60040454.pdf

PDF 223 KB Posted

Attached to
Repair BEQ HP505
Solicitation number
N4008525R2549
Issued by

About this file

This file contains mechanical equipment schedules and specifications for BEQ HP505 repair work at Marine Corps Base Camp Lejeune. The schedules detail requirements for HVAC equipment including dedicated outdoor air systems (DOAS), air handling units, fans, packaged terminal heat pumps (PTHP), ductless split systems, and associated ductwork and air distribution components.

Key specifications include six DOAS units rated 2300-2550 CFM with total energy heat exchangers, premium efficiency motors, and specific filtration requirements; three air handling units rated 600-800 CFM with premium efficiency motors and 2" double wall construction; multiple exhaust fans for laundry, restrooms and mechanical spaces; and wall-mounted PTHP units for sleeping rooms with 12 MBH cooling capacity. The document also contains detailed duct construction and leakage testing requirements, air distribution specifications for aluminum construction components, and louver requirements for various intake/exhaust applications. All cooling and heating coils must have 6000-hour salt spray protective coating, indicating this is for a coastal marine environment.

View the file

Other files

File Type Posted
Amend 0016.pdf PDF
Amend 0015.pdf PDF
Amend 0014.pdf PDF
Amend 0013.pdf PDF
60040360.pdf PDF
60040406.pdf PDF
60040345.pdf PDF
60040373.pdf PDF
60040328.pdf PDF
60040433.pdf PDF
60040414.pdf PDF
N4008523B0034 SpecsAsOne Addendum 01.pdf PDF
60040411.pdf PDF
60040407.pdf PDF
60040434.pdf PDF
60040420.pdf PDF
60040412.pdf PDF
60040343.pdf PDF
Amend 0012.pdf PDF
60040362.pdf PDF
60040342.pdf PDF
60040447.pdf PDF
60040408.pdf PDF
60040436.pdf PDF
60040424.pdf PDF
60040329.pdf PDF
60040422.pdf PDF
60040366.pdf PDF
60040376.pdf PDF
60040359.pdf PDF
Amend 0011.pdf PDF
Amend 0010.pdf PDF
Amend 0009.pdf PDF
Amend 0008.pdf PDF
Amend 0007.pdf PDF
Amend 0006.pdf PDF
Amend 0005.pdf PDF
Amend 0004.pdf PDF
Amend 0003.pdf PDF
Amend 0002.pdf PDF
Amend 0001.pdf PDF
23-0034 Asbestos and Lead Assessment.pdf PDF
23-0034 Appendix D.pdf PDF
N4008523B0034 DWGs.pdf PDF
RFP 230034.pdf PDF
N4008523B0034 SPECS.pdf PDF
Show all 46

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SYM. DESCRIPTION DATE APP.

REVISIONS

DR.

DES.

CHK.

SUBMITTED BY:

DESIGN DIR.

APPROVED: PWO OR OICC

SATISFACTORY TO:

DATE

DATE

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND

CAMP LEJEUNE, NORTH CAROLINA

MARINE CORPS BASE

SIZE CODE IDENT. NO. NAVFAC DRAWING NO.

E1 80091

CONSTR. CONTR. NO.

AS NOTEDSCALE SHEET

M B

F A

N O

SPEC.

M-601

MAS

JDL

MORGAN HUNTER

MAS

REPAIR BEQ HP505

MECHANICAL SCHEDULES

60040454 N40085-23-B-0034

130 176

1. OVERALL BUILDING PRESSURIZATION IS POSITIVE.

REMARKS

DOAS-6 2325 2000 1

DOAS-5 2550 2000 1

DOAS-4 2325 2000 1

DOAS-3 2550 2000 1

DOAS-2 2325 2000 1

DOAS-1 2550 2000 1

AREA OUTSIDE AIR (CFM) EXHAUST AIR (CFM) REMARKS

BUILDING AIR BALANCE CALCULATION

COMM ROOM COOLING 68°F 68°F

HEATING 70°F 55°F

ALL

COOLING 76°F 84°F

SPACE TYPE SEASON OCCUPIED UNIOCCUPIED

INDOOR DESIGN CONDITIONS

84 140

MCDB (°F) W (grains H2O/lbm dry air)

DEHUMDIFICATION CONDITIONS

WINTER 26.0 (99.0% ASHRAE)

SUMMER 91.0 / 77.0 (1% ASHRAE)

SEASON DB/WB (°F)

OUTDOOR DESIGN CONDITIONS

DESIGN CONDITIONS

DUCT LEAKAGE TEST MANUAL.

