S02 Sol 0004 AttJ.7 of 7 VA 585-21-115 Final Bid Drawing Set 01AUG24 VOL.pdf

PDF 8 MB Posted

Attached to
Y1NB--Project 585-21-115 Replace Boiler Plant at the Oscar G. Johnson VA Medical Center in Iron Mountain, MI -- NAICS 236220 General Construction
Solicitation number
36C25225R0004
Issued by

About this file

This is an electrical drawing set containing 18 pages of detailed telecommunications, security, and power system diagrams and specifications for the VA Medical Center boiler plant replacement project in Iron Mountain, MI. The drawings include electrical power plans for roof and ground floor levels, power panel schedules, cable/conduit schedules, telecommunications floor plans for basement through mezzanine levels, network architecture diagrams, and security camera layouts and schedules.

Key technical details include power distribution requirements for boiler equipment, emergency power systems, telecommunications infrastructure with fiber optic connections between buildings, security access control systems for multiple doors, and surveillance camera placements. The drawings specify equipment like AXIS PTZ/IP dome cameras, telecommunications conversion boxes, card readers, and emergency phones. Construction notes indicate phased work coordination requirements between contractors and the COR to maintain continuous operations. The drawings were prepared by Encorus Group as the architect/engineer of record and are marked as 100% bid set dated February 2024.

View the file

Other files

File Type Posted
36C25225R0004 0008.docx DOCX document
S06 36C25223R0004 0007 Att_Updated Dwgs_partial_24JAN25.pdf PDF
S06 36C25223R0004 0007 Att_232213 Steam and Condensate Heating Piping.REV01.pdf PDF
S06 36C25223R0004 0007 Att_232113 Hydronic Piping.REV01.pdf PDF
S06 36C25223R0004 0007 Att_DOD_Anti-Ram_Vehicle Barriers 2024.09.pdf PDF
36C25225R0004 0007.docx DOCX document
S06 36C25223R0004 0007 Att_230510 Common Work Results_Boiler Plant_Steam Gen.REV01.pdf PDF
36C25225R0004 0006.docx DOCX document
S06 0006 Att_S02 SOL 0004 AttH SAM_DB Wage Rates.R1.pdf PDF
36C25225R0004 0005.docx DOCX document
Copy of S06 0005 Att__S02 SOL 0004 AttF Brand Name or Equal_Basis of Design 585-21-115.xlsx XLSX spreadsheet
Copy of S06 0005 Att_22367-Valve List.xlsx XLSX spreadsheet
36C25225R0004 0004.docx DOCX document
S06 0004 Att_Electric Heater product data.pdf PDF
S06 0004 Att Site Visits 1.2.3_Sign Ins_585-21-115.pdf PDF
S06 0003 Att1_S04 Site Visit Sign In_2 585-21-115 2025.01.03.pdf PDF
36C25225R0004 0003.docx DOCX document
36C25225R0004 0002.docx DOCX document
S06 0002 Att4_S02 SOL AttA VAAR 852.219-75 Certification 585-21-115_rev1.pdf PDF
S06 0002 Att2 Solicitation Instruction and Eval Factors.pdf PDF
S06 0002 Att1_S04 Site Visit 585-21-115 2024.12.27.pdf PDF
S06 0002 Att3_S02 SOL AttJ.5d of 7 VA 585-21-115 Final Bid Drawing Set 01AUG24 VOL.pdf PDF
S02 SOL 0004 AttI.2 SPECS_FINAL 585-21-115_01AUG24 VOL 2 of 3_.pdf PDF
S06 36C25225R0004 0001.pdf PDF
S02 SOL 0004 AttI.1 SPECS_FINAL 585-21-115_01AUG24 VOL 1 of 3_.pdf PDF
S02 Sol 0004 AttJ.6b of 7 VA 585-21-115 Final Bid Drawing Set 01AUG24 VOL.pdf PDF
S02 Sol 0004 AttJ.5b of 7 VA 585-21-115 Final Bid Drawing Set 01AUG24 VOL.pdf PDF
S02 Sol 0004 AttJ.6a of 7 VA 585-21-115 Final Bid Drawing Set 01AUG24 VOL.pdf PDF
S02 Sol 0004 AttJ.5c of 7 VA 585-21-115 Final Bid Drawing Set 01AUG24 VOL.pdf PDF
S02 SOL 0004 AttM Past Performance Client Questionnaire 585-21-115.pdf PDF
S02 Sol 0004 AttJ.5a of 7 VA 585-21-115 Final Bid Drawing Set 01AUG24 VOL.pdf PDF
S02 SOL 0004 AttL MI Tax Exempt Form 3520_585-21-115.e__.pdf PDF
S02 SOL 0004 AttK.1_P03 Single Source Justification MEDECO.e.pdf PDF
S02 SOL 0004 AttK.2_P03 Single Source Justification ALLEGION_SCHLAGE.e.pdf PDF
S02 Sol 0004 AttJ.6c of 7 VA 585-21-115 Final Bid Drawing Set 01AUG24 VOL.pdf PDF
S02 Sol 0004 AttJ.3 of 7 VA 585-21-115 Final Bid Drawing Set 01AUG24 VOL.pdf PDF
S02 SOL 0004 AttI.3 SPECS_FINAL 585-21-115_01AUG24 VOL 3 of 3.pdf PDF
S02 Sol 0004 AttJ.4c of 7 VA 585-21-115 Final Bid Drawing Set 01AUG24 VOL.pdf PDF
S02 Sol 0004 AttJ.4a of 7 VA 585-21-115 Final Bid Drawing Set 01AUG24 VOL.pdf PDF
S02 SOL 0004 AttH SAM_DB Wage Rates MI20240117 2024.07.05 current as of 2024.11.19.pdf PDF
S02 SOL 0004 AttE Subcontractor Info Consent 585-21-115.pdf PDF
S02 SOL 0004 AttG Seasonal Influenza Vaccination Program 2020.08.10.pdf PDF
S02 SOL 0004 AttF Brand Name or Equal_Basis of Design 585-21-115.pdf PDF
S02 SOL 0004 AttB Contractor Info 585-21-115.pdf PDF
S02 Sol 0004 AttJ.4e of 7 VA 585-21-115 Final Bid Drawing Set 01AUG24 VOL.pdf PDF
S02 SOL 0004 AttD Financial Disclosure 585-21-115.pdf PDF
S02 SOL 0004 AttA VAAR 852.219-75 Certification 585-21-115.pdf PDF
S02 Sol 0004 AttJ.4b of 7 VA 585-21-115 Final Bid Drawing Set 01AUG24 VOL.pdf PDF
S02 Sol 0004 AttJ.1c of 7 VA 585-21-115 Final Bid Drawing Set 01AUG24 VOL.pdf PDF
S02 Sol 0004 AttJ.1a of 7 VA 585-21-115 Final Bid Drawing Set 01AUG24 VOL.pdf PDF
Show 40 more

Latest 50 of 57 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

W P, G

FC

I

WP, GFCIWP, GFCI

W P, G

FC

I

1' 2'

A'

B'

G'

F'

D'

C'

2.8'

E'

1 2 3

A

B

D

F

H

02-PP5

02-PP5

02-PP5

02-PP5

3'

02-DP4

15,17,19

02-DP4

16,18,20

02-DP4

21,23,25

VIA VFD

ON EP141

VIA VFD

ON EP141

VIA VFD

ON EP141

2-R-EF-001 2-R-EF-002

2-R-EF-004

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10 on e e igh th inc h = on e f oo t thr ee in ch es on e f oo t 6"

6" on e a nd on e h alf in ch es on e f oo t on e i nc h = on e f oo t

6"

6" thr ee qu ar ter s i nc h = on e f oo t on e h alf in ch on e f oo t thr ee ei gh ths in ch on e f oo t on e q ua rte r in ch on e f oo t

REV 0 - 100% BID SET 2024-02-23

100% BID SET REPLACE BOILER PLANT

325 EAST "H" STREET

IRON MOUNTAIN, MI 49801

585-21-115

2024-02-23

EP161

ELECTRICAL POWER PLAN - ROOF

LEVEL 2

KRK LAJ

PARTIALLY SPRINKLERED

KEYPLAN

N AREA OF WORK

12 16

3.

WORK OUTSIDE THE DESIGNATED PHASE AREA MAY BE REQUIRED TO COMPLETE

PHASED WORK. CONTRACTOR IS TO COORDINATE ALL WORK WITH COR AND BETWEEN

ANY AND ALL SUBCONTRACTORS TO ENSURE CONTINUED OPERATIONS AND INTENT

SHOWN THROUGHOUT THIS DRAWING SET.

2. PHASING IS DESIGNATED THROUGHOUT THE DRAWING SET VIA

1. SEE E-001 FOR E-SERIES NOTES AND LEGENDS.

GENERAL NOTES

SCALE: 3/16" = 1'-0"1 ELECTRICAL POWER PLAN - ROOF

N

Revisions: Date:

SHEET 2462/22/2024

PRIMARY NUMBER 1

LIFT STATION

SECONDARY NUMBER 2 LIFT

STATION

POWER ON HIGH LEVEL POWER ON HIGH LEVEL

PUMP 1

RUNNING

PUMP 2

RUNNING

PUMP 1

RUNNING

PUMP 2

RUNNING

ALARM

ON - OFF

ALARM

TEST

NUMBER 3

LIFT STATION ALARM CONTROLS

POWER ON HIGH LEVEL

PUMP 1

RUNNING

PUMP 2

RUNNING

GROUND FLOOR

0' - 0"

A'

MEZZANINE

12' - 0"

2 2

CALL BOX

(4) GENERATOR MONITOR PANELS

TV DATA OUTLET

TV RECEPTACLE

CONVENIENCE

RECEPTACLE

7'

- 5

4'

- 0

3'

- 9

4'

- 8 3/

8"

4'

- 0

1/ 4"5'

- 3

/1 EP121

MED GAS MONITOR

CO AND

COMBUSTIBLE

GAS MONITOR

GROUND FLOOR

0' - 0"

A'

MEZZANINE

12' - 0"

CHEMCIAL FEED PUMP

GFCI RECEPTACLES

5'

- 1

0" 5'

- 0

4'

- 1

" 5'

- 2

4'

- 5

SOLENOID PUMP (TYP)

CHEMICAL DRUM (TYP)

/1 EP121

02-PP3

02-PP3

02-PP3

GROUND FLOOR

0' - 0"

1'

MEZZANINE

12' - 0"

5'

- 4

CHEMCIAL FEED PUMP

GFCI RECEPTACLE

CHEMICAL DRUM (TYP)

SOLENOID PUMP (TYP)

/1 EP121

GROUND FLOOR

0' - 0"

