FA3047-10-R-0012 Atch 2S-Division 5

101 KB Posted

Attached to
Roofing Indefinite Delivery Indefinite Quantity (IDIQ) Federal contract opportunity
Solicitation number
FA3047-10-R-0012-ROOFING
Issued by
Department of the Air Force Air Education and Training Command

About this file

FA3047-10-R-0012 Atch 2S-Division 5 (Specs - 05 30 00) 8 Feb 10 Steel Decks

Text of this file

802 CONS/LGCA-3 FA3047-10-R-0012

Lackland AFB TX Roofing IDIQ

05 30 00

Section J – Attachment 2S Page 1 of 15 8 Feb 2010

SECTION 05 30 00

STEEL DECKS

PART 1 GENERAL

1.1 REFERENCES

The publications listed below form a part of this specification to the extent referenced.

The publications are referred to within the text by the basic designation only.

AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC)

AISC 360(2005) Specification for Structural Steel Buildings, with Commentary

AMERICAN IRON AND STEEL INSTITUTE (AISI)

AISI SG-913(1991) LRFD Cold-formed Steel Design Manual

AISI SG03-3(2002) Cold-Formed Steel Design Manual Set

AMERICAN WELDING SOCIETY (AWS)

AWS D1.1(2008; Errata 2009) Structural Welding Code - Steel

AWS D1.3(2008; Errata 2008) Structural Welding Code - Sheet Steel

ASTM INTERNATIONAL (ASTM)

ASTM A 1008(2009) Standard Specification for Steel, Sheet, Cold-Rolled, Carbon, Structural, High-Strength Low-Alloy and High-Strength Low-Alloy with Improved

Formability, Solution Hardened, and Bake Hardened

ASTM A 108(2007) Standard Specification for Steel Bar, Carbon and Alloy, Cold-

Finished

ASTM A 123(2009) Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on

Iron and Steel Products

ASTM A 36(2008) Standard Specification for Carbon Structural Steel

ASTM A 570(1998) Standard Specification for Steel, Sheet and Strip, Carbon, Hot-

Rolled

05 30 00

Section J – Attachment 2S Page 2 of 15 8 Feb 2010

ASTM A 653(2009) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or

Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process

ASTM A 780(2001; R 2006) Standard Practice for Repair of Damaged and Uncoated

Areas of Hot-Dip Galvanized Coatings

ASTM A 792(2009) Standard Specification for Steel Sheet, 55% Aluminum-Zinc Alloy-

Coated by the Hot-Dip Process

ASTM C 423(2008a) Sound Absorption and Sound Absorption Coefficients by the

Reverberation Room Method

ASTM D 1056(2007) Standard Specification for Flexible Cellular Materials - Sponge or

Expanded Rubber

ASTM D 1149(2007) Standard Test Method for Rubber Deterioration - Surface Ozone

Cracking in a Chamber

ASTM D 746(2007) Standard Test Method for Brittleness Temperature of Plastics and

Elastomers by Impact

ASTM E 84(2009a) Standard Test Method for Surface Burning Characteristics of

Building Materials

FM GLOBAL (FM)

FM DS 1-28(2002) Design Wind Loads

FM P7825(2005) Approval Guide

STEEL DECK INSTITUTE (SDI)

SDI 30(2001) Design Manual for Composite Decks, Form Decks, and Roof Decks

SDI DDMO3(3rd Edition) Diaphragm Design Manual

SDI DDP(1987; R 2000) Deck Damage and Penetrations

SDI MOC2(2006) Manual of Construction with Steel Deck

THE SOCIETY FOR PROTECTIVE COATINGS (SSPC)

SSPC Paint 20(2002; E 2004) Paint Specification No. 20 Zinc-Rich Coating Type I

Inorganic and Type II Organic

U.S. DEPARTMENT OF DEFENSE (DOD)