1. TEST IN ACCORDANCE WITH SPECIFICATION SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC, AND WITH THE PROCEDURES IN SMACNA HVAC AIR

REMARKS:

EXHAUST DUCT - - - - -1 - - - A 6 - - 1 1

- - - - - 1 - - - - A 6 1 1

- - - - -1 - - - - - A 6 1 1

- - - -1 - - - - A 6 - - 1 1DEDICATED OUTDOOR AIR

SYSTEM - DOAS

1 - - - - - A 3 A 6 - - 1 1

- - - -1 - - - - A 6 - - 1 1

AIR HANDLERS

1 - - - - - A 3 A 6 - - 1 1

SUPPLY DUCT

SUPPLY

DUCT(BETWEEN

AHU AND VAV

SUPPLY DUCT

(DOWNSTREAM OF

VAV BOXES)

RETURN

DUCT

EXHAUST/

RELIEF

DUCT

OUTSIDE AIR

DUCT

DUCT SEAL

CLASS

DUCT LEAK

CLASS

DUCT SEAL

CLASS

DUCT LEAK

CLASS

DUCT SEAL

CLASS

DUCT LEAK

CLASS

INCHES OF WATER ROUND / OVAL RECTANGULAR

LOCATION

DUCT PRESSURE CLASS SUPPLY / EXHAUST

RETURN/OUTSIDE AIR

DUCT TEST PRESSURE INCHES

OF WATER COLUMN

REMARKS

DUCT CONSTRUCTION AND LEAKAGE TESTING TABLE

5. PROVIDE GRILLE WITH OBD.

4. PROVIDE BLANKET INSULATION ON THE BACK OF ALL DIFFUSERS.

3. ALL AIR DISTRIBUTION MUST BE 100% ALUMINUM CONSTRUCTION.

2. PROVIDE WITH SQUARE TO ROUND TRANSITION AS NECESSARY.

1. VERIFY ALL CEILING TYPES WITH ARCHITECTURAL PLANS TO DETERMINE MOUNTING DETAILS AND ACCESSORIES REQUIRED. COORDINATE COLOR WITH ARCHITECT.

REMARKS

R1 ALUMINUM FIXED VANE NA 20X10 20X10 600 CFM 800 CFM 30 1,2,3,4

E2 ALUMINUM FIXED VANE NA 12X22 12X22 800 CFM 900 CFM 30 1,2,3,4

E1 ALUMINUM FIXED VANE NA 6X6 6" 25 CFM 100 CFM 30 1,2,3,4,5

S3 ALUMINUM DOUBLE DEFLECTION 4 WAY 16X6 16X6 250 CFM 250 CFM 30 1,2,3,4

S2 SQUARE PLAQUE FACE DIFFUSER 4 WAY 24X24 8" 150 CFM 200 CFM 30 1,2,3,4

S1 ALUMINUM DOUBLE DEFLECTION 4 WAY 8X6 8" 25 CFM 115 CFM 30 1,2,3,4,5

MARK DESCRIPTION THROW FACE SIZE NECK SIZE MINIMUM CFM MAXIMUM CFM MAX. NC REMARKS

AIR DISTRIBUTION SCHEDULE

4. PROVIDE WITH CLASS 1A LOW LEAKAGE MOTORIZED DAMPER. DAMPER TO ACTUATE UPON ACTIVATION OF ASSOCIATED FAN.

3. PROVIDE WITH ALUMINUM BIRDSCREEN.

2. PROVIDE ALL ALUMINUM LOUVER WITH BAKED ENAMEL FINISH TO MATCH BUILDING EXTERIOR.

1. PROVIDE FULL SIZE PLENUM BEHIND LOUVER AND PAINT INSIDE OF PLENUM FLAT BLACK

REMARKS :

L-9,10,11,12 DOAS EXH EXHAUST SEE PLANS 4.00 1000 3000 1,2,3,5

L-5,6,7,8 DOAS OA INTAKE SEE PLANS 4.00 500 3825 1,2,3,5

L-2,3,4 LAUNDRY EXHAUST 8X24 0.70 1000 600 1,2,3

L-1 MECH BLDG INTAKE 40X12 0.95 500 650 1,2,3,4

MARK SERVES FLOW SIZE WxH (in.)

FREE AREA

REQUIRED (s.f.)

