60040424.pdf
PDF 185 KB Posted
- Attached to
- Repair BEQ HP505
- Solicitation number
- N4008525R2549
About this file
This is a drawing legend and abbreviations sheet (M-001) for a construction project at a Marine Corps Base related to the repair of BEQ HP505. The sheet provides comprehensive HVAC and mechanical system symbols, including ductwork components (supply/return diffusers, grilles, dampers), piping symbols (valves, flow indicators, thermometers), and standard mechanical abbreviations used in construction drawings.
The legend includes detailed symbols for duct transitions, fire dampers, smoke detectors, and various types of valves and controls. Common mechanical abbreviations are defined, such as CFM (Cubic Feet per Minute), ESP (External Static Pressure), BAS (Building Automation System), and various temperature/pressure measurements. The sheet appears to be part of a larger set of mechanical drawings for the BEQ repair project, with drawing number 60040424 and sheet number M-001.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Amend 0016.pdf | ||
| Amend 0015.pdf | ||
| Amend 0014.pdf | ||
| Amend 0013.pdf | ||
| 60040360.pdf | ||
| 60040406.pdf | ||
| 60040345.pdf | ||
| 60040454.pdf | ||
| 60040373.pdf | ||
| 60040328.pdf | ||
| 60040433.pdf | ||
| 60040414.pdf | ||
| N4008523B0034 SpecsAsOne Addendum 01.pdf | ||
| 60040411.pdf | ||
| 60040407.pdf | ||
| 60040434.pdf | ||
| 60040420.pdf | ||
| 60040412.pdf | ||
| 60040343.pdf | ||
| Amend 0012.pdf | ||
| 60040362.pdf | ||
| 60040342.pdf | ||
| 60040447.pdf | ||
| 60040408.pdf | ||
| 60040436.pdf | ||
| 60040329.pdf | ||
| 60040422.pdf | ||
| 60040366.pdf | ||
| 60040376.pdf | ||
| 60040359.pdf | ||
| Amend 0011.pdf | ||
| Amend 0010.pdf | ||
| Amend 0009.pdf | ||
| Amend 0008.pdf | ||
| Amend 0007.pdf | ||
| Amend 0006.pdf | ||
| Amend 0005.pdf | ||
| Amend 0004.pdf | ||
| Amend 0003.pdf | ||
| Amend 0002.pdf | ||
| Amend 0001.pdf | ||
| 23-0034 Asbestos and Lead Assessment.pdf | ||
| 23-0034 Appendix D.pdf | ||
| N4008523B0034 DWGs.pdf | ||
| RFP 230034.pdf | ||
| N4008523B0034 SPECS.pdf |
Show all 46
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AS AIR SEPARATOR
EF EXHAUST FAN
CEILING SUPPLY DIFFUSER
SIDEWALL SUPPLY DIFFUSER
CEILING RETURN GRILLE
SIDEWALL RETURN/EXHAUST GRILLE
CEILING EXHAUST GRILLE
WXH
RECTANGULAR DUCT
D"∅
ROUND DUCT
(D = DIAMETER)
(W = WIDTH, H = HEIGHT)
SPIN-IN TAP WITH TRANSITION
FROM HARD TO FLEXIBLE DUCT
MANUAL VOLUME DAMPER
RECTANGULAR DUCT TURNS DOWN
RECTANGULAR DUCT TURNS UP
