S02 Sol 0004 AttJ.3 of 7 VA 585-21-115 Final Bid Drawing Set 01AUG24 VOL.pdf
PDF 7 MB Posted
- Solicitation number
- 36C25225R0004
About this file
This is an architectural drawing set for Project 585-21-115 to replace the boiler plant at the Oscar G. Johnson VA Medical Center in Iron Mountain, MI. The drawings detail architectural plans for a partially sprinklered facility including floor plans, elevations, sections, and details for multiple levels (basement, ground floor, mezzanine, and roof). The building includes spaces such as a boiler room, control room, breakroom, locker room, electrical room, generator room, and propane room. The drawings contain extensive details about fire protection systems, door and window schedules, equipment layouts, signage plans, and finish schedules.
Key technical specifications shown include sprinkler system requirements (wet pipe system with quick response sprinklers rated for different temperature ranges based on room usage), fire barrier details, emergency systems, and equipment placement. The building is designed with various hazard classifications - light hazard areas (breakroom/restrooms), ordinary hazard group 2 (boiler room), and extra hazard group 2 (propane room). The drawings provide comprehensive construction details including wall sections, door/window details, roof details and equipment mounting specifications required for building the replacement boiler plant facility.
View the file
Other files
Show 40 more
Latest 50 of 57 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SHEET 71
SHEET 72
SHEET 73
SHEET 74
SHEET 75
SHEET 76
SHEET 77
SHEET 78
SHEET 79
SHEET 80
SHEET 81
SHEET 82
SHEET 83
SHEET 84
SHEET 85
SHEET 86
SHEET 87
SHEET 88
SHEET 89
SHEET 90
SHEET 91
SHEET 92
SHEET 93
SHEET 94
SHEET 95
SHEET 96
SHEET 97
SHEET 98
SHEET 99
SHEET 100
SHEET 101
SHEET 102
SHEET 103
SHEET 104
SHEET 105
SHEET 106
SHEET 107
SHEET 108
SHEET 109
AJW CJR
REV 0 - 100% BID SET 2024-02-23
SPRINKLER SYMBOLS
PENDANT SPRINKLER, ON DROP NIPPLE
ENDCAP
UPRIGHT SPRINKLER
WET PIPE SPRINKLER RISER
TOP CONNECTION, 45° OR 90°
BOTTOM CONNECTION, 45° OR 90°
CAPPED OUTLET
PENDANT SPRINKLER
UPRIGHT SPRINKLER, ELEVATION
PLUG WITH BLEEDER
GENERIC VALVE SYMBOL
UPRIGHT SPRINKLER WITH GUARD, ELEVATION
PIPE SECTION
■ ■ ■ NEW FIRE BARRIER, 1 HOUR
NEW FIRE BARRIER, 2 HOUR
3/4-HOUR FIRE-RATED DOOR
1 1/2-HOUR FIRE-RATED DOOR
S 3/4-HOUR FIRE-RATED, SMOKE-RESISTANT DOOR
■ ■ ■ EXISTING FIRE BARRIER, 1 HOUR
EXISTING FIRE BARRIER, 2 HOUR■ ■ ■ ■ ■ ■
NEW SMOKE BARRIERS
EXISTING FIRE-BARRIER, SMOKE BARRIER,1 HOUR■S ■S
EXISTING FIRE-BARRIER, SMOKE BARRIER, 2 HOUR■ ■S ■ ■S
S EXISTING SMOKE BARRIER LINE
NEW FIRE-BARRIER, SMOKE BARRIER,1 HOUR■S ■S
NEW FIRE-BARRIER, SMOKE BARRIER, 2 HOUR■ ■S ■ ■S
SMOKE AND FIRE BARRIER SYMBOLS
GENERAL PLUMBING SYMBOLS
GENERAL NOTES
1. NOTIFY CONTRACTING OFFICE REPRESENTATIVE (COR) 2 DAYS PRIOR TO PERFORMING WORK ON FIRE DETECTION OR FIRE
SUPPRESSION SYSTEMS.
2. COMMISSIONING SHALL BE COMPLETED PER SPECIFICATION 019100, AND 280800.
3. PERFORM WORK IN ACCORDANCE WITH APPLICABLE CODES AND STANDARDS. INSTALL ALL EQUIPMENT PER MANUFACTURERS
INSTALLATION INSTRUCTIONS.
