S02 Sol 0004 AttJ.7 of 7 VA 585-21-115 Final Bid Drawing Set 01AUG24 VOL.pdf
PDF 8 MB Posted
- Solicitation number
- 36C25225R0004
About this file
This is an electrical drawing set containing 18 pages of detailed telecommunications, security, and power system diagrams and specifications for the VA Medical Center boiler plant replacement project in Iron Mountain, MI. The drawings include electrical power plans for roof and ground floor levels, power panel schedules, cable/conduit schedules, telecommunications floor plans for basement through mezzanine levels, network architecture diagrams, and security camera layouts and schedules.
Key technical details include power distribution requirements for boiler equipment, emergency power systems, telecommunications infrastructure with fiber optic connections between buildings, security access control systems for multiple doors, and surveillance camera placements. The drawings specify equipment like AXIS PTZ/IP dome cameras, telecommunications conversion boxes, card readers, and emergency phones. Construction notes indicate phased work coordination requirements between contractors and the COR to maintain continuous operations. The drawings were prepared by Encorus Group as the architect/engineer of record and are marked as 100% bid set dated February 2024.
View the file
Other files
Show 40 more
Latest 50 of 57 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
W P, G
FC
I
WP, GFCIWP, GFCI
W P, G
FC
I
1' 2'
A'
B'
G'
F'
D'
C'
2.8'
E'
1 2 3
A
B
D
F
H
02-PP5
02-PP5
02-PP5
02-PP5
3'
02-DP4
15,17,19
02-DP4
16,18,20
02-DP4
21,23,25
VIA VFD
ON EP141
VIA VFD
ON EP141
VIA VFD
ON EP141
2-R-EF-001 2-R-EF-002
2-R-EF-004
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Director
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10 on e e igh th inc h = on e f oo t thr ee in ch es on e f oo t 6"
6" on e a nd on e h alf in ch es on e f oo t on e i nc h = on e f oo t
6"
6" thr ee qu ar ter s i nc h = on e f oo t on e h alf in ch on e f oo t thr ee ei gh ths in ch on e f oo t on e q ua rte r in ch on e f oo t
REV 0 - 100% BID SET 2024-02-23
100% BID SET REPLACE BOILER PLANT
325 EAST "H" STREET
IRON MOUNTAIN, MI 49801
585-21-115
2024-02-23
EP161
ELECTRICAL POWER PLAN - ROOF
LEVEL 2
KRK LAJ
PARTIALLY SPRINKLERED
KEYPLAN
N AREA OF WORK
12 16
3.
WORK OUTSIDE THE DESIGNATED PHASE AREA MAY BE REQUIRED TO COMPLETE
PHASED WORK. CONTRACTOR IS TO COORDINATE ALL WORK WITH COR AND BETWEEN
ANY AND ALL SUBCONTRACTORS TO ENSURE CONTINUED OPERATIONS AND INTENT
SHOWN THROUGHOUT THIS DRAWING SET.
2. PHASING IS DESIGNATED THROUGHOUT THE DRAWING SET VIA
1. SEE E-001 FOR E-SERIES NOTES AND LEGENDS.
GENERAL NOTES
SCALE: 3/16" = 1'-0"1 ELECTRICAL POWER PLAN - ROOF
N
Revisions: Date:
SHEET 2462/22/2024
PRIMARY NUMBER 1
LIFT STATION
SECONDARY NUMBER 2 LIFT
STATION
POWER ON HIGH LEVEL POWER ON HIGH LEVEL
PUMP 1
RUNNING
PUMP 2
RUNNING
PUMP 1
RUNNING
PUMP 2
RUNNING
ALARM
ON - OFF
ALARM
TEST
NUMBER 3
LIFT STATION ALARM CONTROLS
POWER ON HIGH LEVEL
PUMP 1
RUNNING
PUMP 2
RUNNING
GROUND FLOOR
0' - 0"
A'
MEZZANINE
12' - 0"
2 2
CALL BOX
(4) GENERATOR MONITOR PANELS
TV DATA OUTLET
TV RECEPTACLE
CONVENIENCE
RECEPTACLE
7'
- 5
4'
- 0
3'
- 9
4'
- 8 3/
8"
4'
- 0
1/ 4"5'
- 3
/1 EP121
MED GAS MONITOR
CO AND
COMBUSTIBLE
GAS MONITOR
GROUND FLOOR
0' - 0"
A'
MEZZANINE
12' - 0"
CHEMCIAL FEED PUMP
GFCI RECEPTACLES
5'
- 1
0" 5'
- 0
4'
- 1
" 5'
- 2
4'
- 5
SOLENOID PUMP (TYP)
CHEMICAL DRUM (TYP)
/1 EP121
02-PP3
02-PP3
02-PP3
GROUND FLOOR
0' - 0"
1'
MEZZANINE
12' - 0"
5'
- 4
CHEMCIAL FEED PUMP
GFCI RECEPTACLE
CHEMICAL DRUM (TYP)
SOLENOID PUMP (TYP)
/1 EP121
GROUND FLOOR
0' - 0"
2'
MEZZANINE
12' - 0"
FA MANUAL
PULL STATION
E STOP
LIGHT SWITCH
CONVENIENCE
RECEPTACLE
FA CONTROL
PANEL
CONVENIENCE
RECEPTACLE
1'
- 6
4'
- 0
3'
- 1
0"
4'
- 5
/1 EP121
2.8' 3'
2-120A-208E-T-00102-PP102-DP1 2-120A-480E-ATS-002 2-120A-480N-SWBD-001
2"ø
2"ø 2 1/2"ø
2 1/2"ø
2 PARALLEL CONDUITS FROM:
2-120A-480-ATS-001
2 PARALLEL CONDUITS FROM :
2-120A-480-ATS-001
1 CONDUIT FROM:
2-120B-480E-SWBD-001
2 PARALLEL CONDUITS FROM:
BLDG. #2 BOILERHOUSE NORM
/1 EP122
GROUND FLOOR
0' - 0"
2-120A-480E-ATS-001
2"ø 2 1/2"ø
2 PARALLEL CONDUITS FROM:
2-120B-480E-SWBD-001 2 PARALLEL CONDUITS TO:
2-120A-480-ATS-002
2 PARALLEL CONDUITS TO:
02-DP1
/1 EP122
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Director
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10 on e e igh th inc h = on e f oo t thr ee in ch es on e f oo t 6"
6" on e a nd on e h alf in ch es on e f oo t on e i nc h = on e f oo t
6"
6" thr ee qu ar ter s i nc h = on e f oo t on e h alf in ch on e f oo t thr ee ei gh ths in ch on e f oo t on e q ua rte r in ch on e f oo t
REV 0 - 100% BID SET 2024-02-23
FINAL BID SET REPLACE BOILER PLANT
325 EAST "H" STREET
IRON MOUNTAIN, MI 49801
585-21-115
2024-02-23
EP201
ELECTRICAL POWER ELEVATIONS -
GROUND FLOOR LEVEL 2
KRK CJR
PARTIALLY SPRINKLERED
SCALE: 1/2" = 1'-0"1 CONTROL ROOM 130-2 EAST
SCALE: 1/2" = 1'-0"3 CHEMICAL FEED ROOM 128-2 WEST
SCALE: 1/2" = 1'-0"4 CHEMICAL FEED ROOM 128-2 NORTH
SCALE: 1/2" = 1'-0"2 CONTROL ROOM 130-2 NORTH
2. SEE MECHANICAL PLANS FOR ADDITIONAL INFORMATION ON CHEMICAL FEED PUMPS.
1. SEE E-001 FOR E-SERIES NOTES AND LEGENDS.
GENERAL NOTES
CHEMICAL FEED PUMP
GFCI RECEPTACLES
SCALE: 1/2" = 1'-0"5 ELECTRICAL ROOM N WALL ELEVATION
SCALE: 1/2" = 1'-0"6 2-120A-480-ATS-001 ELEVATION
Revisions: Date:
REV 1 - FINAL BID SET 2024-04-04
SHEET 2474/4/2024
2.8'
2-120B-480E-SWBD-001
2-120B-480-GEN-011
2-102B-UH-004
2"ø
1 CONDUIT TO:
2-120A-480-ATS-002
2 PARALLEL CONDUITS TO:
2-120A-480-ATS-001
/1 EP122
GROUND FLOOR
0' - 0"
F'
2"ø
2 1/2"ø
2 CONDUITS FROM:
2-120B-480-GEN-011
1 CONDUIT TO:
2-120A-480-ATS-002
2 PARALLEL CONDUITS TO:
2-120A-480-ATS-001
/1 EP122
SCALE: 1/2" = 1'-0"1 GENERATOR CONDUIT ROUTE
SCALE: 1/2" = 1'-0"2 2-120B-480E-SWBD-001 ELEVATION
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Director
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10 on e e igh th inc h = on e f oo t thr ee in ch es on e f oo t 6"
6" on e a nd on e h alf in ch es on e f oo t on e i nc h = on e f oo t
6"
6" thr ee qu ar ter s i nc h = on e f oo t on e h alf in ch on e f oo t thr ee ei gh ths in ch on e f oo t on e q ua rte r in ch on e f oo t
REV 0 - 100% BID SET 2024-02-23
100% BID SET REPLACE BOILER PLANT
325 EAST "H" STREET
IRON MOUNTAIN, MI 49801
585-21-115
2024-02-23
EP202
ELECTRICAL POWER ELEVATIONS -
GROUND FLOOR LEVEL 2
KRK LAJ
PARTIALLY SPRINKLERED
Revisions: Date:
2. SEE MECHANICAL PLANS FOR ADDITIONAL INFORMATION ON CHEMICAL FEED PUMPS.
1. SEE E-001 FOR E-SERIES NOTES AND LEGENDS.
GENERAL NOTES
SHEET 2482/22/2024
D'
C'
2.8' 1
D
2-119-PMP-001
VFD
2-119-PMP-002
VFD
2-119-PMP-003
VFD
2-119-PMP-004
VFD
2-119-PMP-005
VFD
2-119-PMP-001
2-119-PMP-002
2-119-PMP-003 2-119-PMP-004
2-119-PMP-005
02-DP2
13,15,17
02-DP2
8,10,12
02-DP2
2,4,6
02-DP2
1,3,5
02-DP2
7,9,11
02-PP2
RO
CONTROL
RECEPTACLE
2-119-RO-001
02-DP2
14,16,18
3'
02-PP2
02-PP2
2-119-CP-006
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Director
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10 on e e igh th inc h = on e f oo t thr ee in ch es on e f oo t 6"
6" on e a nd on e h alf in ch es on e f oo t on e i nc h = on e f oo t
6"
6" thr ee qu ar ter s i nc h = on e f oo t on e h alf in ch on e f oo t thr ee ei gh ths in ch on e f oo t on e q ua rte r in ch on e f oo t
REV 0 - 100% BID SET 2024-02-23
FINAL BID SET REPLACE BOILER PLANT
325 EAST "H" STREET
IRON MOUNTAIN, MI 49801
585-21-115
2024-02-23
EP401
ELECTRICAL POWER ENLARGED
PLAN - GROUND FLOOR LEVEL 2
KRK CJR
PARTIALLY SPRINKLERED
SCALE: 1/2" = 1'-0"1 ELECTRICAL POWER ENLARGED PLAN - GROUND FLOOR LEVEL
KEYPLAN
N AREA OF WORK
12 16
1. SEE E-001 FOR E-SERIES NOTES AND LEGENDS.
GENERAL NOTES
N
Revisions: Date:
SHEET 2494/4/2024
G
1200KW @ 0.8PF
13.8KV, 60HZ, 3Ø, 4W
1500kVA
70 AT
LS
200 AF
GEN. #3
G
1200KW @ 0.8PF
13.8KV, 60HZ, 3Ø, 4W
1500kVA
70 AT
LS
200 AF
GEN. #1
G
1200KW @ 0.8PF
13.8KV, 60HZ, 3Ø, 4W
1500kVA
70 AT
LS
200 AF
GEN. #2
A
50 AT
LSI
100 AF
B
120 AT
LSI
200 AF
C
100 AT
LSI
100 AF
D
MIN AT
LSI
200 AF
E
50 AT
LSI
100 AF
F
120 AT
LSI
200 AF
G
50 AT
LSI
100 AF
H
MIN AT
LSI
200 AF
G
1200KW @ 0.8PF
13.8KV, 60HZ, 3Ø, 4W
1500kVA
13.8kV
13.8kV GENERATOR DISTRIBUTION
SUBSTATION GENERATOR BUILDING
ADDITION TO BUILDING #2
FUTURE
GEN. #4
SPARETO BLDG 11 TO BLDG 11TO BLDG 2
EXISTING
EMERGENCY
SWITCHGEAR
TO BLDG 2
EXISTING
EMERGENCY
SWITCHGEAR
1 1
FOR FUTURE
EXPANSION
SPARE FOR FUTURE
EXPANSION
BLR HOUSE SUB
BLDG
ATS #3
208Y/120
E
L
N
BLDG 2 BOILERHOUSE NORM
BLDG
ATS #3
208Y/120
E
L
N BLDG
ATS #3
208Y/120
E
L
N
112.5kVA 480- 208Y/120V
400AF
350AT
250AF
250AT
2-120A-480N-SWBD-001
480/277V 400A 10 kA
E
L
N
600 AF
600 AT
FROM 500kVA 13.8kV-480Y/277V (W/E
ENERGIES DISTRIBUTION #7)
480 DISTRIBUTION
208 SWBD
480-EM
208 EM
BUILDING 2
45kVA 480- 208Y/120V
2-120B-480E-SWBD-001
02-DP1
480/277V 400A 10 kA
100A MCB
FROM BLR HOUSE SUB (B2)
(2) SETS OF
(4) 250 KCMIL
(1) #3 AWG GND
02-DP4
100A
02-DP2
100A
02-DP3
175A
02-DP1
MCB
250AF
250AT
(2) SETS OF
(4) 250 KCMIL
(1) #3 AWG GND
(2) SETS OF
(4) 250 KCMIL
(1) #3 AWG GND
(4) #1 AWG
(1) #6 AWG GND
02-DP4
(4) #1 AWG
(1) #6 AWG GND
(4) #4/0 AWG
(1) #6 AWG GND
100A MCB
02-DP2
175A MCB
02-DP3
150AF
100AT
E
L
N
FROM 2-120B-480E-SWBD-001
02-PP1
208/120V 225A 10 kA
50A MCB
100A 100A 100A
02-PP1
MCB
225AF
200AT
(4) #1AWG
(1) #6 AWG GND
(4) #1 AWG
(1) #6 AWG GND
02-PP2
(4) #1 AWG
(1) #6 AWG GND
(4) #1 AWG
(1) #6 AWG GND
50A MCB
02-PP3
70A MCB
02-PP5
(4) #1 AWG
(1) #6 AWG GND
75KVA
480/208/120V
(4) 350 KCMIL
(1) #3 AWG GND
100A
(4) #1 AWG
(1) #6 AWG GND
70A MCB
02-PP4
FROM BLR HOUSE SUB (B2) FROM BLR HOUSE SUB (B2)
2-120A-480-ATS-001
480V 400A
4 POLE WITH BYPASS-ISOLATION
2-120A-480-ATS-002
480V 400A
4 POLE WITH BYPASS-ISOLATION
BUILDING 2 EM SWBD MCB
400AF
350AT
250AF
250AT
150AF
100AT
2-120A-480-ATS-001 2-120A-480-ATS-002
2-120B-480E-SWBD-001
480/277V 400A 10 kA
G
BUILDING 2 GENERATOR
300kW 480Y/277V
KRK CJR
REV 0 - 100% BID SET 2024-02-23
SCALE: NTS
BUILDING 2 NORMAL POWER SYSTEM1 SCALE: NTS
BUILDING 2 STAND-BY POWER SYSTEM3
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ELECTRICAL POWER ONE-LINE
DIAGRAM
100% BID SET
PARTIALLY SPRINKLERED
REPLACE BOILER PLANT
325 EAST "H" STREET
IRON MOUNTAIN, MI 49801
2024-02-23
EP601
585-21-115
SCALE: NTS
MEDIUM VOLTAGE EMERGENCY POWER SYSTEM2
GENERAL NOTES
1. SEE E-001 FOR E-SERIES NOTES AND LEGENDS.
KEYED NOTES
1 SEE ED171 AND ES171 FOR EXTENT OF EMERGENCY FEEDER DEMOLITION AND NEW
WORK
SHEET 2502/22/2024
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Director
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10 on e e igh th inc h = on e f oo t thr ee in ch es on e f oo t 6"
6" on e a nd on e h alf in ch es on e f oo t on e i nc h = on e f oo t
6"
6" thr ee qu ar ter s i nc h = on e f oo t on e h alf in ch on e f oo t thr ee ei gh ths in ch on e f oo t on e q ua rte r in ch on e f oo t
REV 0 - 100% BID SET 2024-02-23
FINAL BID SET REPLACE BOILER PLANT
325 EAST "H" STREET
IRON MOUNTAIN, MI 49801
585-21-115
2024-02-23
EP602
ELECTRICAL POWER PANEL
SCHEDULES 2
KRK CCW
PARTIALLY SPRINKLERED
NOTES:
TOTAL CONN. CURRENT: 256 A
TOTAL CONN. LOAD: 212969 VA
PANEL TOTALS
LEGEND:
TOTAL AMPS: 256 A 254 A 293 A
TOTAL LOAD: 70851 VA 70262 VA 80969 VA
41 42 39 40 37 38 35 36 33 34 31 32 29 30 27 28 25 26
23 3049 VA -- -- -- 24
21 3049 VA -- -- -- 22
19 -- -- -- 44219 VA 3049 VA 3 20 A LIFT STATION (2-119-CP-004) 20
17 -- -- -- 43264 VA 16653 VA -- -- -- 18
15 02-DP3 175 A 3 44449 VA 16689 VA -- -- -- 16
13 -- -- -- 7019 VA 16759 VA 3 100 A 02-DP2 14
11 -- -- -- 6966 VA 0 VA 1 20 A SPARE 12
9 02-DP5 100 A 3 7049 VA 0 VA 1 20 A SPARE 10
7 RM 120B LTS 20 A 1 102 VA 163 VA 1 20 A RM 120A LTS 8
5 ELECTRIC WATER HEATER 60 A 1 12100 VA 0 VA 1 20 A SPARE 6
3 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 4
1 EXTERIOR LIGHTING 20 A 1 526 VA 0 VA 1 20 A SPARE 2
CKT CIRCUIT DESCRIPTION TRIP POLE
S A B C POLE
S TRIP CIRCUIT DESCRIPTION CKT
NOTES:
ENCLOSURE: TYPE 1 MCB RATING: 225 A
MOUNTING: SURFACE WIRES: 4 MAINS RATING: 400 A
SUPPLY FROM: PHASES: 3 MAINS TYPE:
LOCATION: ELECTRICAL ROOM 120A-2 VOLTS: 480/277 Wye A.I.C. RATING:
BRANCH PANEL: DP1
NOTES:
TOTAL CONN. CURRENT: 60 A
TOTAL CONN. LOAD: 50101 VA
PANEL TOTALS
LEGEND:
TOTAL AMPS: 61 A 60 A 60 A
TOTAL LOAD: 16759 VA 16689 VA 16653 VA
41 42 39 40 37 38 35 36 33 34
31 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 32
29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30
27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28
25 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 26
23 RM 125,127 LTS 20 A 1 80 VA 41 VA 1 20 A LTS OUTSIDE RM 121,122,123 24
