60040454.pdf
PDF 223 KB Posted
- Attached to
- Repair BEQ HP505
- Solicitation number
- N4008525R2549
About this file
This file contains mechanical equipment schedules and specifications for BEQ HP505 repair work at Marine Corps Base Camp Lejeune. The schedules detail requirements for HVAC equipment including dedicated outdoor air systems (DOAS), air handling units, fans, packaged terminal heat pumps (PTHP), ductless split systems, and associated ductwork and air distribution components.
Key specifications include six DOAS units rated 2300-2550 CFM with total energy heat exchangers, premium efficiency motors, and specific filtration requirements; three air handling units rated 600-800 CFM with premium efficiency motors and 2" double wall construction; multiple exhaust fans for laundry, restrooms and mechanical spaces; and wall-mounted PTHP units for sleeping rooms with 12 MBH cooling capacity. The document also contains detailed duct construction and leakage testing requirements, air distribution specifications for aluminum construction components, and louver requirements for various intake/exhaust applications. All cooling and heating coils must have 6000-hour salt spray protective coating, indicating this is for a coastal marine environment.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Amend 0016.pdf | ||
| Amend 0015.pdf | ||
| Amend 0014.pdf | ||
| Amend 0013.pdf | ||
| 60040360.pdf | ||
| 60040406.pdf | ||
| 60040345.pdf | ||
| 60040373.pdf | ||
| 60040328.pdf | ||
| 60040433.pdf | ||
| 60040414.pdf | ||
| N4008523B0034 SpecsAsOne Addendum 01.pdf | ||
| 60040411.pdf | ||
| 60040407.pdf | ||
| 60040434.pdf | ||
| 60040420.pdf | ||
| 60040412.pdf | ||
| 60040343.pdf | ||
| Amend 0012.pdf | ||
| 60040362.pdf | ||
| 60040342.pdf | ||
| 60040447.pdf | ||
| 60040408.pdf | ||
| 60040436.pdf | ||
| 60040424.pdf | ||
| 60040329.pdf | ||
| 60040422.pdf | ||
| 60040366.pdf | ||
| 60040376.pdf | ||
| 60040359.pdf | ||
| Amend 0011.pdf | ||
| Amend 0010.pdf | ||
| Amend 0009.pdf | ||
| Amend 0008.pdf | ||
| Amend 0007.pdf | ||
| Amend 0006.pdf | ||
| Amend 0005.pdf | ||
| Amend 0004.pdf | ||
| Amend 0003.pdf | ||
| Amend 0002.pdf | ||
| Amend 0001.pdf | ||
| 23-0034 Asbestos and Lead Assessment.pdf | ||
| 23-0034 Appendix D.pdf | ||
| N4008523B0034 DWGs.pdf | ||
| RFP 230034.pdf | ||
| N4008523B0034 SPECS.pdf |
Show all 46
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SYM. DESCRIPTION DATE APP.
REVISIONS
DR.
DES.
CHK.
SUBMITTED BY:
DESIGN DIR.
APPROVED: PWO OR OICC
SATISFACTORY TO:
DATE
DATE
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND
CAMP LEJEUNE, NORTH CAROLINA
MARINE CORPS BASE
SIZE CODE IDENT. NO. NAVFAC DRAWING NO.
E1 80091
CONSTR. CONTR. NO.
AS NOTEDSCALE SHEET
M B
F A
N O
SPEC.