MAX AIR VELOCITY

(fpm)

CFM REMARKS

LOUVER SCHEDULE

3. THE 'TOTAL REQUIRED CFM' IS ROUNDED UP TO THE NEAREST 5 IN EACH ROOM, TO GET THE 'TOTAL PROVIDED CFM'.

2. THE 'REQUIRED CFM' IS ADJUSTED BY THE ZONE AIR DISTRIBUTION EFFECTIVENESS (EZ) OF 0.8 TO GET THE 'TOTAL REQUIRED CFM'.

1. CALCULATIONS PERFORMED IN ACCORDANCE WITH ASHRAE 62.1-2016.

REMARKS:

TOTAL 1,210 4,875

77 STORAGE (FUTURE OFFICE) 1 5 0.06 10 12 1,2,3

DOAS-6

3,953 BARRACKS SLEEPING ROOM 40 5 0.06 437 546

2,325

1,2,3

492 LOUNGE 5 7.5 0.06 67 84 1,2,3

DOAS-5

3,953 BARRACKS SLEEPING ROOM 40 5 0.06 437 546

2,550

1,2,3

COMM ROOM 0 5 0.06 0 0 1,2,3

DOAS-4

3,953 BARRACKS SLEEPING ROOM 40 5 0.06 437 546

2,325

1,2,3

492 LOUNGE 5 7.5 0.06 67 84 1,2,3

DOAS-3

3,953 BARRACKS SLEEPING ROOM 40 5 0.06 437 546

2,550

1,2,3

77 OFFICE 1 5 0.06 10 12 1,2,3

DOAS-2

3,953 BARRACKS SLEEPING ROOM 40 5 0.06 437 546

2,325

1,2,3

492 LAUNDRY 5 5 0.12 84 105 1,2,3

DOAS-1

3,953 BARRACKS SLEEPING ROOM 40 5 0.06 437 546

2,550

1,2,3

UNIT MARK

FLOOR AREA

(SQ.FT.)

ASHRAE CLASSIFICATION

TOTAL

PEOPLE

CFM PER

PERSON

CFM PER

SQ. FT.

REQUIRED

CFM

TOTAL

REQUIRED

CFM

TOTAL

PROVIDED

CFM

REMARKS

OUTSIDE AIR CALCULATION

6. PROVIDE UNIT WITH SINGLE POINT POWER CONNECTION.

5. PROVIDE 6000 HR SALT SPRAY PROTECTIVE COATING ON THE REHEAT AND COOLING COILS.

4. CONTRACTOR MUST VERIFY THAT UNIT CAN BE INSTALLED IN LOCATION SHOWN ON DRAWINGS PRIOR TO SUBMITTING FOR APPROVAL.

3. PROVIDE UNIT WITH HORIZONTAL SUPPLY DISCHARGE AND RETURN INLET DUCT CONNECTIONS. UNIT MUST HAVE 2" DOUBLE WALL CONSTRUCTION.

2. PROVIDE PREMIUM EFFICIENCY MOTORS FOR SUPPLY FAN, COMPATIBLE WITH VARIABLE FREQUENCY DRIVES.

1. PROVIDE WITH 2" MERV 13 FINAL FILTER ON THE RETURN AIR INTAKE.

REMARKS:

AHU-3 800 0.50 1.94 34.0 / 20.7 78.0 / 67.0 54.6 / 53.1 44.0 / 54.0 5.0 3.6 6 8.2 31.9 55.0 / 92.0 140 / 110 5.0 1.0 2.0 208/3 1.0 5.75 / 15.0 250 1,2,3,4,5,6

AHU-2 800 0.50 1.94 34.0 / 20.7 78.0 / 67.0 54.6 / 53.1 44.0 / 54.0 5.0 3.6 6 8.2 31.9 55.0 / 92.0 140 / 110 5.0 1.0 2.0 208/3 1.0 5.75 / 15.0 250 1,2,3,4,5,6

AHU-1 600 0.50 1.39 27.8 / 18.0 80.0 / 67.0 52.8 / 51.6 44.0 / 54.0 5.0 2.9 6 5.8 25.7 55.0 / 95.0 140 / 110 5.0 5.0 1.7 208/3 0.5 3.0 / 15.0 250 1,2,3,4,5,6

EWT/LWT

CFM

E.S.P.

"WC

T.S.P.

"WC

TOTAL/

SENSIBLE MBH

EAT (DB/WB)

ºF

LAT

(DB/WB) ºF

WATER TEMP.

(ºF) WATER PD

FT. MAX.

