802 CONS/LGCA-3 FA3047-10-R-0012
Lackland AFB TX Roofing IDIQ
07 21 13
Section J – Attachment 2X Page 1 of 9 8 Feb 2010
SECTION 07 21 13
BOARD AND BLOCK INSULATION
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced.
The publications are referred to within the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM C 1289(2008) Standard Specification for Faced Rigid Cellular Polyisocyanurate
Thermal Insulation Board
ASTM C 165(2007) Standard Test Method for Measuring Compressive Properties of
Thermal Insulations
ASTM C 203(2005a) Breaking Load and Flexural Properties of Block-Type Thermal
Insulation
ASTM C 272(2001; R 2007) Water Absorption of Core Materials for Structural
Sandwich Constructions
ASTM C 552(2007) Standard Specification for Cellular Glass Thermal Insulation
ASTM C 553(2008) Standard Specification for Mineral Fiber Blanket Thermal Insulation for Commercial and Industrial Applications
ASTM C 578(2009e1) Standard Specification for Rigid, Cellular Polystyrene Thermal
Insulation
ASTM C 591(2008a) Standard Specification for Unfaced Preformed Rigid Cellular
Polyisocyanurate Thermal Insulation
ASTM C 612(2004e1) Mineral Fiber Block and Board Thermal Insulation
ASTM C 930(2005) Potential Health and Safety Concerns Associated with Thermal
Insulation Materials and Accessories
ASTM D 1621(2004a) Compressive Properties of Rigid Cellular Plastics
ASTM D 3833(1996; R 2006) Water Vapor Transmission of Pressure-Sensitive Tapes
Section J – Attachment 2X Page 2 of 9 8 Feb 2010
ASTM D 4397(2009) Standard Specification for Polyethylene Sheeting for Construction, Industrial, and Agricultural Applications
ASTM D 828(1997; R 2002) Tensile Properties of Paper and Paperboard Using Constant-
Rate-of-Elongation Apparatus
ASTM E 136(2009) Behavior of Materials in a Vertical Tube Furnace at 750 Degrees C
ASTM E 84(2009a) Standard Test Method for Surface Burning Characteristics of
Building Materials
ASTM E 96(2005) Standard Test Methods for Water Vapor Transmission of Materials
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 211(2006) Chimneys, Fireplaces, Vents, and Solid Fuel-Burning Appliances
NFPA 31(2006; Errata 2006; Errata 2007) Installation of Oil Burning Equipment
NFPA 54(2008) National Fuel Gas Code
NFPA 70(2008; AMD 1 2008) National Electrical Code - 2008 Edition
TECHNICAL ASSOCIATION OF THE PULP AND PAPER INDUSTRY (TAPPI)
TAPPI T803 OM(2006) Puncture Test of Container Board
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
29 CFR 1910.134Respiratory Protection
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation; submittals not having a "G" designation are for Contractor Quality Control approval. The following shall be submitted in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-03 Product Data
Block or board insulation; G
Vapor barrier; G
Pressure sensitive tape; G
07 21 13
Section J – Attachment 2X Page 3 of 9 8 Feb 2010
Protection board or coating; G
Accessories; G
SD-08 Manufacturer's Instructions
Block or Board Insulation
Adhesive
1.3 DELIVERY, STORAGE, AND HANDLING
1.3.1 Delivery
Deliver materials to the site in original sealed wrapping bearing manufacturer's name and brand designation, specification number, type, grade, R-value, and class. Store and handle to protect from damage. Do not allow insulation materials to become wet, soiled, crushed, or covered with ice or snow. Comply with manufacturer's recommendations for handling, storing, and protecting of materials before and during installation.
1.3.2 Storage
Inspect materials delivered to the site for damage; unload and store out of weather in manufacturer's original packaging. Store only in dry locations, not subject to open flames or sparks, and easily accessible for inspection and handling.
1.4 SAFETY PRECAUTIONS
1.4.1 Respirators
Provide installers with dust/mist respirators, training in their use, and protective clothing, all approved by National Institute for Occupational Safety and Health (NIOSH)/Mine
Safety and Health Administration (MSHA) in accordance with 29 CFR 1910.134.
1.4.2 Other Safety Considerations
Consider safety concerns and measures as outlined in ASTM C 930.
