Text version
COVER PAGE OF SELLER’S SUBMITTAL
City Name: Hanford, WA - MSA
Pall Project No.: 01.000287
Job Number: Project L-897, Subcontract 70816
Task Register 6 (Task 1 – VI Submittal Package)
To: (Contractor)
Mission Support Alliance, LLC (MSA)
PO Box 650
Richland, WA 99352
From: (Subcontractor)
Pall Water
A Division of Pall Corporation
839 State Route 13
Cortland, NY 13045
Patty Willis
Phone: 607-758-1699
Name of Project: Hanford, WA, Central Plateau WTF
Pall Document Number: NYCS000015353 Rev: 00
Description of Item: Pulsation Dampeners
Specification Section: 43 21 00
Deviations: See document NYCS000015386
INDEX:
Page 1: Cover Page Information
Page 2: Revision History and Approvals
Page 3: Tab 1 - NYCS000015410,CSS,Pulsation Dampeners,01.287
Pages 4-17: Tab 2 - NYCS000015177,Pulsation Dampener, Wilden,0.5in,WH172231
Date: 12/19/2019
PALL ADVANCED SEPARATIONS SYSTEMS
DIVISION OF PALL CORPORATION, CORTLAND, NY
Rev Name Date Created By
Approved By
Created By
Approved By
Created By
Approved By
Created By
Approved By
Revision Description
Title
Document # Revision griffinju Text Box These commodities, technology, or software may only be exported from the United States in accordance with the Export Administration Regulations. Diversion contrary to U.S. law is prohibited.
Doc Number: NYCS000015410R00 Doc Title: NYCS000015410,CSS,Pulsation Dampeners,01.287.docx
Components Specification Sections
The following specification sections are relevant to the approval of submittal NYCS000015353, Pulsation
Dampeners,01.287:
L‐897,Attachment No. 2 ‐ HNF‐SPEC‐63538, Section 43 21 00, Pumping Equipment – Basic Requirement.
Any exceptions and clarifications to the specification section above can be found in submittal:
NYCS000015386, Es and Cs, Section 43 21 00,01.287.
Pall has taken exceptions and clarifications relevant to the pulsation dampeners proposed.
LarkinD Text Box
NYCS000015177R00
LarkinD Text Box
WH172231
Part #: SD 1/2-PPP-TF
THE EQUALIZER®
All reciprocating pumps experience a pres sure fluctuation. The Equalizer® minimizes unwanted pressure fluctuation by provid ing a supplementary pumping action. This is accomplished by using a diaphragm as a separation membrane within the Equalize~ to trap a given volume of liquid on one side and pressurized air on the other. When the fluid pressure falls in the system , the Equalize~ supplies additional pressure to the discharge line between pump strokes by displacing fluid via diaphragm movement. This movement provides the supplementary pumping action needed to virtually eliminate pressure variation and pulsation.
PHASE1 PHASE 2
LIQUID SIDE LIQUID SIDE
A compressed air line attached to the air regulator body sets and maintains pressure on the air side of the diaphragm. As the reciprocating pump begins its stroke, liquid discharge pressure increases which flexes the Equalizer® diaphragm inward. This action accumulates fluid in the liquid chamber (see
The Equalize~ automatically sets and main tains the correct air pressure matching the variations in liquid flow or discharge pressure generated by the pump. A shaft attached to the Equalize~ diaphragm triggers the addition or deletion of the air within the non-wetted side of the Equalize~. The Equalize~ automatically adjusts to any pressure and/or flow setting of the pump with no need for manual adjustment of the unit and/or system. The Equalizer® has proven to be the cost effective choice for protecting your liquid procezss system from unwanted pulsation or pressure fluctuation.
Contact your local Wilden distributor for fur ther information on the Equalizer® and other pumping solutions.
PHASE3
LIQUID SIDE
AIR
REGULATOR
BODY
AIR
SIDE
phase 2). When the pump redirects its motion upon stroke completion, the liquid discharge pressure decreases forcing the Equalizer® diaphragm to flex outward displacing the fluid into the discharge line (see phase 3). This motion provides the supplementary pumping action needed to minimize pressure fluctuation.