Section J – Attachment 2S Page 3 of 15 8 Feb 2010

UFC 3-310-01Load Assumptions for Buildings

UNDERWRITERS LABORATORIES (UL)

UL 209(2005; Rev thru May 2007) Cellular Metal Floor Raceways and Fittings

UL 580(2006; Rev thru Jul 2009) Tests for Uplift Resistance of Roof Assemblies

UL Bld Mat Dir(2009) Building Materials Directory

1.2 SUBMITTALS

Government approval is required for submittals with a "G" designation; submittals not having a "G" designation are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:

SD-02 Shop Drawings

Fabrication Drawings; G

Cant Strips; G

Ridge and Valley Plates; G

Metal Closure Strips; G

SD-03 Product Data

Accessories; G

Galvanizing Repair Paint

Joint Sealant Material; G

Mechanical Fasteners; G

Piston Tool Operator

Repair Paint

Sound Absorbing Material; G

Welder Qualifications

Welding Equipment

Section J – Attachment 2S Page 4 of 15 8 Feb 2010

Welding Rods and Accessories; G

SD-04 Samples

Metal Roof Deck Units; G

Flexible Closure Strips; G

Accessories; G

SD-05 Design Data

Deck Units; G

Submit manufacturer's design calculations, or applicable published literature for the structural properties of the proposed deck units.

SD-07 Certificates

Decking Material; G

Welding Procedures

Fire Safety

Wind Storm Resistance

1.3 QUALITY ASSURANCE

1.3.1 Deck Units

Furnish deck units and accessory products from a manufacturer regularly engaged in manufacture of steel decking. Provide a 2 sq ft. sample of decking material and each accessory to be used. Provide a sample of acoustical material to be used. Provide manufacturer's certificates attesting that the decking material meets the specified requirements.

1.3.2 Certification of Piston Tool Operator

Manufacturer's certificate attesting that the operators are authorized to use the low velocity piston tool.

1.3.3 Qualifications for Welding Work

05 30 00

Section J – Attachment 2S Page 5 of 15 8 Feb 2010

Follows Welding Procedures in accordance with AWS D1.1. Test specimens shall be made in the presence of Contracting Officer and shall be tested by an approved testing laboratory at the Contractor's expense.

Submit qualified Welder Qualifications in accordance with AWS D1.1, or under an equivalent approved qualification test. Perform tests on test pieces in positions and with clearances equivalent to those actually encountered. If a test weld fails to meet requirements, perform an immediate retest of two test welds until each test weld passes.

Failure in the immediate retest will require the welder be retested after further practice or training, performing a complete set of test welds.

Submit manufacturer's catalog data for Welding Equipment and Welding Rods and

Accessories.

1.3.4 Regulatory Requirements

1.3.4.1 Fire Safety

Test roof deck as a part of a roof deck construction assembly of the type used for this project, listing as fire classified in the UL Bld Mat Dir, or listing as Class I construction in the FM P7825, and so labeled.

1.3.4.2 Wind Storm Resistance

Provide roof construction assembly capable of withstanding an uplift pressure determined in accordance with ASCE 7-05 for field, perimeter and corner zones, as outlined in FM

Loss Prevention Data Sheet 1-29 revised 2009, when tested in accordance with the uplift pressure test described in the FM DS 1-28 or as described in UL 580 and in general compliance with UFC 3-310-01. (Wind uplift calculator available at:

https://roofnav.fmglobal.com.)

1.3.5 Fabrication Drawings

Show type and location of units, location and sequence of connections, bearing on supports, methods of anchoring, attachment of accessories, adjusting plate details, size and location of holes to be cut and reinforcement to be provided, the manufacturer's erection instructions and other pertinent details.

1.4 DELIVERY, STORAGE, AND HANDLING

Deliver deck units to the site in a dry and undamaged condition. Store and handle steel deck in a manner to protect it from corrosion, deformation, and other types of damage.