21 RM 126 LTS 20 A 1 85 VA 71 VA 1 20 A RM 121,122,123 LTS 22
19 LTS UNDER BOILER CATWALK 20 A 1 102 VA 126 VA 1 20 A RM 124 LTS 20
17 -- -- -- 2106 VA 1330 VA -- -- -- 18
15 -- -- -- 2106 VA 1330 VA -- -- -- 16
13 2-119-PMP-001 20 A 3 2106 VA 1330 VA 3 20 A 2-119-RO-001 14
11 -- -- -- 3880 VA 2106 VA -- -- -- 12
9 -- -- -- 3880 VA 2106 VA -- -- -- 10
7 2-119-PMP-005 20 A 3 3880 VA 2106 VA 3 20 A 2-119-PMP-002 8
5 -- -- -- 3880 VA 3880 VA -- -- -- 6
3 -- -- -- 3880 VA 3880 VA -- -- -- 4
1 2-119-PMP-004 20 A 3 3880 VA 3880 VA 3 20 A 2-119-PMP-003 2
CKT CIRCUIT DESCRIPTION TRIP POLE
S A B C POLE
S TRIP CIRCUIT DESCRIPTION CKT
NOTES:
ENCLOSURE: TYPE 1 MCB RATING: 100 A
MOUNTING: SURFACE WIRES: 4 MAINS RATING: 150 A
SUPPLY FROM: DP1 PHASES: 3 MAINS TYPE:
LOCATION: ELECTRICAL ROOM 120A-2 VOLTS: 480/277 Wye A.I.C. RATING:
BRANCH PANEL: 02-DP2
NOTES:
TOTAL CONN. CURRENT: 159 A
TOTAL CONN. LOAD: 131932 VA
PANEL TOTALS
LEGEND:
TOTAL AMPS: 161 A 156 A 160 A
TOTAL LOAD: 44449 VA 43264 VA 44219 VA
41 42 39 40 37 38 35 36 33 34
31 -- -- -- 10254 VA 0 VA 1 20 A SPARE 32
29 -- -- -- 10254 VA 0 VA 1 20 A SPARE 30
27 EM BLR PWR CONN 75 A 3 10254 VA 0 VA 1 20 A SPARE 28
25 BASEMENT EM WALL LIGHTS 20 A 1 100 VA 1100 VA 1 20 A MEZZ EM WALL LTS 26
23 BASEMENT 003-2 LIGHT 20 A 1 20 VA 1100 VA 1 20 A GR FL EM WALL LTS 24
21 -- -- -- 313 VA 33 VA 1 20 A RM 131 LIGHT 22
19 -- -- -- 313 VA 10254 VA -- -- -- 20
17 PROPANE RM EXHAUST FAN 20 A 3 313 VA 10254 VA -- -- -- 18
15 -- -- -- 10254 VA 10254 VA 3 75 A BOILER 3 16
13 -- -- -- 10254 VA 10254 VA -- -- -- 14
11 BOILER 2 75 A 3 10254 VA 10254 VA -- -- -- 12
9 -- -- -- 942 VA 10254 VA 3 75 A BOILER 1 10
7 -- -- -- 942 VA 942 VA -- -- -- 8
5 2-200-SF-001 20 A 3 942 VA 942 VA -- -- -- 6
3 RM 128,129 LTS 20 A 1 80 VA 942 VA 3 20 A 2-200-SF-002 4
1 EXIT SIGNS 20 A 1 35 VA 120 VA 1 20 A RM 130 LTS 2
CKT CIRCUIT DESCRIPTION TRIP POLE
S A B C POLE
S TRIP CIRCUIT DESCRIPTION CKT
NOTES:
ENCLOSURE: TYPE 1 MCB RATING: 175 A
MOUNTING: SURFACE WIRES: 4 MAINS RATING: 250 A
SUPPLY FROM: DP1 PHASES: 3 MAINS TYPE:
LOCATION: BOILER ROOM 119-2 VOLTS: 480/277 Wye A.I.C. RATING:
BRANCH PANEL: 02-DP3
NOTES:
TOTAL CONN. CURRENT: 25 A
TOTAL CONN. LOAD: 21034 VA
PANEL TOTALS
LEGEND:
TOTAL AMPS: 25 A 25 A 25 A
TOTAL LOAD: 7049 VA 6966 VA 7019 VA
41 42 39 40 37 38 35 36 33 34 31 32
29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30
27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28
25 -- -- -- 2106 VA 0 VA 1 20 A SPARE 26
23 -- -- -- 2106 VA 0 VA 1 20 A SPARE 24
21 2-R-EF-004 20 A 3 2106 VA 0 VA 1 20 A SPARE 22
19 -- -- -- 942 VA 942 VA -- -- -- 20
17 -- -- -- 942 VA 942 VA -- -- -- 18
15 2-R-EF-001 20 A 3 942 VA 942 VA 3 20 A 2-R-EF-002 16
13 -- -- -- 1178 VA 1178 VA -- -- -- 14
11 -- -- -- 1178 VA 1178 VA -- -- -- 12
9 2-200-MAU-001 20 A 3 1178 VA 1178 VA 3 20 A 2-200-MAU-002 10
7 BOILER ROOM HIGH BAY LED 20 A 1 693 VA 0 VA -- -- -- 8
5 BOILER ROOM HIGH BAY LED 20 A 1 819 VA 0 VA -- -- -- 6
3 BOILER ROOM HIGH BAY LED 20 A 1 756 VA 0 VA 3 20 A RM 201 COMM RACK 4
1 DA TANK AREA LTS 20 A 1 81 VA 80 VA 1 20 A RM 201 LTS 2
CKT CIRCUIT DESCRIPTION TRIP POLE
S A B C POLE
S TRIP CIRCUIT DESCRIPTION CKT
NOTES:
ENCLOSURE: TYPE 1 MCB RATING: 100 A
MOUNTING: SURFACE WIRES: 4 MAINS RATING: 100 A
SUPPLY FROM: DP1 PHASES: 3 MAINS TYPE:
LOCATION: EQUIPMENT ACCESS 200-2 VOLTS: 480/277 Wye A.I.C. RATING:
BRANCH PANEL: 02-DP4
Revisions: Date:
SHEET 2514/4/2024
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Director
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10 on e e igh th inc h = on e f oo t thr ee in ch es on e f oo t 6"
6" on e a nd on e h alf in ch es on e f oo t on e i nc h = on e f oo t
6"
6" thr ee qu ar ter s i nc h = on e f oo t on e h alf in ch on e f oo t thr ee ei gh ths in ch on e f oo t on e q ua rte r in ch on e f oo t
REV 0 - 100% BID SET 2024-02-23
FINAL BID SET REPLACE BOILER PLANT
325 EAST "H" STREET
IRON MOUNTAIN, MI 49801
585-21-115
2024-02-23
EP603
ELECTRICAL POWER PANEL
SCHEDULES 2
KRK KRK
PARTIALLY SPRINKLERED
NOTES:
TOTAL CONN. CURRENT: 198 A
TOTAL CONN. LOAD: 71458 VA
PANEL TOTALS
LEGEND:
TOTAL AMPS: 187 A 212 A 207 A
TOTAL LOAD: 22393 VA 25125 VA 24485 VA
41 42 39 40 37 38 35 36 33 34 31 32 29 30
27 -- -- -- 6808 VA 28
25 -- -- -- 7027 VA 5992 VA -- -- -- 26
23 02-PP4 100 A 3 6628 VA 6086 VA -- -- -- 24
21 -- -- -- 4104 VA 6417 VA 3 100 A 02-PP5 22
19 -- -- -- 4814 VA 20
17 02-PP3 100 A 3 4659 VA 18
15 3140 VA -- -- -- 16
13 2760 VA -- -- -- 14
11 -- -- -- 3848 VA 2588 VA 3 100 A 02-PP2 12
9 2-EXT-CU-003 50 A 2 3848 VA 10
7 2-200-UH-001, 002, 003 20 A 1 900 VA 8
5 2-200-CF-001 10 A 1 768 VA 270 VA -- -- -- 6
3 RM 120A RCPT 20 A 1 900 VA 270 VA 2 20 A FUEL TANK LIGHTS 4
1 RM 120B RCPT 20 A 1 720 VA 768 VA 1 10 A 2-200-CF-002 2
CKT CIRCUIT DESCRIPTION TRIP POLE
S A B C POLE
S TRIP CIRCUIT DESCRIPTION CKT
NOTES:
ENCLOSURE: TYPE 1 MCB RATING: 200 A
MOUNTING: RECESSED WIRES: 4 MAINS RATING: 400 A
SUPPLY FROM: PHASES: 3 MAINS TYPE:
LOCATION: ELECTRICAL ROOM 120A-2 VOLTS: 120/208 Wye A.I.C. RATING:
BRANCH PANEL: 02-PP1
NOTES:
TOTAL CONN. CURRENT: 23 A
TOTAL CONN. LOAD: 8128 VA
PANEL TOTALS
LEGEND:
TOTAL AMPS: 22 A 23 A 26 A
TOTAL LOAD: 2588 VA 2760 VA 3140 VA
41 42 39 40 37 38 35 36 33 34 31 32
29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30
27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28
25 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 26
23 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 24
21 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 22
19 CONTINUOUS GAS ANALYZER 3 30 A 1 1500 VA 0 VA 1 20 A SPARE 20
17 CONTINUOUS GAS ANALYZER 2 30 A 1 1500 VA 0 VA -- -- -- 18
15 CONTINUOUS GAS ANALYZER 1 30 A 1 1500 VA 0 VA -- -- -- 16
13 2-119-CP-005 20 A 1 180 VA 0 VA 3 30 A SPARE 14
11 -- -- -- 360 VA 200 VA 1 20 A 2-119-CP-009 12
9 -- -- -- 360 VA 180 VA 1 20 A 2-119-CP-006 10
7 RM 119 3P RCPT 30 A 3 360 VA 360 VA -- -- -- 8
5 RM 119 CNTRLN RCPT 20 A 1 720 VA 360 VA -- -- -- 6
3 RM 119 RCPT EAST 20 A 1 360 VA 360 VA 3 30 A RM 119 3P RCPT 4
1 2-100-TK-004 (WATER SOFTENER) 20 A 1 10 VA 180 VA 1 20 A RO CONTROL RECEPTACLE 2
