60040420.pdf
PDF 397 KB Posted
- Attached to
- Repair BEQ HP505
- Solicitation number
- N4008525R2549
About this file
This file contains plumbing detail drawings and specifications for the Repair BEQ HP505 project at Marine Corps Base Camp Lejeune, North Carolina. The drawings include detailed technical specifications for floor drains, roof vents, backflow preventers (BFP-1 and BFP-2), shock absorbers, pipe penetrations through rated and non-rated walls, water heater installations, and pipe designation standards.
The drawings specify requirements such as a 4" RPZ type backflow preventer compliant with Camp Lejeune and Division of Water Resources requirements, turbine type water meters with remote monitoring capability, specific pipe sizing and materials (including Type K copper for certain components), and detailed installation parameters for water heaters including temperature settings (140°F at heater, 110°F mixed) and recirculation systems. The document includes a comprehensive pipe labeling system with color coding requirements: blue/white for compressed air and green/white for water systems. The drawings are part of Naval Facilities Engineering Systems Command (NAVFAC) contract N40085-23-B-0034, specification section P-501.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Amend 0016.pdf | ||
| Amend 0015.pdf | ||
| Amend 0014.pdf | ||
| Amend 0013.pdf | ||
| 60040360.pdf | ||
| 60040406.pdf | ||
| 60040345.pdf | ||
| 60040454.pdf | ||
| 60040373.pdf | ||
| 60040328.pdf | ||
| 60040433.pdf | ||
| 60040414.pdf | ||
| N4008523B0034 SpecsAsOne Addendum 01.pdf | ||
| 60040411.pdf | ||
| 60040407.pdf | ||
| 60040434.pdf | ||
| 60040412.pdf | ||
| 60040343.pdf | ||
| Amend 0012.pdf | ||
| 60040362.pdf | ||
| 60040342.pdf | ||
| 60040447.pdf | ||
| 60040408.pdf | ||
| 60040436.pdf | ||
| 60040424.pdf | ||
| 60040329.pdf | ||
| 60040422.pdf | ||
| 60040366.pdf | ||
| 60040376.pdf | ||
| 60040359.pdf | ||
| Amend 0011.pdf | ||
| Amend 0010.pdf | ||
| Amend 0009.pdf | ||
| Amend 0008.pdf | ||
| Amend 0007.pdf | ||
| Amend 0006.pdf | ||
| Amend 0005.pdf | ||
| Amend 0004.pdf | ||
| Amend 0003.pdf | ||
| Amend 0002.pdf | ||
| Amend 0001.pdf | ||
| 23-0034 Asbestos and Lead Assessment.pdf | ||
| 23-0034 Appendix D.pdf | ||
| N4008523B0034 DWGs.pdf | ||
| RFP 230034.pdf | ||
| N4008523B0034 SPECS.pdf |
Show all 46
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CONCRETE SLAB, SEE
ARCH. AND STRUCT.
DWGS FOR DETAILS
FLOOR DRAIN
PROVIDE TRAP GUARD TO ENSURE
SEWER GASES CANNOT ESCAPE.
SANITARY PIPE
DEEP SEAL "P" TRAP FOR ROOF DETAILS SEE
ARCH. & STRUCT. DWGS.
VENT PIPE SEE FLOOR
PLAN/RISER FOR SIZES
SCREW TO
ROOF DECK
WOOD BLOCK
GALVANIZED METAL FLASHING
HOOD W/ STAINLESS STEEL
CLAMP
WEATHERPROOF
SEALANT
GALVANIZED METAL
COUNTER SECURED TO
ROOF MEMBRANE
W/ ROOF MASTIC
FIN. FLOOR
PROVIDE PROPER
SUPPORT FOR
BACKFLOW
PREVENTER DEVICE
THIS DETAIL APPLIES
TO THE MAIN DOMESTIC
BACKFLOW ONLY (BFP-1)
PROVIDE PRESSURE
REDUCING VALVE AFTER
BACKFLOW PREVENTER.
