila Pedro Closed Ugarte Luis 2/22/2020
20055 PM EF 102 and 103 Labs and BSL3 2/13/2020 at B1 Roof. Davila Pedro Closed Acosta Ricardo 2/15/2020
20054 Repair entrance wall with saliter to ANFAC hallway. 2/13/2020 Hall B2. Davila Pedro Closed Rodriguez Jesus 2/25/2020
20053 Repair wall with saliter in hallway 116. 2/13/2020 ANFAC, Hallway 116. Davila Pedro Closed Rodriguez Jesus 2/21/2020
20052 Touch up with paint ceiling in clean room 117. 2/13/2020 ANFAC, Clean Room 117. Davila Pedro Closed Rodriguez Jesus 2/20/2020
20051 Walls in hall have cracks by room and in the ante room of 114. 2/13/2020 ANFAC Room 114. Davila Pedro Closed Rodriguez Jesus 2/13/2020
20050 Repair double door in Hall way. 2/13/2020 ANFAC Hallway at B2 Davila Pedro Closed Davila Pedro 2/20/2020
20049 Touch up door frame in room 109. 2/13/2020 ANFAC Room 109 Davila Pedro Closed Rodriguez Jesus 2/13/2020
20048 Touch up walls from ante room and animal room 111. 2/13/2020 ANFAC Room 111 Davila Pedro Closed Rodriguez Jesus 2/13/2020
20047 Touch up with paint walls anti room 113. 2/13/2020 ANFAC Room 113 Davila Pedro Closed Rodriguez Jesus 2/18/2020
20046 Touch up with paint Walls and door frames in room 108. 2/13/2020 ANFAC Room 108. Davila Pedro Closed Rodriguez Jesus 2/19/2020
20045 Touch up with paint Walls in room 108. 2/13/2020 ANFAC Room 108 Davila Pedro Closed Rodriguez Jesus 2/19/2020
20044 Three door frames needs some touch up with paint. 2/13/2020 ANFAC Room 107. Davila Pedro Closed Rodriguez Jesus 2/20/2020
20043 CO2 tanks needs to be secure with chain in two rooms. 2/13/2020 ANFAC 112 & 107 Davila Pedro Closed Ugarte Luis 2/14/2020
20042 Install metal mesh in the air inle of the tair conditioner 2/13/2020 ANFAC 114A. Davila Pedro Closed Acosta Ricardo 2/20/2020
20041 Showerhead in Male bathroom needs to be replaced 2/12/2020 Bldg. 2, Floor 2, Male bathroom Abente Eugenio Closed Rodriguez
Jesus 2/13/2020
20040 Colocar trampas en contenedores 2/12/2020 Contenedores Barrera Monica Closed Davila Pedro 2/19/2020
20039 FLORESCENTE QUEMADO 2/12/2020 WH. PLOMO Buendia Tirso Closed Quineche Wilver 2/13/2020
20038 Indipendizar circuito de bomba de agua cuarto limpio ANFAC. 2/12/2020 Room 117 ANFAC Davila Pedro Closed Quineche Wilver 2/12/2020
20037 Clean up and wash the floor from B11 to chiller. 2/11/2020 Davila Pedro Closed Davila Pedro 2/11/2020 20036 Return the equipment for certification of BSC. 2/11/2020 Iquitos. Davila Pedro Closed Davila Pedro 2/11/2020 20035 Inspect the UPS at MdD becasue electrical problems. 2/11/2020 MdD. Davila Pedro Closed Davila Pedro 2/12/2020 20034 Urgency to inspect the electric generator at MdD. 2/11/2020 Electrical room at MdD. Davila Pedro Closed Davila Pedro 2/11/2020 20033 Four inspection to water plant at Iquitos. 2/11/2020 Iquitos. Davila Pedro Closed Davila Pedro 2/11/2020
20032 Peso y medicion de equipos para enviar a Iquitos 2/11/2020 IT Storage container Landauro Paola Closed Acosta
Ricardo 2/12/2020
20031 Arreglar conexion para telefono en escritorio del safe heaven 2/11/2020 Safe heaven Tapia Laura Closed Quineche Wilver 2/11/2020
20030 FALL HAZARD 2/11/2020 CO OFFICE SIDEWALK Cosio Roberto Closed Davila Pedro 2/14/2020