VELOCITY

FPS, MAX

MIN. NUM. OF

ROWS

GPM

TOTAL

MBH

EAT/LAT ºF EWT/LWT ºF

WATER PD

FT. MAX

VELOCITY

FPS, MAX

GPM V/PH

SUPPLY

HP

MCA/MOP

MARK

SUPPLY FAN COOLING CAPACITY (CHILLED WATER) REHEAT HEATING CAPACITY (HOT WATER) ELECTRICAL

UNIT

WEIGHT

(LBS)

REMARKS

AIR HANDLING UNIT SCHEDULE

9. PROVIDE UNIT WITH RECIRCULATION PUMP AT PREHEAT COIL FOR FREEZE PROTECTION. ALSO PROVIDE 120/1 CIRCUIT FOR PUMP. PUMP IS TO BE SIZED FOR 110% OF PREHEAT COIL PRESSURE DROP. SEE HOT WATER PREHEAT COIL DETAIL AND CONTROLS FOR FURTHER INFORMATION.

8. PROVIDE UNIT WITH 3-POINT POWER CONNECTION. A SINGLE CONNECTION FOR THE SUPPLY FAN, A SINGLE CONNECTION FOR THE EXHAUST FAN AND A SINGLE CONNECTION FOR THE MARINE LIGHTS.

7. UNIT MUST HAVE CROSSFLOW FIXED PLATE TOTAL ENERGY HEAT EXCHANGER, PLENUM-TYPE SUPPLY/EXHAUST FANS, PREHEAT COIL, COOLING COIL, REHEAT COIL AND MARINE LIGHTS IN EACH FAN SECTIONS.

6. PROVIDE 6000 HR SALT SPRAY PROTECTIVE COATING ON THE PREHEAT, COOLING AND REHEAT COILS.

5. CONTRACTOR MUST VERIFY THAT UNIT CAN BE INSTALLED IN LOCATION SHOWN ON DRAWINGS PRIOR TO SUBMITTING FOR APPROVAL.

4. PROVIDE UNIT WITH VERTICAL SUPPLY DISCHARGE DUCT CONNECTION AND HORIZONTAL EXHAUST & OUTSIDE AIR DUCT CONNECTIONS. UNIT MUST HAVE 2" DOUBLE WALL CONSTRUCTION.

3. PROVIDE WITH CLASS 1A LOW LEAKAGE DAMPERS ON THE EXHAUST AND OUTSIDE AIR INTAKE UNIT CONNECTIONS.

2. PROVIDE PREMIUM EFFICIENCY MOTORS FOR SUPPLY AND EXHAUST FANS, COMPATIBLE WITH VARIABLE FREQUENCY DRIVES.

1. PROVIDE WITH 2" MERV 8 FILTERS ON THE EXHAUST AND 2" MERV 8 PREFILTERS & 2" MERV 13 FINAL FILTERS ON THE OUTSIDE AIR INTAKE.

REMARKS:

DOAS-6 2325 1.50 4.20 2000 1.50 2.82 84.2 22.0 / 50.0 140 / 110 5.0 2 5.7 220.2 / 83.14 84.0 / 78.6 52.0 / 51.0 44.0 / 54.0 5.0 4 6 43.9 86.3 52.0 / 85.0 140 / 110 5.0 2 5.8 93.0 78.0 76.0 50.0 84.6 74.5 22.0 70.0 35.0 48.6 40.5 50.0% 208/3 2.4 1.4 1.63 / 15.0 115/1 1400 1,2,3,4,5,6,7,8,9

DOAS-5 2550 1.50 4.41 2000 1.50 2.77 88.2 22.0 / 50.0 140 / 110 5.0 2 6.0 242.0 / 91.4 84.0 / 78.6 52.0 / 51.0 44.0 / 54.0 5.0 5 6 48.2 91.5 52.0 / 85.0 140 / 110 5.0 2 6.2 93.0 78.0 76.0 50.0 84.9 74.7 22.0 70.0 35.0 47.4 39.8 50.0% 208/3 2.8 1.4 1.63 / 15.0 115/1 1400 1,2,3,4,5,6,7,8,9

DOAS-4 2300 1.50 4.20 2000 1.50 2.82 84.2 22.0 / 50.0 140 / 110 5.0 2 5.7 220.2 / 83.14 84.0 / 78.6 52.0 / 51.0 44.0 / 54.0 5.0 4 6 43.9 86.3 52.0 / 85.0 140 / 110 5.0 2 5.8 93.0 78.0 76.0 50.0 84.6 74.5 22.0 70.0 35.0 48.6 40.5 50.0% 208/3 2.4 1.4 1.63 / 15.0 115/1 1400 1,2,3,4,5,6,7,8,9