4. SEE THE MOST RECENT EDITION OF THE VA FIRE PROTECTION DESIGN MANUAL FOR SPECIFIC VA REQUIREMENTS.
5. ALL EQUIPMENT AND MATERIALS PROCURED FOR THIS PROJECT SHALL BE NEW. EQUIPMENT AND MATERIALS DIRECTLY RELATED TO
THE FIRE DETECTION OR SUPPRESSION SYSTEM SHALL BE UNDERWRITERS LABORATORY (UL) LISTED OR FACTORY MUTUAL (FM)
APPROVED.
FIRE ALARM AND DETECTION SYSTEM
1. INSTALLATION OF THE FIRE ALARM SYSTEM COMPONENTS SHALL BE IN ACCORDANCE WITH NFPA 72, NATIONAL FIRE ALARM CODE.
2. INSTALLATION OF CONDUIT AND WIRING SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE (NEC).
3. WIRING INSTALLED IN METAL RACEWAYS WITH THE BUILDING THAT IS PROTECTED BY AUTOMATIC SPRINKLER SYSTEM SHALL BE
CONSIDERED TO MEET THE REQUIREMENTS FOR PATHWAY SURVIVABILITY LEVEL 2 IN ACCORDANCE WITH NFPA 72.
4. IDENTIFICATION OF CONDUIT, JUNCTION BOXES AND TERMINAL CABINETS SHALL BE IN ACCORDANCE WITH THE CONTRACT
SPECIFICATIONS AND THE VA DESIGN MANUALS. ENSURE ALL COMPONENTS ARE COLORED RED PER SPECIFICATION 283100. USE FACTORY COLORED CONDUIT AND BOXES WHERE AVAILABLE. FIELD PAINTED COMPONENTS ARE ACCEPTABLE WHEN FACTORY
COLORED CONDUIT AND BOXES ARE NOT AVAILABLE.
5. ALL NEW DEVICES SHALL BE COMPATIBLE WITH THE EXISTING SYSTEM. EXISTING SYSTEM IS A SIMPLEX 4100ES SYSTEM.
6. FIRE ALARM SUBCONTRACTOR SHALL MARKUP (REDLINE) EXISTING FIRE ALARM DRAWINGS TO SHOW CHANGES AND SUBMIT
CHANGES TO THE COR.
7. SMOKE DETECTORS SHALL NOT BE INSTALLED WITHIN 3'-0" OF AN AIR SUPPLY OR RETURN VENT.
8. TESTING, ACCEPTANCE, AND COMMISSIONING: (SEE SPECIFICATIONS FOR CRITERIA)
a. TESTING OF THE FIRE ALARM DEVICES SHALL BE IN ACCORDANCE WITH THE CONTRACT SPECIFICATIONS AND NFPA 72.
b. TESTING WILL ALSO INCLUDE FUNCTION TEST OF THE SPRINKLER FLOW AND TAMPER SWITCH.
c. PROVIDE TESTING REPORTS PER NFPA 72.
d. NOTIFY COR 2 DAYS PRIOR TO PRELIMINARY TESTING.
e. NOTIFY COR 3 DAYS PRIOR TO FINAL COMMISSIONING.
SPRINKLER SYSTEM INSTALLATION
1. ALL WORK TO COMPLY WITH THE VA FIRE PROTECTION DESIGN MANUAL, NFPA 101 LIFE SAFETY CODE, AND ALL OTHER APPLICABLE
CODES ADOPTED BY THE VA. ALL EQUIPMENT AND FIXTURES SHALL BE INSTALLED PER THE MANUFACTURER'S RECOMMENDATIONS.
ALL SPRINKLER PIPING SHALL CONFORM TO NFPA 13 STANDARD FOR THE INSTALLATION OF AUTOMATIC SPRINKLER SYSTEMS.
2. THE CONTRACTOR SHALL COORDINATE PIPE ROUTINGS WITH STRUCTURE, DUCTWORK, PIPING, LIGHTS, ETC. PIPING SHALL NOT BE
INSTALLED ABOVE ELECTRICAL PANELS.
3. PROVIDE FACTORY MUTUAL (FM) APPROVED, QUICK RESPONSE SPRINKLERS IN ALL AREAS.
4. THE CONTRACTOR SHALL COORDINATE SPRINKLER HEAD LOCATIONS WITH STRUCTURE, DUCTWORK, DIFFUSERS, LIGHTS, REFLECTED CEILING PLANS, ETC.