CKT CIRCUIT DESCRIPTION TRIP POLE
S A B C POLE
S TRIP CIRCUIT DESCRIPTION CKT
NOTES:
ENCLOSURE: Type 1 MCB RATING: 100 A
MOUNTING: SURFACE WIRES: 4 MAINS RATING: 100 A
SUPPLY FROM: 02-PP1 PHASES: 3 MAINS TYPE:
LOCATION: ELECTRICAL ROOM 120A-2 VOLTS: 120/208 Wye A.I.C. RATING:
BRANCH PANEL: 02-PP2
NOTES:
TOTAL CONN. CURRENT: 38 A
TOTAL CONN. LOAD: 13536 VA
PANEL TOTALS
LEGEND:
TOTAL AMPS: 40 A 41 A 34 A
TOTAL LOAD: 4659 VA 4814 VA 4104 VA
41 42 39 40 37 38 35 36 33 34 31 32
29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30
27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28
25 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 26
23 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 24
21 MED GAS MONITOR 20 A 1 210 VA 115 VA 1 20 A CO MONITOR 22
19 RM 129 RECPT 20 A 1 720 VA 180 VA 1 20 A RM 003 RCPT 20
17 RM 130 RECPT SOUTH 20 A 1 360 VA 360 VA 1 20 A RM 130 RECPT SOUTH 18
15 -- -- -- 1789 VA 360 VA 1 20 A RM 130 RECPT WEST 16
13 2-EXT-CU-001 25 A 2 1789 VA 360 VA 1 20 A RM 130 RECPT WEST 14
11 RM 129 RECPT 20 A 1 1080 VA 360 VA 1 20 A RM 130 RECPT SOUTH 12
9 RM 003 SUMP PMP 20 A 1 180 VA 1080 VA 1 20 A FA CONTROL PANEL 10
7 RM 130 RECPT EAST 20 A 1 540 VA 1260 VA 1 20 A SEWAGE PUMP PMP-1 8
5 RM 128 RCPT CHEM FD PMP 20 A 1 1080 VA 864 VA 1 20 A RM 128 RCPT CHEM FD PMP 6
3 RM 130 RECPT SOUTH 20 A 1 720 VA 360 VA 1 20 A RM 130 RECPT WEST 4
1 GD-1 20 A 1 0 VA 0 VA 1 20 A GD-4 2
CKT CIRCUIT DESCRIPTION TRIP POLE
S A B C POLE
S TRIP CIRCUIT DESCRIPTION CKT
NOTES:
ENCLOSURE: Type 1 MCB RATING: 100 A
MOUNTING: SURFACE WIRES: 4 MAINS RATING: 100 A
SUPPLY FROM: 02-PP1 PHASES: 3 MAINS TYPE:
LOCATION: BOILER ROOM 119-2 VOLTS: 120/208 Wye A.I.C. RATING:
BRANCH PANEL: 02-PP3
NOTES:
TOTAL CONN. CURRENT: 57 A
TOTAL CONN. LOAD: 20463 VA
PANEL TOTALS
LEGEND:
TOTAL AMPS: 55 A 59 A 57 A
TOTAL LOAD: 6628 VA 7027 VA 6808 VA
41 42 39 40 37 38 35 36 33 34 31 32
29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30
27 SPARE 20 A 1 0 VA 0 VA -- -- -- 28
25 SPARE 20 A 1 0 VA 0 VA -- -- -- 26
23 SPARE 20 A 1 0 VA 0 VA 3 20 A SPARE 24
21 -- -- -- 2667 VA 1273 VA -- -- -- 22
19 -- -- -- 2667 VA 1273 VA -- -- -- 20
17 RM 124 ELEC RANGE 50 A 3 2667 VA 1273 VA 3 20 A DUPLEX FUEL OIL PUMP 18
15 RM 119,121,122,123,126 RECPT 20 A 1 1260 VA 0 VA 1 20 A SPARE 16
13 RM 119 RCPT 20 A 1 540 VA 0 VA 1 20 A SPARE 14
11 RM 124 RCPT 20 A 1 540 VA 360 VA 1 20 A RM 124 CNTRTOP RECPT 12
9 RM 124 RCPT 20 A 1 540 VA 1080 VA 1 20 A RM 125,127 RCPT 10
7 RM 124 CNTRTOP RECPT 20 A 1 360 VA 1789 VA -- -- -- 8
5 RM 124 FRIDGE 20 A 1 180 VA 1789 VA 2 25 A 2-EXT-CU-002 6
3 RM 124 COUNTER LTS 20 A 1 12 VA 195 VA 1 20 A RM 124 WTR FNTN 4
1 GD-2 20 A 1 0 VA 0 VA 1 20 A GD-3 2
CKT CIRCUIT DESCRIPTION TRIP POLE
S A B C POLE
S TRIP CIRCUIT DESCRIPTION CKT
NOTES:
ENCLOSURE: TYPE 1 MCB RATING: 100 A
MOUNTING: RECESSED WIRES: 4 MAINS RATING: 100 A
SUPPLY FROM: 02-PP1 PHASES: 3 MAINS TYPE:
LOCATION: BOILER ROOM 119-2 VOLTS: 120/208 Wye A.I.C. RATING:
BRANCH PANEL: 02-PP4
NOTES:
TOTAL CONN. CURRENT: 51 A
TOTAL CONN. LOAD: 18304 VA
PANEL TOTALS
LEGEND:
TOTAL AMPS: 54 A 51 A 50 A
TOTAL LOAD: 6417 VA 6086 VA 5992 VA
41 42 39 40 37 38 35 36 33 34 31 32
29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30
27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28
25 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 26
23 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 24
21 -- -- -- 0 VA 0 VA 1 20 A SPARE 22
19 SPARE 20 A 2 0 VA 0 VA -- -- -- 20
17 -- -- -- 0 VA 0 VA -- -- -- 18
15 SPARE 30 A 2 0 VA 0 VA 3 20 A SPARE 16
13 -- -- -- 875 VA 180 VA 1 20 A 2-200-CP-006A 14
11 2-200-PMP-001 20 A 2 875 VA 3633 VA -- -- -- 12
9 -- -- -- 1248 VA 3633 VA -- -- -- 10
7 ELECTRIC CHAIN HOIST 30 A 2 1248 VA 3633 VA 3 20 A 2-200-CA-001 8
5 ROOF RCPT 20 A 1 720 VA 875 VA -- -- -- 6
3 RM 201 RCPT 20 A 1 540 VA 875 VA 2 20 A 2-200-PMP-002 4
1 RM 201 RCPT 20 A 1 540 VA 180 VA 1 20 A RM 200 RCPT 2
CKT CIRCUIT DESCRIPTION TRIP POLE
S A B C POLE
S TRIP CIRCUIT DESCRIPTION CKT
NOTES:
ENCLOSURE: TYPE 1 MCB RATING: 100 A
MOUNTING: SURFACE WIRES: 4 MAINS RATING: 100 A
SUPPLY FROM: 02-PP1 PHASES: 3 MAINS TYPE:
LOCATION: EQUIPMENT ACCESS 200-2 VOLTS: 120/208 Wye A.I.C. RATING:
BRANCH PANEL: 02-PP5
Revisions: Date:
SHEET 2524/4/2024
02-DP1 CABLE AND CONDUIT SCHEDULE
LOAD NAME PANEL CIRCUIT NUMBER WIRE SIZE # OF HOT # OF NEUTRAL # OF GROUND CONDUIT # OF RUNS
EXTERIOR LIGHTING 02-DP1 1 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
RM 100 101 EXIT SIGNS 02-DP1 2 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
ELECTRIC WATER HEATER 02-DP1 5 1-#6 1-#6 1-#10 1 1 1 3/4" RMC 1
GENERATOR RM LIGHTS 02-DP1 7 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
ELEC RM LIGHTS 02-DP1 8 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
02-DP4 02-DP1 9 11 13 3-#1 1-#1 1-#6 3 1 1 1-1/2" RMC 1
02-DP2 02-DP1 14 16 18 3-#1 1-#1 1-#6 3 1 1 1-1/2" RMC 1
02-DP3 02-DP1 15 17 19 3-#4/0 1-#4/0 1-#4 3 1 1 2-1/2" RMC 1
LIFT STATION 02-DP1 20 22 24 3-#12 1-#12 3 0 1 3/4" RMC 1
02-DP2 CABLE AND CONDUIT SCHEDULE
LOAD NAME PANEL CIRCUIT NUMBER WIRE SIZE # OF HOT # OF NEUTRAL # OF GROUND CONDUIT # OF RUNS
PMP-004 02-DP2 1 3 5 3-#12 1-#12 3 0 1 3/4" RMC 1
PMP-003 02-DP2 2 4 6 3-#12 1-#12 3 0 1 3/4" RMC 1
PMP-005 02-DP2 7 9 11 3-#12 1-#12 3 0 1 3/4" RMC 1
PMP-002 02-DP2 8 10 12 3-#12 1-#12 3 0 1 3/4" RMC 1
PMP-001 02-DP2 13 15 17 3-#12 1-#12 3 0 1 3/4" RMC 1
RO SYSTEM POWER 02-DP2 14 16 18 3-#12 1-#12 3 0 1 3/4" RMC 1
LTS UNDER BOILER PLATFORMS 02-DP2 19 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
BRK RM 102 LTS 02-DP2 20 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
RM 103 104 LTS 02-DP2 21 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
RM 106 107 108 LTS 02-DP2 22 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
RM 103 105 LTS 02-DP2 23 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
LIGHTING OUTSIDE TOILETS 02-DP2 24 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
02-DP3 CABLE AND CONDUIT SCHEDULE
LOAD NAME PANEL CIRCUIT NUMBER WIRE SIZE # OF HOT # OF NEUTRAL # OF GROUND CONDUIT # OF RUNS