CAUTION: DO NOT EXCEED 125 PSIG AIR PRESSURE.
Maximum temperature limits are based upon mechanical stress only. Certain chemicals will significantly reduce maximum safe operating temperatures. Consult Wilden Chemical Guide for chemical compatibility and temperature limits.
Plastic Equalizers are manufactured with virgin plastic and are not UV stabilized. Direct sunlight for prolonged periods can cause deterioration of these plastics. In this situation a metal Equalizer® is suggested.
Wear safety glasses. When diaphragm rupture occurs, material being pumped may be forced out air exhaust.
WARNING
Prevention of static sparking - If static spark ing occurs, fire or explosion could result. Pump, Equalizer®, valves, and containers must be grounded when handling flammable fluids and whenever dis charge of static electricity is a hazard.
THE WILDEN EQUALIZER®
AUTOMATIC SURGE DAMPENER
BENEFITS:
• Minimizes pipe strain.
• Protects in-line equipment.
• Reduces water hammer.
• Absorbs acceleration head.
• Lowers system maintenance costs.
FEATURES:
• Clamp band construction for ease of maintenance.
• Automatically adjusts to any pressure and/or flow setting of the pump.
• Wide variety of materials to satisfy temperature and chemical compatibility considerations.
• Flow through design utilizing existing Wilden pump parts.
• Regulator Shaft controls the flex pattern of the diaphragm extending part life.
• Equalizer<ID utilizes a proven long-lasting Wilden diaphragm.
SD~
WIL-1901 0-E-04
MATERIALS OF
CONSTRUCTION:
Aluminum Polypropylene
316 S.S. PVDF
Cast Iron (SD1 and SD2) Teflon® PFA (SD1)* Carbon-filled Acetal Teflon® PTFE (SO~)* *All Teflon® Equalizers are assembled in a Class 10,000 Clean Room.
TEMPERATURE LIMITS
FOR PLASTICS:
Polypropylene +32 F ( 0 C) to + 175 F ( 79.4 C) PVDF + 10 F (-12.2 C) to +225 F (1 07.2 C) Teflon® PFA -20 F (-28.9 C) to +225 F (1 07.2 C) Teflon® PTFE -20 F (-28.9 C) to +225 F (1 07.2 C)
TEMPERATURE LIMITS
FOR ELASTOMERS:
Neoprene Buna-N Nordel® Viton Teflon®
0 F (-17.8 C) to +200 F ( 93.3 C) +10 F (-12.2 C) to +180 F ( 82.2 C) -60 F (-51.1 C) to +280 F (137.8 C) -40 F (-40 C) to +350 F (176. 7 C) +40 F (+4 C) to +220 F (104.4 C)
WILDEN PUMP & ENGINEERING, LLC
LarkinD Highlight
LarkinD Highlight
LarkinD Highlight
LarkinD Highlight
LarkinD Highlight
Highlight
DAMPENING EFFECTIVENESS
The following bar charts highlight the effectiveness of the Equalizer® automatic surge dampeners. Pumps were operated at the stated air inlet pressures as the discharge pressure was then varied. The pulsation range was calculated from data points obtained using pressure transducers and an oscilloscope.
~so .e ~ 40 c:c 30 ~ 20 a..
I• WITHOUT EQUALIZER® WITH EQUALIZER® I
%" (6mm) pumps/SO% The above chart reflects the discharge pressure variation of a Wilden model Y.:" (6mm) Polypropylene pump with rubber elastomers com pared to the same X" (6mm) with a model SD~ Equalize~ installed.
20 40 60 80 INLET AIR PRESSURE (psig)
• WITHOUT EQUALIZER® • WITH EQUALIZER"'
%" (13mm) pumps/SO% The above chart reflects the discharge pressure variation of a Wilden model ~ (13mm) Polypropylene pump with rubber elastomers com pared to the same ~(13mm) with a model SD~ Equalize~ installed.