M-601
MAS
JDL
MORGAN HUNTER
MAS
REPAIR BEQ HP505
MECHANICAL SCHEDULES
60040454 N40085-23-B-0034
130 176
1. OVERALL BUILDING PRESSURIZATION IS POSITIVE.
REMARKS
DOAS-6 2325 2000 1
DOAS-5 2550 2000 1
DOAS-4 2325 2000 1
DOAS-3 2550 2000 1
DOAS-2 2325 2000 1
DOAS-1 2550 2000 1
AREA OUTSIDE AIR (CFM) EXHAUST AIR (CFM) REMARKS
BUILDING AIR BALANCE CALCULATION
COMM ROOM COOLING 68°F 68°F
HEATING 70°F 55°F
ALL
COOLING 76°F 84°F
SPACE TYPE SEASON OCCUPIED UNIOCCUPIED
INDOOR DESIGN CONDITIONS
84 140
MCDB (°F) W (grains H2O/lbm dry air)
DEHUMDIFICATION CONDITIONS
WINTER 26.0 (99.0% ASHRAE)
SUMMER 91.0 / 77.0 (1% ASHRAE)
SEASON DB/WB (°F)
OUTDOOR DESIGN CONDITIONS
DESIGN CONDITIONS
DUCT LEAKAGE TEST MANUAL.
1. TEST IN ACCORDANCE WITH SPECIFICATION SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC, AND WITH THE PROCEDURES IN SMACNA HVAC AIR
REMARKS:
EXHAUST DUCT - - - - -1 - - - A 6 - - 1 1
- - - - - 1 - - - - A 6 1 1
- - - - -1 - - - - - A 6 1 1
- - - -1 - - - - A 6 - - 1 1DEDICATED OUTDOOR AIR
SYSTEM - DOAS
1 - - - - - A 3 A 6 - - 1 1
- - - -1 - - - - A 6 - - 1 1
AIR HANDLERS
1 - - - - - A 3 A 6 - - 1 1
SUPPLY DUCT
SUPPLY
DUCT(BETWEEN
AHU AND VAV
SUPPLY DUCT
(DOWNSTREAM OF
VAV BOXES)
RETURN
DUCT
EXHAUST/
RELIEF
DUCT
OUTSIDE AIR
DUCT
DUCT SEAL
CLASS
DUCT LEAK
CLASS
DUCT SEAL
CLASS
DUCT LEAK
CLASS
DUCT SEAL
CLASS
DUCT LEAK
CLASS
INCHES OF WATER ROUND / OVAL RECTANGULAR
LOCATION
DUCT PRESSURE CLASS SUPPLY / EXHAUST
RETURN/OUTSIDE AIR
DUCT TEST PRESSURE INCHES
OF WATER COLUMN
REMARKS
DUCT CONSTRUCTION AND LEAKAGE TESTING TABLE
5. PROVIDE GRILLE WITH OBD.
4. PROVIDE BLANKET INSULATION ON THE BACK OF ALL DIFFUSERS.
3. ALL AIR DISTRIBUTION MUST BE 100% ALUMINUM CONSTRUCTION.
2. PROVIDE WITH SQUARE TO ROUND TRANSITION AS NECESSARY.
1. VERIFY ALL CEILING TYPES WITH ARCHITECTURAL PLANS TO DETERMINE MOUNTING DETAILS AND ACCESSORIES REQUIRED. COORDINATE COLOR WITH ARCHITECT.