2'

MEZZANINE

12' - 0"

FA MANUAL

PULL STATION

E STOP

LIGHT SWITCH

CONVENIENCE

RECEPTACLE

FA CONTROL

PANEL

CONVENIENCE

RECEPTACLE

1'

- 6

4'

- 0

3'

- 1

0"

4'

- 5

/1 EP121

2.8' 3'

2-120A-208E-T-00102-PP102-DP1 2-120A-480E-ATS-002 2-120A-480N-SWBD-001

2"ø

2"ø 2 1/2"ø

2 1/2"ø

2 PARALLEL CONDUITS FROM:

2-120A-480-ATS-001

2 PARALLEL CONDUITS FROM :

2-120A-480-ATS-001

1 CONDUIT FROM:

2-120B-480E-SWBD-001

2 PARALLEL CONDUITS FROM:

BLDG. #2 BOILERHOUSE NORM

/1 EP122

GROUND FLOOR

0' - 0"

2-120A-480E-ATS-001

2"ø 2 1/2"ø

2 PARALLEL CONDUITS FROM:

2-120B-480E-SWBD-001 2 PARALLEL CONDUITS TO:

2-120A-480-ATS-002

2 PARALLEL CONDUITS TO:

02-DP1

/1 EP122

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10 on e e igh th inc h = on e f oo t thr ee in ch es on e f oo t 6"

6" on e a nd on e h alf in ch es on e f oo t on e i nc h = on e f oo t

6"

6" thr ee qu ar ter s i nc h = on e f oo t on e h alf in ch on e f oo t thr ee ei gh ths in ch on e f oo t on e q ua rte r in ch on e f oo t

REV 0 - 100% BID SET 2024-02-23

FINAL BID SET REPLACE BOILER PLANT

325 EAST "H" STREET

IRON MOUNTAIN, MI 49801

585-21-115

2024-02-23

EP201

ELECTRICAL POWER ELEVATIONS -

GROUND FLOOR LEVEL 2

KRK CJR

PARTIALLY SPRINKLERED

SCALE: 1/2" = 1'-0"1 CONTROL ROOM 130-2 EAST

SCALE: 1/2" = 1'-0"3 CHEMICAL FEED ROOM 128-2 WEST

SCALE: 1/2" = 1'-0"4 CHEMICAL FEED ROOM 128-2 NORTH

SCALE: 1/2" = 1'-0"2 CONTROL ROOM 130-2 NORTH

2. SEE MECHANICAL PLANS FOR ADDITIONAL INFORMATION ON CHEMICAL FEED PUMPS.

1. SEE E-001 FOR E-SERIES NOTES AND LEGENDS.

GENERAL NOTES

CHEMICAL FEED PUMP

GFCI RECEPTACLES

SCALE: 1/2" = 1'-0"5 ELECTRICAL ROOM N WALL ELEVATION

SCALE: 1/2" = 1'-0"6 2-120A-480-ATS-001 ELEVATION

Revisions: Date:

REV 1 - FINAL BID SET 2024-04-04

SHEET 2474/4/2024

2.8'

2-120B-480E-SWBD-001

2-120B-480-GEN-011

2-102B-UH-004

2"ø

1 CONDUIT TO:

2-120A-480-ATS-002

2 PARALLEL CONDUITS TO:

2-120A-480-ATS-001

/1 EP122

GROUND FLOOR

0' - 0"

F'

2"ø

2 1/2"ø

2 CONDUITS FROM:

2-120B-480-GEN-011

1 CONDUIT TO:

2-120A-480-ATS-002

2 PARALLEL CONDUITS TO:

2-120A-480-ATS-001

/1 EP122

SCALE: 1/2" = 1'-0"1 GENERATOR CONDUIT ROUTE

SCALE: 1/2" = 1'-0"2 2-120B-480E-SWBD-001 ELEVATION

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10 on e e igh th inc h = on e f oo t thr ee in ch es on e f oo t 6"

6" on e a nd on e h alf in ch es on e f oo t on e i nc h = on e f oo t

6"

6" thr ee qu ar ter s i nc h = on e f oo t on e h alf in ch on e f oo t thr ee ei gh ths in ch on e f oo t on e q ua rte r in ch on e f oo t

REV 0 - 100% BID SET 2024-02-23

100% BID SET REPLACE BOILER PLANT

325 EAST "H" STREET

IRON MOUNTAIN, MI 49801

585-21-115

2024-02-23

EP202

ELECTRICAL POWER ELEVATIONS -

GROUND FLOOR LEVEL 2

KRK LAJ

PARTIALLY SPRINKLERED

Revisions: Date:

2. SEE MECHANICAL PLANS FOR ADDITIONAL INFORMATION ON CHEMICAL FEED PUMPS.

1. SEE E-001 FOR E-SERIES NOTES AND LEGENDS.

GENERAL NOTES

SHEET 2482/22/2024

D'

C'

2.8' 1

D

2-119-PMP-001

VFD

2-119-PMP-002

VFD

2-119-PMP-003

VFD

2-119-PMP-004

VFD

2-119-PMP-005

VFD

2-119-PMP-001

2-119-PMP-002

2-119-PMP-003 2-119-PMP-004

2-119-PMP-005

02-DP2

13,15,17

02-DP2

8,10,12

02-DP2

2,4,6

02-DP2

1,3,5

02-DP2

7,9,11

02-PP2

RO

CONTROL

RECEPTACLE

2-119-RO-001

02-DP2

14,16,18

3'

02-PP2

02-PP2

2-119-CP-006

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10 on e e igh th inc h = on e f oo t thr ee in ch es on e f oo t 6"

6" on e a nd on e h alf in ch es on e f oo t on e i nc h = on e f oo t

6"

6" thr ee qu ar ter s i nc h = on e f oo t on e h alf in ch on e f oo t thr ee ei gh ths in ch on e f oo t on e q ua rte r in ch on e f oo t

REV 0 - 100% BID SET 2024-02-23

FINAL BID SET REPLACE BOILER PLANT

325 EAST "H" STREET

IRON MOUNTAIN, MI 49801

585-21-115

2024-02-23

EP401

ELECTRICAL POWER ENLARGED

PLAN - GROUND FLOOR LEVEL 2

KRK CJR

PARTIALLY SPRINKLERED

SCALE: 1/2" = 1'-0"1 ELECTRICAL POWER ENLARGED PLAN - GROUND FLOOR LEVEL

KEYPLAN

N AREA OF WORK

12 16

1. SEE E-001 FOR E-SERIES NOTES AND LEGENDS.

GENERAL NOTES

N

Revisions: Date:

SHEET 2494/4/2024

G

1200KW @ 0.8PF

13.8KV, 60HZ, 3Ø, 4W

1500kVA

70 AT

LS

200 AF

GEN. #3

G

1200KW @ 0.8PF

13.8KV, 60HZ, 3Ø, 4W

1500kVA

70 AT

LS

200 AF

GEN. #1

G

1200KW @ 0.8PF

13.8KV, 60HZ, 3Ø, 4W

1500kVA

70 AT

LS

200 AF

GEN. #2

A

50 AT

LSI

100 AF

B

120 AT

LSI

200 AF

C

100 AT

LSI

100 AF

D

MIN AT

LSI

200 AF

E

50 AT

LSI

100 AF

F

120 AT

LSI

200 AF

G

50 AT

LSI

100 AF

H

MIN AT

LSI

200 AF

G

1200KW @ 0.8PF

13.8KV, 60HZ, 3Ø, 4W

1500kVA

13.8kV

13.8kV GENERATOR DISTRIBUTION

SUBSTATION GENERATOR BUILDING

ADDITION TO BUILDING #2

FUTURE

GEN. #4

SPARETO BLDG 11 TO BLDG 11TO BLDG 2

EXISTING

EMERGENCY

SWITCHGEAR

TO BLDG 2

EXISTING

EMERGENCY

SWITCHGEAR

1 1

FOR FUTURE

EXPANSION

SPARE FOR FUTURE

EXPANSION

BLR HOUSE SUB

BLDG

ATS #3

208Y/120

E

L

N

BLDG 2 BOILERHOUSE NORM

BLDG

ATS #3

208Y/120

E

L

N BLDG

ATS #3

208Y/120

E

L

N

112.5kVA 480- 208Y/120V

400AF

350AT

250AF

250AT

2-120A-480N-SWBD-001

480/277V 400A 10 kA

E

L

N

600 AF

600 AT

FROM 500kVA 13.8kV-480Y/277V (W/E

ENERGIES DISTRIBUTION #7)

480 DISTRIBUTION

208 SWBD

480-EM

208 EM

BUILDING 2

45kVA 480- 208Y/120V

2-120B-480E-SWBD-001

02-DP1

480/277V 400A 10 kA

100A MCB

FROM BLR HOUSE SUB (B2)

(2) SETS OF

(4) 250 KCMIL

(1) #3 AWG GND

02-DP4

100A

02-DP2

100A

02-DP3

175A

02-DP1

MCB

250AF

250AT

(2) SETS OF

(4) 250 KCMIL

(1) #3 AWG GND

(2) SETS OF

(4) 250 KCMIL

(1) #3 AWG GND

(4) #1 AWG

(1) #6 AWG GND

02-DP4

(4) #1 AWG

(1) #6 AWG GND

(4) #4/0 AWG

(1) #6 AWG GND

100A MCB

02-DP2

175A MCB

02-DP3

150AF

100AT

E

L

N

FROM 2-120B-480E-SWBD-001

02-PP1

208/120V 225A 10 kA

50A MCB

100A 100A 100A

02-PP1

MCB

225AF

200AT

(4) #1AWG

(1) #6 AWG GND

(4) #1 AWG

(1) #6 AWG GND

02-PP2

(4) #1 AWG

(1) #6 AWG GND

(4) #1 AWG

(1) #6 AWG GND

50A MCB

02-PP3

70A MCB

02-PP5

(4) #1 AWG

(1) #6 AWG GND

75KVA

480/208/120V

(4) 350 KCMIL

(1) #3 AWG GND

100A

(4) #1 AWG

(1) #6 AWG GND

70A MCB

02-PP4

FROM BLR HOUSE SUB (B2) FROM BLR HOUSE SUB (B2)