WILDEN PUMP & ENGINEERING, LLC 2
20 40 60 80 INLET AIR PRESSURE (psig)
I • UNDAMPED WITHOUT EQUALIZER®. WITH EQUALIZER"' I
1" (25mm) pumps/S01 The above chart reflects the discharge pressure variation of a Wilden model 1" (25mm) Polypropylene pump with rubber elastomers com pared to the same 1" (25mm) with a model 801 Equalize~ installed.
60r-----------------------------------, ~50 .e ~ 40 c:c 30 ~ 20
"' s 10 a..
20 40 60 80 100
INLET AIR PRESSURE (psig)
• WITHOUT EQUALIZER® • WITH EQUALIZER"
1% (38mm) pumps/S02 The above chart reflects the discharge pressure variation of a Wilden model 1 ~ (38mm) Polypropylene pump with rubber elastomers com pared to the same 1 ~ (38mm) with a model 802 Equalize~ installed.
o;
·u;
.e ~ 40
~ 30
~ 20
"' 5 10 c..
20 40 60 80 100
INLET AIR PRESSURE (psig)
• WITHOUT EQUALIZER® • WITH EQUALIZER"
2" (51mm) pumps/S02 The above chart reflects the discharge pressure variation of a Wilden model 2" (51 mm) Polypropylene pump with rubber elastomers com pared to the same·2" (51 mm) with a model 802 Equalize~ installed.
WIL-19010-E-04
LarkinD Rectangle
LarkinD Line
Line
SD% DIMENSIONAL DRAWING
13 mm (1/2")
BSP (FNPT)
ITEM METAL
A
SO% (W' INLET/DISCHARGE) B
MATERIAL SHP. WT. MATERIAL SHP. WT. c
Aluminum 3.11bs. PVOF 2.91bs.
316 Stainless Steel 4.81bs. Teflon® PFA* 3.7 lbs.
Polypropylene 2.41bs. E
*All Teflon· Equalizers· are assembled in a Class 10,000 Clean Room.
SD1 DIMENSIONAL DRAWING
SD1 (1" INLET /DISCHARGE)
MATERIAL SHP. WT. MATERIAL
Aluminum 181bs. PVOF
316 Stainless Steel 241bs. Teflon® PFA *
Polypropylene 181bs.
*All Teflon· Equalizers• are assembled in a Class 10,000 Clean Room.
SHP.WT.
191bs.
211bs.
25 mm (1")
/ BSP(FNPT)
mm
SD2 DIMENSIONAL DRAWING
13 mm (1/2")
FNPT AIR INLET
SD2 (2" INLET/DISCHARGE)
MATERIAL
Aluminum Cast Iron 316 Stainless Steel
SHP. WT.
271bs.
471bs.
441bs.
51 mm(2")
BSP (FNPT)
MATERIAL
Polypropylene
PVOF
SHP.WT.
281bs.
341bs.
(INCH)
(7.1)
(6.3)
(6.3)
(4.6)
(2.7)
ITEM
A
B c
E
ITEM
A
B c
E
PLASTIC TEFLON® PTFE
mm (INCH) mm (INCH)
180 (7.1) 175 (6.9)
157 (6.2) 157 (6.2)
175 (6.9) 175 (6.9)
142 (5.6) 145 (5.7)
71 (2.8) 71 (2.8)
METAL PLASTIC
mm (INCH) mm (INCH)
279 (11.0) 292 (11.5)
229 (9.0) 236 (9.3)
290 (11.4) 290 (11.4)
295 (11.6) 384 (15.1)
147 (5.8) 191 (7.5)
METAL PLASTIC
mm (INCH) mm (INCH)
305 (12.0) 343 (13.5)
249 (9.8) 267 (10.5)
351 (13.8) 351 (13.8)
455 (17.9) 493 (19.4)
244 (9.6) 274 (10.8)
WIL-19010-E-04 3 WILDEN PUMP & ENGINEERING, LLC
LarkinD Rectangle
LarkinD Line
INSTALLATION
The model SO/';; has a /';;" inlet/discharge. The model S01 has a 1" inlet/discharge. The model S02 has a 2" inlet/discharge. The Equalizer® can be installed in either direction. A variety of materials are available to satisfy tempera ture, chemical compatibility, abrasion and flex concerns. The Equalize~ installed on the dis charge side of the pump minimizes pulsation and protects in-line equipment. It can also be connected on the suction side to prevent water hammer associated with a positive inlet condition.
