This document provides details on a federal contract solicitation for operation and maintenance services at the US Navy Medical Research Unit Six facility in Peru. The solicitation seeks a firm-fixed price contract for a base year and four option years to furnish all personnel, services, materials, and transportation necessary to operate and maintain medical research laboratory facilities and support structures. Requirements include preventative, predictive, demand, and emergency maintenance of architectural, mechanical, electrical, and instrumentation systems. Limited grounds keeping is also required. The contractor must minimize interference with daily laboratory operations and comply with regulatory bodies such as AAALAC. Facilities include BSL-2 and BSL-3 research labs, a vivarium, administrative spaces, parking areas, and supporting utilities. The solicitation will be posted at https://sam.gov/ and issued as a direct download only. The size standard is an average annual gross revenue not exceeding $41.5 million for the past three years under NAICS code 561210.
View the file
Other files
Show all 45
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STANDARD OPERATING PROCEDURE (SOP) – SEMI ANNUAL
PREVENTIVE MAINTENANCE ACTIVITIES FOR CCTV, ACCESS CONTROL
AND PUBLIC ADDRESS SYSTEMS OF NAMRU-6 LIMA AND IQUITOS
SITES
General Requirements for Lima and Iquitos
Access control system in Lima and Iquitos sites and CCTV system in Lima site is LENEL brand.
Only authorized, certified and trained technicians by LENEL can perform maintenance to LENEL systems. In order to verify that a technician can perform work and receive support from LENEL, the company must provide the full names and ID numbers of the technicians that will perform the maintenance activities as well as their certificates. Then, NAMRU-6 facilities department will coordinate and review the information with LENEL representative for Latin America in order to grant authorization only to contractor’s technicians that have a valid updated certification to perform work.
For information purposes and future maintenance planning only, CCTV System in Iquitos is not LENEL brand but it is the intent of the Facilities Department to, in the near future, replace and upgrade existing CCTV with a compatible LENEL system.
Contractor must coordinate with a LENEL local representative and pay to renew on an annual basis the NAMRU-6 licenses of each one of the cameras, servers, LDVRs, LNVRs, HVR, IVSP- SC channels, integrated GO channels, integrated go vision channels, integrated true vision channels, OAAP channels, proximity card readers and all other associated equipment integrated into the LENEL system. Contractor shall renew the licenses so that NAMRU-6 and/or contractor can receive LENEL assistance for troubleshooting and to keep the NAMRU-6 access control and CCTV systems updated in Lima and Iquitos.
As a rule, contractor shall perform the preventive maintenance activities described in this document on a semi-annual basis, unless specified different in any other part of this document for a specific activity. The number of cameras and card readers provided in this document are for information purposes only; it is the responsibility of the contractor to perform a full inspection of the systems and collect all required information to provide a quality preventive maintenance.
In addition, contractor shall review operation manuals for the equipment of the systems under this contract and include any recommended preventive maintenance activities by the manufacturer not mentioned in this document.
Contractor shall elaborate, review and update the drawings on AUTOCAD of the CCTV, access control system and public address systems on an annual basis.
Contractor shall install an anti-virus, Microsoft software and Adobe Acrobat Reader in all the five workstations in Lima and two workstations in Iquitos of the access control and CCTV system (PC Client) and shall keep the software up to date. Contractor must check and/or update software of the PC clients once a month.
Section J - Exhibit 11.2.2 SOP-FAC 001
Contractor shall include all materials, tools and personal protective equipment necessary to perform preventive and corrective maintenance work. Contractor must use the necessary and appropriate equipment to delimit the work area and not allow the pedestrian traffic. The contractor’s staff shall use the appropriate PPE for the activity to perform. NAMRU-6 will not provide any materials, tools nor PPE to the contractor to perform their work.
Due to the installation height of some exterior cameras in Lima (around 25 meters) and for safety purposes, contractor shall use a man lift with basket as the primary means to access and perform maintenance to the exterior cameras. However, some areas are inaccessible by the man lift. In these cases, contractor shall use certified scaffolding. Ladders are not authorize to perform maintenance activities to exterior cameras in Lima. In Iquitos, a man lift is not required but contractor shall evaluate the best safe way to access and maintain the exterior cameras installed approximately at 3 meter high from the floor.
The contractor shall provide a weekly progress report to the NAMRU-6 facilities department, as well as a completion report when completing the maintenance work to include: activities performed with pictures, recommendations, conclusion and future needed corrective maintenance tasks. When a corrective maintenance work is required, the contractor shall submit a report detailing the problem encountered, with a quotation of the solution.
The preventive maintenance work will be coordinated between NAMRU-6 facilities staff and the staff assigned by the contractor.
Contractor shall perform operational testing of the systems at the completion of each preventive maintenance work. NAMRU-6 facilities department will assign a staff to participate in the operational testing and contractor shall prepare an operational testing form (checklist) to be signed by the facilities staff once testing is perform and accepted.
It is the responsibility of the contractor to dispose properly out of NAMRU-6 facilities all consumable materials and garbage generated by the contractor during the performance of the maintenance activities.
Applicable codes:
The following are applicable codes for the elaboration of the preventive maintenance plan, reports and activities mentioned in this document:
EIA/TIA 568-A
EIA/TIA 568-B
EIA-222-F
ANSI/TIA/EIA 569
EIA/TIA-569A-1
EIA/TIA-569A-2
EIA/TIA-569A-3
EIA/TIA-569A-4
EIA/TIA-569A-5
ANSI/TIA/EIA 606
EIA/TIA-607
TIA/EIA TSB-67
TIA/EIA TSB-72
ISO/IEC 11801
ICEA S-104-696
ISO/IEC IS 14763-2
ISO/IEC IS 14763-3
IEEE
NEC
NFPA 730
NFPA 731
Description of work required in Lima and Iquitos
ACCESS CONTROL SYSTEM
The access control system in Lima controls 18 doors and it is composed of electric locks, electric magnets, hydraulic arms, anti-panic bars and sirens, all LENEL brand. There is also a control panel for each building at NAMRU-6 Lima and a main server and 5 workstations (PC client).
The access control system in Iquitos controls 10 doors and it is composed of electrical locks, magnetic contacts, entry and exit readers, hydraulic arms, anti-panic bar and sirens and a control panel for each building at NAMRU-6 Iquitos and a main server and 2 workstations (PC client).
The contractor shall perform the following preventive maintenance activities:
ACCESS CONTROL SYSTEM – LIMA & IQUITOS
Item Sub-system Task Frequency
1 Controllers Electronic part cleaning. Semiannual 2 Controllers Check terminals Semiannual 3 Power Supply / Power Cards Electronic part cleaning Semiannual 4 Power Supply / Power Cards Check terminals Semiannual 5 Power Supply / Power Cards Check battery status Semiannual 6 Electrical Sheet Cleaning of metal structure Semiannual
7 Electrical Sheet Internal cleaning of electrical and mechanical parts Semiannual
8 Server Visual inspection Semiannual
9 Server External cleaning of server using appropriate tools Semiannual
10 Server
Dissemble equipment accessing all its electronic parts: memory, RAM, hard drive, disc reader, coolers, power source, etc.