20029 DISPENSADOR DE JABON LIQUIDO (REMPLAZAR) 2/11/2020 B2-F1-R-BAÑO DE MUJERES. Rodriguez Jesus Closed Rodriguez
Jesus 2/11/2020
20028 Limpieza de Pasamanos y gradas 2/10/2020 Escalera Externa (Edificio 1) Rivera Cecilia Closed Cedillo Jose 2/11/2020
20027 canal de drenaje 2/10/2020 Puerta posterior de Veterinaria y detrás del edificio 10
Flores Carmen Closed Rodriguez
Jesus 2/18/2020
20026 Move Mayu Rivera 2/10/2020 Rivera Maria Closed Davila Pedro 2/11/2020 20025 Trasladar equipos para DRMO del Lab 216 a la Ofic. de BIOMED 2/10/2020 Lab 216 Rengifo Ana Closed Davila Pedro 2/13/2020 20024 Cortar dos piezas de acero inoxidable. 2/10/2020 Iquitos. Davila Pedro Closed Ugarte Luis 2/11/2020
20023 hechar sal industrial al ablandador de agua. 2/10/2020 B1-F1-ABLANDADOR DE AGUA Rodriguez Jesus Closed Rodriguez
Jesus 2/10/2020
20022 Reemplazar fluorescente quemado en baño damas B2F1. 2/7/2020 baño damas B2F1. Davila Pedro Closed Quineche Wilver 2/8/2020
20021 Traba en la base para el teclado 2/7/2020 B1F2 Lab 214 Pinto Luis Closed Rodriguez Jesus 2/10/2020
20020 remove Bishop's plaque 2/7/2020 Building 2, 2nd floor, hallway Reategui Miryam Closed Rodriguez
Jesus 2/12/2020
20019 Extintor vencido 2/7/2020 Safe haven VEID Zamora Jennifher Closed Ugarte Luis 2/12/2020
20018 Safe Heaven door scratches the floor and makes a sound that bothers 2/7/2020 Rivera Maria Closed Quineche Wilver 2/8/2020
20017 Poner soporte a podium. 2/7/2020 Conference Mobil. Davila Pedro Closed Rodriguez Jesus 2/7/2020
20016 Cambio de supresor de picos 2/5/2020 IM/IT Container (Office) Monzon Hernan Closed Quineche
Wilver 2/12/2020
20015 Solicitamos ventiladores en el lunch area 2/5/2020 Nuevo lunch area, afuera del edificio de Biomedical Repair
De Los Santos Maxy Closed Zevallos
Mauricio 2/10/2020
20014 Solicitamos apoyo para trasladar equipos 2/5/2020 Building 2, first floor, room 105 De Los Santos Maxy Closed Quineche
Wilver 2/6/2020
20013 check air conditioning at DFA office 2/5/2020 DFA's office, Building 2, Office 204 Reategui Miryam Closed Acosta
Ricardo 2/6/2020
20012 Reemplazar fluorescente tipo U pasadizo B2, F2. 2/4/2020 B2,F2. Davila Pedro Closed Quineche Wilver 2/8/2020
20011 Instalar luces de Emergencia containers CO, XO y Command Suit 2/4/2020 Container CO, XO y Command Suit. Davila Pedro Closed Quineche Wilver 1/8/2020
20010 PM to MacQuay A/C units at B11. 2/4/2020 B11, Roof Davila Pedro Closed Acosta Ricardo 2/8/2020
20009 PM to EF 202 ANFAC. 2/4/2020 B2 Davila Pedro Closed Acosta Ricardo 2/8/2020
20008 PM to AHU 202 ANFAC. 2/4/2020 B2. Davila Pedro Closed Acosta Ricardo 2/8/2020
20007 Electricity went out today from 12:15 pm to 12:30 pm. 2/3/2020 NAMRU-6 Davila Pedro Closed Davila Pedro 2/3/2020
20006 GYM MATS 2/3/2020 GYM Loza Christian Closed Ugarte Luis 2/6/2020
20005 Transfer cabinets 2/3/2020 Command Suite Temporary Storage Container Rubio Lucy Closed Quineche
Wilver 2/4/2020
20004 Hang up Clocks 2/3/2020 CO and Command Suite Office Rubio Lucy Closed Rodriguez Jesus 1/4/2020
20003 Award Ceremony 2/3/2020 Rubio Lucy Closed Davila Pedro 2/4/2020
20002 BATHROOM 2/3/2020 BUILDING 10 FIRST FLOOR Orellana Milagros Closed Rodriguez
Jesus 2/4/2020
20001 Awards Ceremony - Tuesday 4Feb2020 0900 1/31/2020 In Front…