SET PRV @ 80 PSI.
ROUTE TO
FLOOR DRAIN
(INDIRECT)
SEE SITE PLAN FOR
CONTINUATION
PROVIDE STRAINER
12" MIN -
48" MAX
4" RPZ TYPE BACKFLOW PREVENTER.
COMPLY WITH CAMP LEJEUNE AND
DIVISION OF WATER RESOURCES
(DWR) REQUIREMENTS.
AWWA C701 TURBINE TYPE WITH
REGISTER READING IN LITERS
AND U.S. GALLONS WITH REMOTE
READY CAPABILITY TO DDC FOR
MONITORING.
BARREL FABRICATED OF HARD DRAWN
TYPE "K" COPPER
PISTON TO PROVIDE A PERMANENT
MECHANICAL BARRIER BETWEEN
FLUID AND PRE-LOAD AIR CHARGE
BRASS FREE TURNING PISTON ASTM
B-16 WITH O-RINGS
JOINTS TO BE MADE WITH 95-5
LEAD FREE SOLDER.
BRASS THREADED ADAPTOR
A
B
NPT
SIZE
P.D.I.
SYMBOL
FIXTURE UNIT
RATINGS
A SIZE
1/2" A 1 - 11 5"
B SIZE
1/2"
3/4" B 12 - 32 5" 3/4"
1" C 33 - 60 7" 1" 1-1/4" D 60 - 113 7" 1-1/4"
1-1/2" E 114 - 154 9" 1-1/2"
2" F 155 - 330 9" 2"
PIPE SUPPORT
FRAME
BASE PLATE W/
ANCHOR
PLAN
M A
X
FIN. FLOOR
M
IN
1-1/4" RPZ TYPE
BACKFLOW
PREVENTER.
"BFP-2"
1-1/4" SEE PLANS FOR
CONTINUATION
ROUTE TO FLOOR
DRAIN (INDIRECT)
U-BOLT
(TYP)
STUD
ANGLE
ELEVATION
PRESSURE
GAUGE
1-1/4" MAKE-UP WATER FOR HVAC.
SEE MECH. DWGS FOR CONTINUATION
3" DIAMETER STD.
PIPE SUPPORT POST.
(TYP. OF 2)
1/4" STIFFENER
PLATE EA. SIDE
1/2"x10"x10" BASE PLATE W/
(4) 5/8" EPOXY ADHESIVE
ANCHORS, MIN. EMBED = 3"
-1
/4
SHUTOFF
VALVE
AWWA C701 TURBINE TYPE WITH
REGISTER READING IN LITERS
AND U.S. GALLONS WITH REMOTE
READY CAPABILITY TO DDC FOR
MONITORING.
PIPE
W-L-5039
PIPE
W-J-1010
THROUGH STUD WALL
UL SYSTEM NUMBER
THROUGH CONCRETE WALL
RATED WALL
U.L. APPROVED SLEEVE
SHEET METAL SCREW
4"O.C. PIPING
APPROVED & LISTED
FIRE SAFETY
MATERIAL - U.L.
LISTED
INSULATION
WHERE
APPLICABLE
AT INSULATED PIPE
FIRE CAULK ALL
AROUND (BOTH SIDES)
WALL STRUCTURE
PIPE
SIZE TO ACCOMMODATE
INSULATION AS REQUIRED
SCHEDULE 40 STEEL SLEEVE
EXPANSION TANK
COLD WATER
SUPPLY
HOT WATER OUT
TO FIXTURES
PIPE T&P TO DRAIN.
(TYP. OF 2)
BUILDING
RECIRCULATION LOOP
RETURN
FINISHED FLOOR
110°
ISOLATION
VALVE (TYP)
THERMOSTATIC MIXING VALVE:
DESIGN PARAMETER: RATED FOR 1
GPM MINIMUM FLOW AND 135 GPM
MAXIMUM FLOW
HEAT
TRAP
UNION
CHECK VALVE
(TYP)
140° 140° 140°
0°
D-RCP-1
1/3 HP, 115V, 10 GPM,
IN-LINE PUMP.