Report to user of any issues found in any of the parts
Semiannual
11 Server Remove dust from all electronic parts Semiannual
12 Server
Cleaning of internal components, main contactors and circuits using appropriate cleaning tools
Semiannual
13 Server Measurement of the internal battery of the Semiannual main board. If it is lower than 2.5V, replace battery.
14 Server Assemble of the equipment (NVR) Semiannual
15 Server Turn on and check operation of equipment (NVR) Semiannual
16 Server
Check Onguard management system.
Verify set-up, update credentials, verify RAID, update date and time, calibrate cameras, update firmware
Semiannual
17 Server Perform final diagnosis of the NVR Semiannual
18 UPS – Uninterrupted Power Supply Visual inspection Semiannual
19 UPS – Uninterrupted Power Supply
External cleaning of UPS equipment using appropriate tools Semiannual
20 UPS – Uninterrupted Power Supply
Dissemble equipment accessing all its electronic parts Semiannual
21 UPS – Uninterrupted Power Supply Remove dust from all electronic parts. Semiannual
22 UPS – Uninterrupted Power Supply
Cleaning of internal components, main contactors and circuits using appropriate cleaning tools Semiannual
23 UPS – Uninterrupted Power Supply
Measurement of the internal battery of the main board. If it is lower than 2.5V, replace battery.
Semiannual
24 UPS – Uninterrupted Power Supply
Assemble of UPS Semiannual
25 UPS – Uninterrupted Power Supply Load testing to UPS Semiannual
26 UPS – Uninterrupted Power Supply
Perform final diagnosis to UPS Semiannual
27 Switch Visual inspection Semiannual
28 Switch External cleaning of switch using appropriate tools Semiannual
29 Switch Dissemble equipment accessing all its electronic parts: memory Semiannual
30 Switch Remove dust from all electronic parts. Semiannual
31 Switch Cleaning of internal components, main contactors and circuits using appropriate cleaning tools
Semiannual
32 Switch Assemble of switch Semiannual 33 Switch Test operation of switch Semiannual 34 Switch Perform final diagnosis to switch Semiannual 35 Communication Rack Visual inspection Semiannual
36 Communication Rack External and internal cleaning of Rack using appropriate tools Semiannual
37 Communication Rack Check and organize cables if necessary Semiannual 38 Communication Rack Identification and labeling of cables Semiannual 39 Communication Rack Verify operation of coolers Semiannual 40 Communication Rack Verify grounding of rack Semiannual
41 Control Panel External and internal cleaning Semiannual 42 Control Panel Check and organize cables if necessary Semiannual 43 Control Panel Identification and labeling of cables Semiannual
44 Control Panel Verify operation of the printed circuit board (interface or controller). Semiannual
45 Control Panel Verify grounding Semiannual 46 HID Proximity card readers External and internal cleaning Semiannual 47 HID Proximity card readers Check and organize cables if necessary Semiannual 48 HID Proximity card readers Cleaning of terminal blocks Semiannual 49 HID Proximity card readers Check of terminal joints Semiannual 50 HID Proximity card readers Identification and labeling of cables Semiannual 51 HID Proximity card readers Verify operation of the system Semiannual 52 HID Proximity card readers Test operation of the system Semiannual 53 Biometric devices/panels External and internal cleaning Semiannual 54 Biometric devices/panels Check and organize cables if necessary Semiannual 55 Biometric devices/panels Identification and labeling of cables Semiannual 56 Biometric devices/panels Verify data connection Semiannual 57 Biometric devices/panels Verify operation of the system Semiannual 58 Biometric devices/panels Test operation of the system Semiannual 59 Locks External and internal cleaning Semiannual 60 Locks Check and organize cables if necessary Semiannual 61 Locks Identification and labeling of cables Semiannual 62 Locks Verify data connection Semiannual 63 Locks Test operation of the system Semiannual
64 Others Verify operation of the KVM switch with mountable monitor Semiannual
65 Others
Verify network cabling is not corroded or in bad shape or deteriorated. Proceed to replace cabling, patch cords, etc., if necessary.
Semiannual
66 Others Verify operation of all the access control system Semiannual
67 Others Perform general cleaning and calibration of each door Semiannual
68 Others Perform general cleaning to biometric devices Semiannual
69 Others Verify the operation of all the equipment that is part of the access control system. Semiannual
70 Others
Provide the required maintenance by manufacturer of equipment to maintain in good working conditions all the access control system
Semiannual
71 Others Provide diagnostic and minor corrective activities that not include purchase of materials, such as, update firmware.
Semiannual
72 Others Perform inspections to patch cords and jacks and replace a maximum of 10 patch cords and 10 jacks cat 6
73 Others Provide training to two namru-6 facilities Annual staff on the use and operation of the access control system
74 Others Replace 12V, 7.0AH (NP7-12) batteries on an annual basis of all the electrical control panels Annual
75 Others Elaborate, review and update drawings on AUTOCAD of the access control system Annual
76 Others Renew NAMRU-6 licenses with LENEL of each one of the devices of the access control system
Annual
Contractor will also include requirements per O&M manuals and any additional requirements not mentioned in this document but required or recommended by manufacturer (LENEL) as preventive maintenance activities to perform semi-annually or annually.
CCTV SYSTEM
The CCTV system in Lima has 43 cameras, from different manufacturers, TruVision and Axis. It has two recorders (XNVR) brand TRUVISION (XNVR1 and XNVR2), a main server brand DELL, four communication racks and two stich on posts and a 3KVA UPS for the main rack and five video consoles, workstations (PC clients).
The CCTV system in Iquitos has 14 cameras, from different manufacturers, Panasonic and Axis. It has a Panasonic brand recorder, and a two PC client.
At the completion of the maintenance activities, the contractor shall provide a detailed report of all the cameras in Lima and Iquitos with pictures to evidence the status prior and after execution of preventive maintenance. The contractor shall perform the following preventive maintenance activities:
CCTV SYSTEM – LIMA & IQUITOS
1 PC client Check and/or update software of the PC clients (anti-virus, Microsoft software and
Adobe Acrobat Reader) Monthly
2 Cameras General review of camera status Semiannual 3 Cameras General cleaning Semiannual 4 Cameras Review, check and calibrate the lens. Semiannual 5 Cameras Operation check Semiannual 6 Cameras Review of normal operation of the cameras Semiannual 7 Cameras Validation with the Namru6 control center Semiannual 8 Cameras Verification of support status and housing Semiannual 9 PC client Visual inspection Semiannual
10 PC client External cleaning of PC using appropriate tools Semiannual
11 PC client Dissemble PC accessing all its electronic Semiannual parts 12 PC client Remove dust from all electronic parts. Semiannual 13 PC client Cleaning of internal components Semiannual 14 PC client Assemble PC Semiannual 15 PC client Test operation of PC Semiannual 16 PC client Perform final diagnosis to PC Semiannual 17 Server Visual inspection Semiannual
18 Server External cleaning of server using appropriate tools Semiannual
19 Server
Dissemble equipment accessing all its electronic parts: memory, RAM, hard drive, disc reader, coolers, power source, etc.