REMARKS
R1 ALUMINUM FIXED VANE NA 20X10 20X10 600 CFM 800 CFM 30 1,2,3,4
E2 ALUMINUM FIXED VANE NA 12X22 12X22 800 CFM 900 CFM 30 1,2,3,4
E1 ALUMINUM FIXED VANE NA 6X6 6" 25 CFM 100 CFM 30 1,2,3,4,5
S3 ALUMINUM DOUBLE DEFLECTION 4 WAY 16X6 16X6 250 CFM 250 CFM 30 1,2,3,4
S2 SQUARE PLAQUE FACE DIFFUSER 4 WAY 24X24 8" 150 CFM 200 CFM 30 1,2,3,4
S1 ALUMINUM DOUBLE DEFLECTION 4 WAY 8X6 8" 25 CFM 115 CFM 30 1,2,3,4,5
MARK DESCRIPTION THROW FACE SIZE NECK SIZE MINIMUM CFM MAXIMUM CFM MAX. NC REMARKS
AIR DISTRIBUTION SCHEDULE
4. PROVIDE WITH CLASS 1A LOW LEAKAGE MOTORIZED DAMPER. DAMPER TO ACTUATE UPON ACTIVATION OF ASSOCIATED FAN.
3. PROVIDE WITH ALUMINUM BIRDSCREEN.
2. PROVIDE ALL ALUMINUM LOUVER WITH BAKED ENAMEL FINISH TO MATCH BUILDING EXTERIOR.
1. PROVIDE FULL SIZE PLENUM BEHIND LOUVER AND PAINT INSIDE OF PLENUM FLAT BLACK
REMARKS :
L-9,10,11,12 DOAS EXH EXHAUST SEE PLANS 4.00 1000 3000 1,2,3,5
L-5,6,7,8 DOAS OA INTAKE SEE PLANS 4.00 500 3825 1,2,3,5
L-2,3,4 LAUNDRY EXHAUST 8X24 0.70 1000 600 1,2,3
L-1 MECH BLDG INTAKE 40X12 0.95 500 650 1,2,3,4
MARK SERVES FLOW SIZE WxH (in.)
FREE AREA
REQUIRED (s.f.)
MAX AIR VELOCITY
(fpm)
CFM REMARKS
LOUVER SCHEDULE
3. THE 'TOTAL REQUIRED CFM' IS ROUNDED UP TO THE NEAREST 5 IN EACH ROOM, TO GET THE 'TOTAL PROVIDED CFM'.
2. THE 'REQUIRED CFM' IS ADJUSTED BY THE ZONE AIR DISTRIBUTION EFFECTIVENESS (EZ) OF 0.8 TO GET THE 'TOTAL REQUIRED CFM'.
1. CALCULATIONS PERFORMED IN ACCORDANCE WITH ASHRAE 62.1-2016.
REMARKS:
TOTAL 1,210 4,875
77 STORAGE (FUTURE OFFICE) 1 5 0.06 10 12 1,2,3
DOAS-6
3,953 BARRACKS SLEEPING ROOM 40 5 0.06 437 546
2,325
1,2,3
492 LOUNGE 5 7.5 0.06 67 84 1,2,3
DOAS-5
3,953 BARRACKS SLEEPING ROOM 40 5 0.06 437 546
2,550
1,2,3
COMM ROOM 0 5 0.06 0 0 1,2,3
DOAS-4
3,953 BARRACKS SLEEPING ROOM 40 5 0.06 437 546
2,325
1,2,3
492 LOUNGE 5 7.5 0.06 67 84 1,2,3
DOAS-3
3,953 BARRACKS SLEEPING ROOM 40 5 0.06 437 546
2,550
1,2,3
77 OFFICE 1 5 0.06 10 12 1,2,3
DOAS-2
3,953 BARRACKS SLEEPING ROOM 40 5 0.06 437 546
2,325
1,2,3
492 LAUNDRY 5 5 0.12 84 105 1,2,3
DOAS-1
3,953 BARRACKS SLEEPING ROOM 40 5 0.06 437 546
2,550
1,2,3
UNIT MARK
FLOOR AREA
(SQ.FT.)
ASHRAE CLASSIFICATION
TOTAL
PEOPLE
CFM PER
PERSON
CFM PER
SQ. FT.
REQUIRED
CFM
TOTAL
REQUIRED
CFM
TOTAL
PROVIDED
CFM
REMARKS
OUTSIDE AIR CALCULATION
6. PROVIDE UNIT WITH SINGLE POINT POWER CONNECTION.
5. PROVIDE 6000 HR SALT SPRAY PROTECTIVE COATING ON THE REHEAT AND COOLING COILS.
4. CONTRACTOR MUST VERIFY THAT UNIT CAN BE INSTALLED IN LOCATION SHOWN ON DRAWINGS PRIOR TO SUBMITTING FOR APPROVAL.
3. PROVIDE UNIT WITH HORIZONTAL SUPPLY DISCHARGE AND RETURN INLET DUCT CONNECTIONS. UNIT MUST HAVE 2" DOUBLE WALL CONSTRUCTION.