PART 2 PRODUCTS
2.1 BLOCK OR BOARD INSULATION
Provide only thermal insulating materials recommended by manufacturer for type of application indicated. Provide board or block thermal insulation conforming to the following standards and the physical properties listed below:
07 21 13
Section J – Attachment 2X Page 4 of 9 8 Feb 2010
a. Cellular Glass: ASTM C 552
b. Extruded Preformed Cellular Polystyrene: ASTM C 578
c. Mineral Fiber Block and Board: ASTM C 612
d. Unfaced Preformed Rigid Polyurethane and Polyisocyanurate Board: ASTM C 591
e. Faced Rigid Cellular Polyisocyanurate and Polyurethane Insulation: ASTM C 1289
1. Type I Aluminum Foil on both major surfaces. Class 1 - Non-reinforced core foam.
2. Type II Fibrous felt or glass fiber mat membrane on both major surfaces of the core foam.
3. Type III Perlite insulation board on one major surface of the core foam and a fibrous felt or glass fiber mat membrane on the other major surface of the core foam.
4. Type IV Cellulosic fiber insulating board on the one major surface of the core foam and fibrous felt or glass fiber mat membrane on the other major surface of the core foam.
5. Type V Oriented strand board or water-board on one major surface of the core foam and fibrous felt or glass fiber mat membrane or aluminum foil on the other major surface of the core foam.
6. Type VI Perlite insulation board on both major surfaces of the core foam.
2.1.1 Thermal Resistance
As indicated.
2.1.2 Fire Protection Requirement
a. Flame spread index of 75 or less when tested in accordance with ASTM E 84.
b. Smoke developed index of 200 or less when tested in accordance with ASTM E 84.
2.1.3 Other Material Properties
Provide thermal insulating materials with the following properties:
a. Rigid cellular plastics: Compressive Resistance at Yield: Not less than 10 pounds per square inch (psi) when measured according to ASTM D 1621.
b. Mineral fiber board: Compressive strength: Minimum load required to produce a reduction in thickness of 10 percent, lbf/sft: 25 when tested according to ASTM C 165.
Section J – Attachment 2X Page 5 of 9 8 Feb 2010
b. Flexural strength: Not less than 25 psi when measured according to ASTM C 203.
c. Water Vapor Permeance: Not more than 1.1 Perms or less when measured according to ASTM E 96, desiccant method, in the thickness required to provide the specified thermal resistance, including facings, if any.
d. Water Absorption: Not more than 2 percent by total immersion, by volume, when measured according to ASTM C 272.
e. Water Adsorption: Not more than 1 percent by volume when measured in accordance with paragraph 14 of ASTM C 553.
2.1.4 Premolded Concrete Masonry Insert
ASTM C 578. Install inserts in concrete masonry units at the masonry unit manufacturing plant. Provide insert with thickness not less than 1 1/4 inches.
2.1.5 Recycled Materials
Provide thermal insulation containing recycled materials to the extent practicable, provided that the material meets all other requirements of this section. The minimum required recycled material contents (by weight, not volume) are:
Polyisocyanurate/Polyurethane: 9 percent
Phenolic Rigid Foam : 5 percent
Perlite Board: 23 percent
2.1.6 Prohibited Materials
Do not provide materials containing more than one percent of asbestos.
2.2 VAPOR BARRIER AND DAMPPROOFING
2.2.1 Vapor Retarder in Frame Walls and Roofs
a. 6 mil thick polyethylene sheeting conforming to ASTM D 4397 and having a water vapor permeance of one perm or less when tested in accordance with ASTM E 96.
b. Membrane with the following properties:
Water Vapor Permeance: ASTM E 96: 1 perm
Maximum Flame Spread: ASTM E 84: 25
Combustion Characteristics: Passing ASTM E 136
Puncture Resistance: TAPPI T803 OM: 15
Tensile Strength: ASTM D 828: 15
Section J – Attachment 2X Page 6 of 9 8 Feb 2010
2.3 PRESSURE SENSITIVE TAPE
As recommended by manufacturer of vapor retarder and having a water vapor permeance rating of one perm or less when tested in accordance with ASTM D 3833.
2.4 PROTECTION BOARD OR COATING
As recommended by insulation manufacturer.
2.5 ACCESSORIES
2.5.1 Adhesive
As recommended by insulation manufacturer.
2.5.2 Mechanical Fasteners
Corrosion resistant fasteners as recommended by the insulation manufacturer.