The model SO~ is engineered for use with Wilden ~ (6mm) and Y2 (13mm) pumps. The model S01 is engineered for use with Wilden 1" (25mm) pumps. It can also be used with the 1 /';; (38mm) in applications where the discharge pressure is less than 50 psi. The model S02 is engineered for use with Wilden 1 /';; (38mm) and 2" (51 mm) pumps.
SUGGESTED
INSTALLATION
TROUBLESHOOTING
When there is a significant drop in the fluid discharge pressure, there will be a notice able release of air through the small bleed hole in the air regulator body. This is how the Equalize~ automatically adjusts itself for optimal suppression. This is a good way of verifying proper operation of the unit. If there is a continu ous discharge of air out this hole during steady fluid discharge pressure, the Equalize~ is not functioning properly and should be inspected.
The S01 and S02 air regulator body houses three 0-rings which may need to be replaced.
A few drops of oil in the top of the regulator every 200 hours of operation will significantly extend the life of th"ese 0-rings. The SO/';; uti liz-
WIL-19010-E-04 5
Install the Equalize~ as shown below. The use of flexible connections and a Filter, Regulator, Lubricator (FRL) will extend parts life on the SD1 and S02. Lubrication is not needed for the soy,;. Shut off valves on the suction side of pump and the discharge side of Equalize~ will enable maintenance personnel to safely service the equipment. To maximize effectiveness install the Equalize~ as close as possible to the dis charge of the pump. It is important to support the pipe immediately downstream from the Equalizer®.
Use a tee connector on the pump air sup ply line and connect the line to the Equalizer® regulator body. This tee connector should be installed after the FRL. The Equalizer® con sumes very little air, therefore, a 1/4" hose is more than adequate to supply enough air vol ume. When the air supply to the pump is shut down, the air to the Equalizer® will be shut off as well.
es 3 slipper seals with back-up 0-rings which allow lubrication-free operation.
Fluid leakage around the clamp band area is normally stopped by tightening the clamp band bolts. If leakage continues, unit should be disassembled and inspected.
Air leakage at the bottom of the 801 and S02 air regulator body normally requires the tightening of the three screws located in the air chamber. If leak age continues, the gasket between the air regula tor body and air chamber should be replaced.
If air bubbles in fluid discharge line are present, check for diaphragm rupture and tightness of clamp bands. · ·
WILDEN PUMP & ENGINEERING, LLC
LarkinD Highlight
LarkinD Highlight
Highlight
DIRECTIONS FOR
DISASSEMBLY/ASSEMBLY (SD%)
To expedite parts ordering, please find an exploded view of the Equalizer® models at the back of this manual. If you have any questions, please call your local authorized Wilden dis tributor, or call Wilden Pump & Engineering Co.
at (909) 422-1730.
STEP1
Figure 1
Loosen clamp band with 7 /16" open-ended wrench (Figure 1 ).
WILDEN PUMP & ENGINEERING, LLC 6
TOOLS REQUIRED
SD~ (1/2" INLET/DISCHARGE)
7 /16" Open-Ended Wrench 7 /8" Open-Ended Wrench
0-ring Pick
CAUTION: Before any maintenance or repair is attempted, the compressed air line to the Equalizer® and the pump should be disconnected and all air pres sure allowed to bleed from these units.
Disconnect all intake, discharge, and air lines. Always wear safety glasses and proper clothing for added protection.
PLEASE READ ALL DIRECTIONS BEFORE
STARTING DISASSEMBLY.
STEP2
Figure 2
Remove liquid chambers, inspect for damage, and set aside (Figure 2) .