Report to user of any issues found in any of the parts
Semiannual
20 Server Remove dust from all electronic parts Semiannual
21 Server
Cleaning of internal components, main contactors and circuits using appropriate cleaning tools
22 Server
Measurement of the internal battery of the main board. If it is lower than 2.5V, replace battery.
23 Server Assemble of the equipment (NVR) Semiannual
24 Server Turn on and check operation of equipment (NVR) Semiannual
25 Server
Check Onguard management system.
Verify set-up, update credentials, verify RAID, update date and time, calibrate cameras, update firmware
Semiannual
26 Server Perform final diagnosis of the NVR Semiannual
27 UPS – Uninterrupted Power Supply Visual inspection Semiannual
28 UPS – Uninterrupted Power Supply
External cleaning of UPS equipment using appropriate tools Semiannual
29 UPS – Uninterrupted Power Supply
Dissemble equipment accessing all its electronic parts Semiannual
30 UPS – Uninterrupted Power Supply Remove dust from all electronic parts. Semiannual
31 UPS – Uninterrupted Power Supply
Cleaning of internal components, main contactors and circuits using appropriate cleaning tools Semiannual
32 UPS – Uninterrupted Power Supply
Measurement of the internal battery of the main board. If it is lower than 2.5V, replace battery.
Semiannual
33 UPS – Uninterrupted Power Supply Assemble of UPS Semiannual
34 UPS – Uninterrupted Power Supply Load testing to UPS Semiannual
35 UPS – Uninterrupted Power Perform final diagnosis to UPS Semiannual
Supply 36 Switch Visual inspection Semiannual
37 Switch External cleaning of switch using appropriate tools Semiannual
38 Switch Dissemble equipment accessing all its electronic parts: memory Semiannual
39 Switch Remove dust from all electronic parts. Semiannual
40 Switch Cleaning of internal components, main contactors and circuits using appropriate cleaning tools
Semiannual
41 Switch Assemble of switch Semiannual 42 Switch Test operation of switch Semiannual 43 Switch Perform final diagnosis to switch Semiannual 44 Communication Rack Visual inspection Semiannual
45 Communication Rack External and internal cleaning of Rack using appropriate tools Semiannual
46 Communication Rack Check and organize cables if necessary Semiannual 47 Communication Rack Identification and labeling of cables Semiannual 48 Communication Rack Verify operation of coolers Semiannual 49 Communication Rack Verify grounding of rack Semiannual
50 Others Verify operation of the KVM switch with mountable monitor Semiannual
51 Others
Verify network cabling is not corroded or in bad shape or deteriorated. Proceed to replace cabling, patch cords, etc., if necessary.
Semiannual
52 Others Verify operation of all the CCTV system Semiannual
53 Others Verify the operation of all the equipment that is part of the CCTV system.
54 Others
Provide the required maintenance by manufacturer of equipment to maintain in good working conditions all the CCTV system
Semiannual
55 Others Provide diagnostic and minor corrective activities that not include purchase of materials, such as, update firmware
Semiannual
56 Others Perform inspections to patch cords and jacks and replace a maximum of 10 patch cords and 10 jacks cat 6
Semiannual
57 Others Provide training to two namru-6 facilities staff on the use and operation of the CCTV system
Annual
58 Others Elaborate, review and update drawings on AUTOCAD of the access control system Annual
59 Others Renew NAMRU-6 licenses with LENEL of each one of the devices of the CCTV system
Annual
PUBLIC ADDRESS SYSTEM
The public address system in Lima has two amplifiers, one evacuation panel, one mixer and one sound repeater.
The public address system in Iquitos has one amplifier, one evacuation panel, one mixer and sound repeater.
Contractor shall perform the following preventive maintenance activities:
PUBLIC ADDRESS SYSTEM – LIMA & IQUITOS
1 Amplifiers External and internal cleaning Semiannual 2 Amplifiers Identification and labeling of cables Semiannual 3 Amplifiers Verify data connection Semiannual 4 Amplifiers Test operation of the system Semiannual 5 Speakers External and internal cleaning Semiannual 6 Speakers Identification and labeling of cables Semiannual 7 Speakers Verify electrical connections and data Semiannual 8 Speakers Verify data connection Semiannual 9 Speakers Test operation of the system Semiannual
10 Others
Verify network cabling is not corroded or in bad shape or deteriorated. Proceed to replace cabling, patch cords, etc., if necessary.
Semiannual
11 Others Verify operation of all the public address system Semiannual
12 Others Verify the operation of all the equipment that is part of the public address system. Semiannual
13 Others
Provide the required maintenance by manufacturer of equipment to maintain in good working conditions all the public address system
Semiannual
14 Others Provide diagnostic and minor corrective activities that not include purchase of materials, such as, update firmware
Semiannual
15 Others Provide training to two namru-6 facilities staff on the use and operation of the public address system
Annual
16 Others Elaborate, review and update drawings on AUTOCAD of the public address system Annual
SERVICE LEVELS
Companies working with LENEL systems provide service levels for emergency calls. For the CCTV, access control system and public address system, contractor must provide remote special assistance by a certified LENEL expert technician at any time during working hours (emergency call level #1). In case on site assistant is necessary to solve the issue, contract must include a 24 bank of hours for in situ repairs by a certified LENEL expert technician in both Lima and Iquitos facilities (emergency call level #2). In Lima and Iquitos, the emergency call level #2 will start when technician gets to the NAMRU-6 security gate.
ADDITIONAL INFORMATION
ANNEX 1: PREVENTIVE MAINTENANCE PERFORM IN 2020 TO CCTV SYSTEM IN LIMA
ANNEX 2: PREVENTIVE MAINTENANCE PERFORM IN 2020 TO ACCESS CONTROL
SYSTEM IN LIMA
ANNEX 3: PREVENTIVE MAINTENANCE PERFORM IN 2020 TO PUBLIC ADDRESS
SYSTEM IN LIMA
ANNEX 4: PREVENTIVE MAINTENANCE PERFORM IN 2019 TO CCTV SYSTEM, ACCESS
CONTROL SYSTEM AND PUBLIC ADDRESS SYSTEM IN IQUITOS
ANNEX 1
Electronic Security Systems S.A.C.
Av. Alfredo Benavides 768, Edificio Gerpal, Oficina 1106, Miraflores – Lima Teléfonos: (511) 221-2900 / (511) 221-3378 info@essperu.com – www.essperu.com
MANTENIMIENTO PREVENTIVO DEL SISTEMA
DE CIRCUITO CERRADO DE TV (CCTV)
Proyecto
Naval Medical Research Unit 6 (NAMRU-6) Hospital Centro Médico Naval.
Av. República de Venezuela S/N, Callao
LIMA, PERÚ
NOVIEMBRE 2020
Teléfonos: (511) 221-2900 / (511) 221-3378 info@essperu.com – www.essperu.com
Miraflores, 23 de Noviembre del 2020
Señores Naval Medical Research Unit 6 (NAMRU-6) Dirección: Hospital Centro Médico Naval. Av. República de Venezuela S/N, Bellavista Callao.