DOAS-3 2550 1.50 4.41 2000 1.50 2.77 88.2 22.0 / 50.0 140 / 110 5.0 2 6.0 242.0 / 91.4 84.0 / 78.6 52.0 / 51.0 44.0 / 54.0 5.0 5 6 48.2 91.5 52.0 / 85.0 140 / 110 5.0 2 6.2 93.0 78.0 76.0 50.0 84.9 74.7 22.0 70.0 35.0 47.4 39.8 50.0% 208/3 2.8 1.4 1.63 / 15.0 115/1 1400 1,2,3,4,5,6,7,8,9

DOAS-2 2325 1.50 4.20 2000 1.50 2.82 84.2 22.0 / 50.0 140 / 110 5.0 2 5.7 220.2 / 83.14 84.0 / 78.6 52.0 / 51.0 44.0 / 54.0 5.0 4 6 43.9 86.3 52.0 / 85.0 140 / 110 5.0 2 5.8 93.0 78.0 76.0 50.0 84.6 74.5 22.0 70.0 35.0 48.6 40.5 50.0% 208/3 2.4 1.4 1.63 / 15.0 115/1 1400 1,2,3,4,5,6,7,8,9

DOAS-1 2550 1.50 4.41 2000 1.50 2.77 88.2 22.0 / 50.0 140 / 110 5.0 2 6.0 242.0 / 91.4 84.0 / 78.6 52.0 / 51.0 44.0 / 54.0 5.0 5 6 48.2 91.5 52.0 / 85.0 140 / 110 5.0 2 6.2 93.0 78.0 76.0 50.0 84.9 74.7 22.0 70.0 35.0 47.4 39.8 50.0% 208/3 2.8 1.4 1.63 / 15.0 115/1 1400 1,2,3,4,5,6,7,8,9

EWT/LWT DB WB DB %RH DB WB DB DB %RH DB WB

OA RA SA OA RA SACFM

E.S.P.

"WC

T.S.P.

"WC

CFM

E.S.P.

"WC

T.S.P.

"WC

TOTAL

MBH

EAT/LAT ºF

EWT/LWT

ºF

WATER PD

FT. MAX

VELOCITY

FPS, MAX

GPM

TOTAL/

SENSIBLE MBH

EAT (DB/WB)

ºF

LAT

(DB/WB) ºF

WATER TEMP.

(ºF) WATER PD

FT. MAX.

VELOCITY

FPS, MAX

MIN. NUM.

OF ROWS

GPM

TOTAL

MBH

EAT/LAT

ºF

EWT/LWT

ºF

WATER PD

FT. MAX

VELOCITY

FPS, MAX

GPM

SUMMER WINTER

HX

EFFECT.

V/PH

SUPPLY

HP

EXHAUST

HP

MARINE

LIGHTS

MCA/MOP

MARINE

LIGHTS

V/PH

MARK

SUPPLY FAN EXHAUST FAN PREHEAT HEATING CAPACITY (HOT WATER) COOLING CAPACITY (CHILLED WATER) REHEAT HEATING CAPACITY (HOT WATER) TOTAL ENERGY HEAT EXCHANGER ELECTRICAL

UNIT

WEIGHT

(LBS)

REMARKS

DEDICATED OUTSIDE AIR SYSTEM SCHEDULE

PROVIDE WALL MOUNTED CONTROL SWITCH NEAR ENTRANCE.

5. PROVIDE SIDEWALL MOUNTED FAN WITH TEFC MOTOR, MOTORSIDE GUARD, HANGING VIBRATION ISOLATION KIT, WALL SLEEVE, BACKDRAFT DAMPER AND BIRDSCREEN.

4. PROVIDE FAN WITH TEFC MOTOR AND HANGING VIBRATION ISOLATION KIT.

3. FAN MUST OPERATE CONTINUOUSLY.

2. FAN MUST BE TIED TO THERMOSTAT AND HUMIDISTAT.

1. PROVIDE WITH BACKDRAFT DAMPER, TEFC MOTOR AND HANGING VIBRATION ISOLATION KIT.

REMARKS:

EF-5 CORE ELEC & RESTROOMS INLINE 250 0.75 DIRECT 1350 4.5 118 120/1 30 3,4

EF-2,3,4 LAUNDRY ROOMS WALL MOUNT 200 0.25 DIRECT 835 0.3 137 120/1 25 1,2

EF-1 MECHANICAL BLDG PROPELLER 650 0.25 DIRECT 1050 4.4 1/20 HP 120/1 30 5

WATTS V/PH

MARK AREA SERVED TYPE CFM

ESP

(IN H2O)