WIL-19010-E-04
STEP3
Figure 3
Pull diaphragm assembly (shaft, diaphragm[s], inner and outer piston) away from air regulator body. Loosen outer piston with a 7 /8" wrench or adjustable wrench and inspect diaphragm and shaft for abrasion or chemical attack. Soft jaws in vise may need to be used if outer pis ton does not unfasten easily (Figure 3).
ASSEMBLY
STEP4
Figure 4
Air regulator slipper seals and back-up 0-rings need to be inspected. If worn or chemically attacked they must be removed with an 0-ring pick and replaced (Figure 4). Please refer to exploded view for part numbers.
Prior to assembling the Equalizer®, please read this page first. Then refer to the disassembly instructions for photos and placement of parts.
Rubber Diaphragm
There are two types of diaphragm configura tions available for the SDYf: 1) Rubber dia phragm, and 2) Teflon® primary diaphragm with back-up diaphragm. Observe the "This side out" marking on the convex side of the dia-
WIL-19010-E-04 7
Teflon® Diaphragm phragm. Install the inner piston, diaphragm(s), outer piston plate and stop on shaft. Teflon® fitted Equalizers require Teflon® gasket mate rial tape to properly seal diaphragm bead area.
See page 14 for instructions. ·
WILDEN PUMP & ENGINEERING, LLC
\IVILDEN PUMP DESIGNATION SYSTEM
AIR REGULATOR BODY
AIR CHAMBERS SPECIALTY
WETTED CONSTRUCTION CODE
INLET SIZE (IF APPLICABLE)
EQUALIZER® SURGE DAMPENER
EQUALIZER® SURGE DAMPENER
MATERIAL CODES
INLET SIZE
1;2 = 1;2 INCH
1 = 1 INCH
2 = 21NCH
3 = 31NCH
WETTED CONSTRUCTION
A = ALUMINUM (SDY2, SD1 & SD2)
G = CARBON-FILLED ACETAL (SO~)
K = PVDF (SDV., SOl & SD2) p = POLYPROPYLENE (SO ~. SD1 & SD2)
S = STAINLESS STEEL
T = TEFLON® PTFE ( SO~)
T = TEFLON® PFA (SD1 ONLY)
W = CAST IRON (SD1 AND S02)
AIR CHAMBER
A = ALUMINUM (SD2)
C = TEFLON® COATED (SD1 & SD2)
G = CARBON-FILLED ACETAL (SO~)
M = MILD STEEL (SD1)
P = POLYPROPYLENE ( SDY2)
S = STAINLESS STEEL (SD2 & SD3)
W = CAST IRON (SD2)
AIR REGULATOR BODY
G = CARBON-FILLED ACETAL (SD~ONLY)
P = POLYPROPYLENE
Nordel and Viton are registered trademarks of DuPont Dow Elastomers.
Teflon is a registered trademark of DuPont.
WIL-19010-E-04 15
DIAPHRAGM
BN = BUNA-N (SOY~ SD1 & SD2)
FB = FDA BUNA-N(::>D3 ONLY)
FE = FDA NORDEL (EPDM) (SD3 ONLY)
FG = SANIFLEX™ (SO~. SD1 & SD3)
FW = FDA WIL-FLEXn.(Su3 ONLY)
NO = NORDEL ® (SDY
, SD1 & SD2)
NE = NEOPRENE (SD1 & SD2)
TF = TEFLON® TFE
TS = TEFLON® TFE W/SANIFLEXTM BACKUP
VT = VITON® (SO~, SD1 & SD2)
WF = WIL-FLEX™ (SD 1~ & SD1)
0-RINGS
BN = BUNA-N
TF = TEFLON®
TV = TEFLON® ENCAP. VITON®
SPECIAL TV CODES
003 = ALLOY FITIED (SD1 & SD2)
014 = BSP
015 = ALLOY FITIED, BSP (SD1 & SD2)
040 = BOLTED, ANSI FLANGE (SD2 ONLY)
041 = BOLTED, DIN FLANGE (S02 ONLY)