2-120A-480-ATS-001

480V 400A

4 POLE WITH BYPASS-ISOLATION

2-120A-480-ATS-002

480V 400A

4 POLE WITH BYPASS-ISOLATION

BUILDING 2 EM SWBD MCB

400AF

350AT

250AF

250AT

150AF

100AT

2-120A-480-ATS-001 2-120A-480-ATS-002

2-120B-480E-SWBD-001

480/277V 400A 10 kA

G

BUILDING 2 GENERATOR

300kW 480Y/277V

KRK CJR

REV 0 - 100% BID SET 2024-02-23

SCALE: NTS

BUILDING 2 NORMAL POWER SYSTEM1 SCALE: NTS

BUILDING 2 STAND-BY POWER SYSTEM3

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

ELECTRICAL POWER ONE-LINE

DIAGRAM

100% BID SET

PARTIALLY SPRINKLERED

REPLACE BOILER PLANT

325 EAST "H" STREET

IRON MOUNTAIN, MI 49801

2024-02-23

EP601

585-21-115

SCALE: NTS

MEDIUM VOLTAGE EMERGENCY POWER SYSTEM2

GENERAL NOTES

1. SEE E-001 FOR E-SERIES NOTES AND LEGENDS.

KEYED NOTES

1 SEE ED171 AND ES171 FOR EXTENT OF EMERGENCY FEEDER DEMOLITION AND NEW

WORK

SHEET 2502/22/2024

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10 on e e igh th inc h = on e f oo t thr ee in ch es on e f oo t 6"

6" on e a nd on e h alf in ch es on e f oo t on e i nc h = on e f oo t

6"

6" thr ee qu ar ter s i nc h = on e f oo t on e h alf in ch on e f oo t thr ee ei gh ths in ch on e f oo t on e q ua rte r in ch on e f oo t

REV 0 - 100% BID SET 2024-02-23

FINAL BID SET REPLACE BOILER PLANT

325 EAST "H" STREET

IRON MOUNTAIN, MI 49801

585-21-115

2024-02-23

EP602

ELECTRICAL POWER PANEL

SCHEDULES 2

KRK CCW

PARTIALLY SPRINKLERED

NOTES:

TOTAL CONN. CURRENT: 256 A

TOTAL CONN. LOAD: 212969 VA

PANEL TOTALS

LEGEND:

TOTAL AMPS: 256 A 254 A 293 A

TOTAL LOAD: 70851 VA 70262 VA 80969 VA

41 42 39 40 37 38 35 36 33 34 31 32 29 30 27 28 25 26

23 3049 VA -- -- -- 24

21 3049 VA -- -- -- 22

19 -- -- -- 44219 VA 3049 VA 3 20 A LIFT STATION (2-119-CP-004) 20

17 -- -- -- 43264 VA 16653 VA -- -- -- 18

15 02-DP3 175 A 3 44449 VA 16689 VA -- -- -- 16

13 -- -- -- 7019 VA 16759 VA 3 100 A 02-DP2 14

11 -- -- -- 6966 VA 0 VA 1 20 A SPARE 12

9 02-DP5 100 A 3 7049 VA 0 VA 1 20 A SPARE 10

7 RM 120B LTS 20 A 1 102 VA 163 VA 1 20 A RM 120A LTS 8

5 ELECTRIC WATER HEATER 60 A 1 12100 VA 0 VA 1 20 A SPARE 6

3 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 4

1 EXTERIOR LIGHTING 20 A 1 526 VA 0 VA 1 20 A SPARE 2

CKT CIRCUIT DESCRIPTION TRIP POLE

S A B C POLE

S TRIP CIRCUIT DESCRIPTION CKT

NOTES:

ENCLOSURE: TYPE 1 MCB RATING: 225 A

MOUNTING: SURFACE WIRES: 4 MAINS RATING: 400 A

SUPPLY FROM: PHASES: 3 MAINS TYPE:

LOCATION: ELECTRICAL ROOM 120A-2 VOLTS: 480/277 Wye A.I.C. RATING:

BRANCH PANEL: DP1

NOTES:

TOTAL CONN. CURRENT: 60 A

TOTAL CONN. LOAD: 50101 VA

PANEL TOTALS

LEGEND:

TOTAL AMPS: 61 A 60 A 60 A

TOTAL LOAD: 16759 VA 16689 VA 16653 VA

41 42 39 40 37 38 35 36 33 34

31 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 32

29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30

27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28

25 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 26

23 RM 125,127 LTS 20 A 1 80 VA 41 VA 1 20 A LTS OUTSIDE RM 121,122,123 24

21 RM 126 LTS 20 A 1 85 VA 71 VA 1 20 A RM 121,122,123 LTS 22

19 LTS UNDER BOILER CATWALK 20 A 1 102 VA 126 VA 1 20 A RM 124 LTS 20

17 -- -- -- 2106 VA 1330 VA -- -- -- 18

15 -- -- -- 2106 VA 1330 VA -- -- -- 16

13 2-119-PMP-001 20 A 3 2106 VA 1330 VA 3 20 A 2-119-RO-001 14

11 -- -- -- 3880 VA 2106 VA -- -- -- 12

9 -- -- -- 3880 VA 2106 VA -- -- -- 10

7 2-119-PMP-005 20 A 3 3880 VA 2106 VA 3 20 A 2-119-PMP-002 8

5 -- -- -- 3880 VA 3880 VA -- -- -- 6

3 -- -- -- 3880 VA 3880 VA -- -- -- 4

1 2-119-PMP-004 20 A 3 3880 VA 3880 VA 3 20 A 2-119-PMP-003 2

CKT CIRCUIT DESCRIPTION TRIP POLE

S A B C POLE

S TRIP CIRCUIT DESCRIPTION CKT

NOTES:

ENCLOSURE: TYPE 1 MCB RATING: 100 A

MOUNTING: SURFACE WIRES: 4 MAINS RATING: 150 A

SUPPLY FROM: DP1 PHASES: 3 MAINS TYPE:

LOCATION: ELECTRICAL ROOM 120A-2 VOLTS: 480/277 Wye A.I.C. RATING:

BRANCH PANEL: 02-DP2

NOTES:

TOTAL CONN. CURRENT: 159 A

TOTAL CONN. LOAD: 131932 VA

PANEL TOTALS

LEGEND:

TOTAL AMPS: 161 A 156 A 160 A

TOTAL LOAD: 44449 VA 43264 VA 44219 VA

41 42 39 40 37 38 35 36 33 34

31 -- -- -- 10254 VA 0 VA 1 20 A SPARE 32

29 -- -- -- 10254 VA 0 VA 1 20 A SPARE 30

27 EM BLR PWR CONN 75 A 3 10254 VA 0 VA 1 20 A SPARE 28

25 BASEMENT EM WALL LIGHTS 20 A 1 100 VA 1100 VA 1 20 A MEZZ EM WALL LTS 26

23 BASEMENT 003-2 LIGHT 20 A 1 20 VA 1100 VA 1 20 A GR FL EM WALL LTS 24

21 -- -- -- 313 VA 33 VA 1 20 A RM 131 LIGHT 22

19 -- -- -- 313 VA 10254 VA -- -- -- 20

17 PROPANE RM EXHAUST FAN 20 A 3 313 VA 10254 VA -- -- -- 18

15 -- -- -- 10254 VA 10254 VA 3 75 A BOILER 3 16

13 -- -- -- 10254 VA 10254 VA -- -- -- 14

11 BOILER 2 75 A 3 10254 VA 10254 VA -- -- -- 12

9 -- -- -- 942 VA 10254 VA 3 75 A BOILER 1 10

7 -- -- -- 942 VA 942 VA -- -- -- 8

5 2-200-SF-001 20 A 3 942 VA 942 VA -- -- -- 6

3 RM 128,129 LTS 20 A 1 80 VA 942 VA 3 20 A 2-200-SF-002 4

1 EXIT SIGNS 20 A 1 35 VA 120 VA 1 20 A RM 130 LTS 2

CKT CIRCUIT DESCRIPTION TRIP POLE

S A B C POLE

S TRIP CIRCUIT DESCRIPTION CKT

NOTES:

ENCLOSURE: TYPE 1 MCB RATING: 175 A

MOUNTING: SURFACE WIRES: 4 MAINS RATING: 250 A

SUPPLY FROM: DP1 PHASES: 3 MAINS TYPE:

LOCATION: BOILER ROOM 119-2 VOLTS: 480/277 Wye A.I.C. RATING:

BRANCH PANEL: 02-DP3

NOTES:

TOTAL CONN. CURRENT: 25 A

TOTAL CONN. LOAD: 21034 VA

PANEL TOTALS

LEGEND:

TOTAL AMPS: 25 A 25 A 25 A

TOTAL LOAD: 7049 VA 6966 VA 7019 VA

41 42 39 40 37 38 35 36 33 34 31 32

29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30

27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28

25 -- -- -- 2106 VA 0 VA 1 20 A SPARE 26

23 -- -- -- 2106 VA 0 VA 1 20 A SPARE 24

21 2-R-EF-004 20 A 3 2106 VA 0 VA 1 20 A SPARE 22

19 -- -- -- 942 VA 942 VA -- -- -- 20

17 -- -- -- 942 VA 942 VA -- -- -- 18

15 2-R-EF-001 20 A 3 942 VA 942 VA 3 20 A 2-R-EF-002 16

13 -- -- -- 1178 VA 1178 VA -- -- -- 14

11 -- -- -- 1178 VA 1178 VA -- -- -- 12

9 2-200-MAU-001 20 A 3 1178 VA 1178 VA 3 20 A 2-200-MAU-002 10

7 BOILER ROOM HIGH BAY LED 20 A 1 693 VA 0 VA -- -- -- 8

5 BOILER ROOM HIGH BAY LED 20 A 1 819 VA 0 VA -- -- -- 6

3 BOILER ROOM HIGH BAY LED 20 A 1 756 VA 0 VA 3 20 A RM 201 COMM RACK 4

1 DA TANK AREA LTS 20 A 1 81 VA 80 VA 1 20 A RM 201 LTS 2

CKT CIRCUIT DESCRIPTION TRIP POLE

S A B C POLE

S TRIP CIRCUIT DESCRIPTION CKT

NOTES:

ENCLOSURE: TYPE 1 MCB RATING: 100 A

MOUNTING: SURFACE WIRES: 4 MAINS RATING: 100 A

SUPPLY FROM: DP1 PHASES: 3 MAINS TYPE:

LOCATION: EQUIPMENT ACCESS 200-2 VOLTS: 480/277 Wye A.I.C. RATING:

BRANCH PANEL: 02-DP4

Revisions: Date:

SHEET 2514/4/2024

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10 on e e igh th inc h = on e f oo t thr ee in ch es on e f oo t 6"

6" on e a nd on e h alf in ch es on e f oo t on e i nc h = on e f oo t

6"

6" thr ee qu ar ter s i nc h = on e f oo t on e h alf in ch on e f oo t thr ee ei gh ths in ch on e f oo t on e q ua rte r in ch on e f oo t