Presente.-
Referencia: OC# N4485220P0133
Me es grato saludarlos y enviarles la descripción detallada del 1er servicio de
Mantenimiento preventivo realizado al sistema de circuito cerrado de TV (CCTV).
De acuerdo a este servicio, se ha generado el siguiente informe técnico donde se describen los trabajos realizados desde el día 02 al 16 de noviembre de 2020.
A continuación, se presenta el detalle del informe.
Atentamente, Hadib J. Camargo Arb Supervisor de Mantenimiento Electronic Security Systems SAC
Teléfonos: (511) 221-2900 / (511) 221-3378 info@essperu.com – www.essperu.com
INFORME.ESS - MANTTO CCTV- NAMRU6 -23-11-2020
SISTEMA: SISTEMA DE CIRCUITO CERRADO DE TV
ESPECIALIDAD: SEGURIDAD ELECTRONICA
EJECUTADO POR: ELECTRONIC SECURITY SYSTEMS SAC.
PROPIETARIO: Naval Medical Research Unit 6 (NAMRU-6)
UBICACION:
Hospital Centro Médico Naval. Av. República de Venezuela S/N, Bellavista Callao
SUPERVISOR: Hadib J. Camargo Arb
1. DESCRIPCION DEL SISTEMA
El sistema de circuito cerrado de TV se encuentra instalado en el conjunto de edificios y áreas que comprenden la Naval Medical Research Unit 6 (NAMRU-6), ubicado en las instalaciones del Hospital Centro Médico Naval, Av. República de
Venezuela S/N Bellavista Callao. Dichas edificaciones cuentan con un sistema de
CCTV que contempla cámaras fijas, cámaras tipo domo y cámaras PTZ.
El sistema de CCTV de NAMRU6 se centraliza en dos NVR´s ubicados en cuarto de supervisión del edificio 2, nivel sótano, es de ahí que el sistema en mención se distribuye para observar las áreas estratégicas de las instalaciones.
2. ALCANCE
Mantenimiento preventivo del sistema de Circuito Cerrado de TV de NAMRU6.
3. OBJETIVO
Revalidar el desempeño de funcionamiento del sistema de Circuito Cerrado de TV, NAMRU6, para garantizar su correcto funcionamiento.
Antes de iniciar con los trabajos se realizó la inspección visual de los DVR’s, Cámaras y demás dispositivos que componen el sistema de CCTV.
4. DESCRIPCIÓN DEL MANTENIMIENTO
Se realizó mantenimiento preventivo a los dispositivos del sistema de circuito cerrado de
TV. Asimismo, se verificaron cuidadosamente las señales de video, como también las lecturas respectivas de voltaje a los adaptadores de las cámaras.
Se realizó el mantenimiento de cámaras fijas, cámaras domo y ptz, realizando la limpieza manual y la eliminación de polvo. Se destapa su cobertor superior y se inicia a la limpieza de la tarjeta electrónica y la limpieza suave en el lente ocular.
Se realizó el mantenimiento de los NVR y demás dispositivos del sistema de Circuito
Cerrado de TV.
5. DISPOSITIVOS Y/O EQUIPOS REVISADOS
Cámara tipo Domo. (24) Marca: Interlogix Truvision Modelo: TVD-N245V-2-N
Cámara tipo Domo. (03) Marca: AXIS Modelo: --
Cámara tipo PTZ. (06) Marca: AXIS
Cámara tipo Tubular. (10)
Modelo: TVB-5303
Cámara tipo Box. (04)
Modelo: TVC-N240-1-N
Estación de trabajo Workstation. (02) Marca: DELL Modelo: PRECISION 5820
Estación de trabajo Workstation. (01) Marca: DELL
Modelo: PRECISION T1650
Estación de trabajo Workstation. (01) Marca: DELL Modelo: PRECISION TOWER 5810
Consola en Rack Monitor y Teclado. (01) Marca: DELL Modelo: 1U KMM 17FP Monitor
Monitor 32”. (04) Marca: Interlogix Modelo: --
Monitor 19”. (01) Marca: Interlogix Modelo: --
Monitor 19”. (01) Marca: DELL Modelo: --
Grabador NVR. (02) Marca: Truvision Modelo: NVR70
Switch Ethernet. (03) Marca: Allied Telesis Modelo: AT-8000S
Switch Ethernet. (01) Marca: PLANET Modelo: --
Switch Ethernet. (01) Marca: CISCO Modelo: Catalyst 9300
6. DESCRIPCION DEL SERVICIO MANTENIMIENTO PREVENTIVO.
El servicio de Mantenimiento Preventivo al Sistema de circuito cerrado de TV se sugiere realizar con frecuencia semestral y contempla las siguientes actividades de ser aplicables:
6.1. Verificación del Estado General del Sistema. Para ello se tomará nota de:
Cantidad de cámaras reportados en el Monitor de visualización Cantidad de Problemas Activos reportados en el Monitor de visualización Observaciones relativas
6.2. Mantenimiento a las cámaras
Revisión general de estado Limpieza exterior Limpieza interior Verificación, ajuste y corrección de conexiones Verificación, ajuste de instalación Verificación y ajuste de Alineamiento
6.3. Mantenimiento al NVR
Revisión general de estado Limpieza exterior Limpieza interior Verificación, ajuste y corrección de conexiones.
7. REGISTRO GRÁFICO DEL SERVICIO
Antes y después de Mantenimiento Cámara PTZ Edificio 10
Antes y después de Mantenimiento Cámaras PTZ en poste costado Edificio 10
Antes y después de Mantenimiento Cámaras Tubular y PTZ Edificio 2
Antes y después de Mantenimiento Cámara PTZ Edificio 11
Antes y después de Mantenimiento Cámara Tubular Edificio 11
Antes y después de Mantenimiento a Cámara Tubular ubicada en Tanque de Agua
Antes y después de Mantenimiento a Workstations en cuarto de control edificio 10
Antes y después de Mantenimiento a Workstation y NVR en cuarto de supervisión edificio 2, nivel sótano.
Antes y después de Mantenimiento a Cámara Tubular edificio 1 escalera de emergencia
Antes y después de Mantenimiento a Cámara Box edificio 1 escalera de emergencia
Antes y después de Mantenimiento a Cámara Tubular en tranquera vehicular
Antes y después de Mantenimiento a Cámara PTZ en pasadizo Warehouse
Antes y después de Mantenimiento a Cámaras domo y gabinetes de control en Laboratorios.
Mantenimiento a Cámaras, racks y otros dispositivos en áreas internas de edificios.
8. OBSERVACIONES Y RECOMENDACIONES
Se recomienda realizar el mantenimiento preventivo cada seis meses, para asegurar el correcto funcionamiento de sistema y la integridad de todos sus componentes.
Se encontró cámara tipo Box inoperativa en edificio 10, piso 2 ingreso cuarto de control. Se sugiere su reemplazo.
Se encontró deterioro por corrosión en soportes de cámaras PTZ.
Se observaron rayas en las cúpulas de las cámaras de los laboratorios 113, 119 y
109.