CONTROL RM 111 EXIT SIGNS 02-DP3 1 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
RM 109 110 111 LTS 02-DP3 2 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
RM 109 110 111 LTS 02-DP3 3 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
SUPPLY FAN 1 02-DP3 4 6 8 3-#12 1-#12 3 0 1 3/4" RMC 1
SUPPLY FAN 2 02-DP3 5 7 9 3-#12 1-#12 3 0 1 3/4" RMC 1
BOILER 1 02-DP3 10 12 14 3-#4 1-#4 1-#8 3 1 1 1-1/2" RMC 1
BOILER 2 02-DP3 11 13 15 3-#4 1-#4 1-#8 3 1 1 1-1/2" RMC 1
BOILER 3 02-DP3 16 18 20 3-#4 1-#4 1-#8 3 1 1 1-1/2" RMC 1
PROPANE RM EXHAUST FAN 02-DP3 17 19 21 3-#12 1-#12 3 0 1 3/4" RMC 1
PROPANE ROOM LIGHT 02-DP3 22 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
BASEMENT 003-2 LIGHT 02-DP3 23 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
GR FL EM WALL LTS 02-DP3 24 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
BASEMENT EM WALL LIGHTS 02-DP3 25 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
MEZZ EM WALL LTS 02-DP3 26 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
BOILER EMERGENCY POWER POINT 02-DP3 27, 29, 31 3-#4 1-#4 1-#8 3 1 1 1-1/2" RMC 1
02-DP4 CABLE AND CONDUIT SCHEDULE
LOAD NAME PANEL CIRCUIT NUMBER WIRE SIZE # OF HOT # OF NEUTRAL # OF GROUND CONDUIT # OF RUNS
DA TANK LIGHTING 02-DP4 1 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
CONTROL IT RM LIGHTING 02-DP4 2 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
BOILER ROOM HIGH BAY LED 02-DP4 3 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
COMMS RACK 02-DP4 4 6 8 3-#12 1-#12 3 0 1 3/4" RMC 1
BOILER ROOM HIGH BAY LED 02-DP4 5 1-#10 1-#10 1-#10 1 1 1 3/4" RMC 1
BOILER ROOM HIGH BAY LED 02-DP4 7 1-#10 1-#10 1-#10 1 1 1 3/4" RMC 1
MAU-001 02-DP4 9 11 13 3-#12 1-#12 3 0 1 3/4" RMC 1
MAU-002 02-DP4 10 12 14 3-#12 1-#12 3 0 1 3/4" RMC 1
2-R-EF-001 02-DP4 15 17 19 3-#12 1-#12 3 0 1 3/4" RMC 1
2-R-EF-002 02-DP4 16 18 20 3-#12 1-#12 3 0 1 3/4" RMC 1
2-R-EF-004 02-DP4 21 23 25 3-#12 1-#12 3 0 1 3/4" RMC 1
02-PP1 CABLE AND CONDUIT SCHEDULE
LOAD NAME PANEL CIRCUIT NUMBER WIRE SIZE # OF HOT # OF NEUTRAL # OF GROUND CONDUIT # OF RUNS
GEN RM RECEPTACLES 02-PP1 1 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
2-200-CF-002 02-PP1 2 1-#12 1-#12 1-#14 1 1 1 3/4" RMC 1
RECEPTACLE 02-PP1 3 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
FUEL TANK LIGHTS 02-PP1 4 6 2-#12 1-#12 2 0 1 3/4" RMC 1
2-200-CF-001 02-PP1 5 1-#12 1-#12 1-#14 1 1 1 3/4" RMC 1
2-200-UH-001 002 003 02-PP1 7 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
2-EXT-CU-003 02-PP1 9 11 2-#6 1-#6 2 0 1 3/4" RMC 1
02-PP2 02-PP1 12 14 16 3-#1 1-#1 1-#4 3 1 1 1-1/2" RMC 1
02-PP3 02-PP1 17 19 21 3-#1 1-#1 1-#4 3 1 1 1-1/2" RMC 1
02-PP5 02-PP1 22 24 26 3-#1 1-#1 1-#4 3 1 1 1-1/2" RMC 1
02-PP4 02-PP1 23 25 27 3-#1 1-#1 1-#4 3 1 1 1-1/2" RMC 1
02-PP2 CABLE AND CONDUIT SCHEDULE
LOAD NAME PANEL CIRCUIT NUMBER WIRE SIZE # OF HOT # OF NEUTRAL # OF GROUND CONDUIT # OF RUNS
2-100-TK-004 02-PP2 1 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
RO CONTROL RECEPTACLE 02-PP2 2 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
BOILER RM 100 REC EAST WALL 02-PP2 3 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
BOILER RM 100 3P REC 02-PP2 4 6 8 3-#8 1-#8 3 0 1 3/4" RMC 1
BOILER RM 100 REC CENTERLINE 02-PP2 5 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
BOILER RM 100 3P REC 02-PP2 7 9 11 3-#8 1-#8 3 0 1 3/4" RMC 1
02-PP3 CABLE AND CONDUIT SCHEDULE
LOAD NAME PANEL CIRCUIT NUMBER WIRE SIZE # OF HOT # OF NEUTRAL # OF GROUND CONDUIT # OF RUNS
GARAGE DOOR 1 02-PP3 1 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
GARAGE DOOR 4 02-PP3 2 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
RECEPTACLES WEST WALL 02-PP3 3 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
CONTROL RM 111 REC 02-PP3 4 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
CHEMICAL FEED PUMPS 02-PP3 5 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
CHEMICAL FEED PUMPS 02-PP3 6 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
RECEPTACLE 02-PP3 7 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
SEWAGE PUMP PMP-1 02-PP3 8 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
RECEPTACLE 02-PP3 9 1-#10 1-#10 1-#10 1 1 1 3/4" RMC 1
FA CONTROL PANEL 02-PP3 10 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
SUPERVISOR RM 110 REC 02-PP3 11 1-#10 1-#10 1-#10 1 1 1 3/4" RMC 1
CONTROL RM 111 REC 02-PP3 12 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
2-EXT-OU-001 02-PP3 13 15 2-#10 1-#6 2 0 1 3/4" RMC 1
02-PP4 CABLE AND CONDUIT SCHEDULE
LOAD NAME PANEL CIRCUIT NUMBER WIRE SIZE # OF HOT # OF NEUTRAL # OF GROUND CONDUIT # OF RUNS
GARAGE DOOR 2 02-PP4 1 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
GARAGE DOOR 3 02-PP4 2 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
BRK RM 102 COUNTER LTS 02-PP4 3 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
WATER FOUNTAIN/BOTTLE FILL 02-PP4 4 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
2-EXT-OU-002 02-PP4 6 8 2-#12 1-#10 2 0 1 3/4" RMC 1
BRK RM 102 COUNTERTOP REC 02-PP4 7 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
BRK RM 102 REFRIGERATOR 02-PP4 9 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
RM 103 105 RECEPTACLE 02-PP4 10 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
BREAKROOM RECEPTACLES 02-PP4 11 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
BOILER RM 100 REC 02-PP4 13 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
RM 104 106 107 108 REC 02-PP4 15 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
BREAKROOM RECEPTACLES 02-PP4 16 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
ELECTRIC RANGE 02-PP4 17 19 21 3-#8 1-#10 3 0 1 3/4" RMC 1
DUPLEX FUEL OIL PUMP 02-PP4 18 20 22 3-#12 1-#12 3 0 1 3/4" RMC 1
02-PP5 CABLE AND CONDUIT SCHEDULE
LOAD NAME PANEL CIRCUIT NUMBER WIRE SIZE # OF HOT # OF NEUTRAL # OF GROUND CONDUIT # OF RUNS
RM 201 REC 02-PP5 1 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
RM 201 REC 02-PP5 3 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1
HOT WATER CIRC PUMP 02-PP5 4 6 2-#12 1-#12 2 0 1 3/4" RMC 1
RECEPTACLE 02-PP5 5 1-#10 1-#10 1-#10 1 1 1 3/4" RMC 1