REV 0 - 100% BID SET 2024-02-23

FINAL BID SET REPLACE BOILER PLANT

325 EAST "H" STREET

IRON MOUNTAIN, MI 49801

585-21-115

2024-02-23

EP603

ELECTRICAL POWER PANEL

SCHEDULES 2

KRK KRK

PARTIALLY SPRINKLERED

NOTES:

TOTAL CONN. CURRENT: 198 A

TOTAL CONN. LOAD: 71458 VA

PANEL TOTALS

LEGEND:

TOTAL AMPS: 187 A 212 A 207 A

TOTAL LOAD: 22393 VA 25125 VA 24485 VA

41 42 39 40 37 38 35 36 33 34 31 32 29 30

27 -- -- -- 6808 VA 28

25 -- -- -- 7027 VA 5992 VA -- -- -- 26

23 02-PP4 100 A 3 6628 VA 6086 VA -- -- -- 24

21 -- -- -- 4104 VA 6417 VA 3 100 A 02-PP5 22

19 -- -- -- 4814 VA 20

17 02-PP3 100 A 3 4659 VA 18

15 3140 VA -- -- -- 16

13 2760 VA -- -- -- 14

11 -- -- -- 3848 VA 2588 VA 3 100 A 02-PP2 12

9 2-EXT-CU-003 50 A 2 3848 VA 10

7 2-200-UH-001, 002, 003 20 A 1 900 VA 8

5 2-200-CF-001 10 A 1 768 VA 270 VA -- -- -- 6

3 RM 120A RCPT 20 A 1 900 VA 270 VA 2 20 A FUEL TANK LIGHTS 4

1 RM 120B RCPT 20 A 1 720 VA 768 VA 1 10 A 2-200-CF-002 2

CKT CIRCUIT DESCRIPTION TRIP POLE

S A B C POLE

S TRIP CIRCUIT DESCRIPTION CKT

NOTES:

ENCLOSURE: TYPE 1 MCB RATING: 200 A

MOUNTING: RECESSED WIRES: 4 MAINS RATING: 400 A

SUPPLY FROM: PHASES: 3 MAINS TYPE:

LOCATION: ELECTRICAL ROOM 120A-2 VOLTS: 120/208 Wye A.I.C. RATING:

BRANCH PANEL: 02-PP1

NOTES:

TOTAL CONN. CURRENT: 23 A

TOTAL CONN. LOAD: 8128 VA

PANEL TOTALS

LEGEND:

TOTAL AMPS: 22 A 23 A 26 A

TOTAL LOAD: 2588 VA 2760 VA 3140 VA

41 42 39 40 37 38 35 36 33 34 31 32

29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30

27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28

25 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 26

23 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 24

21 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 22

19 CONTINUOUS GAS ANALYZER 3 30 A 1 1500 VA 0 VA 1 20 A SPARE 20

17 CONTINUOUS GAS ANALYZER 2 30 A 1 1500 VA 0 VA -- -- -- 18

15 CONTINUOUS GAS ANALYZER 1 30 A 1 1500 VA 0 VA -- -- -- 16

13 2-119-CP-005 20 A 1 180 VA 0 VA 3 30 A SPARE 14

11 -- -- -- 360 VA 200 VA 1 20 A 2-119-CP-009 12

9 -- -- -- 360 VA 180 VA 1 20 A 2-119-CP-006 10

7 RM 119 3P RCPT 30 A 3 360 VA 360 VA -- -- -- 8

5 RM 119 CNTRLN RCPT 20 A 1 720 VA 360 VA -- -- -- 6

3 RM 119 RCPT EAST 20 A 1 360 VA 360 VA 3 30 A RM 119 3P RCPT 4

1 2-100-TK-004 (WATER SOFTENER) 20 A 1 10 VA 180 VA 1 20 A RO CONTROL RECEPTACLE 2

CKT CIRCUIT DESCRIPTION TRIP POLE

S A B C POLE

S TRIP CIRCUIT DESCRIPTION CKT

NOTES:

ENCLOSURE: Type 1 MCB RATING: 100 A

MOUNTING: SURFACE WIRES: 4 MAINS RATING: 100 A

SUPPLY FROM: 02-PP1 PHASES: 3 MAINS TYPE:

LOCATION: ELECTRICAL ROOM 120A-2 VOLTS: 120/208 Wye A.I.C. RATING:

BRANCH PANEL: 02-PP2

NOTES:

TOTAL CONN. CURRENT: 38 A

TOTAL CONN. LOAD: 13536 VA

PANEL TOTALS

LEGEND:

TOTAL AMPS: 40 A 41 A 34 A

TOTAL LOAD: 4659 VA 4814 VA 4104 VA

41 42 39 40 37 38 35 36 33 34 31 32

29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30

27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28

25 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 26

23 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 24

21 MED GAS MONITOR 20 A 1 210 VA 115 VA 1 20 A CO MONITOR 22

19 RM 129 RECPT 20 A 1 720 VA 180 VA 1 20 A RM 003 RCPT 20

17 RM 130 RECPT SOUTH 20 A 1 360 VA 360 VA 1 20 A RM 130 RECPT SOUTH 18

15 -- -- -- 1789 VA 360 VA 1 20 A RM 130 RECPT WEST 16

13 2-EXT-CU-001 25 A 2 1789 VA 360 VA 1 20 A RM 130 RECPT WEST 14

11 RM 129 RECPT 20 A 1 1080 VA 360 VA 1 20 A RM 130 RECPT SOUTH 12

9 RM 003 SUMP PMP 20 A 1 180 VA 1080 VA 1 20 A FA CONTROL PANEL 10

7 RM 130 RECPT EAST 20 A 1 540 VA 1260 VA 1 20 A SEWAGE PUMP PMP-1 8

5 RM 128 RCPT CHEM FD PMP 20 A 1 1080 VA 864 VA 1 20 A RM 128 RCPT CHEM FD PMP 6

3 RM 130 RECPT SOUTH 20 A 1 720 VA 360 VA 1 20 A RM 130 RECPT WEST 4

1 GD-1 20 A 1 0 VA 0 VA 1 20 A GD-4 2

CKT CIRCUIT DESCRIPTION TRIP POLE

S A B C POLE

S TRIP CIRCUIT DESCRIPTION CKT

NOTES:

ENCLOSURE: Type 1 MCB RATING: 100 A

MOUNTING: SURFACE WIRES: 4 MAINS RATING: 100 A

SUPPLY FROM: 02-PP1 PHASES: 3 MAINS TYPE:

LOCATION: BOILER ROOM 119-2 VOLTS: 120/208 Wye A.I.C. RATING:

BRANCH PANEL: 02-PP3

NOTES:

TOTAL CONN. CURRENT: 57 A

TOTAL CONN. LOAD: 20463 VA

PANEL TOTALS

LEGEND:

TOTAL AMPS: 55 A 59 A 57 A

TOTAL LOAD: 6628 VA 7027 VA 6808 VA

41 42 39 40 37 38 35 36 33 34 31 32

29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30

27 SPARE 20 A 1 0 VA 0 VA -- -- -- 28

25 SPARE 20 A 1 0 VA 0 VA -- -- -- 26

23 SPARE 20 A 1 0 VA 0 VA 3 20 A SPARE 24

21 -- -- -- 2667 VA 1273 VA -- -- -- 22

19 -- -- -- 2667 VA 1273 VA -- -- -- 20

17 RM 124 ELEC RANGE 50 A 3 2667 VA 1273 VA 3 20 A DUPLEX FUEL OIL PUMP 18

15 RM 119,121,122,123,126 RECPT 20 A 1 1260 VA 0 VA 1 20 A SPARE 16

13 RM 119 RCPT 20 A 1 540 VA 0 VA 1 20 A SPARE 14

11 RM 124 RCPT 20 A 1 540 VA 360 VA 1 20 A RM 124 CNTRTOP RECPT 12

9 RM 124 RCPT 20 A 1 540 VA 1080 VA 1 20 A RM 125,127 RCPT 10

7 RM 124 CNTRTOP RECPT 20 A 1 360 VA 1789 VA -- -- -- 8

5 RM 124 FRIDGE 20 A 1 180 VA 1789 VA 2 25 A 2-EXT-CU-002 6

3 RM 124 COUNTER LTS 20 A 1 12 VA 195 VA 1 20 A RM 124 WTR FNTN 4

1 GD-2 20 A 1 0 VA 0 VA 1 20 A GD-3 2

CKT CIRCUIT DESCRIPTION TRIP POLE

S A B C POLE

S TRIP CIRCUIT DESCRIPTION CKT

NOTES:

ENCLOSURE: TYPE 1 MCB RATING: 100 A

MOUNTING: RECESSED WIRES: 4 MAINS RATING: 100 A

SUPPLY FROM: 02-PP1 PHASES: 3 MAINS TYPE:

LOCATION: BOILER ROOM 119-2 VOLTS: 120/208 Wye A.I.C. RATING:

BRANCH PANEL: 02-PP4

NOTES:

TOTAL CONN. CURRENT: 51 A

TOTAL CONN. LOAD: 18304 VA

PANEL TOTALS

LEGEND:

TOTAL AMPS: 54 A 51 A 50 A

TOTAL LOAD: 6417 VA 6086 VA 5992 VA

41 42 39 40 37 38 35 36 33 34 31 32

29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30

27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28

25 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 26

23 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 24

21 -- -- -- 0 VA 0 VA 1 20 A SPARE 22

19 SPARE 20 A 2 0 VA 0 VA -- -- -- 20

17 -- -- -- 0 VA 0 VA -- -- -- 18

15 SPARE 30 A 2 0 VA 0 VA 3 20 A SPARE 16

13 -- -- -- 875 VA 180 VA 1 20 A 2-200-CP-006A 14

11 2-200-PMP-001 20 A 2 875 VA 3633 VA -- -- -- 12

9 -- -- -- 1248 VA 3633 VA -- -- -- 10

7 ELECTRIC CHAIN HOIST 30 A 2 1248 VA 3633 VA 3 20 A 2-200-CA-001 8

5 ROOF RCPT 20 A 1 720 VA 875 VA -- -- -- 6

3 RM 201 RCPT 20 A 1 540 VA 875 VA 2 20 A 2-200-PMP-002 4

1 RM 201 RCPT 20 A 1 540 VA 180 VA 1 20 A RM 200 RCPT 2

CKT CIRCUIT DESCRIPTION TRIP POLE

S A B C POLE

S TRIP CIRCUIT DESCRIPTION CKT

NOTES:

ENCLOSURE: TYPE 1 MCB RATING: 100 A

MOUNTING: SURFACE WIRES: 4 MAINS RATING: 100 A

SUPPLY FROM: 02-PP1 PHASES: 3 MAINS TYPE:

LOCATION: EQUIPMENT ACCESS 200-2 VOLTS: 120/208 Wye A.I.C. RATING:

BRANCH PANEL: 02-PP5

Revisions: Date:

SHEET 2524/4/2024

02-DP1 CABLE AND CONDUIT SCHEDULE

LOAD NAME PANEL CIRCUIT NUMBER WIRE SIZE # OF HOT # OF NEUTRAL # OF GROUND CONDUIT # OF RUNS

EXTERIOR LIGHTING 02-DP1 1 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

RM 100 101 EXIT SIGNS 02-DP1 2 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

ELECTRIC WATER HEATER 02-DP1 5 1-#6 1-#6 1-#10 1 1 1 3/4" RMC 1

GENERATOR RM LIGHTS 02-DP1 7 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

ELEC RM LIGHTS 02-DP1 8 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

02-DP4 02-DP1 9 11 13 3-#1 1-#1 1-#6 3 1 1 1-1/2" RMC 1

02-DP2 02-DP1 14 16 18 3-#1 1-#1 1-#6 3 1 1 1-1/2" RMC 1

02-DP3 02-DP1 15 17 19 3-#4/0 1-#4/0 1-#4 3 1 1 2-1/2" RMC 1

LIFT STATION 02-DP1 20 22 24 3-#12 1-#12 3 0 1 3/4" RMC 1

02-DP2 CABLE AND CONDUIT SCHEDULE

LOAD NAME PANEL CIRCUIT NUMBER WIRE SIZE # OF HOT # OF NEUTRAL # OF GROUND CONDUIT # OF RUNS

PMP-004 02-DP2 1 3 5 3-#12 1-#12 3 0 1 3/4" RMC 1

PMP-003 02-DP2 2 4 6 3-#12 1-#12 3 0 1 3/4" RMC 1

PMP-005 02-DP2 7 9 11 3-#12 1-#12 3 0 1 3/4" RMC 1

PMP-002 02-DP2 8 10 12 3-#12 1-#12 3 0 1 3/4" RMC 1

PMP-001 02-DP2 13 15 17 3-#12 1-#12 3 0 1 3/4" RMC 1

RO SYSTEM POWER 02-DP2 14 16 18 3-#12 1-#12 3 0 1 3/4" RMC 1

LTS UNDER BOILER PLATFORMS 02-DP2 19 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

BRK RM 102 LTS 02-DP2 20 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

RM 103 104 LTS 02-DP2 21 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

RM 106 107 108 LTS 02-DP2 22 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

RM 103 105 LTS 02-DP2 23 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

LIGHTING OUTSIDE TOILETS 02-DP2 24 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

02-DP3 CABLE AND CONDUIT SCHEDULE

LOAD NAME PANEL CIRCUIT NUMBER WIRE SIZE # OF HOT # OF NEUTRAL # OF GROUND CONDUIT # OF RUNS

CONTROL RM 111 EXIT SIGNS 02-DP3 1 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

RM 109 110 111 LTS 02-DP3 2 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

RM 109 110 111 LTS 02-DP3 3 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

SUPPLY FAN 1 02-DP3 4 6 8 3-#12 1-#12 3 0 1 3/4" RMC 1

SUPPLY FAN 2 02-DP3 5 7 9 3-#12 1-#12 3 0 1 3/4" RMC 1

BOILER 1 02-DP3 10 12 14 3-#4 1-#4 1-#8 3 1 1 1-1/2" RMC 1

BOILER 2 02-DP3 11 13 15 3-#4 1-#4 1-#8 3 1 1 1-1/2" RMC 1

BOILER 3 02-DP3 16 18 20 3-#4 1-#4 1-#8 3 1 1 1-1/2" RMC 1

PROPANE RM EXHAUST FAN 02-DP3 17 19 21 3-#12 1-#12 3 0 1 3/4" RMC 1

PROPANE ROOM LIGHT 02-DP3 22 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

BASEMENT 003-2 LIGHT 02-DP3 23 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

GR FL EM WALL LTS 02-DP3 24 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

BASEMENT EM WALL LIGHTS 02-DP3 25 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

MEZZ EM WALL LTS 02-DP3 26 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

BOILER EMERGENCY POWER POINT 02-DP3 27, 29, 31 3-#4 1-#4 1-#8 3 1 1 1-1/2" RMC 1

02-DP4 CABLE AND CONDUIT SCHEDULE

LOAD NAME PANEL CIRCUIT NUMBER WIRE SIZE # OF HOT # OF NEUTRAL # OF GROUND CONDUIT # OF RUNS

DA TANK LIGHTING 02-DP4 1 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

CONTROL IT RM LIGHTING 02-DP4 2 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

BOILER ROOM HIGH BAY LED 02-DP4 3 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

COMMS RACK 02-DP4 4 6 8 3-#12 1-#12 3 0 1 3/4" RMC 1

BOILER ROOM HIGH BAY LED 02-DP4 5 1-#10 1-#10 1-#10 1 1 1 3/4" RMC 1

BOILER ROOM HIGH BAY LED 02-DP4 7 1-#10 1-#10 1-#10 1 1 1 3/4" RMC 1

MAU-001 02-DP4 9 11 13 3-#12 1-#12 3 0 1 3/4" RMC 1

MAU-002 02-DP4 10 12 14 3-#12 1-#12 3 0 1 3/4" RMC 1

2-R-EF-001 02-DP4 15 17 19 3-#12 1-#12 3 0 1 3/4" RMC 1

2-R-EF-002 02-DP4 16 18 20 3-#12 1-#12 3 0 1 3/4" RMC 1

2-R-EF-004 02-DP4 21 23 25 3-#12 1-#12 3 0 1 3/4" RMC 1

02-PP1 CABLE AND CONDUIT SCHEDULE

LOAD NAME PANEL CIRCUIT NUMBER WIRE SIZE # OF HOT # OF NEUTRAL # OF GROUND CONDUIT # OF RUNS

GEN RM RECEPTACLES 02-PP1 1 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

2-200-CF-002 02-PP1 2 1-#12 1-#12 1-#14 1 1 1 3/4" RMC 1

RECEPTACLE 02-PP1 3 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

FUEL TANK LIGHTS 02-PP1 4 6 2-#12 1-#12 2 0 1 3/4" RMC 1

2-200-CF-001 02-PP1 5 1-#12 1-#12 1-#14 1 1 1 3/4" RMC 1

2-200-UH-001 002 003 02-PP1 7 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

2-EXT-CU-003 02-PP1 9 11 2-#6 1-#6 2 0 1 3/4" RMC 1

02-PP2 02-PP1 12 14 16 3-#1 1-#1 1-#4 3 1 1 1-1/2" RMC 1

02-PP3 02-PP1 17 19 21 3-#1 1-#1 1-#4 3 1 1 1-1/2" RMC 1

02-PP5 02-PP1 22 24 26 3-#1 1-#1 1-#4 3 1 1 1-1/2" RMC 1

02-PP4 02-PP1 23 25 27 3-#1 1-#1 1-#4 3 1 1 1-1/2" RMC 1

02-PP2 CABLE AND CONDUIT SCHEDULE

LOAD NAME PANEL CIRCUIT NUMBER WIRE SIZE # OF HOT # OF NEUTRAL # OF GROUND CONDUIT # OF RUNS

2-100-TK-004 02-PP2 1 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

RO CONTROL RECEPTACLE 02-PP2 2 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

BOILER RM 100 REC EAST WALL 02-PP2 3 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

BOILER RM 100 3P REC 02-PP2 4 6 8 3-#8 1-#8 3 0 1 3/4" RMC 1

BOILER RM 100 REC CENTERLINE 02-PP2 5 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

BOILER RM 100 3P REC 02-PP2 7 9 11 3-#8 1-#8 3 0 1 3/4" RMC 1

02-PP3 CABLE AND CONDUIT SCHEDULE

LOAD NAME PANEL CIRCUIT NUMBER WIRE SIZE # OF HOT # OF NEUTRAL # OF GROUND CONDUIT # OF RUNS

GARAGE DOOR 1 02-PP3 1 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

GARAGE DOOR 4 02-PP3 2 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

RECEPTACLES WEST WALL 02-PP3 3 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

CONTROL RM 111 REC 02-PP3 4 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

CHEMICAL FEED PUMPS 02-PP3 5 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

CHEMICAL FEED PUMPS 02-PP3 6 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

RECEPTACLE 02-PP3 7 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

SEWAGE PUMP PMP-1 02-PP3 8 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

RECEPTACLE 02-PP3 9 1-#10 1-#10 1-#10 1 1 1 3/4" RMC 1

FA CONTROL PANEL 02-PP3 10 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

SUPERVISOR RM 110 REC 02-PP3 11 1-#10 1-#10 1-#10 1 1 1 3/4" RMC 1

CONTROL RM 111 REC 02-PP3 12 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

2-EXT-OU-001 02-PP3 13 15 2-#10 1-#6 2 0 1 3/4" RMC 1

02-PP4 CABLE AND CONDUIT SCHEDULE

LOAD NAME PANEL CIRCUIT NUMBER WIRE SIZE # OF HOT # OF NEUTRAL # OF GROUND CONDUIT # OF RUNS

GARAGE DOOR 2 02-PP4 1 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

GARAGE DOOR 3 02-PP4 2 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

BRK RM 102 COUNTER LTS 02-PP4 3 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

WATER FOUNTAIN/BOTTLE FILL 02-PP4 4 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

2-EXT-OU-002 02-PP4 6 8 2-#12 1-#10 2 0 1 3/4" RMC 1

BRK RM 102 COUNTERTOP REC 02-PP4 7 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

BRK RM 102 REFRIGERATOR 02-PP4 9 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

RM 103 105 RECEPTACLE 02-PP4 10 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

BREAKROOM RECEPTACLES 02-PP4 11 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

BOILER RM 100 REC 02-PP4 13 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

RM 104 106 107 108 REC 02-PP4 15 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

BREAKROOM RECEPTACLES 02-PP4 16 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