072 = SANIFLO" USDA(SD3 ONLY)
315 = W/TEFLON® COATED HARDWARE/SSP
502 = W/TEFLON® COATED HARDWARE
WILDEN PUMP & ENGINEERING, LLC
LarkinD Highlight
LarkinD Highlight
LarkinD Highlight
LarkinD Highlight
LarkinD Highlight
LarkinD Highlight
LarkinD Text Box
WH172231
Part #: SD 1/2-PPP-TF
THE EQUALIZER®
(SD%)
Exploded View
WILDEN PUMP & ENGINEERING, LLC
cb-7 --13
---6
--9
WIL-19010-E-04
SO% EQUALIZER® POLYPROPYLENE PVOF CARBON-FILLED
ACETAL
ITEM PART DESCRIPTION OTY. SD112/PPP SD1!2/KPP SD112/GGG
1 Air Regulator Body' 1 72-8500-20 72-8500-20 72-8500-16
2 Slipper Seal 3 01-3210-55-200 01-3210-55-200 01-3210-55-200 3 Back-Up D-Ring 3 01-2390-52 01-2390-52 01-2390-52 4 Reducer Bushing 1 72-6950-07 72-6950-07 72-6950-07 5 Straight Shaft 1 01-3800-03-07 01-3800-03-07 01-3800-03-07 6 S.S. Threaded Stud 1 NA NA NA 7 Inner Piston 1 01-3710-01 01-3710-01 01-3710-01 8 Outer Piston 1 01-4570-20-500 01-4570-21-500 01-4570-16 9 Liquid Chamber' 1 72-5000-20 72-5000-21 72-5000-16
10 Clamp Band Assembly 1 01-7300-03 01-7300-03 01-7300-03 11 Carriage Bolt, 1/4-20 x 2 2 01-6070-03 01-6070-03 01-6070-03 12 Nut, HEX (1/4-20) 2 04-6400-03 04-6400-03 04-6400-03 13 Primary Diaphragm' 1 * * * 14 Back-Up Diaphragm' 1 01-1060-51 01-1060-51 01-1060-51
Grounding Strap (Not Shown) 1 N/A N/A 00-8300-99
'Air regulator body includes slipper seals and back-up 0-rings.
'Liquid chamber is available with BSP threads. The additional digits "14" added to the end of the part number designated BSP threads.
'Back-up diaphragm is only utilized with Teflon00 primary diaphragm.
'Teflon00 Gasket Kit, P/N 01-9500-99, required.
*Refer to page 30 for elastomer options.
All bold face items are primary wear parts.
ALUMINUM STAINLESS STEEL
ITEM PART DESCRIPTION OTY. SD112/APP SD112/SPP
1 Air Regulator Body' 1 72-8500-20 72-8500-20
2 Slipper Seal 3 01-3210-55-200 01-3210-55-200 3 Back-Up D-Ring 3 01-2390-52 01-2390-52 4 Reducer Bushing 1 72-6950-07 72-6950-07
5 Straight Shaft 1 01-3800-03-07 01-3800-03-07 6 S.S. Threaded Stud 1 NA 01-6150-03 7 Inner Piston 1 01-3710-01 01-3710-01 8 Outer Piston 1 01-4570-01 01-4570-03 9 Liquid Chamber' 1 72-5000-01 72-5000-03
10 Clamp Band Assembly 1 01-7300-03 01-7300-03 11 Carriage Bolt, 1/4-20 x 2 2 01-6070-03 01-6070-03 12 Nut, HEX (1/4-20) 2 04-6400-03 04-6400-03 13 Primary Diaphragm' 1 * * 14 Back-Up Diaphragm' 1 01-1060-51 01-1060-51
'Air regulator body includes slipper seals and back-up 0-rings.
'Liquid chamber is available with BSP threads. The additional digits "14" added to the end ofthe part number designated BSP threads.
'Refer to page 30 for elastomer options.
'Back-up diaphragm is only utilized with Teflon00 primary diaphragm.
All bold face items are primary wear parts.