Do not use decking for storage or as working platform until units have been fastened into position. Exercise care not to damage material or overload decking during construction.

Must not exceed the design live load. The maximum uniform distributed storage load.

Stack decking on platforms or pallets and cover with weathertight ventilated covering.

05 30 00

Section J – Attachment 2S Page 6 of 15 8 Feb 2010

Elevate one end during storage to provide drainage. Maintain deck finish at all times to prevent formation of rust. Repair deck finish using touch-up paint. Replace damaged material.

1.5 DESIGN REQUIREMENTS FOR ROOF DECKS

1.5.1 Properties of Sections

Properties of metal roof deck sections must comply with engineering design width as limited by the provisions of AISI SG-913.

1.5.2 Allowable Loads

Indicate total uniform dead and live load for detailing purposes.

PART 2 PRODUCTS

2.1 MATERIALS

2.1.1 Steel Sheet

Flat rolled carbon steel sheets of structural quality, thickness not less than 0.028 inch before coating, meeting the requirements of AISI SG03-3, except as modified herein. For acoustical steel deck units, provide perforated sheets with 5/32 inch diameter holes staggered 3/8 inch on-centers.

2.1.2 Steel Coating

ASTM A 653 designation G90 galvanized, or ASTM A 792 designation AZ55, aluminum-zinc alloy. Apply coating to both sides of sheet. Conform to UL 209 for coating on decking provided as wire raceways.

2.1.3 Galvanized Steel Angles for Roof Decks

Provide hot-rolled carbon steel angles conforming to ASTM A 36, merchant quality, Grade Designation SAE/AISI 1023 or SAE/AISI 1025, and hot-dip galvanized in accordance with ASTM A 123.

2.1.4 Joint Sealant Material for Roof Decks

Provide a nonskinning, gun-grade, bulk compound material as recommended by the manufacturer.

2.1.5 Galvanizing Repair Paint for Roof Decks

05 30 00

Section J – Attachment 2S Page 7 of 15 8 Feb 2010

Provide a high zinc-dust content paint for regalvanizing welds in galvanized steel and shall conform to ASTM A 780.

2.1.6 Flexible Closure Strips for Roof Decks

Provide strips made of elastomeric material specified and premolded to the configuration required to provide tight-fitting closures at open ends and sides of steel roof decking. Do not use in fire-resistance-rated construction assemblies.

Provide a vulcanized, closed-cell, expanded chloroprene elastomer having approximately

3.5 psi compressive-deflection at 25 percent deflection (limits), conforming to ASTM D

1056, Grade No. SCE 41, with the following additional properties:

Brittleness temperature of minus 40 degrees F when tested in accordance with ASTM D

746.

Flammability resistance with a flame spread rating of less than 25 when tested in accordance with ASTM E 84.

Resistance to ozone must be "no cracks" after exposure of a sample kept under a surface tensile strain of 25 percent to an ozone concentration of 100 parts per million of air by volume in air for 100 hours at 104 degrees F and tested in accordance with ASTM D

1149.

Provide a elastomeric type adhesive with a chloroprene base as recommended by the manufacturer of the flexible closure strips.

2.1.7 Sound Absorbing Material

Provide glass fiber in roll or premolded form for acoustical noncellular steel roof deck or glass fiber rigid strip for acoustical cellular steel deck in accordance with the manufacturer's standards.

2.2 ACCESSORIES

Provide accessories of same material as deck, unless specified otherwise. Provide manufacturer's standard type accessories, as specified.

2.2.1 Adjusting Plates

Provide adjusting plates, or segments of deck units, of same thickness and configuration as deck units in locations too narrow to accommodate full size units. Provide factory cut plates of predetermined size where possible.

2.2.2 End Closures

05 30 00

Section J – Attachment 2S Page 8 of 15 8 Feb 2010

Fabricated of sheet metal by the deck manufacturer. Provide end closures minimum

0.028 inch thick to close open ends at parapets, end walls, eaves, and openings through deck.