ELECTRIC RANGE 02-PP4 17 19 21 3-#8 1-#10 3 0 1 3/4" RMC 1

DUPLEX FUEL OIL PUMP 02-PP4 18 20 22 3-#12 1-#12 3 0 1 3/4" RMC 1

02-PP5 CABLE AND CONDUIT SCHEDULE

LOAD NAME PANEL CIRCUIT NUMBER WIRE SIZE # OF HOT # OF NEUTRAL # OF GROUND CONDUIT # OF RUNS

RM 201 REC 02-PP5 1 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

RM 201 REC 02-PP5 3 1-#12 1-#12 1-#12 1 1 1 3/4" RMC 1

HOT WATER CIRC PUMP 02-PP5 4 6 2-#12 1-#12 2 0 1 3/4" RMC 1

RECEPTACLE 02-PP5 5 1-#10 1-#10 1-#10 1 1 1 3/4" RMC 1

ELECTRIC CHAIN HOIST 02-PP5 7 9 2-#10 1-#10 2 0 1 3/4" RMC 1

AIR COMPRESSOR 02-PP5 8 10 12 3-#10 1-#10 3 0 1 3/4" RMC 1

HOT WATER CIRC PUMP 02-PP5 11 13 2-#12 1-#12 2 0 1 3/4" RMC 1

GENERATOR CABLE AND CONDUIT SCHEDULE

LOAD NAME PANEL CIRCUIT NUMBER WIRE SIZE # OF HOT # OF NEUTRAL # OF GROUND CONDUIT # OF RUNS

2-120B-480E-SWBD-001 GENERATOR 3-#250 1-#250 1-#3 6 2 2 2-1/2" RMC 2

NORMAL POWER CABLE AND CONDUIT SCHEDULE

LOAD NAME PANEL CIRCUIT NUMBER WIRE SIZE # OF HOT # OF NEUTRAL # OF GROUND CONDUIT # OF RUNS

2-120A-480N-SWBD-001 NORMAL SWITCHGEAR 3-#250 1-#250 1-#3 6 2 2 2-1/2" RMC 2

PANEL C (EXISTING) CABLE AND CONDUIT SCHEDULE

LOAD NAME PANEL CIRCUIT NUMBER WIRE SIZE # OF HOT # OF NEUTRAL # OF GROUND CONDUIT # OF RUNS

EMERGECNY FUEL OIL SHUT OFF PANEL C 14 16 18 3-#12 1-#12 3 0 1 3/4" RMC 1

2-202-UH-001 -002 -003 PANEL C 20 1-#10 1-#10 1-#10 1 1 1 3/4" RMC 1

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10 on e e igh th inc h = on e f oo t thr ee in ch es on e f oo t 6"

6" on e a nd on e h alf in ch es on e f oo t on e i nc h = on e f oo t

6"

6" thr ee qu ar ter s i nc h = on e f oo t on e h alf in ch on e f oo t thr ee ei gh ths in ch on e f oo t on e q ua rte r in ch on e f oo t

REV 0 - 100% BID SET 2024-02-23

FINAL BID SET REPLACE BOILER PLANT

325 EAST "H" STREET

IRON MOUNTAIN, MI 49801

585-21-115

2024-02-23

EP604

ELECTRICAL POWER CABLE AND

CONDUIT SCHEDULES 2

KRK LAJ

PARTIALLY SPRINKLERED

Revisions: Date:

SHEET 2534/4/2024

GMC KRL

FIBEROPTICS LINE = FO

COMMUNICATION SYMBOLS

OUTLET DATA ONLY

2 = DUAL PORT

OUTLET; LETTER INDICATES AS FOLLOWS:

A = AUDIO V = VIDEO I = INTERCOM

1PH SINGLE-PHASE

1P SINGLE POLE

2/C TWO-CONDUCTOR

3/C THREE-CONDUCTOR

3PH THREE-PHASE

4/C FOUR-CONDUCTOR

4W FOUR-WIRE

A/C UNIT AIR CONDITIONING UNIT

A/E ARCHITECT/ENGINEER

AAP ALARM ANNUNCIATOR PANEL

AC ALTERNATING CURRENT OR ARMORED CABLE

ACC ACCESSIBLE

ADDL ADDITIONAL

ADJ ADJACENT, ADJOINING

ADO AUTOMATIC DOOR OPENER

AFC ABOVE FINISHED COUNTER

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHJ AUTHORITY HAVING JURISDICTION

ALT ALTERNATE

AMB OR A AMBIENT

ARCH ARCHITECT

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AV AUDIO VISUAL

BAT BATTERY

BC BARE COPPER

BD BOARD

BFF BELOW FINISH FLOOR

BLDG BUILDING

BPIP BOILER PLANT INSTRUMENTATION PANEL

BYP BY PASS

C CONDUIT

CAB CABINET

CALC CALCULATE

CAP CAPACITY

CAT CATALOG

CATV COMMUNITY ANTENNA TELEVISION

CCR CONTROL CONTACTOR

CCTV CLOSED CIRCUIT TELEVISION

CD CONSTRUCTION DOCUMENTS

CF CONTRACTOR FURNISHED

CF/CI CONTRACTOR FURNISHED/CONTRACTOR INSTALLED

CF/OI CONTRACTOR FURNISHED/OWNER INSTALLED

CFE CONTRACTOR FURNISHED EQUIPMENT

CLG CEILING

CMU CONCRETE MASONRY UNIT

COAX COAX CABLE

COMM COMMUNICATION

COMPT COMPARTMENT

CONC CONCRETE

CONT CONTINUE

CONTR CONTRACTOR

COORD COORDINATE

CTV CABLE TELEVISION

CU COPPER

CU FT CUBIC FEET

CUR CURRENT

DB DECIBEL OR DIRECT BURIAL

DC DIRECT CURRENT

DEG C DEGREES CELSIUS

DEG F DEGREES FAHRENHEIT

DEMO DEMOLITION

DIAG DIAGRAM

DISTR DISTRIBUTION

DN DOWN

DRSW DOOR SWITCH

DWG DRAWING

EC EMPTY CONDUIT

EG EQUIPMENT GROUND

EL ELEVATION

ELEC ELECTRIC OR ELECTRICAL

ELEV ELEVATOR

EMER EMERGENCY

EMI ELECTROMAGNETIC INTERFERENCE

EMT ELECTRICAL METALLIC TUBING

ENCL ENCLOSURE

EPO EMERGENCY POWER OFF

ESMT EASEMENT

EXIST EXISTING

FLEX FLEXIBLE METALLIC CONDUIT

FO FIBER OPTIC CABLE

FOUTT TELEPHONE FLOOR OUTLET

FP FIRE PROTECTION

FT FEET OR FOOT

FU SW FUSED SWITCH

G OR GND GROUND OR GENERATOR

GEN GENERATOR

GTB GROUND TERMINAL BOX

HOA HAND-OFF-AUTOMATIC

HT HEIGHT

HZ HERTZ

IMC INTERMEDIATE METAL CONDUIT

IR INFRARED

J-BOX JUNCTION BOX

LF LINEAR FEET (FOOT)

LTNG LIGHTNING

LV LOW VOLTAGE

MATV MASTER ANTENNA TELEVISION SYSTEM

MAX MAXIMUM

MECH MECHANICAL

MH MANHOLE

MIN MINIMUM

MT MOUNT

MTD MOUNTED

MTG MOUNTING

NA NOT APPLICABLE

NEC NATIONAL ELECTRICAL CODE

NEUT OR N NEUTRAL

NIC NOT IN CONTRACT

NS NO SCALE

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

P POLE

PA PUBLIC ADDRESS

PB PANELBOARD, PULL BOX, OR PUSHBUTTON

PBPU PREFABRICATED BEDSIDE PATIENT UNIT

PED PEDESTAL

PEND PENDANT

PF POWER FACTOR

PH PHASE

PNL PANEL

PVC POLYVINYL CHLORIDE (PLASTIC)

PWR POWER

RCP REFLECTED CEILING PLAN

REC RECESSED

RECPT RECEPTACLE

RGS RIGID GALVANIZED STEEL

RM ROOM

REQD REQUIRED

SF SQUARE FOOT (FEET)

SHT SHEET

SI INTERNATIONAL SYSTEM OF UNITS

SPEC SPECIFICATION

SURF SURFACE

SW SWITCH

TEL TELEPHONE

TP TWISTED PAIR

TPS TWISTED PAIR SHIELDED

TTB TELEPHONE TERMINAL BOARD

TV TELEVISION

TYP TYPICAL

UFD UNDERFLOOR DUCT

UGND UNDERGROUND

UL UNDERWRITERS LABORATORY

UON UNLESS OTHERWISE NOTED

UPS UNINTERRUPTIBLE POWER SUPPLY

UTIL UTILITY

V VOLT

WP WEATHERPROOF

WAP WIRELESS ACCESS POINT

COMMUNICATION AND ELECTRONIC SAFETY AND SECURITY ABBREVIATIONS

APPLICABLE CODES

THE APPLICABLE MODEL CODES, STANDARDS AND REFERENCES DOCUMENTS

PERTINENT TO THE PROJECT ARE AS FOLLOWS:

· NFPA 101 LIFE SAFETY CODE (LATEST EDITION)

· NATIONAL ELECTRICAL CODE NFPA70 (LATEST EDITION)

· SEE PROJECT SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

1. VERIFY LOCATIONS WITH COR PRIOR TO ROUGHING IN THE INSTALLATION.

2. ALL WALL MOUNTED BACK BOXES TO A MINIMUM OF 18 INCHES ABOVE THE

FINISHED FLOOR UNLESS OTHERWISE SPECIFIED.

3. FOR SPACES WITH DROP CEILINGS, ALL DATA AND PHONE LINES SHALL BE

INSTALLED IN A MINIMUM 1" EMT CONDUIT RUN VERTICALLY IN THE WALLS

AND STUBBING ABOVE THE CEILING BY AT LEAST 1 INCH. INSTALL WITH A

PULL STRING.

4. ALL WIRING FOR COMMUNICATION DEVICES SHALL BE INSTALLED WITH A

PULL STRING.

5. USE EXISTING TIE-IN POINTS FOR WIRE TERMINATION.

6. ALL WIRING ABOVE SUSPENDED CEILING WILL BE SUSPENDED USING

APPROVED WIRE HANGERS OR BASKET CABLE TRAYS.

7. OUTLET BOXES SHALL BE THE SAME MINIMUM SIZE AS NEC STANDARD 6 IN x

6 IN x 2.5 IN THAT COULD CONTAIN DUAL DUPLEX ELECTRICAL OUTLETS.

8. OUTLET BOXES SHALL BE EQUIPPED WITH FULL COVERED WALL FACEPLATES

THAT SHALL COVER THE ENTIRE BOX WITHOUT TRIM RINGS ADDED, AND

SHALL EMPLOY TWO EACH MODULAR CATEGORY 6A (OR BETTER) RJ-45

JACKS FOR DATA. THE BOX SHALL ALSO PROVIDE SPACE FOR THE ADDITION

OF TWO ADDITIONAL CATEGORY 6A.

9. PLENUM/ CMP RATED WIRE OR CABLE SHALL BE PROVIDED IN ALL

AIR-HANDLING PLENUM LOCATIONS. NON-PLENUM/CM WIRE OR CABLE MAY

BE PROVIDED IN ALL OTHER AREAS.