TEFLON00 PTFE
SD112/TPP
72-8500-20
01-3210-55-200 01-2390-52 72-6950-07
01-3800-03-07
NA
01-3710-01 01-4570-22-500
72-5000-55 01-7300-03 01-6070-03 04-6400-03
01-1060-51
N/A
WIL-19010-E-04 19 WILDEN PUMP & ENGINEERING, LLC
LarkinD Rectangle
LarkinD Rectangle
LarkinD Line
ELASTOMER OPTIONS
ELASTOMER DIAPHRAGM
METAL Teflon" PTFE 01-1010-55
AND Buna-N 01-1010-52
PLASTIC Viton" 01-1010-53 sox SaniflexTM 01-1010-56
EQUALIZER® Wii-Fiex™ 01-1010-58
Neoprene - Teflon" PTFE 04-1010-55
Buna-N 04-1010-52
METAL Neoprene 04-1010-51
SD1 Nordel" 04-1010-54
EQUALIZER® Viton" 04-1010-53
Wii-Fiex™ 04-1010-58
Saniflex™ 04-1010-56
Tello n" PTFE 04-1010-55
Teflon" Encapsulated Viton" NA
PLASTIC
Buna-N 04-1010-52
Neoprene 04-1010-51 SD1 Nordel" 04-1010-54
EQUALIZER® Viton" 04-1010-53
Wii-FiexTM 04-1010-58
Saniflex™ 04-1010-56
Teflon" PTFE 08-1010-55
METAL
Buna-N 08-1010-52-06
Neoprene 08-1010-51-06 SD2 Nordel" 08-1010-54-06
EQUALIZER® Viton" 08-1010-53-06
SaniflexTM N/A
Teflon" PTFE 08-1010-55
Teflon"' Encapsulated Viton" NA
PLASTIC Buna-N 08-1010-52-06
SD2 Neoprene 08-1010-51 -06
EQUALIZER® Nordel" 08-1010-54-06
Viton" 08-1010-53-06
Saniflex™ N/A
METALS03
Saniflex™ 08-1010-56
30FDA Wii-Fiex™ 08-1010-57 SAN I FLO™ FDA Buna-N 08-1010-69
EQUALIZER® FDA Nordel" 08-1010-74
Buna-N, Nordel and Vi ton are registered trademarks of DuPont Dow Elastomers.
Teflon is a registered trademark of DuPont.
WILDEN PUMP & ENGINEERING, LLC 30
BACK-UP DIAPHRAGM 0-RINGS
NA NA
NA NA
NA NA
NA NA
NA NA
01 -1060-51 NA
NA 70-1280-55
NA 70-1280-52
04-1060-51 NA
NA NA
NA NA
NA NA
04-1060-56 NA
NA NA
NA 70-1270-60
NA 70-1270-52
04-1060-51 NA
NA NA
NA NA
NA NA
04-1060-56 NA
NA 71-1281-55
NA 71-1281-52
08-1060-51 NA
NA NA
NA NA
08-1060-56 NA
NA NA
NA 71 -1270-60
NA 71 -1270-52
08-1060-51 NA
NA NA
NA NA
08-1060-56 NA
NA NA
NA NA
NA NA
NA NA
WIL-19010-E-04
LarkinD Highlight
LarkinD Highlight
LarkinD Highlight
LarkinD Line
TORQUE SPECIFICATIONS
DESCRIPTION OF PART MAXIMUM TORQUE
METAL AND Air Regulator Body 75 in.-lbs. [8 m-N]
PLASTIC
Outer Piston 75 in.-lbs. [8 m-N]
SD/4
Clamp Band Assembly- Rubber-Fitted 65 in.-lbs. [7.4 m-N] EQUALIZER® Clamp Band Assembly- Teflon®-fitted 85 in.-lbs. [9.6 m-N]
Air Regulator Body 11 ft.-lbs. [14.9 m-N]
METAL Shaft Assembly 33 ft.-lbs. [44.7 m-N]
SD1 Small Clamp Band 30 in.-lbs. [3.4 m-N]
EQUALIZER® Large Clamp Band- Rubber 100 in.-lbs. [11.3 m-N]
Large Clamp Band- Teflon® 120 in.-lbs. [13.6 m-N]
PLASTIC
Air Regulator Body 11 ft.-lbs. [14.9 m-N]
