This is a fire suppression system construction drawing showing the second floor plan for Building BEQ HP505 at Marine Corps Base Camp Lejeune, North Carolina. The drawing details sprinkler system requirements for sleeping rooms, mechanical rooms, plumbing chases, and corridors.
The plan specifies that sprinklers must be provided throughout the outlined area, with typical hazard classifications for sleeping rooms per NFPA 13R requirements. The corridor is noted as an unconditioned space requiring dry sidewall sprinklers, with heat-traced wet pipe sprinkler piping where crossing the corridor. The drawing includes floor control assembly locations and shows various rooms including storage, laundry, electrical, communications room, and lounge areas. The drawing was prepared by Jensen Hughes, stamped by Professional Engineer Aaron P. Freid (VA License #044409), and includes revision updates dated January 17, 2025.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Amend 0016.pdf | ||
| Amend 0015.pdf | ||
| Amend 0014.pdf | ||
| Amend 0013.pdf | ||
| 60040360.pdf | ||
| 60040406.pdf | ||
| 60040345.pdf | ||
| 60040454.pdf | ||
| 60040373.pdf | ||
| 60040328.pdf | ||
| 60040433.pdf | ||
| 60040414.pdf | ||
| N4008523B0034 SpecsAsOne Addendum 01.pdf | ||
| 60040411.pdf | ||
| 60040434.pdf | ||
| 60040420.pdf | ||
| 60040412.pdf | ||
| 60040343.pdf | ||
| Amend 0012.pdf | ||
| 60040362.pdf | ||
| 60040342.pdf | ||
| 60040447.pdf | ||
| 60040408.pdf | ||
| 60040436.pdf | ||
| 60040424.pdf | ||
| 60040329.pdf | ||
| 60040422.pdf | ||
| 60040366.pdf | ||
| 60040376.pdf | ||
| 60040359.pdf | ||
| Amend 0011.pdf | ||
| Amend 0010.pdf | ||
| Amend 0009.pdf | ||
| Amend 0008.pdf | ||
| Amend 0007.pdf | ||
| Amend 0006.pdf | ||
| Amend 0005.pdf | ||
| Amend 0004.pdf | ||
| Amend 0003.pdf | ||
| Amend 0002.pdf | ||
| Amend 0001.pdf | ||
| 23-0034 Asbestos and Lead Assessment.pdf | ||
| 23-0034 Appendix D.pdf | ||
| N4008523B0034 DWGs.pdf | ||
| RFP 230034.pdf | ||
| N4008523B0034 SPECS.pdf |
Show all 46
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
201A
205A
204A
208A
213A
212A
217A
216A
241 242 243
FX102
B1
FX102
B2
FX102
B3
200 202
201 203
OH
RES RES
RESRES
Room
2 2
2 2
Room
F C
A
OH
OH
OH
STORAGE
STAIR
242 LAUNDRY
TOILET
ELECTRICAL
CORRIDOR
COMM ROOM
LOUNGE
OH
OH
LH
OH
LH
LH
OH
KEY NOTES
1.
2.
3.
4.
5.
6.
PROVIDE SPRINKLERS THROUGHOUT THE OUTLINED AREA.
HAZARD CLASSIFICATION IS TYPCIAL FOR SLEEPING ROOMS.
SPRINKLERS MUST BE PROVIDED THROUGHOUT THE
SLEEPING ROOMS AS REQUIRED BY NFPA 13R.
HAZARD CLASSIFICATION IS TYPCIAL FOR MECHANICAL
ROOMS.
HAZARD CLASSIFICATION IS TYPCIAL FOR PLUMBING CHASES.
PROVIDE FLOOR CONTROL ASSEMBLY.
THE CORRIDOR IS AN UNCONDITIONED SPACE. PROVIDE DRY
SIDEWALL SPRINKLERS TO PROTECT THE CORRIDOR. WET
PIPE SPRINKLER PIPING CROSSING THE CORRIDOR MUST BE
HEAT TRACED WITH AN APPROVED HEAT TRACE SYSTEM.
GENERAL SHEET NOTES:
1. FOR FIRE SUPPRESSION GENERAL NOTES AND LEGEND,
SEE SHEET FX001.
Lic. No. 044409
AARON P FREIDC
O M M O
N W
EA
LTHOF
V
IR
G
IN
I A
P R O F
E
SSIONAL EN
G
IN
E E R
29 MAY 2024
F ile
P ri n t
SYM. DESCRIPTION DATE APP.
REVISIONS
DR.
DES.
CHK.
SUBMITTED BY:
DESIGN DIR.
APPROVED: PWO OR OICC
SATISFACTORY TO:
DATE
DATE
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND
CAMP LEJEUNE, NORTH CAROLINA
MARINE CORPS BASE
SIZE CODE IDENT. NO. NAVFAC DRAWING NO.
E1 80091
CONSTR. CONTR. NO.
AS NOTEDSCALE SHEET
M B
F A
N O
SPEC.
C U s e rs \a fr e id
\O n e
D ri v e
J e n s e n H u g h e s \D o c u m e n ts \2
F
IR
E a fr e id
.r v t
/1
/2
:4 :2
P
M
FX102
AHE
KEC
MORGAN HUNTER
APF
APF
REPAIR BEQ HP505
FIRE SUPPRESSION SECOND FLOOR PLAN - CONSTRUCTION
60040407 N40085-23-B-0034
GRAPHIC SCALE: 1/8"=1'-0"
8' 0 4' 8' 16'
GRAPHIC SCALE: 3/32"=1'-0"
8' 0 4' 8' 16'
SCALE: 3/32" = 1'-0"
D1
FIRE SUPPRESSION SECOND FLOOR PLAN - CONSTRUCTION
N
SCALE: 1/8" = 1'-0"
B1
SECOND FLOOR PARTIAL PLAN
SCALE: 1/8" = 1'-0"
B2
SECOND FLOOR PARTIAL PLAN
SCALE: 1/8" = 1'-0"
B3
SECOND FLOOR PARTIAL PLAN
1 PPI UPDATES 01/17/25 APF