2. PROVIDE PREMIUM EFFICIENCY MOTORS FOR SUPPLY FAN, COMPATIBLE WITH VARIABLE FREQUENCY DRIVES.
1. PROVIDE WITH 2" MERV 13 FINAL FILTER ON THE RETURN AIR INTAKE.
REMARKS:
AHU-3 800 0.50 1.94 34.0 / 20.7 78.0 / 67.0 54.6 / 53.1 44.0 / 54.0 5.0 3.6 6 8.2 31.9 55.0 / 92.0 140 / 110 5.0 1.0 2.0 208/3 1.0 5.75 / 15.0 250 1,2,3,4,5,6
AHU-2 800 0.50 1.94 34.0 / 20.7 78.0 / 67.0 54.6 / 53.1 44.0 / 54.0 5.0 3.6 6 8.2 31.9 55.0 / 92.0 140 / 110 5.0 1.0 2.0 208/3 1.0 5.75 / 15.0 250 1,2,3,4,5,6
AHU-1 600 0.50 1.39 27.8 / 18.0 80.0 / 67.0 52.8 / 51.6 44.0 / 54.0 5.0 2.9 6 5.8 25.7 55.0 / 95.0 140 / 110 5.0 5.0 1.7 208/3 0.5 3.0 / 15.0 250 1,2,3,4,5,6
EWT/LWT
CFM
E.S.P.
"WC
T.S.P.
"WC
TOTAL/
SENSIBLE MBH
EAT (DB/WB)
ºF
LAT
(DB/WB) ºF
WATER TEMP.
(ºF) WATER PD
FT. MAX.
VELOCITY
FPS, MAX
MIN. NUM. OF
ROWS
GPM
TOTAL
MBH
EAT/LAT ºF EWT/LWT ºF
WATER PD
FT. MAX
VELOCITY
FPS, MAX
GPM V/PH
SUPPLY
HP
MCA/MOP
MARK
SUPPLY FAN COOLING CAPACITY (CHILLED WATER) REHEAT HEATING CAPACITY (HOT WATER) ELECTRICAL
UNIT
WEIGHT
(LBS)
REMARKS
AIR HANDLING UNIT SCHEDULE
9. PROVIDE UNIT WITH RECIRCULATION PUMP AT PREHEAT COIL FOR FREEZE PROTECTION. ALSO PROVIDE 120/1 CIRCUIT FOR PUMP. PUMP IS TO BE SIZED FOR 110% OF PREHEAT COIL PRESSURE DROP. SEE HOT WATER PREHEAT COIL DETAIL AND CONTROLS FOR FURTHER INFORMATION.
8. PROVIDE UNIT WITH 3-POINT POWER CONNECTION. A SINGLE CONNECTION FOR THE SUPPLY FAN, A SINGLE CONNECTION FOR THE EXHAUST FAN AND A SINGLE CONNECTION FOR THE MARINE LIGHTS.
7. UNIT MUST HAVE CROSSFLOW FIXED PLATE TOTAL ENERGY HEAT EXCHANGER, PLENUM-TYPE SUPPLY/EXHAUST FANS, PREHEAT COIL, COOLING COIL, REHEAT COIL AND MARINE LIGHTS IN EACH FAN SECTIONS.
6. PROVIDE 6000 HR SALT SPRAY PROTECTIVE COATING ON THE PREHEAT, COOLING AND REHEAT COILS.
5. CONTRACTOR MUST VERIFY THAT UNIT CAN BE INSTALLED IN LOCATION SHOWN ON DRAWINGS PRIOR TO SUBMITTING FOR APPROVAL.
4. PROVIDE UNIT WITH VERTICAL SUPPLY DISCHARGE DUCT CONNECTION AND HORIZONTAL EXHAUST & OUTSIDE AIR DUCT CONNECTIONS. UNIT MUST HAVE 2" DOUBLE WALL CONSTRUCTION.