Debido a imposibilidad del acceso de un manlit, no fue posible realizar el mantenimiento a la cámara PTZ ubicada en el tanque de agua.
Debido a falta de acceso, no fue posible realizar el mantenimiento a la cámara domo ubicada en el edificio 2 laboratorio 215.
9. CONCLUSIONES GENERALES
El sistema de Circuito Cerrado de TV de NAMRU6, se encuentra operativo y en funcionamiento.
Nombre de Contratista: _HADIB CAMARGO____________________ Fecha: 23-11-12020
ESS - SAC
Firma:
Nombre del cliente o representante: __________________________ Fecha: 23-11-2020
NAMRU6
ANNEX 2
Teléfonos: (511) 221-2900 / (511) 221-3378 info@essperu.com – www.essperu.com
MANTENIMIENTO PREVENTIVO DEL SISTEMA
CONTROL DE ACCESO E INTRUSIÓN (CAI)
Proyecto
Naval Medical Research Unit 6 (NAMRU-6) Hospital Centro Médico Naval.
Av. República de Venezuela S/N, Callao
Teléfonos: (511) 221-2900 / (511) 221-3378 info@essperu.com – www.essperu.com
Miraflores, 23 de Noviembre del 2020
Señores Naval Medical Research Unit 6 (NAMRU-6) Dirección: Hospital Centro Médico Naval. Av. República de Venezuela S/N, Bellavista Callao.
Presente.-
Referencia: OC# N4485220P0133
Me es grato saludarlo y enviarle la descripción detallada del 1er servicio de mantenimiento preventivo realizado al sistema de control de acceso e instrucción
(CAI), De acuerdo a este servicio, se ha generado el siguiente informe técnico donde se describen los trabajos realizados desde el día 02 al 16 de noviembre de
2020.
A continuación, se presenta el detalle del informe.
Atentamente, Hadib J. Camargo Arb
INFORME.ESS - MANTTO CAI- NAMRU6 -23-11-2020
SISTEMA: SISTEMA DE CONTROL DE ACCESO E INTRUSIÓN
ESPECIALIDAD: SEGURIDAD ELECTRONICA
EJECUTADO POR: ELECTRONIC SECURITY SYSTEMS SAC.
PROPIETARIO: Naval Medical Research Unit 6 (NAMRU-6)
UBICACION:
Hospital Centro Médico Naval. Av. República de Venezuela S/N, Mantenimiento preventivo del sistema de control de acceso e intrusión que se encuentra instalado en el conjunto de edificios y áreas que comprenden la Naval
Medical Research Unit 6 (NAMRU-6), ubicado en las instalaciones del Hospital
Centro Médico Naval, Av. República de Venezuela S/N Bellavista Callao. Dichas edificaciones cuentan con un sistema que ocupa tarjetas de control, lectoras de tarjetas de acceso, tranquera vehicular, cerraduras electromagnéticas y contactos magnéticos.
Mantenimiento preventivo del sistema de Control de Accesos e Intrusión de
NAMRU6.
Revalidar el desempeño de funcionamiento del sistema de Control de Accesos e
Intrusión, NAMRU6, para garantizar su correcto funcionamiento.
Antes de iniciar los trabajos se procedió al reconocimiento de campo en adelante, la programación de tareas, el requerimiento de accesos y llaves para facilidades para realizar los trabajos.
Al comenzar el servicio se toma nota de todo el funcionamiento del sistema de control de acceso en las instalaciones de la unidad de investigación. Se ven las observaciones por parte del cliente y se enfoca las revisiones en los puntos mencionados. Se intervienen los controladores, cerraduras, lectoras, fuentes y sus terminales.
El trabajo se finaliza con el informe final con el estado del sistema de control de acceso e intrusión.
5. DISPOSITIVOS Y/O EQUIPOS REVISADOS
Cerraduras Electromagnéticas. (12) Marca: SECOLARM
Lectora de tarjeta de Proximidad. (29) Marca: HID Modelo: Proxpoint Plus 6500
Lectora de tarjeta de Proximidad. (1) Marca: HID Modelo: MaxiProx 5375
Contacto magnético semipesado. (12) Marca: SECOLARM Modelo: SM 216Q/BR
Pulsador de aborto. (03) Marca: ENFORCE Modelo: --
Tarjeta de control de accesos. (03) Marca: LENEL Modelo: LNL3300
Tarjeta de control de accesos. (08) Marca: LENEL Modelo: LNL1007
Tarjeta de control de accesos. (07) Marca: LENEL Modelo: LNL1300
El servicio de Mantenimiento Preventivo al Sistema de Control de Accesos e Intrusión se sugiere realizar con frecuencia semestral y contempla las siguientes actividades de ser aplicables:
6.1. Verificación del Estado General del Sistema. Para ello se tomará nota de:
Cantidad de dispositivos reportados en el monitor de visualización.
Cantidad de Problemas Activos reportados en el Monitor de visualización.
Observaciones relativas.
6.2. Mantenimiento a cerraduras electromagnéticas
Revisión general de estado Limpieza exterior Verificación, ajuste y corrección de conexiones Verificación, ajuste de instalación Verificación y ajuste de Alineamiento
6.3. Mantenimiento a lectoras de tarjetas de proximidad
Revisión general de estado Limpieza exterior Verificación, ajuste y corrección de conexiones.
6.4. Mantenimiento a pulsadores de salida
Revisión general de estado Limpieza exterior Limpieza interior Verificación, ajuste y corrección de conexiones.
6.4. Mantenimiento a tarjetas de control de acceso y fuentes
Revisión general de estado Limpieza exterior Limpieza interior Verificación de niveles de voltaje en baterías.
Ajuste y corrección de conexiones.
Antes y después de Mantenimiento dispositivos de campo: contactos magnéticos, cerraduras electromagnéticas y lectoras de tarjetas de proximidad.
Antes y después de Mantenimiento sensor foto eléctrico a tranquera vehicular.
Antes y después de Mantenimiento a gabinetes de tarjetas de control de acceso y fuentes componentes.
Se observaron niveles de voltaje fuera de rango en las baterías del gabinete #7 ubicado en el sótano del edificio 2. Se sugiere su reemplazo.
Se observó que el gabinete de la fuente de alimentación veterinaria BSL114C no posee batería. Se sugiere su colocación.
La tranquera de ingreso vehicular no posee plumilla. Personal indica que fue retirada por razones operativas.
El sistema de Control de Accesos e Intrusión de NAMRU6, se encuentra operativo y en funcionamiento.
ANNEX 3
MANTENIMIENTO PREVENTIVO DEL SISTEMA
DE AUDIO (PERIFONEO)
Proyecto
Naval Medical Research Unit 6 (NAMRU-6)
Hospital Centro Médico Naval.
Av. República de Venezuela S/N, Callao
Teléfonos: (511) 221-2900 / (511) 221-3378 info@essperu.com – www.essperu.com
Miraflores, 23 de Noviembre del 2020
Señores Naval Medical Research Unit 6 (NAMRU-6) Dirección: Hospital Centro Médico Naval. Av. República de Venezuela S/N, Bellavista Callao.