ELECTRIC CHAIN HOIST 02-PP5 7 9 2-#10 1-#10 2 0 1 3/4" RMC 1
AIR COMPRESSOR 02-PP5 8 10 12 3-#10 1-#10 3 0 1 3/4" RMC 1
HOT WATER CIRC PUMP 02-PP5 11 13 2-#12 1-#12 2 0 1 3/4" RMC 1
GENERATOR CABLE AND CONDUIT SCHEDULE
LOAD NAME PANEL CIRCUIT NUMBER WIRE SIZE # OF HOT # OF NEUTRAL # OF GROUND CONDUIT # OF RUNS
2-120B-480E-SWBD-001 GENERATOR 3-#250 1-#250 1-#3 6 2 2 2-1/2" RMC 2
NORMAL POWER CABLE AND CONDUIT SCHEDULE
LOAD NAME PANEL CIRCUIT NUMBER WIRE SIZE # OF HOT # OF NEUTRAL # OF GROUND CONDUIT # OF RUNS
2-120A-480N-SWBD-001 NORMAL SWITCHGEAR 3-#250 1-#250 1-#3 6 2 2 2-1/2" RMC 2
PANEL C (EXISTING) CABLE AND CONDUIT SCHEDULE
LOAD NAME PANEL CIRCUIT NUMBER WIRE SIZE # OF HOT # OF NEUTRAL # OF GROUND CONDUIT # OF RUNS
EMERGECNY FUEL OIL SHUT OFF PANEL C 14 16 18 3-#12 1-#12 3 0 1 3/4" RMC 1
2-202-UH-001 -002 -003 PANEL C 20 1-#10 1-#10 1-#10 1 1 1 3/4" RMC 1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Director
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10 on e e igh th inc h = on e f oo t thr ee in ch es on e f oo t 6"
6" on e a nd on e h alf in ch es on e f oo t on e i nc h = on e f oo t
6"
6" thr ee qu ar ter s i nc h = on e f oo t on e h alf in ch on e f oo t thr ee ei gh ths in ch on e f oo t on e q ua rte r in ch on e f oo t
REV 0 - 100% BID SET 2024-02-23
FINAL BID SET REPLACE BOILER PLANT
325 EAST "H" STREET
IRON MOUNTAIN, MI 49801
585-21-115
2024-02-23
EP604
ELECTRICAL POWER CABLE AND
CONDUIT SCHEDULES 2
KRK LAJ
PARTIALLY SPRINKLERED
Revisions: Date:
SHEET 2534/4/2024
GMC KRL
FIBEROPTICS LINE = FO
COMMUNICATION SYMBOLS
OUTLET DATA ONLY
2 = DUAL PORT
OUTLET; LETTER INDICATES AS FOLLOWS:
A = AUDIO V = VIDEO I = INTERCOM
1PH SINGLE-PHASE
1P SINGLE POLE
2/C TWO-CONDUCTOR
3/C THREE-CONDUCTOR
3PH THREE-PHASE
4/C FOUR-CONDUCTOR
4W FOUR-WIRE
A/C UNIT AIR CONDITIONING UNIT
A/E ARCHITECT/ENGINEER
AAP ALARM ANNUNCIATOR PANEL
AC ALTERNATING CURRENT OR ARMORED CABLE
ACC ACCESSIBLE
ADDL ADDITIONAL
ADJ ADJACENT, ADJOINING
ADO AUTOMATIC DOOR OPENER
AFC ABOVE FINISHED COUNTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHJ AUTHORITY HAVING JURISDICTION
ALT ALTERNATE
AMB OR A AMBIENT
ARCH ARCHITECT
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AV AUDIO VISUAL
BAT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISH FLOOR
BLDG BUILDING
BPIP BOILER PLANT INSTRUMENTATION PANEL
BYP BY PASS
C CONDUIT
CAB CABINET
CALC CALCULATE
CAP CAPACITY
CAT CATALOG
CATV COMMUNITY ANTENNA TELEVISION
CCR CONTROL CONTACTOR
CCTV CLOSED CIRCUIT TELEVISION
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED/CONTRACTOR INSTALLED
CF/OI CONTRACTOR FURNISHED/OWNER INSTALLED
CFE CONTRACTOR FURNISHED EQUIPMENT
CLG CEILING
CMU CONCRETE MASONRY UNIT
COAX COAX CABLE
COMM COMMUNICATION
COMPT COMPARTMENT
CONC CONCRETE
CONT CONTINUE
CONTR CONTRACTOR
COORD COORDINATE
CTV CABLE TELEVISION
CU COPPER
CU FT CUBIC FEET
CUR CURRENT
DB DECIBEL OR DIRECT BURIAL
DC DIRECT CURRENT
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLITION
DIAG DIAGRAM
DISTR DISTRIBUTION
DN DOWN
DRSW DOOR SWITCH
DWG DRAWING
EC EMPTY CONDUIT
EG EQUIPMENT GROUND
EL ELEVATION
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
EMER EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EPO EMERGENCY POWER OFF
ESMT EASEMENT
EXIST EXISTING
FLEX FLEXIBLE METALLIC CONDUIT
FO FIBER OPTIC CABLE
FOUTT TELEPHONE FLOOR OUTLET
FP FIRE PROTECTION
FT FEET OR FOOT
FU SW FUSED SWITCH
G OR GND GROUND OR GENERATOR
GEN GENERATOR
GTB GROUND TERMINAL BOX
HOA HAND-OFF-AUTOMATIC
HT HEIGHT
HZ HERTZ
IMC INTERMEDIATE METAL CONDUIT
IR INFRARED
J-BOX JUNCTION BOX
LF LINEAR FEET (FOOT)
LTNG LIGHTNING
LV LOW VOLTAGE
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MECH MECHANICAL
MH MANHOLE
MIN MINIMUM
MT MOUNT
MTD MOUNTED
MTG MOUNTING
NA NOT APPLICABLE
NEC NATIONAL ELECTRICAL CODE
NEUT OR N NEUTRAL
NIC NOT IN CONTRACT
NS NO SCALE
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
P POLE
PA PUBLIC ADDRESS
PB PANELBOARD, PULL BOX, OR PUSHBUTTON
PBPU PREFABRICATED BEDSIDE PATIENT UNIT
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PNL PANEL
PVC POLYVINYL CHLORIDE (PLASTIC)
PWR POWER
RCP REFLECTED CEILING PLAN
REC RECESSED
RECPT RECEPTACLE
RGS RIGID GALVANIZED STEEL
RM ROOM
REQD REQUIRED
SF SQUARE FOOT (FEET)
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SPEC SPECIFICATION
SURF SURFACE
SW SWITCH
TEL TELEPHONE
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
TYP TYPICAL
UFD UNDERFLOOR DUCT
UGND UNDERGROUND
UL UNDERWRITERS LABORATORY
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
UTIL UTILITY
V VOLT
WP WEATHERPROOF
WAP WIRELESS ACCESS POINT
COMMUNICATION AND ELECTRONIC SAFETY AND SECURITY ABBREVIATIONS
APPLICABLE CODES
THE APPLICABLE MODEL CODES, STANDARDS AND REFERENCES DOCUMENTS
PERTINENT TO THE PROJECT ARE AS FOLLOWS:
· NFPA 101 LIFE SAFETY CODE (LATEST EDITION)
· NATIONAL ELECTRICAL CODE NFPA70 (LATEST EDITION)
· SEE PROJECT SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
1. VERIFY LOCATIONS WITH COR PRIOR TO ROUGHING IN THE INSTALLATION.
2. ALL WALL MOUNTED BACK BOXES TO A MINIMUM OF 18 INCHES ABOVE THE
FINISHED FLOOR UNLESS OTHERWISE SPECIFIED.
3. FOR SPACES WITH DROP CEILINGS, ALL DATA AND PHONE LINES SHALL BE
INSTALLED IN A MINIMUM 1" EMT CONDUIT RUN VERTICALLY IN THE WALLS
AND STUBBING ABOVE THE CEILING BY AT LEAST 1 INCH. INSTALL WITH A
PULL STRING.
4. ALL WIRING FOR COMMUNICATION DEVICES SHALL BE INSTALLED WITH A
PULL STRING.
5. USE EXISTING TIE-IN POINTS FOR WIRE TERMINATION.
6. ALL WIRING ABOVE SUSPENDED CEILING WILL BE SUSPENDED USING
APPROVED WIRE HANGERS OR BASKET CABLE TRAYS.
7. OUTLET BOXES SHALL BE THE SAME MINIMUM SIZE AS NEC STANDARD 6 IN x
6 IN x 2.5 IN THAT COULD CONTAIN DUAL DUPLEX ELECTRICAL OUTLETS.
8. OUTLET BOXES SHALL BE EQUIPPED WITH FULL COVERED WALL FACEPLATES
THAT SHALL COVER THE ENTIRE BOX WITHOUT TRIM RINGS ADDED, AND
SHALL EMPLOY TWO EACH MODULAR CATEGORY 6A (OR BETTER) RJ-45
JACKS FOR DATA. THE BOX SHALL ALSO PROVIDE SPACE FOR THE ADDITION
OF TWO ADDITIONAL CATEGORY 6A.
9. PLENUM/ CMP RATED WIRE OR CABLE SHALL BE PROVIDED IN ALL
AIR-HANDLING PLENUM LOCATIONS. NON-PLENUM/CM WIRE OR CABLE MAY
BE PROVIDED IN ALL OTHER AREAS.