5. WATER SUPPLY FOR ALL CONTROL VALVES SHALL BE ELECTRICALLY SUPERVISED AND MECHANICALLY LOCKED FOR PROPER
POSITION. WATER FLOW AND SUPERVISORY CIRCUITS SHALL BE IN ACCORDANCE WITH NFPA 13 STANDARD FOR THE INSTALLATION
OF AUTOMATIC SPRINKLER SYSTEMS AND NFPA 72 NATIONAL FIRE ALARM CODE.
6. ALL PENETRATIONS THROUGH FIRE RATED CONSTRUCTION SHALL BE FIRESTOPPED. REFER TO SPECIFICATIONS.
7. ALL PIPING TO BE PAINTED RED PER SPECIFICATION.
HYDRANT FLOW TEST DATA:
1. FLOW TEST DATA
A. LOCATION: NORTH OF BOILER PLANT, BUILDING 2
B. BY: CHRIS RASMUSSEN
C. DATE: 08/22/2023
D. STATIC PRESSURE: 83 PSI (HYDRANT: SOUTH OF BUILDING 1 LOADING DOCK)
E. RESIDUAL PRESSURE: 53 PSI (HYDRANT: SOUTH OF BUILDING 1 LOADING DOCK)
F. FLOW: 1275 GPM (HYDRANT; NORTHWEST OF BUILDING 11)
2. CONTRACTOR SHALL OBTAIN CURRENT FLOW TEST DATA AS REQUIRED BY CODE.
NAC NOTIFICATION APPLIANCE CIRCUIT
BATTERIESBATT
FSC FAN SHUTDOWN CONTROL
AHU AIR HANDLING UNIT
EOL
XX
END OF LINE DEVICE
XX=TYPE: R=RESISTOR
FIRE ALARM EQUIPMENT
PANELS/CABINETS/MISC DEVICES
FACP
FACC
FAA
OPA
FIRE ALARM CONTROL PANEL
FIRE ALARM CENTRAL CONSOLE
FIRE ALARM MASTER CONTROL UNIT
FIRE ALARM ANNUNCIATOR
OPERATOR STATION
UPS UNINTERRUPTIBLE POWER SUPPLY
MFACU
PRN PRINTER
MIC MICROPHONE
FACU FIRE ALARM CONTROL UNIT
FATC FIRE ALARM TERMINAL CABINET
CARBON MONOXIDE DETECTOR
E=EXISTING
FIRE PROTECTION MISC SYMBOLS
COMBINATION SPEAKER/VISIBLE
C=CEILING MOUNT
CD = CANDELA RATING
W = SPEAKER WATTAGE
CD
W
DUCT SMOKE DETECTOR
P = PHOTOELECTRIC
WP = WEATHERPROOF
S P/WP
ALARM, SPEAKER ONLY
X LETTER INDICATES AS FOLLOWS:
C=CEILING MOUNTED
W=WATTAGE
XX LETTER INDICATES AS FOLLOWS:
WP = WEATHERPROOF
X
XX
S
ADDRESSABLE INPUT MODULE
2 = DUAL INPUTAIM
WF FLOW DETECTOR SWITCH
AOM ADDRESSABLE ALARM OUTPUT MODULE
FIRE EXTINGUISHER - CLEAN AGENT
FIRE DAMPER
S
SMOKE DAMPER
SPD
TSS
LOW TEMPERATURE SWITCH
(AMBIENT AIR TEMPERATURE)
SURGE PROTECTION DEVICE
GENERAL SYMBOLS
DEMOLISH/REMOVE DEVICE
GENERAL LINETYPES
DEMOLITION LINE
ROOM NAME AND NUMBERC2
CORRIDOR
ELECTRICAL ABBREVIATIONS
VOICE EVACUATION CONTROL UNIT
LCD LCD ANNUNCIATOR/DISPLAY
EVAC
WCU WIRELESS CONTROL UNIT
FIBER OPTIC/RUI LINEFO
DATA/COMMUNICATION LINECOMM
ECCU EMERGENCY COMMUNICATION CONTROL UNIT
BLDG BUILDING
CORR CORRIDOR
DEMO DEMOLITION
DN PIPE DOWN
DWG DRAWING
ELEC ELECTRIC
EMER EMERGENCY
ENCL ENCLOSURE
EQUIP EQUIPMENT
FO FIBER OPTIC
FP FIRE PROTECTION
HVLS HIGH VELOCITY LOW SPEED
J-BOX JUNCTION BOX
MACH MACHINE
MACH RM MACHINE ROOM
MAINT MAINTENANCE
MECH MECHANICAL
MECH RM MECHANICAL ROOM
N NORTH
NA NOT APPLICABLE
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