2.2.3 Partition Closures

Provide closures for closing voids above interior walls and partitions that are perpendicular to the direction of the configurations. Provide rubber, plastic, or sheet steel closures above typical partitions. Provide minimum one inch thick soft composition rubber closures above walls and partitions contiguous to acoustical steel deck. Provide sheet steel closures above fire-resistant interior walls and partitions located on both sides of wall or partition. Provide glass fiber blanket insulation in the space between pairs of closures at acoustical partitions.

2.2.4 Closure Plates for Composite Deck

Support and retain concrete at each floor level. Provide edge closures at all edges of the slab of sufficient strength and stiffness to support the wet concrete. Provide metal closures for all openings in composite steel deck 1/4 inch and over.

2.2.5 Sheet Metal Collar

Where deck is cut for passage of pipes, ducts, columns, etc., and deck is to remain exposed, provide a neatly cut sheet metal collar to cover edges of deck. Do not cut deck until after installation of supplemental supports.

2.2.6 Cover Plates

Sheet metal to close panel edge and end conditions, and where panels change direction or butt. Polyethylene-coated, self-adhesive, 2 inch wide joint tape may be provided in lieu of cover plates on flat-surfaced decking butt joints.

Fabricate cover plates for abutting floor deck units from the specified structural-quality steel sheets not less than nominal thick before galvanizing. Provide 6 inch wide cover plates and form to match the contour of the floor deck units.

2.2.7 Roof Sump Pans

Sump pans must be provided for roof drains and must be minimum 0.075 inch thick steel, recessed type. Shape sump pans to meet roof slope by the supplier or by a sheet metal specialist. Provide bearing flanges of sump pans to overlap steel deck a minimum of 3 inch. Shape, size, and reinforce the opening in bottom of the sump pan to receive roof drain.

2.2.8 Column Closures

05 30 00

Section J – Attachment 2S Page 9 of 15 8 Feb 2010

Sheet metal, minimum 0.0358 inch thick or metal rib lath.

2.2.9 Access Hole Covers

Sheet metal, minimum 0.0474 inch thick.

2.2.10 Hanger

Provide clips or loops for utility systems and suspended ceilings of one or more of the following types:

a. Lip tabs or integral tabs where noncellular decking or flat plate of cellular section is

0.0474 inch thick or more, and a structural concrete fill is used over deck.

b. Slots or holes punched in decking for installation of pigtails.

c. Tabs driven from top side of decking and arranged so as not to pierce electrical cells.

d. Decking manufacturer's standard as approved by the Contracting Officer.

2.2.11 Shear Connectors

Provide shear connectors as headed stud type, ASTM A 108, Grade 1015 or 1020, cold finished carbon steel with dimensions complying with AISC 360 or strap type, ASTM A

570, Grade D, hot-rolled carbon steel.

2.2.12 Mechanical Fasteners

Provide mechanical fasteners, such as powder actuated or pneumatically driven fasteners, for anchoring the deck to structural supports and adjoining units that are designed to meet the loads indicated. Provide positive locking-type fasteners standard with the Steel Deck

Institute and the steel deck manufacturer, as approved by the Contracting Officer.

2.2.13 Miscellaneous Accessories

Furnish the manufacturer's standard accessories to complete the deck installation.

Furnish metal accessories of the same material as the deck and with the minimum design thickness as follows: saddles, 0.0474 inch; welding washers, 0.0598 inch cant strip,

0.0295 inch other metal accessories, 0.0358 inch unless otherwise indicated. Accessories must include but not be limited to saddles, welding washers, fasteners, cant strips, butt cover plates, underlapping sleeves, and ridge and valley plates.

2.3 FABRICATION

Furnish sample of Metal Roof Deck Units used to illustrate actual cross section dimensions and configurations.

Section J – Attachment 2S Page 10 of 15 8 Feb 2010

Furnish one sample of each type Flexible Closure Strips, 12 inch long.