GENERAL NOTES
FO
A
NETWORK EQUIPMENT, TYPE=X
R = TYPE 1 EQUIPMENT RACK
W = TYPE 4 WALL MOUNT
CONDUIT SYMBOLS
CONDUIT UP
CONDUIT DOWN
VERTICAL RISER
FL
RK
SECURITY SYMBOLS
ELECTRONIC LOCK
X
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL RK-RACK S-SURFACE FL-FLOOR W-WALL
T=TECHNOLOGY/TYPE (SPECIFIC TO DEVICE)
D-DOCUMENT IP-IP CAM IR-INFARED HD-HIGH DEFINITION
LETTER INDICATES AS FOLLOWS:
T M
T2
O-OUTDOOR R-ROOF REC-RECESSED G-GROUND
L#-LENS ANGLE VIEW M-MOTION DETECTOR PT-PAN/TILT
PTZ-PAN/TILT/ZOOM PZ-PAN/ZOOM T#-PANNING TRAVERSE ANGLE
T2=SECONDARY TECHNOLOGY
X=LEGEND REF
E - EXISTING
SECURITY ACCESS, VIDEO CAMERA WITH LENS, ANGLE OF VIEW ;
RF REPEATER OR ACCESS POINT; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK/TABLE F-FLUSH FL-FLOOR G-GROUND
H-HIDDEN M-MULLION O-OUTDOOR P-PEDESTAL RK-RACK
R-ROOF REC-RECESSED S-SURFACE W-WALL PL-POLE
T=TECHNOLOGY/TYPE
C-CELLULAR REPEATER PR-PHONE REPEATER RX-RECEIVER
TR-TRANSCEIVER TX-TRANSMITTER WAP-WIRELESS ACCESS POINT
WP-WIRELESS PROCESSOR REPEATER A-ANTENNA A-ANTENNA
T2=SECONDARY TECHNOLOGY
X=LEGEND REF
E-EXISTING VZ-VERIZON WIRELESS OD-OMNI-DIRECTIONAL
M T
T2 X
CARD ACCESS READER; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
B-BARCODE F-ELEVATOR FLOOR CALL H-HYBRID
M-MAG STRIP P-PROXIMITY D=DEADBOLT S-STRIKE
T-TOKEN L=LATCH SET
M
T
MOTION DETECTOR; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
D-DUAL TECHNOLOGY IR-INFRARED M-MICROWAVE U-ULTRASONIC
X-REQUEST-FOR-EXIT
M
T
SECURITY ACCESS, BUZZER. MTD 1'-6" [457mm] AFF UNLESS OTHERWISE NOTED
INTERCOM; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
M-MASTER S-SUBSTATION
M
T
GENERAL SYMBOLS
ROOM NAME AND NUMBER
DEMOLISH/REMOVE
A1
ROOM
2 OUTLET, COMBINATION TELEPHONE/DATA COMMUNICATION
2 = DUAL PORT (TYPE B FACEPLATE)
CARD READER WITH KEYPAD; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
M
AUDIO DEVICE; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
B-BELL C-CHIME H-HORN K-KLAXON
L-LISTEN-IN M-MICROPHONE S-SPEAKER Z-BUZZER
M
T
SECURITY SYMBOLS CONTINUED
MONITOR; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
D-DATA G-GRAPHIC M-MULTISCREEN V-VIDEO
M
T
PUSH BUTTON; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
B-BELL PUSH D-DURESS P-PANIC R-DOOR RELEASE
X-REQUEST-FOR-EXIT
M
T
VIDEO MOTION DETECTOR
CONTROL PANEL; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
B-BURGLAR D-DOOR F-FIRE P-PERIMETER
T
M
REV 0 - 100% BID SET 2024-02-23
REV 1 - FINAL BID SET 2024-04-04
COPPER COMMUNICATION LINE = CUCU
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ELECTRICAL TELECOMMUNICATIONS
- NOTES AND LEGENDS
FINAL BID SET
PARTIALLY SPRINKLERED
REPLACE BOILER PLANT
325 EAST "H" STREET
IRON MOUNTAIN, MI 49801
2024-02-23
ET001
585-21-115
EMERGENCY PHONE
CARBON MONOXIDE DETECTOR
COMBUSTIBLE GAS DETECTOR
SHEET 2544/4/2024
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
CO
GAS
UP
RK
GAS
A'
B'
D'
C'
2.8'
E'
RK-001-2
EMERGENCY
PHONE (EP3)
SEE 3/ET503 FOR
DETAIL
BASEMENT HALLWAY
002-2
STORAGE
RM/TUNNEL ACCESS
001-2
1 2 3
A
B
D
F
H
WAP
(EXT)
D002
18" WIDE CABLE TRAY (EXISTING)
PACS PANEL (NEW)
TO BUILDING 1
MOUNT 1' AFF
BASEMENT
003-2
3'
D003
4" EMT COND.TO NEW BOILER
TO EXISTING BOILER
EXISTING
CAMERA
CAMERA 9
UP TO GROUND FLOOR
(SEE ET121)
ALL EQUIPMENT IN ROOM
IS EXISTING UNLESS NOTED
SEE EI121 AND EI141 FOR
LOCATIONS OF REMAINING
GAS DETECTION SYSTEM DEVICES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Director
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10 on e e igh th inc h = on e f oo t thr ee in ch es on e f oo t 6"
6" on e a nd on e h alf in ch es on e f oo t on e i nc h = on e f oo t
6"
6" thr ee qu ar ter s i nc h = on e f oo t on e h alf in ch on e f oo t thr ee ei gh ths in ch on e f oo t on e q ua rte r in ch on e f oo t
REV 0 - 100% BID SET 2024-02-23
FINAL BID SET REPLACE BOILER PLANT
325 EAST "H" STREET
IRON MOUNTAIN, MI 49801
585-21-115
2024-02-23
ET101
ELECTRICAL TELECOMMUNICATIONS
PLAN - BASEMENT LEVEL 2
GMC KRL
PARTIALLY SPRINKLERED
SCALE: 3/16" = 1'-0"1 ELECTRICAL TELECOMMUNICATIONS - BASEMENT LEVEL
KEYPLAN
N AREA OF WORK
12 16
4. SEE ET603 FOR CAMERA SCHEDULE.
3.
WORK OUTSIDE THE DESIGNATED PHASE AREA MAY BE REQUIRED TO COMPLETE
PHASED WORK. CONTRACTOR IS TO COORDINATE ALL WORK WITH COR AND BETWEEN
ANY AND ALL SUBCONTRACTORS TO ENSURE CONTINUED OPERATIONS AND INTENT
SHOWN THROUGHOUT THIS DRAWING SET.
2. PHASING IS DESIGNATED THROUGHOUT THE DRAWING SET VIA
1. SEE ET001 FOR ET-SERIES NOTES AND LEGENDS.
GENERAL NOTES
N
Revisions: Date:
SHEET 2554/4/2024
MF
AC
U
MFACP
F F
1' 2'
A'
B'
G'
F'
D'
C'
2.8'
E'
NETWORK
OUTLETS FOR
ATS REPORTING.
WAP
PACS PANEL
EMERGENCY
PHONE (EP1)
SEE 3/ET503
FOR DETAIL
WAP
PACS PANEL
EMERGENCY
PHONE (EP2)
SEE 3/ET503
FOR DETAIL
BOILER ROOM
119-2
CONTROL ROOM
130-2
SUPERVISOR
129-2
CHEM FEED
128-2
GENERATOR ROOM
120B-2
JANITOR
121-2
TOILET
122-2
TOILET
123-2
BREAK ROOM
124-2
LOCKER ROOM
125-2
SHOWER AREA
126-2
CHANGING AREA
127-2
PROPANE
131-2
CAMERA 3
CAMERA 8
CAMERA 1
CAMERA 2
1 2 3
A
B
D
F
H
M
D130B
D119A D120B
W
IP
W
IP
W
IP
W
IP
W
IP
W
IP
SECURITY SCREEN
D119F
PARALLEL
SWITCHING GEAR
101B-2
BOILER ROOM
101-2
D119G
CAMERA 8
TELECOMMUNICATION CONDUIT LOCATED
BELOW CABLE TRAY
3'
2-119-CP-001
2-119-CP-002
2-119-CP-003
W
IP
PHONE HORN/ LIGHT
IP OUTLET
CAMERA 6
CAMERA 4
24"x24"x6" MARSHALLING BOX 2" EMT COND 12"x12"x6"
J-BOX
24"x24"x6"
MARSHALLING BOX
4" EMT COND
4" EMT COND
2" EMT COND
12"x12"x6"
MARSHALLING BOX
4" EMT COND
24"X24"X6"
MARSHALLING BOX
DOWN TO BASEMENT
(SEE ET101)
24"x24"x6"
MARSHALLING BOX
MASTER
CONTROLLER
CRT-6
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Director
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10 on e e igh th inc h = on e f oo t thr ee in ch es on e f oo t 6"
6" on e a nd on e h alf in ch es on e f oo t on e i nc h = on e f oo t
6"
6" thr ee qu ar ter s i nc h = on e f oo t on e h alf in ch on e f oo t thr ee ei gh ths in ch on e f oo t on e q ua rte r in ch on e f oo t
REV 0 - 100% BID SET 2024-02-23
FINAL BID SET REPLACE BOILER PLANT
325 EAST "H" STREET
IRON MOUNTAIN, MI 49801
585-21-115
2024-02-23
ET121
ELECTRICAL TELECOMMUNICATIONS
PLAN - GROUND FLOOR LEVEL 2
GMC KRL
PARTIALLY SPRINKLERED
SCALE: 3/16" = 1'-0"1 ELECTRICAL TELECOMMUNICATIONS FLOOR PLAN - GROUND FLOOR LEVEL N
5. ONLY CONDUIT SIZED ABOVE 2" DIAMETER ARE SHOWN ON DRAWINGS.
4. MOUNT ALL CONDUITS AND MARSHALLING BOXES 9'-8" AFF UNLESS
OTHERWISE NOTED.
3.
WORK OUTSIDE THE DESIGNATED PHASE AREA MAY BE REQUIRED TO COMPLETE
PHASED WORK. CONTRACTOR IS TO COORDINATE ALL WORK WITH COR AND BETWEEN
ANY AND ALL SUBCONTRACTORS TO ENSURE CONTINUED OPERATIONS AND INTENT
SHOWN THROUGHOUT THIS DRAWING SET.
2. PHASING IS DESIGNATED THROUGHOUT THE DRAWING SET VIA
1. SEE ET001 FOR ET-SERIES NOTES AND LEGENDS.
GENERAL NOTES
KEYPLAN
N AREA OF WORK
12 16
Revisions: Date:
SHEET 2564/4/2024
RK
1' 2'
A'
B'
G'
F'
D'
C'
2.8'
E'
OPEN TO BELOW
EQUIPMENT ACCESS
200-2
CONTROL IT
201-2
A
B
D
F
H
M
W
IP
3'
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Director
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10 on e e igh th inc h = on e f oo t thr ee in ch es on e f oo t 6"
6" on e a nd on e h alf in ch es on e f oo t on e i nc h = on e f oo t
6"
6" thr ee qu ar ter s i nc h = on e f oo t on e h alf in ch on e f oo t thr ee ei gh ths in ch on e f oo t on e q ua rte r in ch on e f oo t
REV 0 - 100% BID SET 2024-02-23
FINAL BID SET REPLACE BOILER PLANT
325 EAST "H" STREET
IRON MOUNTAIN, MI 49801
585-21-115
2024-02-23
ET141
ELECTRICAL TELECOMMUNICATIONS
PLAN - MEZZANINE LEVEL 2
KRK KRL
PARTIALLY SPRINKLERED
KEYPLAN
N AREA OF WORK
12 16
3.