3. PROVIDE WITH CLASS 1A LOW LEAKAGE DAMPERS ON THE EXHAUST AND OUTSIDE AIR INTAKE UNIT CONNECTIONS.
2. PROVIDE PREMIUM EFFICIENCY MOTORS FOR SUPPLY AND EXHAUST FANS, COMPATIBLE WITH VARIABLE FREQUENCY DRIVES.
1. PROVIDE WITH 2" MERV 8 FILTERS ON THE EXHAUST AND 2" MERV 8 PREFILTERS & 2" MERV 13 FINAL FILTERS ON THE OUTSIDE AIR INTAKE.
REMARKS:
DOAS-6 2325 1.50 4.20 2000 1.50 2.82 84.2 22.0 / 50.0 140 / 110 5.0 2 5.7 220.2 / 83.14 84.0 / 78.6 52.0 / 51.0 44.0 / 54.0 5.0 4 6 43.9 86.3 52.0 / 85.0 140 / 110 5.0 2 5.8 93.0 78.0 76.0 50.0 84.6 74.5 22.0 70.0 35.0 48.6 40.5 50.0% 208/3 2.4 1.4 1.63 / 15.0 115/1 1400 1,2,3,4,5,6,7,8,9
DOAS-5 2550 1.50 4.41 2000 1.50 2.77 88.2 22.0 / 50.0 140 / 110 5.0 2 6.0 242.0 / 91.4 84.0 / 78.6 52.0 / 51.0 44.0 / 54.0 5.0 5 6 48.2 91.5 52.0 / 85.0 140 / 110 5.0 2 6.2 93.0 78.0 76.0 50.0 84.9 74.7 22.0 70.0 35.0 47.4 39.8 50.0% 208/3 2.8 1.4 1.63 / 15.0 115/1 1400 1,2,3,4,5,6,7,8,9
DOAS-4 2300 1.50 4.20 2000 1.50 2.82 84.2 22.0 / 50.0 140 / 110 5.0 2 5.7 220.2 / 83.14 84.0 / 78.6 52.0 / 51.0 44.0 / 54.0 5.0 4 6 43.9 86.3 52.0 / 85.0 140 / 110 5.0 2 5.8 93.0 78.0 76.0 50.0 84.6 74.5 22.0 70.0 35.0 48.6 40.5 50.0% 208/3 2.4 1.4 1.63 / 15.0 115/1 1400 1,2,3,4,5,6,7,8,9
DOAS-3 2550 1.50 4.41 2000 1.50 2.77 88.2 22.0 / 50.0 140 / 110 5.0 2 6.0 242.0 / 91.4 84.0 / 78.6 52.0 / 51.0 44.0 / 54.0 5.0 5 6 48.2 91.5 52.0 / 85.0 140 / 110 5.0 2 6.2 93.0 78.0 76.0 50.0 84.9 74.7 22.0 70.0 35.0 47.4 39.8 50.0% 208/3 2.8 1.4 1.63 / 15.0 115/1 1400 1,2,3,4,5,6,7,8,9
DOAS-2 2325 1.50 4.20 2000 1.50 2.82 84.2 22.0 / 50.0 140 / 110 5.0 2 5.7 220.2 / 83.14 84.0 / 78.6 52.0 / 51.0 44.0 / 54.0 5.0 4 6 43.9 86.3 52.0 / 85.0 140 / 110 5.0 2 5.8 93.0 78.0 76.0 50.0 84.6 74.5 22.0 70.0 35.0 48.6 40.5 50.0% 208/3 2.4 1.4 1.63 / 15.0 115/1 1400 1,2,3,4,5,6,7,8,9
DOAS-1 2550 1.50 4.41 2000 1.50 2.77 88.2 22.0 / 50.0 140 / 110 5.0 2 6.0 242.0 / 91.4 84.0 / 78.6 52.0 / 51.0 44.0 / 54.0 5.0 5 6 48.2 91.5 52.0 / 85.0 140 / 110 5.0 2 6.2 93.0 78.0 76.0 50.0 84.9 74.7 22.0 70.0 35.0 47.4 39.8 50.0% 208/3 2.8 1.4 1.63 / 15.0 115/1 1400 1,2,3,4,5,6,7,8,9
EWT/LWT DB WB DB %RH DB WB DB DB %RH DB WB
OA RA SA OA RA SACFM
E.S.P.