2.3.1 Roof Deck

Conform to ASTM A 792 or ASTM A 1008 for deck used in conjunction with insulation and built-up roofing. Fabricate roof deck units of the steel design thickness required by the design drawings and galvanized.

2.3.1.1 Cant Strips for Roof Decks

Fabricate cant strips from the specified commercial-quality steel sheets not less than nominal 0.0359 inch thick before galvanizing. Bend strips to form a 45-degree cant not less than 5 inch wide, with top and bottom flanges a minimum 3 inch wide. Length of strips 10 feet.

2.3.1.2 Ridge and Valley Plates for Roof Decks

Fabricate plates from the specified structural-quality steel sheets, not less than nominal

0.0359 inch thick before galvanizing. Provide plates of minimum 4-1/2 inch wide and bent to provide tight fitting closures at ridges and valleys. Provide a minimum length of ridge and valley plates of 10 feet.

2.3.1.3 Metal Closure Strips for Roof Decks

Fabricate strips from the specified commercial-quality steel sheets not less than nominal

0.0359 inch thick before galvanizing. Provide strips from the configuration required to provide tight-fitting closures at open ends and sides of steel roof decking.

2.3.2 Form Deck

Conform to ASTM A 653 or ASTM A 1008 for deck used as formwork for concrete.

Fabricate form deck of the steel design thickness required by the design drawings. Zinc-coat in conformance with ASTM A 653, G90 coating class.

2.3.3 Composite Deck

Conform to ASTM A 653 or ASTM A 1008 for composite deck assembly. Fabricate deck used as the tension reinforcing in composite deck of the steel design thickness required by the design drawings. Zinc-coat in conformance with ASTM A 653, G90 coating class.

In addition to resisting shear, provide devices to resist vertical separation between the steel deck and the concrete. Provide one of the following types of shear devices:

05 30 00

Section J – Attachment 2S Page 11 of 15 8 Feb 2010

a. Mechanically fixed shear devices such as embossments, holes, or welded buttons.

b. Mechanically fixed shear devices such as inverted, triangular-shaped ribs.

2.3.4 Acoustical Steel Deck

Provide a Noise Reduction Coefficient (NRC) rating of not less than 0.70 or as indicated, when tested in accordance with ASTM C 423, Standard Mounting No. 6. Provide sound absorbing materials with either glass fiber in roll or premolded form for acoustical steel deck (noncellular) or glass fiber rigid strip for acoustical steel deck (cellular) in accordance with manufacturer's standards.

2.3.5 Venting

To ensure positive venting from the underside, provide slotted or perforated steel deck to receive concrete fill, overlay, or a poured concrete deck.

2.3.6 Shop Priming

Shop prime accessories and underside of deck at the factory after coating. Clean surfaces in accordance with the manufacturer's standard procedure followed by a spray, dip or roller coat of rust-inhibitive primer, oven cured. Provide shop primer compatible with field applied finish painting, as specified in Section 09 90 00 Paints and Coatings.

2.3.7 Touch-Up Paint

Provide touch-up paint for shop-painted units of the same type used for the shop painting, and touch-up paint for zinc-coated units of an approved galvanizing repair paint with a high-zinc dust content. Touch-up welds with paint conforming to SSPC Paint 20 in accordance with ASTM A 780. Maintain finish of deck units and accessories by using touch-up paint whenever necessary to prevent the formation of rust.

After roof decking installation, wire brush, clean, and touchup paint the scarred areas on top and bottom surfaces of metal roof decking. The scarred areas include welds, weld scars, bruises, and rust spots. Touchup galvanized surfaces with galvanizing repair paint.

Touchup painted surfaces with repair paint of painted surfaces.

PART 3 EXECUTION

3.1 EXAMINATION

Prior to installation of decking units and accessories, examine worksite to verify that as-built structure will permit installation of decking system without modification.