WORK OUTSIDE THE DESIGNATED PHASE AREA MAY BE REQUIRED TO COMPLETE
PHASED WORK. CONTRACTOR IS TO COORDINATE ALL WORK WITH COR AND BETWEEN
ANY AND ALL SUBCONTRACTORS TO ENSURE CONTINUED OPERATIONS AND INTENT
SHOWN THROUGHOUT THIS DRAWING SET.
2. PHASING IS DESIGNATED THROUGHOUT THE DRAWING SET VIA
1. SEE ET001 FOR ET-SERIES NOTES AND LEGENDS.
GENERAL NOTES
SCALE: 3/16" = 1'-0"1 ELECTRICAL TELECOMMUNICATIONS FLOOR PLAN - MEZZANINE LEVEL
N
RK-201-2
REV 1 - FINAL BID SET 2024-04-04
Revisions: Date:
SHEET 2574/4/2024
RUN 1" EMT CONDUIT BACK TO TELECOMMUNICATIONS
ROOM. PROVIDE LARGER CONDUIT AS REQUIRED IF USING
PRE-TERMINATED CABLES.
PROVIDE SINGLE-GANG DEVICE BOX FOR
DATA PORTS. RJ-45 WITH 568A
PUNCH DOWN. FLUSH FACEPLATE
EQUIVALENT IN SIZE, COLOR, AND
PERFORMANCE SPECS TO UNIPRISE L TYPE,
ONE PORT IVORY.
LABEL (TYP)
FACEPLATE BY
CABLING VENDOR
CEILING
T568A CONNECTOR
COLOR: AS SPECIFIED
WIRELESS ACCESS POINT,
MOUNT IN ACCORDANCE
WITH MANUFACTURERS
INSTRUCTIONS
GENERAL NOTES:
1. RUN ONE (1) DATA CAT 6 CABLE. TERMINATE, LABEL, AND TEST EACH CABLE AND
JACK. JACKET COLOR SHALL BE AS SPECIFIED. WIRE IN DIRECT RUNS. NO SPLICES
IN RUN TO DATA ROOM. DO NOT LAY ON CEILING DO NOT USE ZIP TIES. DO NOT TIE
TO PIPING.
2. PORTS USED SHALL BE EQUIVALENT IN SIZE, COLOR AND PERFORMANCE SPECS
TO UNIPRISE UNJ600 INFORMATION OUTLETS.
3. ALL HOME RUNS TO END IN SPECIFIED DATA CLOSETS.
DETAIL A-A
A A
NOTES:
1. PROVIDE WHEREVER PLANS
CALL FOR TWO (2) DATA JACKS
AND ONE (1) PHONE JACK
GROUPED TOGETHER. ALL
HOME RUNS TO END IN RM 18.
RUN TWO (2) DATA CAT 6A CABLES. TERMINATE, LABEL
AND TEST EACH CABLE AND JACK. CABLE JACKET
COLORS SHALL BE BLUE FOR DATA A PORT, WHITE FOR
DATA B PORT. WIRE IN DIRECT RUNS. NO SPLICES IN RUN
TO DATA ROOM. DO NOT LAY ON CEILING. DO NOT USE
ZIP-TIES. DO NOT TIE TO PIPING.
RUN 1" EMT CONDUIT
UP TO CEILING SPACE
FUTURE USE
ANGLE TOWARDS DIRECTION
OF DATA/TELEPHONE MAIN
RACEWAY OR CABLE BUNDLES
FACEPLATE BY
CABLING VENDOR
NYLON BUSHING
LABEL
CEILING
UNLESS OTHERWISE NOTED, PROVIDE
SINGLE-GANG DEVICE BOX FOR TELEPHONE AND
DATA PORTS MOUNT IN THE FOLLOWING
LOCATIONS/HEIGHTS:
GENERAL: 18" AFF
COUNTERS: 42" AFF (6" ABOVE COUNTER)
OTHER: BETWEEN 18" AND 44" AFF
RJ-45 WITH 568A PUNCH DOWN
SPACE
PROVIDE VERTICAL CABLE
MANAGEMENT SYSTEM
(NOT SHOW)
45U ENCLOSED RACK
WITH INTEGRATED
POWER DISTRIBUTION
(EXT) FIBER OPTIC
PATCH PANEL
HORIZONTAL CABLE
MANAGEMENT (TYP)
48 PORT NETWORK
SWITCHES (VA
NETWORK)
(EXT) UPS BATTERY
(EXT) UPS
SPACE
EXISTING SERVER
(EXT) EQUIPMENT
BUS BAR (BACK)
SPACE
(NEW) SECURITY SWITCH
PROVIDE WITH PoE
CONTROLLER
CARD READER
CONDUIT AND
WIRING TO PACS
CONTROL PANEL
24V
TRANSFORMER
SECURE AREA
CEILING LINE
TYP CONDUIT &
WIRING FROM
CONTROLLER FOR
DOOR RELEASE
(TYP) DOOR
CONTACT SWITCH
CONDUIT &
WIRING TO CARD
READER
LOCKSET
(PROVIDED BY
GENERAL CONTR)
NOTE:
1. CONTRACTOR TO COORDINATE WITH DOOR VENDOR THE REQUIRED DOOR LOCKING
HARDWARE
2. CONDUIT AND WIRE SIZE AS RECOMMENDED BY PACS MANUFACTURER
3. CONTRACTOR TO MATCH EXISTING MANUFACTURER
NOTES:
1. ALL BUSBARS SHALL BE 1/4" X 4" X 24" PRE-DRILLED
TIN-PLATED COPPER. MOUNT ON WALL WITH 2" STANDOFF
INSULATORS
2. ALL CABLE CONNECTIONS TO TGB'S ARE TWO HOLE TONGUE
COMPRESSION LUGS.
3. TBB SHALL GENERALLY BE RUN OPEN WITH PLASTIC
SUPPORTS WHERE RUN IN STEEL CONDUITS LONGER THAN
36", BOND CONDUIT TO TBB OR GE AT BOTH ENDS
4. TBB SHALL BE RUN WITHOUT SPLICES WHEREVER POSSIBLE.
ANY SPLICES MUST BE MADE WITH NON-REVERSABLE
COMPRESSION CONNECTORS OR CADWELD. ALL GROUND
WIRES SHALL BE COPPER CONDUCTORS WITH GREEN
INSULATION OR
5. DISTINCTIVE GREEN MARKING
BASEMENT
FIRST FLOOR
TO TYPICAL EQUIPMENT
TGB 1-1
TELECOMMUNICATIONS MAIN
GROUNDING BUSBAR (TMGB) TO BE
LOCATED IN TELECOMMUNICATIONS
ENTRANCE ROOM
TELECOMMUNICATIONS
BONDING BACKBONE
(TBB) #3/0 COPPER
BUILDING POWER SYSTEM
MAIN GROUND BUS
BONDING CONDUCTOR FOR
TELECOMMUNICATIONS
#3/0 COPPER
BUILDING
GROUNDING
ELECTRODE SYSTEM
EQUIPMENT
RACKS CABLE
TRAY
ALL TELECOMM
SLEEVES AND
RACEWAYS
TYPICAL EQUIPMENT
BONDED TO ALL
TGB'S AND TMGB H-TAP, CADWELD, OR OTHER
NON-REVERSABLE SPLICE
(TYPICAL)
THIS CONNECTION IS NOT
REQUIRED FOR SLEEVES OR
RACEWAYS BONDED TO THE
TBB. SEE NOTE 3
PANELS SERVING BUILDING
STEEL TELECOMM ROOMS
WHERE AVAILABLE
#3/0 TBB
TO BE PROVIDED
BY VA
# 6 COPPER BONDING
CONDUCTOR (TYPICAL)
NOTES:
1. INTEGRAL GALVANIZED LIPPED STEEL MOUNTING CHANNEL LONGER THAN 36" SHALL
BE INSTALLED WITH A CENTER SUPPORT ROD.
2. FASTEN THREADED ROD TO STRUCTURE BY APPROVED METHOD PER SPECIFICATION
26 05 33, RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS (FIELD VERIFY EXACT
CONDITIONS).
3. FOR TRAPEZE INSTALLATIONS IN SEISMIC AREAS REFER TO SPECIFICATION SECTION
13 05 41, SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS.
4. EACH THREADED ROD SHALL BE ONE CONTINUOUS PIECE.
5. LOCATION OF CABLE TRAY IN MOUNTING CHANNEL INCLUDING WETHER CABLE TRAY
IS INSTALLED ON THE SAME CHANNEL AS CONDUITS OR SEPARATE SHALL BE BASED
ON FIELD CONDITIONS AND AVAILABLE HEIGHT ABOVE CEILING WITH OTHER UTILITIES.
CONTRACTOR TO INSTALL AND BOND CABLE TRAY PER SPECIFICATION 27 05 33.
WASHER AND
LOCKNUT
INTEGRAL
GALVANIZED LIPPED
STEEL MOUNTING
CHANNEL
LOCKING SQUARE
WASHER AND
LOCKNUT
3/8" MIN GALVANIZED
THREADED ROD, TYP
REFER TO PLANS
FOR QUANTITY AND
SIZE OF CONDUITS
CONDUIT CLAMP
(SIZE AS REQUIRED)
INTEGRAL GALVANIZED
LIPPED STEEL
MOUNTING CHANNEL
TRAY CLIP TO
MOUNTING CHANNEL
CONTROLLER
CARD READER
CONDUIT…
This is the start of the file's text. The full file is on GovTribe.