"WC
T.S.P.
"WC
CFM
E.S.P.
"WC
T.S.P.
"WC
TOTAL
MBH
EAT/LAT ºF
EWT/LWT
ºF
WATER PD
FT. MAX
VELOCITY
FPS, MAX
GPM
TOTAL/
SENSIBLE MBH
EAT (DB/WB)
ºF
LAT
(DB/WB) ºF
WATER TEMP.
(ºF) WATER PD
FT. MAX.
VELOCITY
FPS, MAX
MIN. NUM.
OF ROWS
GPM
TOTAL
MBH
EAT/LAT
ºF
EWT/LWT
ºF
WATER PD
FT. MAX
VELOCITY
FPS, MAX
GPM
SUMMER WINTER
HX
EFFECT.
V/PH
SUPPLY
HP
EXHAUST
HP
MARINE
LIGHTS
MCA/MOP
MARINE
LIGHTS
V/PH
MARK
SUPPLY FAN EXHAUST FAN PREHEAT HEATING CAPACITY (HOT WATER) COOLING CAPACITY (CHILLED WATER) REHEAT HEATING CAPACITY (HOT WATER) TOTAL ENERGY HEAT EXCHANGER ELECTRICAL
UNIT
WEIGHT
(LBS)
REMARKS
DEDICATED OUTSIDE AIR SYSTEM SCHEDULE
PROVIDE WALL MOUNTED CONTROL SWITCH NEAR ENTRANCE.
5. PROVIDE SIDEWALL MOUNTED FAN WITH TEFC MOTOR, MOTORSIDE GUARD, HANGING VIBRATION ISOLATION KIT, WALL SLEEVE, BACKDRAFT DAMPER AND BIRDSCREEN.
4. PROVIDE FAN WITH TEFC MOTOR AND HANGING VIBRATION ISOLATION KIT.
3. FAN MUST OPERATE CONTINUOUSLY.
2. FAN MUST BE TIED TO THERMOSTAT AND HUMIDISTAT.
1. PROVIDE WITH BACKDRAFT DAMPER, TEFC MOTOR AND HANGING VIBRATION ISOLATION KIT.
REMARKS:
EF-5 CORE ELEC & RESTROOMS INLINE 250 0.75 DIRECT 1350 4.5 118 120/1 30 3,4
EF-2,3,4 LAUNDRY ROOMS WALL MOUNT 200 0.25 DIRECT 835 0.3 137 120/1 25 1,2
EF-1 MECHANICAL BLDG PROPELLER 650 0.25 DIRECT 1050 4.4 1/20 HP 120/1 30 5
WATTS V/PH
MARK AREA SERVED TYPE CFM
ESP
(IN H2O)
DRIVE RPM MAX. SONES
ELECTRICAL OPER.WEIGHT
(LBS)
REMARKS
FAN SCHEDULE
6. AUXILARY HEAT SHALL BE LOCKED OUT UNLESS THE HEATING SETPOINT IS UNABLE TO BE MAINTAINED WITH COMPRESSOR RUNNING CONTINUOUSLY IN HEATING MODE. AUXILARY HEAT WILL REMAIN ENERGIZED UNTIL SETPOINT IS
REACHED
5. PROVIDE TAMPER PROOF, FULL ENCLOSURE FOR UNIT. SEPARATE ENCLOSURE TO BE PROVIDED FOR CONDENSATE LINES, ELECTRICAL WIRING AND CONTROLS WITH ACCESS PANEL.