3.2 INSTALLATION

05 30 00

Section J – Attachment 2S Page 12 of 15 8 Feb 2010

Install steel deck units in accordance with SDI 30, SDI DDMO3 and approved shop drawings. Place units on structural supports, properly adjusted, leveled, and aligned at right angles to supports before permanently securing in place. Damaged deck and accessories including material which is permanently stained or contaminated, deformed, or with burned holes shall not be installed. Extend deck units over three or more supports unless absolutely impractical. Report inaccuracies in alignment or leveling to the

Contracting Officer and make necessary corrections before permanently anchoring deck units. Locate deck ends over supports only. Do not use unanchored deck units as a work or storage platform. Do not fill unanchored deck with concrete. Permanently anchor units placed by the end of each working day. Do not support suspended ceilings, light fixtures, ducts, utilities, or other loads by steel deck unless indicated. Distribute loads by appropriate means to prevent damage. Prepare shoring in position before concrete placement begins in composite or form deck. Size cellular decking provided as electrical raceways to accommodate indicated wiring systems. Chip off burrs and eliminate sharp edges which may damage wiring. Mesh decking panels accurately and place in accordance with UL 209. Neatly fit acoustical material into the rib voids.

3.2.1 Attachment

Immediately after placement and alignment, and after correcting inaccuracies, permanently fasten steel deck units to structural supports and to adjacent deck units by welding with normal 5/8 inch diameter puddle welds or fastened with screws, powder-actuated fasteners, or pneumatically driven fasteners as indicated on the design drawings and in accordance with manufacturer's recommended procedure and SDI 30. Clamp or weight deck units to provide firm contact between deck units and structural supports while performing welding or fastening. Attachment of adjacent deck units by button-punching is prohibited.

3.2.1.1 Welding

Perform welding in accordance with AWS D1.3 using methods and electrodes recommended by the manufacturers of the base metal alloys being used. Ensure only operators previously qualified by tests prescribed in AWS D1.1 and AWS D1.3 make welds. Immediately recertify, or replace qualified welders, that are producing unsatisfactory welding. Conform to the recommendations of the Steel Deck Institute and the steel deck manufacturer for location, size, and spacing of fastening. Do not use welding washers at the connections of the deck to supports. Do not use welding washers at sidelaps. Holes and similar defects will not be acceptable. If studs are being welded to the top flanges of beams, butt deck ends. Otherwise, lap deck ends 2 inches. Attach all partial or segments of deck units to structural supports in accordance with Section 2.5 of

SDI DDMO3. Attach shear connectors as shown and welded as per AWS D1.1 through the steel deck to the steel member. Immediately clean welds by chipping and wire brushing. Heavily coat welds, cut edges and damaged portions of coated finish with zinc-dust paint conforming to ASTM A 780, shop primed or painted finish with the manufacturer's standard touch-up paint.

05 30 00

Section J – Attachment 2S Page 13 of 15 8 Feb 2010

3.2.1.2 Fastening

Anchor deck to structural supports and adjoining units with mechanical deck fasteners as recommended by the Steel Deck Institute and the steel deck manufacturer, as approved by the Contracting Officer. Drive the powder-actuated fasteners with a low-velocity piston tool by an operator authorized by the manufacturer of the piston tool. Drive pneumatically fasteners with a low-velocity fastening tool and comply with the manufacturer's recommendations.

3.2.2 Openings

Cut or drill all holes and openings required and be coordinated with the drawings, specifications, and other trades. Frame and reinforce openings through the deck in conformance with SDI DDP.

3.2.3 Deck Damage

SDI MOC2, for repair of deck damage.

3.2.4 Accessory Installation

3.2.4.1 Adjusting Plates

Install as shown on shop drawings.

3.2.4.2 End Closures

Provide end closure to close open ends of cells at columns, walls, and openings in deck.