OCC OCCUPY
OFF OFFICE
OPNG OPENING
OSHA OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION
RM ROOM
TYP TYPICAL
TTB TELEPHONE TERMINAL BOARD
UP PIPE UP
VALVE SUPERVISORY SWITCH
H
FIRE SERVICE OR EMERGENCY PHONE STATION
H=HANDSET
ALARM, FIRE, MANUAL PULL STATION
E=EXISTING
F
TRN FIRE ALARM TRANSPONDER
VS
DETECTOR, SMOKE;
X LETTER INDICATES AS FOLLOWS:
H=HEAT SMOKE
I=IONIZATION SMOKE
P=PHOTOELECTRIC SMOKE
IH=IONIZATION AND HEAT SMOKE
IP=IONIZATION AND PHOTOELECTRIC SMOKE
PH=PHOTOELECTRIC AND HEAT SMOKE
IPH=IONIZATION, PHOTOELECTRIC, AND HEAT
XX LETTER INDICATES AS FOLLOWS:
SB=SOUNDER BASE
SL=STROBE LIGHT
WET CHEMICAL SYSTEMWC
H F
H R/F
DETECTOR, HEAT
R/F=COMBINATION RATE OF RISE/FIXED TEMPERATURE
DETECTOR, HEAT
F=FIXED TEMPERATURE
SPD SURGE PROTECTION DEVICE
T
CU
TELEPHONE
ELECTRICAL COPPER
3-WAY VALVE
OS&Y VALVE
REDUCED PRESSURE ZONE RPZ
(INDICATE IF IT IS A DETECTOR TYPE)
ANGLE VALVE
ALARM CHECK VALVE
ALARM, WET CHEMICAL MANUAL PULL STATION
E=EXISTING
WC
POINT OF CONNECTION BETWEEN NEW
AND EXISTING WORK
LIMIT OF DEMOLITION
SMOKE DETECTOR/ HEAT DETECTOR COMBINATIONH
X
S
S
XX
SINGLE FIRE DEPARTMENT CONNECTION
DH DOOR HOLDER
CD
CD
VISIBILITY ONLY (STROBE) - CEILING MOUNT
CD = CANDELA RATING
VISIBILITY ONLY (STROBE) - WALL MOUNT
CD = CANDELA RATING
PHASE CALLOUT#
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
FIRE PROTECTION NOTES AND
LEGENDS
FINAL BID SET
PARTIALLY SPRINKLERED
REPLACE BOILER PLANT
325 EAST "H" STREET
IRON MOUNTAIN, MI 49801
2024-02-23 F-001
585-21-115
FW FEED WATER
SPRINKLER SCHEDULE
LOCATION TYPE TEMPERATURE
RATING
BOILER ROOM 119-2 QUICK RESPONSE HIGH
PROPANE ROOM 131-2 QUICK RESPONSE INTERMEDIATE
GENERATOR ROOM 120B-2 QUICK RESPONSE INTERMEDIATE
BREAKROOM AND RESTROOMS QUICK RESPONSE ORDINARY
CONTROL ROOM 130-2,
SUPERVISOR 129-2 & CHEM FEED
128-2
QUICK RESPONSE ORDINARY
SYSTEM DESIGNATIONS & HAZARD CLASSIFICATIONS
ROOMS/AREAS SYSTEM TYPE CODE HAZARD
CATEGORY DESIGN AREA COVERAGE/SPRINK
LER
DESIGN
DENSITY
HOSE
STREAM
BREAKROOM AND RESTROOM AREAS WET PIPE NFPA 13 LIGHT HAZARD 1500 SQFT 225 SQFT 0.10 GPM/SQFT 100 GPM
BOILER ROOM WET PIPE NFPA 13 ORDINARY HAZARD GROUP
2 1500 SQFT 130 SQFT 0.20 GPM/SQFT 250 GPM
PROPANE ROOM WET-PIPE NFPA13 EXTRA HAZARD GROUP 2 2500 SQFT 100 SQFT 0.30 GPM/SQFT 500 GPM
CARBON MONOXIDE (CO) AND EXPLOSIVE GAS DETECTION UNITGAS
SIDEWALL SPRINKLER
PS PRESSURE SWITCH
REV 1 - FINAL BID SET 2024-04-05
SHEET 1104/5/2024
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
CO
AutoCAD SHX Text X
File details come from the government source that posted it. Updated .