This is a fire suppression system floor plan drawing for the third floor of Building HP505 (BEQ) at Marine Corps Base Camp Lejeune, North Carolina. The drawing shows the layout and specifications for sprinkler system coverage throughout the floor.
The plan details specific requirements including: sprinkler coverage throughout all sleeping rooms per NFPA 13R standards, dry sidewall sprinklers for the unconditioned corridor and stair shaft spaces, floor control assembly locations, and heat trace requirements for wet pipe sprinkler piping crossing the corridor. The drawing includes three partial floor plans at 1/8"=1'-0" scale and one full floor plan at 3/32"=1'-0" scale, showing room layouts with numbered spaces including sleeping rooms, a lounge, corridor, linen storage, electrical room, toilet, laundry, and stair areas. The drawing was prepared by Jensen Hughes, signed by Professional Engineer Aaron P. Freid (VA License #044409), and includes recent PPI updates dated January 17, 2025.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Amend 0016.pdf | ||
| Amend 0015.pdf | ||
| Amend 0014.pdf | ||
| Amend 0013.pdf | ||
| 60040360.pdf | ||
| 60040406.pdf | ||
| 60040345.pdf | ||
| 60040454.pdf | ||
| 60040373.pdf | ||
| 60040328.pdf | ||
| 60040433.pdf | ||
| 60040414.pdf | ||
| N4008523B0034 SpecsAsOne Addendum 01.pdf | ||
| 60040411.pdf | ||
| 60040407.pdf | ||
| 60040434.pdf | ||
| 60040420.pdf | ||
| 60040412.pdf | ||
| 60040343.pdf | ||
| Amend 0012.pdf | ||
| 60040362.pdf | ||
| 60040342.pdf | ||
| 60040447.pdf | ||
| 60040436.pdf | ||
| 60040424.pdf | ||
| 60040329.pdf | ||
| 60040422.pdf | ||
| 60040366.pdf | ||
| 60040376.pdf | ||
| 60040359.pdf | ||
| Amend 0011.pdf | ||
| Amend 0010.pdf | ||
| Amend 0009.pdf | ||
| Amend 0008.pdf | ||
| Amend 0007.pdf | ||
| Amend 0006.pdf | ||
| Amend 0005.pdf | ||
| Amend 0004.pdf | ||
| Amend 0003.pdf | ||
| Amend 0002.pdf | ||
| Amend 0001.pdf | ||
| 23-0034 Asbestos and Lead Assessment.pdf | ||
| 23-0034 Appendix D.pdf | ||
| N4008523B0034 DWGs.pdf | ||
| RFP 230034.pdf | ||
| N4008523B0034 SPECS.pdf |
Show all 46
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
301A
300A
305A
304A
309A
308A
313A
312A
317A
316A
341 342 343
FX103
B1
FX103
B2
FX103
B3
300 302
301 303
OH
RES RES
RESRES
Room
2 2
2 2
Room
F C
A
OH
OH
OH
LOUNGE
CORRIDOR
LINEN STORAGE
ELECTRICAL
TOILET
LAUNDRY
STAIR
STORAGE
OH
OH
LH
OH
LH
LH
OH
KEY NOTES
1.
2.
3.
4.
5.
6.
7.
PROVIDE SPRINKLERS THROUGHOUT THE OUTLINED AREA.
HAZARD CLASSIFICATION IS TYPCIAL FOR SLEEPING ROOMS.
SPRINKLERS MUST BE PROVIDED THROUGHOUT THE
SLEEPING ROOMS AS REQUIRED BY NFPA 13R.
HAZARD CLASSIFICATION IS TYPCIAL FOR MECHANICAL
ROOMS.
HAZARD CLASSIFICATION IS TYPCIAL FOR PLUMBING CHASES.
PROVIDE FLOOR CONTROL ASSEMBLY.
THE CORRIDOR IS AN UNCONDITIONED SPACE. PROVIDE DRY
SIDEWALL SPRINKLERS TO PROTECT THE CORRIDOR. WET
PIPE SPRINKLER PIPING CROSSING THE CORRIDOR MUST BE
HEAT TRACED WITH AN APPROVED HEAT TRACE SYSTEM.
THE STAIR SHAFT IS AN UNCONDITIONED SPACE. PROVIDE
DRY SIDEWALL SPRINKLERS TO PROTECT THE TOP OF THE
STAIR SHAFT. WET PIPE SPRINKLER PIPING IS PROHIBITED IN
THE STAIR SHAFT.
GENERAL SHEET NOTES:
1. FOR FIRE SUPPRESSION GENERAL NOTES AND LEGEND,
SEE SHEET FX001.
Lic. No. 044409
AARON P FREIDC
O M M O
N W
EA
LTHOF
V
IR
G
IN
I A
P R O F
E
SSIONAL EN
G
IN
E E R
29 MAY 2024
F ile
P ri n t
SYM. DESCRIPTION DATE APP.
REVISIONS
DR.
DES.
CHK.
SUBMITTED BY:
DESIGN DIR.
APPROVED: PWO OR OICC
SATISFACTORY TO:
DATE
DATE
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND
CAMP LEJEUNE, NORTH CAROLINA
MARINE CORPS BASE
SIZE CODE IDENT. NO. NAVFAC DRAWING NO.
E1 80091
CONSTR. CONTR. NO.
AS NOTEDSCALE SHEET
M B
F A
N O
SPEC.
C U s e rs \a fr e id
\O n e
D ri v e
J e n s e n H u g h e s \D o c u m e n ts \2
F
IR
E a fr e id
.r v t
/1
/2
:4 :2
P
M
FX103
AHE
KEC
MORGAN HUNTER
APF
APF
REPAIR BEQ HP505
FIRE SUPPRESSION THIRD FLOOR PLAN - CONSTRUCTION
60040408 N40085-23-B-0034
GRAPHIC SCALE: 1/8"=1'-0"
8' 0 4' 8' 16'
GRAPHIC SCALE: 3/32"=1'-0"
8' 0 4' 8' 16'
N
SCALE: 3/32" = 1'-0"
D1
FIRE SUPPRESSION THIRD FLOOR PLAN - CONSTRUCTION
SCALE: 1/8" = 1'-0"
B1
THIRD FLOOR PARTIAL PLAN
SCALE: 1/8" = 1'-0"
B2
THIRD FLOOR PARTIAL PLAN
SCALE: 1/8" = 1'-0"
B3
THIRD FLOOR PARTIAL PLAN
1 PPI UPDATES 01/17/25 APF