60040373.pdf

PDF 144 KB Posted

Attached to
Repair BEQ HP505
Solicitation number
N4008525R2549
Issued by

About this file

This is an architectural drawing sheet (A-501) showing detailed wall, ceiling, and roof assembly specifications for a Bachelor Enlisted Quarters (BEQ) building repair project at Marine Corps Base Camp Lejeune, North Carolina. The drawing includes construction details for various wall assemblies including 8" CMU exterior walls, 4"/6"/8" masonry partitions, and metal stud interior walls with specific gauges and spacing requirements.

The sheet provides detailed specifications for ceiling systems, including suspended acoustical tile ceilings with 15/16" exposed grid systems and suspended gypsum board ceilings with steel framing. Roof assembly details are shown for both the main BEQ building and mechanical building, featuring standing seam metal roofing, multiple layers of rigid insulation, ice & water shield, and structural metal roof decking. The drawing also includes a slab patch detail and existing roof/attic detail. All assemblies are drawn to scale (1-1/2"=1'-0" or 3"=1'-0") with specific dimensions, materials, and installation requirements clearly noted.

View the file

Other files

File Type Posted
Amend 0016.pdf PDF
Amend 0015.pdf PDF
Amend 0014.pdf PDF
Amend 0013.pdf PDF
60040360.pdf PDF
60040406.pdf PDF
60040345.pdf PDF
60040454.pdf PDF
60040328.pdf PDF
60040433.pdf PDF
60040414.pdf PDF
N4008523B0034 SpecsAsOne Addendum 01.pdf PDF
60040411.pdf PDF
60040407.pdf PDF
60040434.pdf PDF
60040420.pdf PDF
60040412.pdf PDF
60040343.pdf PDF
Amend 0012.pdf PDF
60040362.pdf PDF
60040342.pdf PDF
60040447.pdf PDF
60040408.pdf PDF
60040436.pdf PDF
60040424.pdf PDF
60040329.pdf PDF
60040422.pdf PDF
60040366.pdf PDF
60040376.pdf PDF
60040359.pdf PDF
Amend 0011.pdf PDF
Amend 0010.pdf PDF
Amend 0009.pdf PDF
Amend 0008.pdf PDF
Amend 0007.pdf PDF
Amend 0006.pdf PDF
Amend 0005.pdf PDF
Amend 0004.pdf PDF
Amend 0003.pdf PDF
Amend 0002.pdf PDF
Amend 0001.pdf PDF
23-0034 Asbestos and Lead Assessment.pdf PDF
23-0034 Appendix D.pdf PDF
N4008523B0034 DWGs.pdf PDF
RFP 230034.pdf PDF
N4008523B0034 SPECS.pdf PDF
Show all 46

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

3 ROWS OF CHANNEL

STIFFENERS, MIN

ACOUSTICAL INSULATION

3-5/8" 20 GAUGE METAL

STUDS @ 16" O.C.

3 5/8"

1/2" CEMENT BOARD

SHEATHING EACH SIDE

BRICK VENEER

R-5 RIGID INSULATION

CAVITY AND AIR SPACE

AIR AND MOISTURE BARRIER

CONCRETE MASONRY UNIT

HORIZONTAL JOINT REINFORCING

AT 1'-4" ON CENTER

1'-1 1/2"

3 5/8" 7 5/8"

HORIZONTAL JOINT

REINFORCEMENT AT 1'-4" ON

CENTER

CONCRETE MASONRY UNITS

3 5/8"

3 ROWS OF CHANNEL

STIFFENERS, MIN

ACOUSTICAL INSULATION

3-5/8" 20 GAUGE METAL

STUDS @ 16" O.C.

5/8" ABUSE RESISTANT

GYPSUM BOARD ONE

SIDE

3 5/8"

1/2" SMOOTH BARS x 18"

LONG AT 12" ON CENTER -

GREASE BAR IN NEW

CONCRETE AND EPOXY BAR

IN EXISTING CONCRETE

EXISTING

CONCRETE

NEW

CONCRETE

6" 6"

15/16" 7/8"

HANGER WIRE TO

STRUCTURE ABOVE

LAY-IN

ACOUSTICAL

TILE

WALL

BULB TEE

EXPOSED GRID

SYSTEM

FIELD SECTION PERIMETER SECTION

5/8" MOISTURE RESISTANT

GYPSUM BOARD CEILING.

FINISH JOINTS AND PAINT.

