60040436.pdf

PDF 297 KB Posted

Attached to
Repair BEQ HP505
Solicitation number
N4008525R2549
Issued by

About this file

This file is a mechanical drawing showing the layout of typical sleeping rooms in a Marine Corps Base Bachelor Enlisted Quarters (BEQ) facility. The drawing, labeled M-104, displays a detailed mechanical plan for four sleeping rooms (numbered 100-103) at 1/2" = 1'-0" scale. The plan includes specifications for various HVAC components including PTHP (Packaged Terminal Heat Pump) units and ductwork with sizes ranging from 4"x8" to 8"x10". Equipment designations include E1(25), E2(100), and S1(115) units positioned throughout the rooms.

The drawing is part of a repair project (Repair BEQ HP505) at a Marine Corps Base, with drawing number 60040436. The mechanical layout appears to be focusing on the heating, ventilation, and air conditioning systems for these sleeping quarters, with detailed specifications for equipment placement and ductwork routing. General notes and equipment schedules are included in the right-hand portion of the drawing.

View the file

Other files

File Type Posted
Amend 0016.pdf PDF
Amend 0015.pdf PDF
Amend 0014.pdf PDF
Amend 0013.pdf PDF
60040360.pdf PDF
60040406.pdf PDF
60040345.pdf PDF
60040454.pdf PDF
60040373.pdf PDF
60040328.pdf PDF
60040433.pdf PDF
60040414.pdf PDF
N4008523B0034 SpecsAsOne Addendum 01.pdf PDF
60040411.pdf PDF
60040407.pdf PDF
60040434.pdf PDF
60040420.pdf PDF
60040412.pdf PDF
60040343.pdf PDF
Amend 0012.pdf PDF
60040362.pdf PDF
60040342.pdf PDF
60040447.pdf PDF
60040408.pdf PDF
60040424.pdf PDF
60040329.pdf PDF
60040422.pdf PDF
60040366.pdf PDF
60040376.pdf PDF
60040359.pdf PDF
Amend 0011.pdf PDF
Amend 0010.pdf PDF
Amend 0009.pdf PDF
Amend 0008.pdf PDF
Amend 0007.pdf PDF
Amend 0006.pdf PDF
Amend 0005.pdf PDF
Amend 0004.pdf PDF
Amend 0003.pdf PDF
Amend 0002.pdf PDF
Amend 0001.pdf PDF
23-0034 Asbestos and Lead Assessment.pdf PDF
23-0034 Appendix D.pdf PDF
N4008523B0034 DWGs.pdf PDF
RFP 230034.pdf PDF
N4008523B0034 SPECS.pdf PDF
Show all 46

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

T T1

PTHP PTHP

PTHP PTHP

T T

Room

Room

Room

Room

8"x8"

4"x8"

S1

S1

4"x8"

6"x8" 8"x10"

E1

E1

8"x10"6"x8"

4"x8"

E1

E1

E2

E2

E1

E1

S1

S1

E1

E1

8"x8"

4"x8"

A3

M-301

1 1

SYM. DESCRIPTION DATE APP.

REVISIONS

DR.

DES.

CHK.

SUBMITTED BY:

DESIGN DIR.

APPROVED: PWO OR OICC

SATISFACTORY TO:

DATE

DATE

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND

CAMP LEJEUNE, NORTH CAROLINA

MARINE CORPS BASE

SIZE CODE IDENT. NO. NAVFAC DRAWING NO.

E1 80091

CONSTR. CONTR. NO.

AS NOTEDSCALE SHEET

M B

F A

N O

SPEC.

M-104

MAS

JDL

MORGAN HUNTER

MAS

REPAIR BEQ HP505

TYPICAL FLOOR PLAN - SLEEPING ROOM - MECHANICAL

60040436 N40085-23-B-0034

112 176

1/2" = 1'-0" A3

TYPICAL SLEEPING ROOMS - MECHANICAL

GRAPHIC SCALE: 1/2"=1'-0"

2' 0 1' 2' 4'

# PLAN NOTES

1 PROVIDE NEW WALL-MOUNTED THERMOSTAT/CONTROLLER.

MOUNT AT 54" A.F.F. (TYP)

2 PROVIDE NEW VENTILATION AIR DUCTWORK AND SUPPLY

GRILLE WITH OPPOSED BLADE DAMPER (OBD) AS SHOWN

(TYP).

3 EACH BATHROOM EXHAUST GRILLE SHALL BE CONNECTED TO

BRANCH DUCT AS SHOWN. PROVIDE EXHAUST GRILLE WITH

OBD. COORDINATE GRILLE LOCATION WITH ASSOCIATED

PLUMBING ABOVE.

4 PROVIDE NEW PTHP UNIT WITH LIGATURE PROOF

PROTECTIVE COVER, CORROSION RESISTANT CHASSIS, AND

3/4" CONDENSATE DRAIN WITH EXTERIOR CLEANOUT. THE 3/4"

CONDENSATE IS TO BE ROUTED TO CHASE AS SHOWN AND

ROUTED DOWN TO EXTERIOR. PAINT ALL DDC CONDUIT

EXPOSED IN OCCUPIED AREAS TO MATCH INTERIOR.

COORDINATE WITH ARCHITECTURAL AND INTERIOR PLANS.

(TYP)

GENERAL NOTES:

1. SEE SHEET M-001 FOR GENERAL NOTES, LEGEND &

ABBREVIATIONS

2. PLAN DRAWINGS ARE DIAGRAMMATIC IN NATURE AND DO NO

ILLUSTRATE ALL SPECIFIC DUCT TAKE-OFF CONFIGURATIONS,

TAPS, ETC. PROVIDE FLEXIBLE DUCTWORK RUNOUTS TO ALL

SUPPLY AND RETURN GRILLES WITH A MAXIMUM LENGTH OF 5

FEET AND SINGLE BENDS NO GREATER THAN 45 DEGREES.

REFER TO PROJECT SPECIFICATIONS AND DUCTWORK

DETAILS FOR SPECIFIC REQUIREMENTS.

3. PIPING IS TO BE INSTALLED SO THAT ALL VALVES, STRAINERS,

UNIONS, TRAPS AND FLANGES REQUIRING ACCESS ARE

EASILY ACCESSIBLE. ALL VALVES MUST BE INSTALLED SO

THAT THE SYSTEM REMAINS IN SERVICE WHEN EQUIPMENT

OR PIPING (ON EQUIPMENT SIDE OF VALVE) IS REMOVED. ALL

BALANCING VALVES AND BUTTERFLY VALVES MUST BE

PROVIDED WITH POSITION INDICATORS AND MAXIMUM

ADJUSTABLE STOPS. ALL VALVES (EXCEPT CONTROL VALVES)

AND STRAINERS MUST BE FULL SIZE OF PIPE BEFORE

REDUCING SIZE TO MAKE CONNECTIONS TO EQUIPMENT OR

CONTROLS.

N

1 PPI Responses 01.17.25

Sheets
M-104 - TYPICAL FLOOR PLAN - SLEEPING ROOM - MECHANICAL

File details come from the government source that posted it. Updated .