4. THE ROOM SHALL BE PROVIDED WITH A WALL MOUNTED PROGRAMMABLE THERMOSTAT AND INTERFACED WITH THE DDC CONTROL SYSTEM.
3. PROVIDE UNIT WITH WALL SLEEVE, POLYCARBONATE OR STAINLESS STEEL DRAIN PAN, CENTER HOLE CONDENSATE DRAIN KIT AND OUTDOOR GRILLE.
2. PTHP SHOULD BE CORROSION RESISTANT AND FITTED WITH A METAL LIGATURE PROOF SECURITY COVER.
1. PROVIDE PACKAGED TERMINAL HEAT PUMP WITH AUXILIARY ELECTRIC HEAT. HARDWIRE TO ELECTRICAL CONNECTION.
REMARKS:
PTHP-1 SLEEPING ROOMS HEAT PUMP 12.0 320 9.9 350 3.0 KW 3.1 11.8 208/1 100 1,2,3,4,5,6
TOTAL MBH CFM TOTAL MBH CFM AMPS V/PH
MARK AREA SERVED TYPE
COOLING HEATING AUXILARY
ELEC HEAT
DEHUMIDIFICATION
(PINTS/HR)
ELECTRICAL OPER.WEIGHT
(LBS)
REMARKS
PTHP SCHEDULE
5. PROVIDE CONDENSATE PUMP FOR USE WITH UNIT, PROVIDE BACNET MS/TP CAPABILITY, 10 GPH AT 20' HEAD, 1/30 HP, 120/1, 1.5 FLA.
4. DUCTLESS SPLIT SYSTEM MUST BE CAPABLE OF HANDLING 100 FEET OF REFRIGERANT LINE BETWEEN AC AND CU.
3. AHU IS POWERED FROM CONDENSING UNIT.
2. PROVIDE UNIT WITH WALL MOUNTED CONDENSATE PUMP, WIRED TO MOTOR RATED SWITCH.
1. PROVIDE UNIT WITH WIRED WALL MOUNTED THERMOSTAT, AND CLEANABLE TYPE FILTERS.
REMARKS:
DAC-1 2ND FLR COMM AC 450 1.0 R-410A 35 1,2,3,4,5
MARK SERVES TYPE CFM MCA REFRIG. TYPE WEIGHT (LBS) REMARKS
DUCTLESS SPLIT SYSTEM AIR HANDLING UNIT SCHEDULE
2. DUCTLESS SPLIT SYSTEM MUST BE CAPABLE OF HANDLING 100 FEET OF REFRIGERANT LINE BETWEEN AC AND CU.
QUANTITIES.
SALT-HOUR SEACOAST CONSTRUCTION. COATINGS MUST NOT REDUCE UNIT PERFORMANCE BELOW SCHEDULED
1. PROVIDE ALL ACCESSORIES REQUIRED FOR LOW AMBIENT OPERATION TO 0ºF. PROVIDE COIL GUARDS AND 6,000
REMARKS:
DCU-1 2ND FLR COMM 1 1/2 AC 19.8 208/1 11 28 100 1,2
MARK SERVES
NOMINAL
TONS
TYPE SEER VOLT/PH MCA MOCP
WEIGHT
(LBS)
REMARKS
DUCTLESS SPLIT SYSTEM CONDENSING UNIT SCHEDULE
1 PPI Responses 01.17.25
| Sheets |
| M-601 - MECHANICAL SCHEDULES |
File details come from the government source that posted it. Updated .