GENERAL NOTES

FO

A

NETWORK EQUIPMENT, TYPE=X

R = TYPE 1 EQUIPMENT RACK

W = TYPE 4 WALL MOUNT

CONDUIT SYMBOLS

CONDUIT UP

CONDUIT DOWN

VERTICAL RISER

FL

RK

SECURITY SYMBOLS

ELECTRONIC LOCK

X

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL RK-RACK S-SURFACE FL-FLOOR W-WALL

T=TECHNOLOGY/TYPE (SPECIFIC TO DEVICE)

D-DOCUMENT IP-IP CAM IR-INFARED HD-HIGH DEFINITION

LETTER INDICATES AS FOLLOWS:

T M

T2

O-OUTDOOR R-ROOF REC-RECESSED G-GROUND

L#-LENS ANGLE VIEW M-MOTION DETECTOR PT-PAN/TILT

PTZ-PAN/TILT/ZOOM PZ-PAN/ZOOM T#-PANNING TRAVERSE ANGLE

T2=SECONDARY TECHNOLOGY

X=LEGEND REF

E - EXISTING

SECURITY ACCESS, VIDEO CAMERA WITH LENS, ANGLE OF VIEW ;

RF REPEATER OR ACCESS POINT; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK/TABLE F-FLUSH FL-FLOOR G-GROUND

H-HIDDEN M-MULLION O-OUTDOOR P-PEDESTAL RK-RACK

R-ROOF REC-RECESSED S-SURFACE W-WALL PL-POLE

T=TECHNOLOGY/TYPE

C-CELLULAR REPEATER PR-PHONE REPEATER RX-RECEIVER

TR-TRANSCEIVER TX-TRANSMITTER WAP-WIRELESS ACCESS POINT

WP-WIRELESS PROCESSOR REPEATER A-ANTENNA A-ANTENNA

T2=SECONDARY TECHNOLOGY

X=LEGEND REF

E-EXISTING VZ-VERIZON WIRELESS OD-OMNI-DIRECTIONAL

M T

T2 X

CARD ACCESS READER; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

B-BARCODE F-ELEVATOR FLOOR CALL H-HYBRID

M-MAG STRIP P-PROXIMITY D=DEADBOLT S-STRIKE

T-TOKEN L=LATCH SET

M

T

MOTION DETECTOR; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

D-DUAL TECHNOLOGY IR-INFRARED M-MICROWAVE U-ULTRASONIC

X-REQUEST-FOR-EXIT

M

T

SECURITY ACCESS, BUZZER. MTD 1'-6" [457mm] AFF UNLESS OTHERWISE NOTED

INTERCOM; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

M-MASTER S-SUBSTATION

M

T

GENERAL SYMBOLS

ROOM NAME AND NUMBER

DEMOLISH/REMOVE

A1

ROOM

2 OUTLET, COMBINATION TELEPHONE/DATA COMMUNICATION

2 = DUAL PORT (TYPE B FACEPLATE)

CARD READER WITH KEYPAD; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

M

AUDIO DEVICE; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

B-BELL C-CHIME H-HORN K-KLAXON

L-LISTEN-IN M-MICROPHONE S-SPEAKER Z-BUZZER

M

T

SECURITY SYMBOLS CONTINUED

MONITOR; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

D-DATA G-GRAPHIC M-MULTISCREEN V-VIDEO

M

T

PUSH BUTTON; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

B-BELL PUSH D-DURESS P-PANIC R-DOOR RELEASE

X-REQUEST-FOR-EXIT

M

T

VIDEO MOTION DETECTOR

CONTROL PANEL; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

B-BURGLAR D-DOOR F-FIRE P-PERIMETER

T

M

REV 0 - 100% BID SET 2024-02-23

REV 1 - FINAL BID SET 2024-04-04

COPPER COMMUNICATION LINE = CUCU

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

ELECTRICAL TELECOMMUNICATIONS

- NOTES AND LEGENDS

FINAL BID SET

PARTIALLY SPRINKLERED

REPLACE BOILER PLANT

325 EAST "H" STREET

IRON MOUNTAIN, MI 49801

2024-02-23

ET001

585-21-115

EMERGENCY PHONE

CARBON MONOXIDE DETECTOR

COMBUSTIBLE GAS DETECTOR

SHEET 2544/4/2024

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text

CO

GAS

UP

RK

GAS

A'

B'

D'

C'

2.8'

E'

RK-001-2

EMERGENCY

PHONE (EP3)

SEE 3/ET503 FOR

DETAIL

BASEMENT HALLWAY

002-2

STORAGE

RM/TUNNEL ACCESS

001-2

1 2 3

A

B

D

F

H

WAP

(EXT)

D002

18" WIDE CABLE TRAY (EXISTING)

PACS PANEL (NEW)

TO BUILDING 1

MOUNT 1' AFF

BASEMENT

003-2

3'

D003

4" EMT COND.TO NEW BOILER

TO EXISTING BOILER

EXISTING

CAMERA

CAMERA 9

UP TO GROUND FLOOR

(SEE ET121)

ALL EQUIPMENT IN ROOM

IS EXISTING UNLESS NOTED

SEE EI121 AND EI141 FOR

LOCATIONS OF REMAINING

GAS DETECTION SYSTEM DEVICES

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10 on e e igh th inc h = on e f oo t thr ee in ch es on e f oo t 6"

6" on e a nd on e h alf in ch es on e f oo t on e i nc h = on e f oo t

6"

6" thr ee qu ar ter s i nc h = on e f oo t on e h alf in ch on e f oo t thr ee ei gh ths in ch on e f oo t on e q ua rte r in ch on e f oo t

REV 0 - 100% BID SET 2024-02-23

FINAL BID SET REPLACE BOILER PLANT

325 EAST "H" STREET

IRON MOUNTAIN, MI 49801

585-21-115

2024-02-23

ET101

ELECTRICAL TELECOMMUNICATIONS

PLAN - BASEMENT LEVEL 2

GMC KRL

PARTIALLY SPRINKLERED

SCALE: 3/16" = 1'-0"1 ELECTRICAL TELECOMMUNICATIONS - BASEMENT LEVEL

KEYPLAN

N AREA OF WORK

12 16

4. SEE ET603 FOR CAMERA SCHEDULE.

3.

WORK OUTSIDE THE DESIGNATED PHASE AREA MAY BE REQUIRED TO COMPLETE

PHASED WORK. CONTRACTOR IS TO COORDINATE ALL WORK WITH COR AND BETWEEN

ANY AND ALL SUBCONTRACTORS TO ENSURE CONTINUED OPERATIONS AND INTENT

SHOWN THROUGHOUT THIS DRAWING SET.

2. PHASING IS DESIGNATED THROUGHOUT THE DRAWING SET VIA

1. SEE ET001 FOR ET-SERIES NOTES AND LEGENDS.

GENERAL NOTES

N

Revisions: Date:

SHEET 2554/4/2024

MF

AC

U

MFACP

F F

1' 2'

A'

B'

G'

F'

D'

C'

2.8'

E'

NETWORK

OUTLETS FOR

ATS REPORTING.

WAP

PACS PANEL

EMERGENCY

PHONE (EP1)

SEE 3/ET503

FOR DETAIL

WAP

PACS PANEL

EMERGENCY

PHONE (EP2)

SEE 3/ET503

FOR DETAIL

BOILER ROOM

119-2

CONTROL ROOM

130-2

SUPERVISOR

129-2

CHEM FEED

128-2

GENERATOR ROOM

120B-2

JANITOR

121-2

TOILET

122-2

TOILET

123-2

BREAK ROOM

124-2

LOCKER ROOM

125-2

SHOWER AREA

126-2

CHANGING AREA

127-2

PROPANE

131-2

CAMERA 3

CAMERA 8

CAMERA 1

CAMERA 2

1 2 3

A

B

D

F

H

M

D130B

D119A D120B

W

IP

W

IP

W

IP

W

IP

W

IP

W

IP

SECURITY SCREEN

D119F

PARALLEL

SWITCHING GEAR

101B-2

BOILER ROOM

101-2

D119G

CAMERA 8

TELECOMMUNICATION CONDUIT LOCATED

BELOW CABLE TRAY

3'

2-119-CP-001

2-119-CP-002

2-119-CP-003

W

IP

PHONE HORN/ LIGHT

IP OUTLET

CAMERA 6

CAMERA 4

24"x24"x6" MARSHALLING BOX 2" EMT COND 12"x12"x6"

J-BOX

24"x24"x6"

MARSHALLING BOX

4" EMT COND

4" EMT COND

2" EMT COND

12"x12"x6"

MARSHALLING BOX

4" EMT COND

24"X24"X6"

MARSHALLING BOX

DOWN TO BASEMENT

(SEE ET101)

24"x24"x6"

MARSHALLING BOX

MASTER

CONTROLLER

CRT-6

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10 on e e igh th inc h = on e f oo t thr ee in ch es on e f oo t 6"

6" on e a nd on e h alf in ch es on e f oo t on e i nc h = on e f oo t

6"

6" thr ee qu ar ter s i nc h = on e f oo t on e h alf in ch on e f oo t thr ee ei gh ths in ch on e f oo t on e q ua rte r in ch on e f oo t

REV 0 - 100% BID SET 2024-02-23

FINAL BID SET REPLACE BOILER PLANT

325 EAST "H" STREET

IRON MOUNTAIN, MI 49801

585-21-115

2024-02-23

ET121

ELECTRICAL TELECOMMUNICATIONS

PLAN - GROUND FLOOR LEVEL 2

GMC KRL

PARTIALLY SPRINKLERED

SCALE: 3/16" = 1'-0"1 ELECTRICAL TELECOMMUNICATIONS FLOOR PLAN - GROUND FLOOR LEVEL N

5. ONLY CONDUIT SIZED ABOVE 2" DIAMETER ARE SHOWN ON DRAWINGS.

4. MOUNT ALL CONDUITS AND MARSHALLING BOXES 9'-8" AFF UNLESS

OTHERWISE NOTED.

3.

WORK OUTSIDE THE DESIGNATED PHASE AREA MAY BE REQUIRED TO COMPLETE

PHASED WORK. CONTRACTOR IS TO COORDINATE ALL WORK WITH COR AND BETWEEN

ANY AND ALL SUBCONTRACTORS TO ENSURE CONTINUED OPERATIONS AND INTENT

SHOWN THROUGHOUT THIS DRAWING SET.