Presente.-
Referencia: OC# N4485220P0133
Me es grato saludarlo y enviarle la descripción detallada del 1er servicio de mantenimiento preventivo realizado al sistema de perifoneo. De acuerdo a este servicio, se ha generado el siguiente informe técnico donde se describen las actividades realizadas desde el día 02 al 16 de noviembre de 2020.
A continuación, se presenta el detalle del informe.
Atentamente, Hadib J. Camargo Arb
INFORME.ESS - MANTTO PERIFONEO- NAMRU6 -23-11-2020
SISTEMA: SISTEMA DE AUDIO (PERIFONEO)
ESPECIALIDAD: SEGURIDAD ELECTRONICA
EJECUTADO POR: ELECTRONIC SECURITY SYSTEMS SAC.
PROPIETARIO: Naval Medical Research Unit 6 (NAMRU-6)
UBICACION:
Hospital Centro Médico Naval. Av. República de Venezuela S/N, Mantenimiento preventivo del sistema de Perifoneo que se encuentra instalado en el conjunto de edificios y áreas que comprenden la Naval Medical Research Unit 6
(NAMRU-6), ubicado en las instalaciones del Hospital Centro Médico Naval, Av.
República de Venezuela S/N Bellavista Callao. Dichas edificaciones cuentan con un sistema que audio (perifoneo) con equipos principales ubicados en el centro de control del edificio 10, punto desde el cual se conectan a la red de parlantes distribuidos en los edificios de la unidad.
Mantenimiento preventivo del sistema de Perifoneo de NAMRU6.
Revalidar el desempeño de funcionamiento del sistema de Perifoneo, NAMRU6, para garantizar su correcto funcionamiento.
Antes de iniciar los trabajos se procedió al reconocimiento de campo en adelante, la programación de tareas, el requerimiento de accesos y llaves para facilidades para realizar los trabajos.
Al comenzar el servicio se toma nota de todo el funcionamiento del sistema de
Perifoneo en las instalaciones de la unidad de investigación. Se ven las observaciones por parte del cliente y se enfoca las revisiones en los puntos mencionados. Se intervienen los parlantes, mezcladores y amplificadores.
El trabajo se finaliza con el informe final con el estado del sistema de audio (perifoneo).
5. DISPOSITIVOS Y/O EQUIPOS REVISADOS
Parlante redondo. (42) Marca: PERFECTION Modelo: RMS
Parlante Cuadrado. (04) Marca: GENTEX Modelo: SSP-KCL-PR
Parlante Cuadrado. (07) Marca: WEELOCK Modelo: E70
Micrófono Unidireccional. (01) Marca: TOA COPORATION Modelo: PM-660U
Amplificador PA. (02) Marca: TOA COPORATION Modelo: P-1812 ER
Repetidor de sonido. (01) Marca: TOA COPORATION Modelo: EV-20R
Mezclador de 4 zonas. (01) Marca: SAMSON
El servicio de Mantenimiento Preventivo al Sistema de Audio (Perifoneo) se sugiere realizar con frecuencia semestral y contempla las siguientes actividades de ser aplicables:
6.1. Verificación del Estado General del Sistema. Para ello se tomará nota de:
Cantidad de Problemas Activos reportados por el personal del cliente.
Observaciones relativas.
6.2. Mantenimiento a parlantes
Revisión general de estado
Limpieza exterior
Limpieza interior
Verificación, ajuste y corrección de conexiones
Verificación, ajuste de instalación
6.3. Mantenimiento a equipos amplificadores
Revisión general de estado
Limpieza exterior
Limpieza interior
Verificación, ajuste y corrección de conexiones
6.4. Mantenimiento a equipos mezcladores
Revisión general de estado
Limpieza exterior
Limpieza interior
Verificación, ajuste y corrección de conexiones
6.4. Mantenimiento a micrófonos
Revisión general de estado
Limpieza exterior
Ajuste y verificación de conexiones
Antes y después del Mantenimiento dispositivos de campo: parlantes distribuidos por el campus, amplificadores y mezclador ubicados en centro de control edificio 10 piso 2.
MEZCLADOR
AMPLIFICADORES
REPETIDOR DE SONIDO
MICROFONO
PARLANTES
componentes.
Se observaron dos parlantes marca GENTEX en el edificio 11, desconectados y con cables empalmados dentro de la caja de paso. Se sugiere verificación.
Se realizaron pruebas de operatividad del sistema, sin resultados positivos.
Se verificaron las conexiones entre los equipos principales, pudiendo visualizar movimiento en el indicador de dB del mezclador, sin embargo no se obtuvo emisión de audio en ningún ambiente. Se sugiere realizar una revisión completa a los componentes del sistema para determinar la operatividad de los mismos.
El sistema de Control de Audio (Perifoneo) de NAMRU6, no se encuentra operativo, requiere revisión.
ANNEX 4
MANTENIMIENTO PREVENTIVO DE
SISTEMA DE CCTV, ACS Y PERIFONEO
SEDE IQUITOS
INFORME TÉCNICO
Febrero 2019
MANTENIMIENTO PREVENTIVO SISTEMA DE CCTV, ACS Y PERIFONEO, NAMRU6 - IQUITOS 2
VIDITEK – Tecnología de Seguridad Corporativa Cal. José Gabriel Chariarse Nro. 151 - int. 1A, Miraflores - Lima 41, PERÚ T. (51-1) 612-5500 www.viditek.com
INDICE
Contenido
1. OBJETIVO
2. ALCANCE DEL SERVICIO
3. MANTENIMIENTO PREVENTIVO
3.1. Inspección Inicial
3.2. Mantenimiento Preventivo
3.2.1. Sistema de Control de Acceso
3.2.1.1. Puerta acceso a UPS Room & Electrical Room
3.2.1.2. Puerta Laboratorio
3.2.1.3. Puerta Laboratorio VEID
3.2.1.4. Puerta Insectario 1er Piso Posterior
3.2.1.5. Puerta Insectario 1er Piso Frontal
3.2.1.6. Puerta Insectario 2do Piso Lateral Frontal
3.2.1.7. Puerta Insectario 2do Piso Posterior
3.2.1.8. Paneles ACS en Security Comm 208
3.2.1.9. Servidor OnGuard sistema ACS
3.2.2. Sistema de CCTV
3.2.2.1. Cámara analógica CH1
3.2.2.2. Cámara analógica CH2
3.2.2.3. Cámara analógica CH3
3.2.2.4. Cámara analógica CH4
3.2.2.5. Cámara analógica CH5
3.2.2.6. Cámara IP PTZ frontal 1er piso Insectaria
3.2.2.7. Cámara IP PTZ posterior 1er piso Insectaria
3.2.2.8. Cámara IP PTZ frontal 2do piso Insectaria
3.2.2.9. Cámara IP PTZ posterior 2do piso Insectaria
3.2.2.10. Equipos CCTV en Garita Vigilancia
3.2.2.11. Equipos CCTV en Security Room 208
3.2.2.12. Fuentes de alimentación de cámaras analógicas
3.2.3. Sistema de Perifoneo
4. CONCLUSIONES
5. RECOMENDACIONES FINALES
MANTENIMIENTO PREVENTIVO SISTEMA DE CCTV, ACS Y PERIFONEO, NAMRU6 - IQUITOS 3
Cal. José Gabriel Chariarse Nro. 151 - int. 1A, Miraflores - Lima 41, PERÚ T. (51-1) 612-5500 www.viditek.com
1. OBJETIVO
El objetivo del presente informe es reportar el estado de los Sistemas de CCTV, ACS y perifoneo de Namru-6 sede Iquitos, así como los correctivos requeridos y las recomendaciones respectivas luego de finalizado el servicio de mantenimiento.