ROUND DUCT TURNS DOWN
ROUND DUCT TURNS UP
FIRE DAMPER
HVAC SYSTEM EMERGENCY
SD DUCT MOUNTED SMOKE DETECTOR
A
DIFFUSER TAG
DIFFUSER TYPE
CFM
EXISTING DUCT, DIFFUSER
OR EQUIPMENT TO BE DEMOLISHED
DRAWING LEGEND MARKS
EXISTING DUCT, DIFFUSER
OR EQUIPMENT
ET EXPANSION TANK
DOAS DEDICATED OUTSIDE AIR SYSTEM
SHUTDOWN SWITCH
E
FD
MOTORIZED DAMPERM
T WALL MOUNTED THERMOSTAT
DRAWING LEGEND
AUTOMATIC AIR VENT
CONCENTRIC REDUCER
DIRECTION OF FLOW
TEMPERATURE TRANSMITTER
PRESSURE TRANSMITTER ORPT/PS
TH
TT
THERMOMETER
PRESSURE SWITCH
THREE WAY CONTROL VALVE
BALANCING VALVE
SWING CHECK VALVE
BUTTERFLY VALVE
BALL VALVE
FS FLOW SWITCH
GATE VALVE
UNION - SCREWED OR FLANGED
PRESSURE INDICATOR
PI
TWO WAY CONTROL VALVE
STRAINER WITH BLOW OFF VALVE
CHWP CHILLED WATER INLINE PUMP
PHWP PRIMARY HOT WATER INLINE PUMP
AFC ABOVE FINISHED CEILING
AFF ABOVE FINISHED FLOOR
AFMS AIR FLOW MONITORING STATION
BAS BUILDING AUTOMATION SYSTEM
BTUH BRITISH THERMAL UNIT PER HOUR
CFM CUBIC FEET PER MINUTE
CU. FT. CUBIC FEET
DB DRY BULB
EA, E/A EXHAUST AIR FLOW
EAT ENTERING AIR TEMPERATURE
ESP EXTERNAL STATIC PRESSURE
W.G. INCHES OF WATER GAUGE
EWT ENTERING WATER TEMPERATURE
F FAHRENHEIT
FOT FLAT ON TOP
HP HORSEPOWER
HZ HERTZ
IN. WC INCHES OF WATER COLUMN
KW TOTAL POWER INPUT, KILOWATTS
LAT LEAVING AIR TEMPERATURE
LBS POUNDS
LRA LOCKED ROTOR AMPS
LWT LEAVING WATER TEMPERATURE
MC MECHANICAL CONTRACTOR
MFG MANUFACTURER
MCA MINIMUM CIRCUIT AMPS
MOCP MAXIMUM OVER CURRENT PROTECTION
MVD MANUAL VOLUME DAMPER
OA, O/A OUTSIDE AIR FLOW
PH PHASE
PSI POUNDS PER SQUARE INCH
RA, R/A RETURN AIR FLOW
RLA RATED LOAD AMPS
RPM REVOLUTIONS PER MINUTE
SA, S/A SUPPLY AIR FLOW
SP STATIC PRESSURE
TEMP TEMPERATURE
TON 12,000 BTUH OF COOLING CAPACITY
TYP TYPICAL
VFD VARIABLE FREQUENCY DRIVE
WB WET BULB TEMPERATURE
TA, T/A TRANSFER AIR FLOW
ABBREVIATIONS
CHWS CHILLED WATER SUPPLY
CHWR CHILLED WATER RETURN
HWS HOT WATER SUPPLY
HWR HOT WATER RETURN
BFP BACKFLOW PREVENTER
FD FIRE DAMPER
DR FLOOR DRAIN
STM STEAM
COND CONDENSATE
HPC HIGH PRESSURE CONDENSATE
HPS HIGH PRESSURE STEAM (ABOVE 15 PSI)
LPC LOW PRESSURE CONDENSATE
LPS LOW PRESSURE STEAM (15 PSI AND LESS)
PC PUMPED CONDENSATE
GENERAL NOTES
1. CONTRACTOR SHALL COMPLY WITH ALL REQUIREMENTS OF 2021 NC
MECHANICAL CODE WITH REGARDS TO ALL MECHANICAL WORK.
2. CONTRACTOR MUST COORDINATE THE INSTALLATION OF ALL EQUIPMENT,
PIPING, AND DUCTWORK UNDER THIS CONTRACT WITH THE BUILDING
STRUCTURE. CONTRACTOR MUST MAKE ADJUSTMENTS WHERE NECESSARY
WITHOUT ADDITIONAL COST TO GOVERNMENT.