Shaft Assembly 33 ft.-lbs. [44.7 m-N]
SD1
Small Clamp Bands 85 in.-lbs. [9.6 m-N]
EQUALIZER®
Large Clamp Bands 165 in.-lbs. [18.6 m-N]
Air Regulator Body 28 ft.-lbs. [38.0 m-N]
METAL
Shaft Assembly- Rubber 33 ft.-lbs. [44.7 m-N]
Shaft Assembly- Teflon® 58 ft.-lbs. [78.6 m-N] SD2 Small Clamp Band- Rubber 27 in.-lbs. [3.0 m-N]
EQUALIZER®
Small Clamp Band- Teflon® 58 in.-lbs. [6.6 m-N]
Large Clamp Band 28 ft.-lbs. [38.0 m-N]
Air Regulator Body 28 ft.-lbs. [38.0 m-N]
PLASTIC Shaft Assembly- Rubber 33 ft.-lbs. [44.7 m-N]
SD2 Shaft Assembly- Teflon® 58 ft.-lbs. [78.6 m-N]
EQUALIZER® Small Clamp Band 90 in.-lbs. [10.2 m-N]
Large Clamp Band 28 ft.-lbs. [38.0 m-N]
METAL
Air Regulator Body 28 ft.-lbs. [38.0 m-N]
Shaft Assembly- Rubber 33 ft.-lbs.[44.7 m-N] SD2 BOLTED Shaft Assembly -Teflon® 58 ft.-lbs. [78.6 m-N]
EQUALIZER®
Liquid to Air Chamber 20 ft.-lbs. [27.1 m-N]
METALSD3
Air Regulator Body 28 ft.-lbs. [38.0 m-N]
Shaft Assembly- Rubber 33 ft.-lbs.[44.7 m-N] SAN I FLO™ Shaft Assembly -Teflon® 58 ft.-lbs. [78.6 m-N]
EQUALIZER®
Liquid to Air Chamber N/A
WIL-19010-E-04 31 WILDEN PUMP & ENGINEERING, LLC
LarkinD Rectangle
LarkinD Line
PRESSURE VARIATION BAND
BAR FEET PSIG
6.8 240 100
5.4 180 80
4.1 140 60
2.7 100 40
1.3 40 20
Water Discharge GPM Flowrates (Umin)
(18.9)
WITHOUT EQUALIZER I
WITH SD1 EQUALIZER
(37.9)
(56.8)
The above curve reflects the discharge pressure variation of a Wilden model T1 compared to an T1 with the Equalizer" (model SD1) installed. Plotted data points were obtained from an Oscilloscope.
WILDEN PUMP & ENGINEERING, LLC 32 WIL-19010-E-04
| Cover Page Information |
| Revision History and Approvals |
| Tab 1 - NYCS000015410,CSS,Pulsation Dampeners |
| Tab 2 - NYCS000015177,Pulsation Dampener,Wilden,0.5in |
| Title: Pulsation Dampeners, 01.287 |
| Document: NYCS000015353 |
| Revision: 00 |
| RevRow1: 0 |
| NameCreated By: DMLarkin |
| DateCreated By: 11-DEC-2019 |
| NameApproved By: JHoskins |
| DateApproved By: 11-DEC-2019 |
| Revision DescriptionRow1: Initial Issue |
| RevRow2: |
| NameCreated By_2: |
| DateCreated By_2: |
| NameApproved By_2: |
| DateApproved By_2: |
| Revision DescriptionRow2: |
| RevRow3: |
| NameCreated By_3: |
| DateCreated By_3: |
| NameApproved By_3: |
| DateApproved By_3: |
| Revision DescriptionRow3: |
| RevRow4: |
| NameCreated By_4: |
| DateCreated By_4: |
| NameApproved By_4: |
| DateApproved By_4: |
| Revision DescriptionRow4: |
File details come from the government source that posted it. Updated .