2. PHASING IS DESIGNATED THROUGHOUT THE DRAWING SET VIA

1. SEE ET001 FOR ET-SERIES NOTES AND LEGENDS.

GENERAL NOTES

KEYPLAN

N AREA OF WORK

12 16

Revisions: Date:

SHEET 2564/4/2024

RK

1' 2'

A'

B'

G'

F'

D'

C'

2.8'

E'

OPEN TO BELOW

EQUIPMENT ACCESS

200-2

CONTROL IT

201-2

A

B

D

F

H

M

W

IP

3'

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10 on e e igh th inc h = on e f oo t thr ee in ch es on e f oo t 6"

6" on e a nd on e h alf in ch es on e f oo t on e i nc h = on e f oo t

6"

6" thr ee qu ar ter s i nc h = on e f oo t on e h alf in ch on e f oo t thr ee ei gh ths in ch on e f oo t on e q ua rte r in ch on e f oo t

REV 0 - 100% BID SET 2024-02-23

FINAL BID SET REPLACE BOILER PLANT

325 EAST "H" STREET

IRON MOUNTAIN, MI 49801

585-21-115

2024-02-23

ET141

ELECTRICAL TELECOMMUNICATIONS

PLAN - MEZZANINE LEVEL 2

KRK KRL

PARTIALLY SPRINKLERED

KEYPLAN

N AREA OF WORK

12 16

3.

WORK OUTSIDE THE DESIGNATED PHASE AREA MAY BE REQUIRED TO COMPLETE

PHASED WORK. CONTRACTOR IS TO COORDINATE ALL WORK WITH COR AND BETWEEN

ANY AND ALL SUBCONTRACTORS TO ENSURE CONTINUED OPERATIONS AND INTENT

SHOWN THROUGHOUT THIS DRAWING SET.

2. PHASING IS DESIGNATED THROUGHOUT THE DRAWING SET VIA

1. SEE ET001 FOR ET-SERIES NOTES AND LEGENDS.

GENERAL NOTES

SCALE: 3/16" = 1'-0"1 ELECTRICAL TELECOMMUNICATIONS FLOOR PLAN - MEZZANINE LEVEL

N

RK-201-2

REV 1 - FINAL BID SET 2024-04-04

Revisions: Date:

SHEET 2574/4/2024

RUN 1" EMT CONDUIT BACK TO TELECOMMUNICATIONS

ROOM. PROVIDE LARGER CONDUIT AS REQUIRED IF USING

PRE-TERMINATED CABLES.

PROVIDE SINGLE-GANG DEVICE BOX FOR

DATA PORTS. RJ-45 WITH 568A

PUNCH DOWN. FLUSH FACEPLATE

EQUIVALENT IN SIZE, COLOR, AND

PERFORMANCE SPECS TO UNIPRISE L TYPE,

ONE PORT IVORY.

LABEL (TYP)

FACEPLATE BY

CABLING VENDOR

CEILING

T568A CONNECTOR

COLOR: AS SPECIFIED

WIRELESS ACCESS POINT,

MOUNT IN ACCORDANCE

WITH MANUFACTURERS

INSTRUCTIONS

GENERAL NOTES:

1. RUN ONE (1) DATA CAT 6 CABLE. TERMINATE, LABEL, AND TEST EACH CABLE AND

JACK. JACKET COLOR SHALL BE AS SPECIFIED. WIRE IN DIRECT RUNS. NO SPLICES

IN RUN TO DATA ROOM. DO NOT LAY ON CEILING DO NOT USE ZIP TIES. DO NOT TIE

TO PIPING.

2. PORTS USED SHALL BE EQUIVALENT IN SIZE, COLOR AND PERFORMANCE SPECS

TO UNIPRISE UNJ600 INFORMATION OUTLETS.

3. ALL HOME RUNS TO END IN SPECIFIED DATA CLOSETS.

DETAIL A-A

A A

NOTES:

1. PROVIDE WHEREVER PLANS

CALL FOR TWO (2) DATA JACKS

AND ONE (1) PHONE JACK

GROUPED TOGETHER. ALL

HOME RUNS TO END IN RM 18.

RUN TWO (2) DATA CAT 6A CABLES. TERMINATE, LABEL

AND TEST EACH CABLE AND JACK. CABLE JACKET

COLORS SHALL BE BLUE FOR DATA A PORT, WHITE FOR

DATA B PORT. WIRE IN DIRECT RUNS. NO SPLICES IN RUN

TO DATA ROOM. DO NOT LAY ON CEILING. DO NOT USE

ZIP-TIES. DO NOT TIE TO PIPING.

RUN 1" EMT CONDUIT

UP TO CEILING SPACE

FUTURE USE

ANGLE TOWARDS DIRECTION

OF DATA/TELEPHONE MAIN

RACEWAY OR CABLE BUNDLES

FACEPLATE BY

CABLING VENDOR

NYLON BUSHING

LABEL

CEILING

UNLESS OTHERWISE NOTED, PROVIDE

SINGLE-GANG DEVICE BOX FOR TELEPHONE AND

DATA PORTS MOUNT IN THE FOLLOWING

LOCATIONS/HEIGHTS:

GENERAL: 18" AFF

COUNTERS: 42" AFF (6" ABOVE COUNTER)

OTHER: BETWEEN 18" AND 44" AFF

RJ-45 WITH 568A PUNCH DOWN

SPACE

PROVIDE VERTICAL CABLE

MANAGEMENT SYSTEM

(NOT SHOW)

45U ENCLOSED RACK

WITH INTEGRATED

POWER DISTRIBUTION

(EXT) FIBER OPTIC

PATCH PANEL

HORIZONTAL CABLE

MANAGEMENT (TYP)

48 PORT NETWORK

SWITCHES (VA

NETWORK)

(EXT) UPS BATTERY

(EXT) UPS

SPACE

EXISTING SERVER

(EXT) EQUIPMENT

BUS BAR (BACK)

SPACE

(NEW) SECURITY SWITCH

PROVIDE WITH PoE

CONTROLLER

CARD READER

CONDUIT AND

WIRING TO PACS

CONTROL PANEL

24V

TRANSFORMER

SECURE AREA

CEILING LINE

TYP CONDUIT &

WIRING FROM

CONTROLLER FOR

DOOR RELEASE

(TYP) DOOR

CONTACT SWITCH

CONDUIT &

WIRING TO CARD

READER

LOCKSET

(PROVIDED BY

GENERAL CONTR)

NOTE:

1. CONTRACTOR TO COORDINATE WITH DOOR VENDOR THE REQUIRED DOOR LOCKING

HARDWARE

2. CONDUIT AND WIRE SIZE AS RECOMMENDED BY PACS MANUFACTURER

3. CONTRACTOR TO MATCH EXISTING MANUFACTURER

NOTES:

1. ALL BUSBARS SHALL BE 1/4" X 4" X 24" PRE-DRILLED

TIN-PLATED COPPER. MOUNT ON WALL WITH 2" STANDOFF

INSULATORS

2. ALL CABLE CONNECTIONS TO TGB'S ARE TWO HOLE TONGUE

COMPRESSION LUGS.

3. TBB SHALL GENERALLY BE RUN OPEN WITH PLASTIC

SUPPORTS WHERE RUN IN STEEL CONDUITS LONGER THAN

36", BOND CONDUIT TO TBB OR GE AT BOTH ENDS

4. TBB SHALL BE RUN WITHOUT SPLICES WHEREVER POSSIBLE.

ANY SPLICES MUST BE MADE WITH NON-REVERSABLE

COMPRESSION CONNECTORS OR CADWELD. ALL GROUND

WIRES SHALL BE COPPER CONDUCTORS WITH GREEN

INSULATION OR

5. DISTINCTIVE GREEN MARKING

BASEMENT

FIRST FLOOR

TO TYPICAL EQUIPMENT

TGB 1-1

TELECOMMUNICATIONS MAIN

GROUNDING BUSBAR (TMGB) TO BE

LOCATED IN TELECOMMUNICATIONS

ENTRANCE ROOM

TELECOMMUNICATIONS

BONDING BACKBONE

(TBB) #3/0 COPPER

BUILDING POWER SYSTEM

MAIN GROUND BUS

BONDING CONDUCTOR FOR

TELECOMMUNICATIONS

#3/0 COPPER

BUILDING

GROUNDING

ELECTRODE SYSTEM

EQUIPMENT

RACKS CABLE

TRAY

ALL TELECOMM

SLEEVES AND

RACEWAYS

TYPICAL EQUIPMENT

BONDED TO ALL

TGB'S AND TMGB H-TAP, CADWELD, OR OTHER

NON-REVERSABLE SPLICE

(TYPICAL)

THIS CONNECTION IS NOT

REQUIRED FOR SLEEVES OR

RACEWAYS BONDED TO THE

TBB. SEE NOTE 3

PANELS SERVING BUILDING

STEEL TELECOMM ROOMS

WHERE AVAILABLE

#3/0 TBB

TO BE PROVIDED

BY VA

# 6 COPPER BONDING

CONDUCTOR (TYPICAL)

NOTES:

1. INTEGRAL GALVANIZED LIPPED STEEL MOUNTING CHANNEL LONGER THAN 36" SHALL

BE INSTALLED WITH A CENTER SUPPORT ROD.

2. FASTEN THREADED ROD TO STRUCTURE BY APPROVED METHOD PER SPECIFICATION

26 05 33, RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS (FIELD VERIFY EXACT

CONDITIONS).

3. FOR TRAPEZE INSTALLATIONS IN SEISMIC AREAS REFER TO SPECIFICATION SECTION

13 05 41, SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS.

4. EACH THREADED ROD SHALL BE ONE CONTINUOUS PIECE.

5. LOCATION OF CABLE TRAY IN MOUNTING CHANNEL INCLUDING WETHER CABLE TRAY

IS INSTALLED ON THE SAME CHANNEL AS CONDUITS OR SEPARATE SHALL BE BASED

ON FIELD CONDITIONS AND AVAILABLE HEIGHT ABOVE CEILING WITH OTHER UTILITIES.

CONTRACTOR TO INSTALL AND BOND CABLE TRAY PER SPECIFICATION 27 05 33.

WASHER AND

LOCKNUT

INTEGRAL

GALVANIZED LIPPED

STEEL MOUNTING

CHANNEL

LOCKING SQUARE

WASHER AND

LOCKNUT

3/8" MIN GALVANIZED

THREADED ROD, TYP

REFER TO PLANS

FOR QUANTITY AND

SIZE OF CONDUITS

CONDUIT CLAMP

(SIZE AS REQUIRED)

INTEGRAL GALVANIZED

LIPPED STEEL

MOUNTING CHANNEL

TRAY CLIP TO

MOUNTING CHANNEL

CONTROLLER

CARD READER

CONDUIT…

This is the start of the file's text. The full file is on GovTribe.