3.2.4.3 Closures Above Partitions

Provide for closing voids between cells over partitions that are perpendicular to direction of cells. Provide a one-piece closure strip for partitions 4 inch nominal or less in thickness and two-piece closure strips for wider partitions. Provide sheet metal closures above fire-rated partitions at both sides of partition with space between filled with fiberglass insulation. Provide flexible rubber closures above acoustic-rated partitions at both sides of partition with space between filled with blanket insulation.

3.2.4.4 Cover Plates

Provide metal cover plates, or joint tape, at joints between cellular decking sheets to be used as electrical raceways. Where concrete leakage would be a problem, provide metal cover plates, or joint tape, at joints between decking sheets, cellular or noncellular, to be covered with concrete fill.

3.2.4.5 Access Hole Covers

Section J – Attachment 2S Page 14 of 15 8 Feb 2010

Provide to seal holes cut in decking to facilitate welding of decking to structural supports.

3.2.4.6 Hangers

Provide as indicated to support utility system and suspended ceilings. Space devices as indicated.

3.2.5 Sound Absorbing Material

Install sound absorbing glass fiber roll or premolded form, neatly in voids between perforated webs of acoustical noncellular steel deck or glass fiber rigid strip, in cells of acoustical cellular steel deck. Keep sound absorbing material dry before, during and after installation.

3.2.6 Concrete Work

Prior to placement of concrete, inspect installed decking to ensure that there has been no permanent deflection or other damage to decking. Replace decking which has been damaged or permanently deflected as approved by the Contracting Officer. Place concrete on metal deck in accordance with Construction Practice of SDI 30. Concrete fill over metal deck is specified in Section 03 30 00 Cast-In-Place Concrete.

3.2.7 Preparation of Fire-Proofed Surfaces

Provide deck surfaces, both composite and noncomposite, which are to receive sprayed-on fireproofing, galvanized and free of all grease, mill oil, paraffin, dirt, salt, and other contaminants which impair adhesion of the fireproofing. Complete any required cleaning prior to steel deck installation using a cleaning method that is compatible with the sprayed-on fireproofing.

3.3 JOINT SEALING FOR ROOF DECKS

Seal sidelaps and endlaps with manufacturer's recommended joint sealing material. Shop or field apply the material. Before applying the sealing material, completely remove dust, dirt, moisture, and other foreign material from the surfaces to which the sealing material is to be applied. Apply sealing material in strict accordance with the sealing material manufacturer's printed instructions.

3.4 ROOF SUMP PANS

Place sump pans over openings in roof decking and fusion welded to top surface of roof decking. Do not exceed spacing of welds of 12 inch with not less than one weld at each corner. Field cut opening in the bottom of each roof sump pan to receive the roof drain as part of the work of this section.

05 30 00

Section J – Attachment 2S Page 15 of 15 8 Feb 2010

3.5 CANT STRIPS FOR ROOF DECKS

Provide strips to be fusion welded to surface of roof decking, secured to wood nailers by galvanized screws or to steel framing by galvanized self-tapping screws or welds. Do not exceed spacing of welds and fasteners of 12 inch. Lap end joints a minimum 3 inch and secure with galvanized sheet metal screws spaced a maximum 4 inch on center.

3.6 RIDGE AND VALLEY PLATES FOR ROOF DECKS

Provide plates to be fusion welded to top surface of roof decking. Lap end joints a minimum 3 inch. For valley plates, provide endlaps to be in the direction of water flow.

3.7 CLOSURE STRIPS FOR ROOF DECKS

Provide closure strips at open, uncovered ends and edges of the roof decking and in voids between roof decking and top of walls and partitions where indicated. Install closure strips in position in a manner to provide a weathertight installation.

3.8 ROOF INSULATION SUPPORT FOR ROOF DECKS

Provide metal closure strips for support of roof insulation where rib openings in top surface of metal roof decking occur adjacent to edges and openings. Weld metal closure strips in position.