DRIVE RPM MAX. SONES

ELECTRICAL OPER.WEIGHT

(LBS)

REMARKS

FAN SCHEDULE

6. AUXILARY HEAT SHALL BE LOCKED OUT UNLESS THE HEATING SETPOINT IS UNABLE TO BE MAINTAINED WITH COMPRESSOR RUNNING CONTINUOUSLY IN HEATING MODE. AUXILARY HEAT WILL REMAIN ENERGIZED UNTIL SETPOINT IS

REACHED

5. PROVIDE TAMPER PROOF, FULL ENCLOSURE FOR UNIT. SEPARATE ENCLOSURE TO BE PROVIDED FOR CONDENSATE LINES, ELECTRICAL WIRING AND CONTROLS WITH ACCESS PANEL.

4. THE ROOM SHALL BE PROVIDED WITH A WALL MOUNTED PROGRAMMABLE THERMOSTAT AND INTERFACED WITH THE DDC CONTROL SYSTEM.

3. PROVIDE UNIT WITH WALL SLEEVE, POLYCARBONATE OR STAINLESS STEEL DRAIN PAN, CENTER HOLE CONDENSATE DRAIN KIT AND OUTDOOR GRILLE.

2. PTHP SHOULD BE CORROSION RESISTANT AND FITTED WITH A METAL LIGATURE PROOF SECURITY COVER.

1. PROVIDE PACKAGED TERMINAL HEAT PUMP WITH AUXILIARY ELECTRIC HEAT. HARDWIRE TO ELECTRICAL CONNECTION.

REMARKS:

PTHP-1 SLEEPING ROOMS HEAT PUMP 12.0 320 9.9 350 3.0 KW 3.1 11.8 208/1 100 1,2,3,4,5,6

TOTAL MBH CFM TOTAL MBH CFM AMPS V/PH

MARK AREA SERVED TYPE

COOLING HEATING AUXILARY

ELEC HEAT

DEHUMIDIFICATION

(PINTS/HR)

ELECTRICAL OPER.WEIGHT

(LBS)

REMARKS

PTHP SCHEDULE

5. PROVIDE CONDENSATE PUMP FOR USE WITH UNIT, PROVIDE BACNET MS/TP CAPABILITY, 10 GPH AT 20' HEAD, 1/30 HP, 120/1, 1.5 FLA.

4. DUCTLESS SPLIT SYSTEM MUST BE CAPABLE OF HANDLING 100 FEET OF REFRIGERANT LINE BETWEEN AC AND CU.

3. AHU IS POWERED FROM CONDENSING UNIT.

2. PROVIDE UNIT WITH WALL MOUNTED CONDENSATE PUMP, WIRED TO MOTOR RATED SWITCH.

1. PROVIDE UNIT WITH WIRED WALL MOUNTED THERMOSTAT, AND CLEANABLE TYPE FILTERS.

REMARKS:

DAC-1 2ND FLR COMM AC 450 1.0 R-410A 35 1,2,3,4,5

MARK SERVES TYPE CFM MCA REFRIG. TYPE WEIGHT (LBS) REMARKS

DUCTLESS SPLIT SYSTEM AIR HANDLING UNIT SCHEDULE

2. DUCTLESS SPLIT SYSTEM MUST BE CAPABLE OF HANDLING 100 FEET OF REFRIGERANT LINE BETWEEN AC AND CU.

QUANTITIES.

SALT-HOUR SEACOAST CONSTRUCTION. COATINGS MUST NOT REDUCE UNIT PERFORMANCE BELOW SCHEDULED

1. PROVIDE ALL ACCESSORIES REQUIRED FOR LOW AMBIENT OPERATION TO 0ºF. PROVIDE COIL GUARDS AND 6,000

REMARKS:

DCU-1 2ND FLR COMM 1 1/2 AC 19.8 208/1 11 28 100 1,2

MARK SERVES

NOMINAL

TONS

TYPE SEER VOLT/PH MCA MOCP

WEIGHT

(LBS)

REMARKS

DUCTLESS SPLIT SYSTEM CONDENSING UNIT SCHEDULE

1 PPI Responses 01.17.25

Sheets
M-601 - MECHANICAL SCHEDULES

File details come from the government source that posted it. Updated .