This file is a mechanical drawing showing the layout of typical sleeping rooms in a Marine Corps Base Bachelor Enlisted Quarters (BEQ) facility. The drawing, labeled M-104, displays a detailed mechanical plan for four sleeping rooms (numbered 100-103) at 1/2" = 1'-0" scale. The plan includes specifications for various HVAC components including PTHP (Packaged Terminal Heat Pump) units and ductwork with sizes ranging from 4"x8" to 8"x10". Equipment designations include E1(25), E2(100), and S1(115) units positioned throughout the rooms.
The drawing is part of a repair project (Repair BEQ HP505) at a Marine Corps Base, with drawing number 60040436. The mechanical layout appears to be focusing on the heating, ventilation, and air conditioning systems for these sleeping quarters, with detailed specifications for equipment placement and ductwork routing. General notes and equipment schedules are included in the right-hand portion of the drawing.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Amend 0016.pdf | ||
| Amend 0015.pdf | ||
| Amend 0014.pdf | ||
| Amend 0013.pdf | ||
| 60040360.pdf | ||
| 60040406.pdf | ||
| 60040345.pdf | ||
| 60040454.pdf | ||
| 60040373.pdf | ||
| 60040328.pdf | ||
| 60040433.pdf | ||
| 60040414.pdf | ||
| N4008523B0034 SpecsAsOne Addendum 01.pdf | ||
| 60040411.pdf | ||
| 60040407.pdf | ||
| 60040434.pdf | ||
| 60040420.pdf | ||
| 60040412.pdf | ||
| 60040343.pdf | ||
| Amend 0012.pdf | ||
| 60040362.pdf | ||
| 60040342.pdf | ||
| 60040447.pdf | ||
| 60040408.pdf | ||
| 60040424.pdf | ||
| 60040329.pdf | ||
| 60040422.pdf | ||
| 60040366.pdf | ||
| 60040376.pdf | ||
| 60040359.pdf | ||
| Amend 0011.pdf | ||
| Amend 0010.pdf | ||
| Amend 0009.pdf | ||
| Amend 0008.pdf | ||
| Amend 0007.pdf | ||
| Amend 0006.pdf | ||
| Amend 0005.pdf | ||
| Amend 0004.pdf | ||
| Amend 0003.pdf | ||
| Amend 0002.pdf | ||
| Amend 0001.pdf | ||
| 23-0034 Asbestos and Lead Assessment.pdf | ||
| 23-0034 Appendix D.pdf | ||
| N4008523B0034 DWGs.pdf | ||
| RFP 230034.pdf | ||
| N4008523B0034 SPECS.pdf |
Show all 46
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
T T1
PTHP PTHP
PTHP PTHP
T T
Room
Room
Room
Room
8"x8"
4"x8"
S1
S1
4"x8"
6"x8" 8"x10"
E1
E1
8"x10"6"x8"
4"x8"
E1
E1
E2
E2
E1
E1
S1
S1
E1
E1
8"x8"
4"x8"
A3
M-301
1 1
SYM. DESCRIPTION DATE APP.
REVISIONS
DR.
DES.
CHK.
SUBMITTED BY:
DESIGN DIR.
APPROVED: PWO OR OICC
SATISFACTORY TO:
DATE
DATE
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND
CAMP LEJEUNE, NORTH CAROLINA
MARINE CORPS BASE
SIZE CODE IDENT. NO. NAVFAC DRAWING NO.
E1 80091
CONSTR. CONTR. NO.
AS NOTEDSCALE SHEET
M B
F A
N O
SPEC.
M-104
MAS
JDL
MORGAN HUNTER
MAS
REPAIR BEQ HP505
TYPICAL FLOOR PLAN - SLEEPING ROOM - MECHANICAL
60040436 N40085-23-B-0034
112 176
1/2" = 1'-0" A3
TYPICAL SLEEPING ROOMS - MECHANICAL
GRAPHIC SCALE: 1/2"=1'-0"
2' 0 1' 2' 4'
# PLAN NOTES
1 PROVIDE NEW WALL-MOUNTED THERMOSTAT/CONTROLLER.
MOUNT AT 54" A.F.F. (TYP)
2 PROVIDE NEW VENTILATION AIR DUCTWORK AND SUPPLY
GRILLE WITH OPPOSED BLADE DAMPER (OBD) AS SHOWN
(TYP).
3 EACH BATHROOM EXHAUST GRILLE SHALL BE CONNECTED TO
BRANCH DUCT AS SHOWN. PROVIDE EXHAUST GRILLE WITH
OBD. COORDINATE GRILLE LOCATION WITH ASSOCIATED
PLUMBING ABOVE.
4 PROVIDE NEW PTHP UNIT WITH LIGATURE PROOF
PROTECTIVE COVER, CORROSION RESISTANT CHASSIS, AND
3/4" CONDENSATE DRAIN WITH EXTERIOR CLEANOUT. THE 3/4"
CONDENSATE IS TO BE ROUTED TO CHASE AS SHOWN AND
ROUTED DOWN TO EXTERIOR. PAINT ALL DDC CONDUIT
EXPOSED IN OCCUPIED AREAS TO MATCH INTERIOR.
COORDINATE WITH ARCHITECTURAL AND INTERIOR PLANS.
(TYP)
GENERAL NOTES:
1. SEE SHEET M-001 FOR GENERAL NOTES, LEGEND &
ABBREVIATIONS
2. PLAN DRAWINGS ARE DIAGRAMMATIC IN NATURE AND DO NO
ILLUSTRATE ALL SPECIFIC DUCT TAKE-OFF CONFIGURATIONS,
TAPS, ETC. PROVIDE FLEXIBLE DUCTWORK RUNOUTS TO ALL
SUPPLY AND RETURN GRILLES WITH A MAXIMUM LENGTH OF 5
FEET AND SINGLE BENDS NO GREATER THAN 45 DEGREES.
REFER TO PROJECT SPECIFICATIONS AND DUCTWORK
DETAILS FOR SPECIFIC REQUIREMENTS.
3. PIPING IS TO BE INSTALLED SO THAT ALL VALVES, STRAINERS,
UNIONS, TRAPS AND FLANGES REQUIRING ACCESS ARE
EASILY ACCESSIBLE. ALL VALVES MUST BE INSTALLED SO
THAT THE SYSTEM REMAINS IN SERVICE WHEN EQUIPMENT
OR PIPING (ON EQUIPMENT SIDE OF VALVE) IS REMOVED. ALL
BALANCING VALVES AND BUTTERFLY VALVES MUST BE
PROVIDED WITH POSITION INDICATORS AND MAXIMUM
ADJUSTABLE STOPS. ALL VALVES (EXCEPT CONTROL VALVES)
AND STRAINERS MUST BE FULL SIZE OF PIPE BEFORE
REDUCING SIZE TO MAKE CONNECTIONS TO EQUIPMENT OR
CONTROLS.
N
1 PPI Responses 01.17.25
| Sheets |
| M-104 - TYPICAL FLOOR PLAN - SLEEPING ROOM - MECHANICAL |