60040408.pdf

PDF 382 KB Posted

Attached to
Repair BEQ HP505
Solicitation number
N4008525R2549
Issued by

About this file

This is a fire suppression system floor plan drawing for the third floor of Building HP505 (BEQ) at Marine Corps Base Camp Lejeune, North Carolina. The drawing shows the layout and specifications for sprinkler system coverage throughout the floor.

The plan details specific requirements including: sprinkler coverage throughout all sleeping rooms per NFPA 13R standards, dry sidewall sprinklers for the unconditioned corridor and stair shaft spaces, floor control assembly locations, and heat trace requirements for wet pipe sprinkler piping crossing the corridor. The drawing includes three partial floor plans at 1/8"=1'-0" scale and one full floor plan at 3/32"=1'-0" scale, showing room layouts with numbered spaces including sleeping rooms, a lounge, corridor, linen storage, electrical room, toilet, laundry, and stair areas. The drawing was prepared by Jensen Hughes, signed by Professional Engineer Aaron P. Freid (VA License #044409), and includes recent PPI updates dated January 17, 2025.

View the file

Other files

File Type Posted
Amend 0016.pdf PDF
Amend 0015.pdf PDF
Amend 0014.pdf PDF
Amend 0013.pdf PDF
60040360.pdf PDF
60040406.pdf PDF
60040345.pdf PDF
60040454.pdf PDF
60040373.pdf PDF
60040328.pdf PDF
60040433.pdf PDF
60040414.pdf PDF
N4008523B0034 SpecsAsOne Addendum 01.pdf PDF
60040411.pdf PDF
60040407.pdf PDF
60040434.pdf PDF
60040420.pdf PDF
60040412.pdf PDF
60040343.pdf PDF
Amend 0012.pdf PDF
60040362.pdf PDF
60040342.pdf PDF
60040447.pdf PDF
60040436.pdf PDF
60040424.pdf PDF
60040329.pdf PDF
60040422.pdf PDF
60040366.pdf PDF
60040376.pdf PDF
60040359.pdf PDF
Amend 0011.pdf PDF
Amend 0010.pdf PDF
Amend 0009.pdf PDF
Amend 0008.pdf PDF
Amend 0007.pdf PDF
Amend 0006.pdf PDF
Amend 0005.pdf PDF
Amend 0004.pdf PDF
Amend 0003.pdf PDF
Amend 0002.pdf PDF
Amend 0001.pdf PDF
23-0034 Asbestos and Lead Assessment.pdf PDF
23-0034 Appendix D.pdf PDF
N4008523B0034 DWGs.pdf PDF
RFP 230034.pdf PDF
N4008523B0034 SPECS.pdf PDF
Show all 46

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

301A

300A

305A

304A

309A

308A

313A

312A

317A

316A

341 342 343

FX103

B1

FX103

B2

FX103

B3

300 302

301 303

OH

RES RES

RESRES

Room

2 2

2 2

Room

F C

A

OH

OH

OH

LOUNGE

CORRIDOR

LINEN STORAGE

ELECTRICAL

TOILET

LAUNDRY

STAIR

STORAGE

OH

OH

LH

OH

LH

LH

OH

KEY NOTES

1.

2.

3.

4.

5.

6.

7.

PROVIDE SPRINKLERS THROUGHOUT THE OUTLINED AREA.

HAZARD CLASSIFICATION IS TYPCIAL FOR SLEEPING ROOMS.

SPRINKLERS MUST BE PROVIDED THROUGHOUT THE

SLEEPING ROOMS AS REQUIRED BY NFPA 13R.

HAZARD CLASSIFICATION IS TYPCIAL FOR MECHANICAL

ROOMS.

HAZARD CLASSIFICATION IS TYPCIAL FOR PLUMBING CHASES.

PROVIDE FLOOR CONTROL ASSEMBLY.

THE CORRIDOR IS AN UNCONDITIONED SPACE. PROVIDE DRY

SIDEWALL SPRINKLERS TO PROTECT THE CORRIDOR. WET

PIPE SPRINKLER PIPING CROSSING THE CORRIDOR MUST BE

HEAT TRACED WITH AN APPROVED HEAT TRACE SYSTEM.

THE STAIR SHAFT IS AN UNCONDITIONED SPACE. PROVIDE

DRY SIDEWALL SPRINKLERS TO PROTECT THE TOP OF THE

STAIR SHAFT. WET PIPE SPRINKLER PIPING IS PROHIBITED IN

THE STAIR SHAFT.

GENERAL SHEET NOTES:

1. FOR FIRE SUPPRESSION GENERAL NOTES AND LEGEND,

SEE SHEET FX001.

Lic. No. 044409

AARON P FREIDC

O M M O

N W

EA

LTHOF

V

IR

G

IN

I A

P R O F

E

SSIONAL EN

G

IN

E E R

29 MAY 2024

F ile

P ri n t

SYM. DESCRIPTION DATE APP.

REVISIONS

DR.

DES.

CHK.

SUBMITTED BY:

DESIGN DIR.

APPROVED: PWO OR OICC

SATISFACTORY TO:

DATE

DATE

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND

CAMP LEJEUNE, NORTH CAROLINA

MARINE CORPS BASE

SIZE CODE IDENT. NO. NAVFAC DRAWING NO.

E1 80091

CONSTR. CONTR. NO.

AS NOTEDSCALE SHEET

M B

F A

N O

SPEC.

C U s e rs \a fr e id

\O n e

D ri v e

J e n s e n H u g h e s \D o c u m e n ts \2

F

IR

E a fr e id

.r v t

/1

/2

:4 :2

P

M

FX103

AHE

KEC

MORGAN HUNTER

APF

APF

REPAIR BEQ HP505

FIRE SUPPRESSION THIRD FLOOR PLAN - CONSTRUCTION

60040408 N40085-23-B-0034

GRAPHIC SCALE: 1/8"=1'-0"

8' 0 4' 8' 16'

GRAPHIC SCALE: 3/32"=1'-0"

8' 0 4' 8' 16'

N

SCALE: 3/32" = 1'-0"

D1

FIRE SUPPRESSION THIRD FLOOR PLAN - CONSTRUCTION

SCALE: 1/8" = 1'-0"

B1

THIRD FLOOR PARTIAL PLAN

SCALE: 1/8" = 1'-0"

B2

THIRD FLOOR PARTIAL PLAN

SCALE: 1/8" = 1'-0"

B3

THIRD FLOOR PARTIAL PLAN

1 PPI UPDATES 01/17/25 APF