This is a construction drawing showing the fire suppression system plan for the first floor of Building HP505 (BEQ - Bachelor Enlisted Quarters) at Marine Corps Base Camp Lejeune, North Carolina. The drawing details sprinkler system requirements throughout the building, including sleeping rooms, mechanical rooms, plumbing chases, laundry facilities, and corridors.
The plan specifies key requirements including: sprinklers throughout all sleeping rooms per NFPA 13R standards, dry sidewall sprinklers for unconditioned spaces like the dryer chase and corridor, heat trace systems for wet pipe sprinkler piping crossing the corridor, backflow preventer test connections, fire department connections, RPZ backflow preventer assembly, and floor control assemblies for the first floor sprinkler system. The drawing was prepared by Jensen Hughes, approved by professional engineer Aaron P. Freid (VA License #044409), and includes construction contract number N40085-23-B-0034. A revision for PPI updates is noted as of January 17, 2025.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Amend 0016.pdf | ||
| Amend 0015.pdf | ||
| Amend 0014.pdf | ||
| Amend 0013.pdf | ||
| 60040360.pdf | ||
| 60040345.pdf | ||
| 60040454.pdf | ||
| 60040373.pdf | ||
| 60040328.pdf | ||
| 60040433.pdf | ||
| 60040414.pdf | ||
| N4008523B0034 SpecsAsOne Addendum 01.pdf | ||
| 60040411.pdf | ||
| 60040407.pdf | ||
| 60040434.pdf | ||
| 60040420.pdf | ||
| 60040412.pdf | ||
| 60040343.pdf | ||
| Amend 0012.pdf | ||
| 60040362.pdf | ||
| 60040342.pdf | ||
| 60040447.pdf | ||
| 60040408.pdf | ||
| 60040436.pdf | ||
| 60040424.pdf | ||
| 60040329.pdf | ||
| 60040422.pdf | ||
| 60040366.pdf | ||
| 60040376.pdf | ||
| 60040359.pdf | ||
| Amend 0011.pdf | ||
| Amend 0010.pdf | ||
| Amend 0009.pdf | ||
| Amend 0008.pdf | ||
| Amend 0007.pdf | ||
| Amend 0006.pdf | ||
| Amend 0005.pdf | ||
| Amend 0004.pdf | ||
| Amend 0003.pdf | ||
| Amend 0002.pdf | ||
| Amend 0001.pdf | ||
| 23-0034 Asbestos and Lead Assessment.pdf | ||
| 23-0034 Appendix D.pdf | ||
| N4008523B0034 DWGs.pdf | ||
| RFP 230034.pdf | ||
| N4008523B0034 SPECS.pdf |
Show all 46
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
101A
100A
107A
104A
109A
108A
113A
112A
117A
141 142
121A
120A
125A
FX101
B1
FX101
B2
FX101
B3
100 102
101 103
OH
RES RES
RESRES
MECHANICAL
2 2
2 2
MECHANICAL
F C
A
OH
OH
OH
STORAGE
STAIR
LAUNDRY
TOILET
ELECTRICAL
CORRIDOR
DUTY
LAUNDRY
OH
OH
OH
OH
LH
LH
LH
KEY NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
PROVIDE SPRINKLERS THROUGHOUT THE OUTLINED AREA.
HAZARD CLASSIFICATION IS TYPCIAL FOR SLEEPING ROOMS.
SPRINKLERS MUST BE PROVIDED THROUGHOUT THE
SLEEPING ROOMS AS REQUIRED BY NFPA 13R.
HAZARD CLASSIFICATION IS TYPCIAL FOR MECHANICAL
ROOMS.
HAZARD CLASSIFICATION IS TYPCIAL FOR PLUMBING CHASES.
PROVIDE BACKFLOW PREVENTER TEST CONNECTION.
PROVIDE FIRE DEPARTMENT CONNECTION.
PROVIDE RPZ BACKFLOW PREVENTER ASSEMBLY.
PROVIDE FLOOR CONTROL ASSEMBLIES FOR THE FIRST
FLOOR SPINKLER SYSTEM.
THE DRYER CHASE IS AN UNCONDITIONED SPACE. PROVIDE
DRY SIDEALL SPRINKLERS TO PROTECT THE DRYER CHASE.
WET PIPE SPRINKLER PIPING IS PROHIBITEDIN THE DRYER
CHASE.
THE CORRIDOR IS AN UNCONDITIONED SPACE. PROVIDE DRY
SIDEWALL SPRINKLERS TO PROTECT THE CORRIDOR. WET
PIPE SPRINKLER PIPING CROSSING THE CORRIDOR MUST BE
HEAT TRACED WITH AN APPROVED HEAT TRACE SYSTEM.
GENERAL SHEET NOTES:
1. FOR FIRE SUPPRESSION GENERAL NOTES AND LEGEND,
SEE SHEET FX001.
Lic. No. 044409
AARON P FREIDC
O M M O
N W
EA
LTHOF
V
IR
G
IN
I A
P R O F
E
SSIONAL EN
G
IN
E E R
29 MAY 2024
F ile
P ri n t
SYM. DESCRIPTION DATE APP.
REVISIONS
DR.
DES.
CHK.
SUBMITTED BY:
DESIGN DIR.
APPROVED: PWO OR OICC
SATISFACTORY TO:
DATE
DATE
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND
CAMP LEJEUNE, NORTH CAROLINA
MARINE CORPS BASE
SIZE CODE IDENT. NO. NAVFAC DRAWING NO.
E1 80091
CONSTR. CONTR. NO.
AS NOTEDSCALE SHEET
M B
F A
N O
SPEC.
C U s e rs \a fr e id
\O n e
D ri v e
J e n s e n H u g h e s \D o c u m e n ts \2
F
IR
E a fr e id
.r v t
/1
/2
:4 :2
P
M
FX101
AHE
KEC
MORGAN HUNTER
APF
APF
REPAIR BEQ HP505
FIRE SUPPRESSION FIRST FLOOR PLAN - CONSTRUCTION
60040406 N40085-23-B-0034
SCALE: 3/32" = 1'-0"
D1
FIRE SUPPRESSION FIRST FLOOR PLAN - CONSTRUCTION
N
GRAPHIC SCALE: 1/8"=1'-0"
8' 0 4' 8' 16'
GRAPHIC SCALE: 3/32"=1'-0"
8' 0 4' 8' 16'
SCALE: 1/8" = 1'-0"
B1
FIRST FLOOR PARTIAL PLAN
SCALE: 1/8" = 1'-0"
B2
FIRST FLOOR PARTIAL PLAN
SCALE: 1/8" = 1'-0"
B3
FIRST FLOOR PARTIAL PLAN
1 PPI UPDATES 01/17/25 APF
File details come from the government source that posted it. Updated .