VERTICAL WIRES AT

4'-0" ON CENTER

WIRES SPLAYED AT 90° AT 8'-0" ON

CENTER ALONG MAIN RUNNERS

AND WITHIN 2" OF A CROSS

RUNNER

SUSPENDED STEEL FRAMING SYSTEM

OF HEAVY DUTY 1 1/2" MAIN RUNNERS

AT 4'-0" ON CENTER AND 7/8" HAT

CHANNEL CROSS RUNNERS AT 1'-4"

ON CENTER

STANDING SEAM

METAL ROOFING

(1) 1" LAYER AND (2) 2"

LAYERS RIGID INSULATION -

TAPE ALL JOINTS

ICE & WATER SHIELD

STRUCTURAL METAL

ROOF DECKING OVER

LIGHT GAUGE METAL

TRUSSES - SEE

STRUCTURAL

NOTES:

1. INSULATION AND SHEET METAL ROOFING SYSTEM

FASTENERS SHALL NOT PENETRATE BEYOND THE

LOWER PAN OF THE METAL ROOF DECKING.

COORDINATE FASTENER LENGTH AS REQUIRED.

ROOF DECK AIR AND

MOISTURE BARRIER

STANDING SEAM

METAL ROOFING

METAL STUD ROOF

FRAMING - SEE

STRUCTURAL

HORIZONTAL JOINT

REINFORCEMENT AT 1'-4" ON

CENTER

CONCRETE MASONRY UNITS

5 5/8"

HORIZONTAL JOINT

REINFORCEMENT AT 1'-4" ON

CENTER

CONCRETE MASONRY UNITS

7 5/8"

1-5/8" 20 GAUGE METAL

STUDS @ 16" O.C.

1/2" CEMENT BOARD

SHEATHING ONE SIDE

1 5/8"

3/8" AIR SPACE (TYP.)

BRICK VENEER

R-10 RIGID INSULATION

CAVITY AND AIR SPACE

AIR AND MOISTURE BARRIER

CONCRETE MASONRY UNIT

HORIZONTAL JOINT REINFORCING

AT 1'-4" ON CENTER

1'-3 1/2"

3 5/8" 7 5/8"

FLUID APPLIED AIR AND

MOISTURE BARRIER

R-38 BLOWN-IN

INSULATION

EXISTING PRECAST

CONCRETE ROOF

STRUCTURE

F ile

P ri n t

SYM. DESCRIPTION DATE APP.

REVISIONS

T

T C

E

TI

HCRAD

R E

G I S

ERE

A N

I

L

ORA

N O

R

T H

C

N

D A

R

N

DE

.J UE

ER

III

C

N

NRB E

E W

M

A

P.

STCETIHCRA

FB

BERN N.C

.NEW

CERT. NO.

UTCETIHCRA

DERET

SI

G E R

N

OI

TA

RO

PR

OC

LAR

CAROLINANORTH

50679

DR.

DES.

CHK.

SUBMITTED BY:

DESIGN DIR.

APPROVED: PWO OR OICC

SATISFACTORY TO:

DATE

DATE

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND

CAMP LEJEUNE, NORTH CAROLINA

MARINE CORPS BASE

SIZE CODE IDENT. NO. NAVFAC DRAWING NO.

E1 80091

CONSTR. CONTR. NO.

AS NOTEDSCALE SHEET

M B

F A

N O

SPEC.

S p ro je c ts

\2

\2

C

L R e p a ir B

E Q

H P

\2

D e s ig n \2

D w g s \2

A

R C

H

.r v t

/1

/2

:0 :2

P

M

A-501

Approver

Author

Checker

MORGAN HUNTER

Designer

REPAIR BEQ HP505

ASSEMBLIES

60040373 N40085-23-B-0034

29 MAY 2024

SCALE: 1 1/2" = 1'-0"

G

3 5/8" INTERIOR MTL STUD WALL

SCALE: 1 1/2" = 1'-0"

A

8" CMU EXTERIOR WALL

SCALE: 1 1/2" = 1'-0"

C

4" MASONRY PARTITION

SCALE: 1 1/2" = 1'-0"

H

3 5/8" INTERIOR MTL STUD WALL

SCALE: 3" = 1'-0"

B4

SLAB PATCH DETAIL

SCALE: 3" = 1'-0"

A3

SUSPENDED ATC CEILING - 15/16" GRID

SCALE: 1 1/2" = 1'-0"

A1

SUSPENDED GYPSUM BOARD CEILING DETAIL

GRAPHIC SCALE: 1 1/2"=1'-0"

1' 6" 3" 0 1'

GRAPHIC SCALE: 3"=1'-0"

0 3" 6" 1'

SCALE: 1 1/2" = 1'-0"

B2

ROOF DETAIL - MECH BLDG

SCALE: 1 1/2" = 1'-0"

B1

ROOF DETAIL - BEQ

SCALE: 1 1/2" = 1'-0"

D

6" MASONRY PARTITION

SCALE: 1 1/2" = 1'-0"

E

8" MASONRY PARTITION

SCALE: 1 1/2" = 1'-0"

F

1 5/8" INTERIOR MTL STUD WALL

SCALE: 1 1/2" = 1'-0"

B

8" CMU EXTERIOR WALL

SCALE: 1 1/2" = 1'-0"

B3

ROOF DETAIL - EXISTING/ATTIC

1 ADDENDUM 01 01.17.25

File details come from the government source that posted it. Updated .