PART 3 EXECUTION
3.1 EXISTING CONDITIONS
Before installing insulation, ensure that all areas that will be in contact with the insulation are dry and free of projections which could cause voids, compressed insulation, or punctured vapor retarders. If moisture or other conditions are found that do not allow the proper installation of the insulation, do not proceed but notify the Contracting Officer of such conditions.
3.2 PREPARATION
3.2.1 Blocking Around Heat Producing Devices
Unless using insulation board that passes ASTM E 136 in addition to the requirements in
Part 2, install non-combustible blocking around heat producing devices to provide the following clearances:
a. Recessed lighting fixtures, including wiring compartments, ballasts, and other heat producing devices, unless certified for installation surrounded by insulation: 3 inches from outside face of fixtures and devices or as required by NFPA 70 and, if insulation is to be placed above fixture or device, 24 inches above fixture.
b. Masonry chimneys or masonry enclosing a flue: 2 inches from outside face of masonry. Masonry chimneys for medium and high heat operating appliances: Minimum clearances required by NFPA 211.
Section J – Attachment 2X Page 7 of 9 8 Feb 2010
c. Vents and vent connectors used for venting products of combustion, flues, and chimneys other than masonry chimneys: minimum clearances as required by NFPA 211.
f. Gas Fired Appliances: Clearances as required in NFPA 54.
g. Oil Fired Appliances: Clearances as required in NFPA 31.
Blocking is not required if chimneys or flues are certified by the Manufacturer for use in contact with insulating materials.
3.3 INSTALLATION
3.3.1 Insulation Board
Install and handle insulation in accordance with the manufacturer's installation instructions. Keep material dry and free of extraneous materials. Observe safe work practices.
3.3.2 Electrical Wiring
Do not install insulation in a manner that would sandwich electrical wiring between two layers of insulation.
3.3.3 Installation at Pipes
Place insulation to the outside of pipes.
3.3.4 Continuity of Insulation
Butt tightly against adjoining boards, studs, rafters, joists, sill plates, headers and obstructions. Provide continuity and integrity of insulation at corners, wall to ceiling joint, roof, and floor. Avoid creating any thermal bridges or voids.
3.4 INSTALLATION ON WALLS
3.4.1 Installation using Furring Strips
Install insulation continuously, on members as recommended by insulation manufacturer.
3.4.2 Installation on Masonry Walls
Apply board directly to masonry with adhesive or fasteners as recommended by the insulation manufacturer. Fit between obstructions without impaling board on ties or anchors. Apply in parallel courses with joints breaking midway over course below. Put ends in moderate contact with adjoining insulation without forcing. Cut and shape as
07 21 13
Section J – Attachment 2X Page 8 of 9 8 Feb 2010 required to fit around wall penetrations, projections or openings to accommodate conduit or other services. Seal around cut-outs with sealant. Install board in wall cavities so that it leaves at least a nominal one inch free air space outside of the insulation to allow for cavity drainage.
Insert premolded or board insulation into masonry unit hollow cores as recommended by the insulation manufacturer. Where possible, use in conjunction with continuous insulation system.
3.4.3 Adhesive Attachment to Concrete and Masonry Walls
Apply adhesive to wall and completely cover wall with insulation.
a. Full back bed method
b. Spot method: Provide at least six spots having diameter of approximately 4 inches, located at each corner and mid-points of each of the longer sides of each board.
c. As recommended by the insulation manufacturer.
d. Use only full back method for pieces of one square foot or less.
e. Butt all edges of insulation and seal edges with tape.
3.4.4 Mechanical Attachment on Concrete and Masonry Walls
Cut insulation to cover walls. Apply adhesive to wall and set clip or other mechanical fastener in adhesive as recommended by manufacturer. After curing of adhesive, install insulation over fasteners, bend split prongs flush with insulation. Butt all edges of insulation and seal with tape.
3.4.5 Protection Board or Coating
Install protection board or coating in accordance with manufacturer's instructions. Install protection over all exterior exposed insulation board and down to 1 foot below grade.
3.5 VAPOR RETARDER
Apply a continuous vapor retarder as indicated. Overlap all joints at least 6 inches and seal with pressure sensitive tape. Seal at sill, header, windows, doors and utility penetrations. Repair punctures or tears with pressure sensitive tape.
3.6 ACCESS PANELS AND DOORS
07 21 13
Section J – Attachment 2X Page 9 of 9 8 Feb 2010
Affix insulation to all access panels greater than one square foot and all access doors in insulated floors and ceilings. Use insulation with same R-Value as that for adjacent floor or ceiling.
--End of Section--