3.9 CLEANING AND PROTECTION FOR ROOF DECKS

Upon completion of the deck, sweep surfaces clean and prepare for installation of the roofing.

3.10 FIELD QUALITY CONTROL

3.10.1 Decks Not Receiving Concrete

Inspect the decking top surface for distortion after installation. For roof decks not receiving concrete, verify distortion by placing a straight edge across three adjacent top flanges. The maximum allowable gap between the straight edge and the top flanges is

1/16 inch; when gap is more than 1/16 inch, provide corrective measures or replacement.

Reinspect decking after performing corrective measures or replacement.

--End of Section--

Other files for this federal contract opportunity

Other files attached to Roofing Indefinite Delivery Indefinite Quantity (IDIQ), newest first.
File Type Posted
FA3047-10-R-0012-0004 Amendment to RFP —
FA3047-10-R-0012-0003 Amendment to RFP Roofing IDIQ.pdf PDF
FA3047-10-R-0012-0002 Amendment to RFP Roofing IDIQ —
FA3047-10-R-0012 Attendance Record —
FA3047-10-R-0012 Atch 1 —
FA3047-10-R-0012 Atch 2N-Division 2 —
FA3047-10-R-0012 Atch 2AA-Division 7 —
FA3047-10-R-0012 Atch 2P-Division 2 —
FA3047-10-R-0012 Atch 2R-Division 2 —
FA3047-10-R-0012 Atch 2AD-Division 7 —
FA3047-10-R-0012 Atch 3 —
FA3047-10-R-0012 Atch 2Y-Division 7 —
FA3047-10-R-0012 RFP for Roofing IDIQ —
FA3047-10-R-0012 Atch 2AK —
FA3047-10-R-0012 Atch 2J-Division 1 —
FA3047-10-R-0012 Atch 2A - 8 Feb 10 Table of Contents.pdf PDF
FA3047-10-R-0012 Atch 2Q-Division 2 —
FA3047-10-R-0012 Atch 2AH-Division 8 —
FA3047-10-R-0012 Atch 2X-Division 7 —
FA3047-10-R-0012 Atch 2F-Division 1 —
FA3047-10-R-0012 Atch 2O-Division 2 —
FA3047-10-R-0012 Atch 2V-Division 5 —
FA3047-10-R-0012 Atch 2Z-Division 7 —
FA3047-10-R-0012 Atch 2AB-Division 7 —
FA3047-10-R-0012 Atch 2AG-Division 7 —
FA3047-10-R-0012 Atch 2AI-Division 9 —
FA3047-10-R-0012 Atch 2U-Division 5 —
FA3047-10-R-0012 Atch 2AE-Division 7 —
FA3047-10-R-0012 Atch 1 —
FA3047-10-R-0012 Atch 2T-Division 5 —
FA3047-10-R-0012 Atch 2C-Division 1 —
FA3047-10-R-0012 Atch 2K-Division 1 —
FA3047-10-R-0012 Atch 2M-Division 2 —
FA3047-10-R-0012 Atch 2L-Division 1 —
FA3047-10-R-0012 Atch 2D-Division 1 —
FA3047-10-R-0012 Atch 2AJ-Division 26 —
FA3047-10-R-0012 Atch 2B-Division 0 —
FA3047-10-R-0012 Atch 2AC-Division 7 —
FA3047-10-R-0012 Atch 2I-Division 1 —
FA3047-10-R-0012 Atch 2G-Division 1 —
FA3047-10-R-0012 Atch 2W-Division 6 —
FA3047-10-R-0012 Atch 2E-Division 1 —
FA3047-10-R-0012 Atch 4 —
FA3047-10-R-0012_SBDC_Informational_Map.pdf PDF
FA3047-10-R-0012 Atch 2AF-Division 7 —
FA3047-10-R-0012 Atch 2H-Division 1 —
Show all 46

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

File details come from the government source that posted it. Updated .