2. ALCANCE DEL SERVICIO
El alcance del servicio incluye lo descrito en el documento “Scope of Work":
- El sistema de control de acceso cuenta con 10 puertas, el cual está conformado entre cerraduras eléctricas, contactos magnéticos, lectoras de ingreso y salida, brazos hidráulicos, barra anti pánico y sirenas, todos con la marca LENEL. Cuenta además con sus paneles de control dentro de cada edificio.
- El sistema de CCTV cuenta con un total de 14 cámaras, de diferentes fabricantes, Panasonic y Axis. Cuenta con un grabador de marca Panasonic, acompañado de una PC cliente.
- El sistema de perifoneo cuenta con 1 amplificador, 1 panel de evacuación, 1 mixer y repetidor de sonido.
3. MANTENIMIENTO PREVENTIVO
Los trabajos se realizaron entre los días 11 de febrero de 2019 y el 13 de febrero de 2019, por personal técnico de Viditek S.A.C. en la sede Namru-6 Iquitos.
A continuación, se detallan los trabajos de mantenimiento preventivo para los sistemas ACS, CCTV y perifoneo.
3.1. Inspección Inicial
El día 08 de febrero de 2019 se realizó una inspección visual de los sistemas involucrados en el mantenimiento.
ACS
Se encontraron 7 puertas instaladas en las siguientes áreas:
- Laboratorio
- Laboratorio VEID
- Acceso sala UPS y sala eléctrica
- Insectario Piso 1 frontal
- Insectario Piso 1 posterior
- Insectario Piso 2 frontal
- Insectario Piso 1 posterior
Las demás puertas se encuentran desmontadas por trabajos de construcción según indicó personal de Namru-6 en sitio.
Los controladores ACS se encontraron en antesala hacia sala UPS y sala eléctrica y en Security Room en el segundo piso del edificio Insectario.
También se encontraron equipos de control de asistencia a un costado de garita de vigilancia.
MANTENIMIENTO PREVENTIVO SISTEMA DE CCTV, ACS Y PERIFONEO, NAMRU6 - IQUITOS 4
Cal. José Gabriel Chariarse Nro. 151 - int. 1A, Miraflores - Lima 41, PERÚ T. (51-1) 612-5500 www.viditek.com
Fig. 1 - ACS en Laboratorio
Fig. 2 - ACS en Laboratorio VEID
Fig. 3 - Tablero ACS en hall en antesala a sala UPS y sala Eléctrica
Fig. 4 - Equipos de Control de Asistencia al costado de garita de vigilancia
Fig. 5 - Gabinetes de ACS en Security Room dentro de Insectario
MANTENIMIENTO PREVENTIVO SISTEMA DE CCTV, ACS Y PERIFONEO, NAMRU6 - IQUITOS 5
Cal. José Gabriel Chariarse Nro. 151 - int. 1A, Miraflores - Lima 41, PERÚ T. (51-1) 612-5500 www.viditek.com
Fig. 6 - Puertas en edificio Insectario
CCTV
Se encontraron las siguientes cámaras:
- 4 cámaras fijas analógicas en housing para exteriores alrededor del estacionamiento
- 1 cámara fija analógica en housing para exteriores dentro del Laboratorio
- 4 cámaras PTZ IP en la parte exterior frontal y posterior del primer y segundo piso del
Insectario
En la garita de vigilancia se encontró un monitor conectado a un DVR analógica el cual se controla mediante un mouse óptico, se tiene video de 4 de las 5 cámaras analógicas.
También se dispone de una estación cliente con software iVMS-4200 de Hikvision para visualización de las 4 cámaras PTZ y un joystick el cual se encontró apagado.
Fig. 7 - DVR y monitor para cámaras analógicas
Fig. 8 - Cámaras analógicas en estacionamiento
MANTENIMIENTO PREVENTIVO SISTEMA DE CCTV, ACS Y PERIFONEO, NAMRU6 - IQUITOS 6
Cal. José Gabriel Chariarse Nro. 151 - int. 1A, Miraflores - Lima 41, PERÚ T. (51-1) 612-5500 www.viditek.com
Fig. 9 - Estación cliente para cámaras IP Hikvision
Fig. 10 - Cámaras PTZ en Insectario
Perifoneo
En la garita de CCTV se encontró:
- Amplificador de audio marca Perfection
- 1 micrófono
Dentro del área Laboratorio se encontró un micrófono
Fig. 11 - Amplificador de audio en garita de vigilancia
MANTENIMIENTO PREVENTIVO SISTEMA DE CCTV, ACS Y PERIFONEO, NAMRU6 - IQUITOS 7
Cal. José Gabriel Chariarse Nro. 151 - int. 1A, Miraflores - Lima 41, PERÚ T. (51-1) 612-5500 www.viditek.com
3.2. Mantenimiento Preventivo
Entre los días 11 y 13 febrero de 2019 se realizó el mantenimiento preventivo de los equipos existentes de los sistemas ACS, CCTV y perifoneo, en base a la inspección inicial.
Se realizó también limpieza de los equipos de Control de Asistencia (fuera del alcance).
3.2.1. Sistema de Control de Acceso
3.2.1.1. Puerta acceso a UPS Room & Electrical Room
Esta puerta cuenta con:
- Lectora de ingreso
- Chapa eléctrica EFS-07503L
- Interruptor de salida
Se encontraron 2 tableros con equipos de ACS:
- Tablero 1:
o Tarjeta LNL-1300 con dirección 4 o Fuente 220VAC a 24VDC @ 3A
- Tablero 2 o Tarjeta controladora LNL-1100 con dirección 9 o Tarjeta controladora LNL-500 con dirección 16 o Transformador 220/110VAC o Tarjeta OLS75 o Batería 12VDC @ 7Ah
Mediciones de voltaje:
- Salida de tarjeta OLS75: 13.48VDC
- Salida Batería: 12.98VDC
Se realizó limpieza interna, externa de gabinetes, tarjetas electrónicas, lectora de entrada, interruptor de salida, chapa eléctrica, asimismo se aseguraron conexiones de cableado en borneras de tarjetas electrónicas.
Se realizaron pruebas de operatividad con tarjeta con privilegios de acceso quedando todo operativo.
Observaciones:
- El pulsador de salida es un interruptor de luz ordinario.
- No existe contacto magnético para puerta.