ET-1
REGULATOR
NEUTRALIZATION KIT (TO REDUCE CONDENSATE PH),
SIZED TO RECEIVE CONDENSATE FROM TWO (2) WHS.
FLOOR MOUNT AND PIPE TO NEAREST FLOOR DRAIN PER
MANUFACTURER'S INSTALLATION INSTRUCTIONS.
CONDENSATE DRAIN PIPING PER
MANUFACTURER'S INSTALLATION
INSTRUCTIONS.
3"
1-1/2"
3"
3"3"
1- 1/
2"
3" 3"
3" 3"
3"
3" 3" 3"
NATURAL GAS PIPING.
SEE MECHANICAL PLANS
FOR SIZING.
3"
1- 1/
2"
1-1/2"1-1/2"
1-1/2" 1-1/2"
4" HOUSEKEEPING PAD (TYP)
ENSURE NEUTRALIZATION TANK CAN BE REFILLED
WITHOUT DISCONNECTING PIPEWORK
UNION
UNION
ADD POINTS AS NEEDED TO
CONTROL THE RECIRC
PUMP WITH THE DDC.
1.25" HIGH LETTERS (MINIMUM)
12" OR LONGER SNAP-ON OR WRAP-AROUND
POLYESTER LABELS WITH ADHESIVE STRIP(S)
FLOW DIRECTION ARROW
DCW
DCW
2" TO 6" O.D. PIPING AND ABOVE (O.D. INCLUDES INSULATION WHERE REQUIRED)
DHW
DHW
.75" HIGH LETTERS (MINIMUM)
8" OR LONGER SNAP-ON OR WRAP-AROUND
POLYESTER LABELS WITH ADHESIVE STRIP(S)
FLOW DIRECTION ARROW
1.5" O.D. PIPING (O.D. INCLUDES INSULATION WHERE REQUIRED)
LABEL TEXT AND COLOR LEGEND
PIPE SYSTEM
DESCRIPTION
LETTER
COLOR
BACKGROUND
COLOR
COMPRESSED AIR BLUE WHITE
COLD WATER SUPPLY GREEN WHITE
HOT WATER SUPPLY GREEN WHITE
HOT WATER RETURN GREEN WHITE
SYM. DESCRIPTION DATE APP.
REVISIONS
DR.
DES.
CHK.
SUBMITTED BY:
DESIGN DIR.
APPROVED: PWO OR OICC
SATISFACTORY TO:
DATE
DATE
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND
CAMP LEJEUNE, NORTH CAROLINA
MARINE CORPS BASE
SIZE CODE IDENT. NO. NAVFAC DRAWING NO.
E1 80091
CONSTR. CONTR. NO.
AS NOTEDSCALE SHEET
M B
F A
N O
SPEC.
P-501
DLB
DJG
PRC
MORGAN HUNTER
PRC
REPAIR BEQ HP505
PLUMBING DETAILS
60040420 N40085-23-B-0034
NTS
E1
FLOOR DRAIN DETAIL
NTS
E2
VENT THRU ROOF DETAIL
NTS
E3
BACKFLOW PREVENTER DETAIL (BFP-1)
NTS
E4
SHOCK ABSORBER DETAIL
NTS
C1
BACKFLOW PREVENTER DETAIL (BFP-2)
NTS
C3
PIPE THRU FIRE WALL DETAIL
NTS
E5
PIPE THRU NON-RATED WALL DETAIL
NTS
B4
WATER HEATER DETAIL (D-WH-1)
NTS
C4
PIPE DESIGNATOR DETAIL
1 PPI RESPONSES 01.17.25
user.dj.german Model
File details come from the government source that posted it. Updated .