3. COORDINATE ALL SUPPLY, RETURN AND EXHAUST GRILLE LOCATIONS WITH
ARCHITECTURAL REFLECTED CEILING PLAN.
4. VERIFY PIPE SIZES AND LOCATIONS OF NEW PIPE ROUTING.
5. ALL NEW BULDING CONTROLS MUST TIE INTO THE EXISTING BASEWIDE JCI
EMCS. ALL NEW WATER AND ELECTRIC METERS MUST BE BACNET COMPATIBLE
AND MUST COMMUNICATE WITH THE BAS HEADEND. COORDINATE WITH THE
INSTALLATION ENERGY MANAGER ON THE TIE-IN OF THE UTILITY METERS TO THE
ECMS.
6. UNLESS OTHERWISE INDICATED, ALL MECHANICAL PIPING MUST BE RUN IN THE
DESIGNATED OR MAIN SERVICE CHASES. PIPING MUST NOT BE RUN OVERHEAD
IN THE SLEEPING AREAS OF THE ROOM, BUT MAY BE RUN IN SOFFITS OVER
BATHROOMS, SINK AND CLOSET AREAS.
7. WHERE NEW SMALLER DUCTS ARE INSTALLED REUSING EXISTING LARGER
WALL/FLOOR OPENINGS, THE EXISTING OPENINGS MUST BE FILLED TO MATCH
EXISTING ADJACENT CONSTRUCTION AND BE FIRE PROOFED AS REQUIRED TO
MEET ALL APPLICABLE CODES AND REGULATIONS.
8. THE CONTRACTOR MUST DEMOLISH ALL MATERIALS AS SHOWN AND NOTED ON
THE DEMOLITION PLANS FOR THIS BUILDING. ALL SUBSTANCES FOUND IN, ON OR
AROUND THESE DEMOLISHED MATERIALS MUST BE SAFELY HANDLED AND
DISPOSED OF TO SATISFY ALL ENVIRONMENTAL REGULATIONS.
9. ALL EXPOSED DUCTWORK MUST BE INSULATED WITH RIGID DUCT BOARD
INSULATION PER SPECIFICATIONS.
BT BUFFER TANK
EX EXISTING
UNDERGROUND PIPING
SUPPLY/RETURN PIPING
LOUVER
AHU AIR HANDLING UNIT
PTHP PACKAGED TERMINAL HEAT PUMP
UH HOT WATER UNIT HEATER
DAC DUCTLESS SPLIT AIR CONDITIONING UNIT
DCU DUCTLESS SPLIT CONDENSING UNIT
CH AIR-COOLED CHILLER
L LOUVER
B BOILER
SHWP SECONDARY HOT WATER INLINE PUMP
DH DEHUMIDIFIER
DDC DIRECT DIGITAL CONTROL
B-BC BACNET-BUILDING CONTROLLER
DTW DUAL-TEMP WATER
CIRCUIT SETTER VALVE
SYM. DESCRIPTION DATE APP.
REVISIONS
DR.
DES.
CHK.
SUBMITTED BY:
DESIGN DIR.
APPROVED: PWO OR OICC
SATISFACTORY TO:
DATE
DATE
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND
CAMP LEJEUNE, NORTH CAROLINA
MARINE CORPS BASE
SIZE CODE IDENT. NO. NAVFAC DRAWING NO.
E1 80091
CONSTR. CONTR. NO.
AS NOTEDSCALE SHEET
M B
F A
N O
SPEC.
M-001
MAS
JDL
MORGAN HUNTER
MAS
REPAIR BEQ HP505
MECHANICAL NOTES, LEGEND & ABBREVIATIONS
60040424 N40085-23-B-0034
100 176
1 PPI Responses 01.17.25
| Sheets |
| M-001 - MECHANICAL NOTES, LEGEND & ABBREVIATIONS |
File details come from the government source that posted it. Updated .