- Se realizó calibración del freno de puerta para asegurar cierre automático
- El cableado de data entre tarjetas controladoras LNL-1100 y LNL-500 encontró haciendo falso contacto, se procedió a asegurar conexiones.
Fig. 12 - Tablero 1 puerta Acceso a UPS Room & Electrical Room 110
MANTENIMIENTO PREVENTIVO SISTEMA DE CCTV, ACS Y PERIFONEO, NAMRU6 - IQUITOS 8
Cal. José Gabriel Chariarse Nro. 151 - int. 1A, Miraflores - Lima 41, PERÚ T. (51-1) 612-5500 www.viditek.com
Fig. 13 - Tablero 2 puerta Acceso a UPS Room & Electrical Room 110
Fig. 14 - Detalle de interruptor de salida en acceso a UPS Room & Electrical Room 110
Fig. 15 - Chapa eléctrica y lectora de ingreso en acceso a UPS Room & Electrical Room
MANTENIMIENTO PREVENTIVO SISTEMA DE CCTV, ACS Y PERIFONEO, NAMRU6 - IQUITOS 9
Cal. José Gabriel Chariarse Nro. 151 - int. 1A, Miraflores - Lima 41, PERÚ T. (51-1) 612-5500 www.viditek.com
3.2.1.2. Puerta Laboratorio
Esta puerta cuenta con:
- Lectora de ingreso
- Lectora de salida
- Chapa eléctrica
- Barra antipánico
Se encontraron 1 tablero con equipos de ACS:
o Tarjeta LNL-1300 con dirección 5 para lectora de entrada o Tarjeta LNL-1300 con dirección 6 para lectora de salida o Fuente de alimentación a 24VDC
- Salida de fuente: 23.8VDC
Se realizó limpieza interna, externa de gabinetes, tarjetas electrónicas, lectora de entrada y de salida, barra antipánico, chapa eléctrica, asimismo se aseguraron conexiones de cableado en borneras de tarjetas electrónicas.
Se realizaron pruebas de operatividad con tarjeta con privilegios de acceso quedando todo operativo.
Observaciones:
- La lectora de salida no libera la chapa eléctrica, por el contrario, el cableado de salida se dirige a la barra antipánico.
- La barra antipánico se encontró inoperativa, se requiere cambio del equipo.
- En modo normal de operación la barra antipánico al recibir señal de la tarjeta LNL-1300 permite que la puerta se abra sin que se accione la sirena, en cambio, ante una apertura de la barra antipánico sin pasar tarjeta por lectora de salida igual permitirá una apertura de puerta, pero accionará la sirena alertando a personal de seguridad.
- No se encontró contacto magnético instalado en esta puerta.
- La chapa eléctrica se encontró con bornes soldados en mal estado, se procedió a restaurar soldadura y aislar fases.
- El freno de la puerta se reguló para asegurar cierre automático.
Fig. 16 - Tablero de interfaz y lectora de salida en puerta Laboratorio
MANTENIMIENTO PREVENTIVO SISTEMA DE CCTV, ACS Y PERIFONEO, NAMRU6 - IQUITOS 10
Cal. José Gabriel Chariarse Nro. 151 - int. 1A, Miraflores - Lima 41, PERÚ T. (51-1) 612-5500 www.viditek.com
Fig. 17 - Chapa eléctrica y lectora de ingreso
Fig. 18 - Detalle de chapa antes y después de soldadura en puerta Laboratorio
Fig. 19 - Barra antipánico inoperativa en puerta Laboratorio
MANTENIMIENTO PREVENTIVO SISTEMA DE CCTV, ACS Y PERIFONEO, NAMRU6 - IQUITOS 11
Cal. José Gabriel Chariarse Nro. 151 - int. 1A, Miraflores - Lima 41, PERÚ T. (51-1) 612-5500 www.viditek.com
3.2.1.3. Puerta Laboratorio VEID
Esta puerta cuenta con:
- Lectora de ingreso
- Lectora de salida
Se encontraron 1 tablero con equipos de ACS:
o Tarjeta LNL-1300 con dirección 8 para lectora de entrada o Tarjeta LNL-1300 con dirección 7 para lectora de salida o Fuente de alimentación a 24VDC
- Salida de fuente: 24.07VDC
Se realizó limpieza interna, externa de gabinetes, tarjetas electrónicas, lectora de entrada y de sallida, chapa eléctrica, asimismo se aseguraron conexiones de cableado en borneras de tarjetas electrónicas.
Se realizaron pruebas de operatividad con tarjeta con privilegios de acceso quedando todo operativo.
Observaciones:
- La tarjeta LNL-1300 con dirección 8 presenta un relé averiado y cuenta con un relé externo conectado para apertura de puerta de entrada.
- La apertura de salida del Laboratorio VEID se registra con la lectora de salida, pero no se libera chapa eléctrica, no existe conexión de relé de salida.
- Se encontró chapa eléctrica oxidada, pero operativa. Está sujeta a una base de aluminio adaptada y empotrada a pared.
- La puerta se encontró descuadrada, se requiere alineamiento (fuera del alcance del servicio).
- La tapa de gabinete se encontró con rastros de pintura blanca, se realizó limpieza.
- Se reguló freno de puerta, se aumentó velocidad para asegurar cierre automático.
Fig. 20 - Lectora de ingreso y salida Laboratorio VEID
MANTENIMIENTO PREVENTIVO SISTEMA DE CCTV, ACS Y PERIFONEO, NAMRU6 - IQUITOS 12
Cal. José Gabriel Chariarse Nro. 151 - int. 1A, Miraflores - Lima 41, PERÚ T. (51-1) 612-5500 www.viditek.com
Fig. 21 - Tablero interfaz puerta Laboratorio VEID, se aprecia detalle de tarjeta inferior con un relé externo conectado con cables rojos al pie de tablero.
Fig. 22 - Detalle chapa eléctrica en Laboratorio VEID
3.2.1.4. Puerta Insectario 1er Piso Posterior
Esta puerta cuenta con:
- Lectora de ingreso
- Lectora de salida
- Contacto magnético empotrado
No se aprecia tablero de interfaz cercano a la puerta.
Se realizó limpieza interna, externa de lectora de entrada y salida, chapa eléctrica y contacto magnético.
Se realizaron pruebas de operatividad con tarjeta con privilegios de acceso quedando todo operativo.
MANTENIMIENTO PREVENTIVO SISTEMA DE CCTV, ACS Y PERIFONEO, NAMRU6 - IQUITOS 13
Cal. José Gabriel Chariarse Nro. 151 - int. 1A, Miraflores - Lima 41, PERÚ T. (51-1) 612-5500 www.viditek.com
Observaciones:
- Ninguna.
Fig. 23 - Chapa eléctrica marca Schlage en puerta Insectario 1er Piso posterior
Fig. 24 - Lectora de salida puerta Insectario 1er Piso posterior
Fig. 25 - Contacto magnético empotrado en puerta Insectario 1er Piso posterior
MANTENIMIENTO PREVENTIVO SISTEMA DE CCTV, ACS Y PERIFONEO, NAMRU6 - IQUITOS 14
Cal. José Gabriel Chariarse Nro. 151 - int.