Addendum 003 - Analytical Instrumentation - Flow Instrumentation R1.pdf

PDF 25 MB Posted

Attached to
Request for Proposal - Construction Services for Project L-897, Central Plateau Water Treatment Facility
Solicitation number
338214
Issued by

View the file

Other files

File Type Posted
Addendum 003 - O and M Manual - Prelim Oper and Maint Manual - Template R0.pdf PDF
Addendum 003 - Equipment - Automatic Strainers R0.pdf PDF
Addendum 003 - Valves - Other Check Valves R0.pdf PDF
Addendum 003 - Recommended Electrical Spare Parts List R0.pdf PDF
Addendum 003 - Equipment - Tab 3 - Anchor Bolt List R0.pdf PDF
Addendum 003 - Valves - Butterfly Valves R0.pdf PDF
Addendum 003 - Electrical Drawings - REMOTE IO 24VDC POWER PANEL.pdf PDF
Addendum 003 - Valves - Air Release Valves R0.pdf PDF
Addendum 003 - Analytical Instrumentation Valve List R0.pdf PDF
Addendum 003 - Valves - Auto Drain Valve R0.pdf PDF
Addendum 003 - Equipment - Commissioning Plan R0.pdf PDF
Addendum 003 - Valves - Diaphragm Valves R0.pdf PDF
Addendum 003 - VDL 006-006 RFP Const Bidder Pall Documents.xlsx XLSX spreadsheet
Addendum 003 - Valves - Other Solenoid Valves R0.pdf PDF
Addendum 003 - Electrical Drawings - FEED STRAINER PLC IO PANEL.pdf PDF
Addendum 003 - Valves - Other Air Pressure Valves R0.pdf PDF
Addendum 003 - Valves - Solenoid Valves R0.pdf PDF
Addendum 003 - Equipment - Actuator Torque Tables R1.pdf PDF
Addendum 003 - Equipment - Filter Elements R0.pdf PDF
Addendum 003 - Valves - Dual Disc Check Valves R0.pdf PDF
Addendum 003 - Equipment - FRP Tanks R0.pdf PDF
Addendum 003 - Equipment - Equipment List R0 - Pall Comments.pdf PDF
Addendum 003 - O and M Manual - System Functional Description (SFD) R0.pdf PDF
Addendum 003 - Electrical Drawings - MAIN CONTROL PANEL.pdf PDF
Addendum 003 - Electrical Drawings - MF VALVE RACK PANEL.pdf PDF
Addendum 003 - Electrical Drawings - Main CP 24VDC Power Panel.pdf PDF
Addendum 003 - Analytical Instrumentation - Level Instrumentation R1.pdf PDF
Addendum 003 - Valves - Air Pressure Control Valves R0.pdf PDF
Addendum 003 - Equipment - FRP Tanks attachment.pdf PDF
Addendum 003 - Contractual Electrical Spare Parts List R0.pdf PDF
Addendum 003 - Equipment - Air System R1.pdf PDF
Addendum 003 - Analytical Instrumentation - Temperature Instrumentation R1.pdf PDF
Addendum 003 - Valves - Ball Valves R0.pdf PDF
Addendum 003 - Valves - Chemical Pressure Control Valves R0.pdf PDF
Addendum 003 - Major Electrical Comp R0.pdf PDF
Addendum 003 - Electrical Drawings - CIP CAUSTIC ROOM PLC IO PANEL.pdf PDF
Addendum 003 - Exceptions and Clarifications - Specification Cross Reference Matrix R0.pdf PDF
Addendum 003 - Equipment - Calibration Columns R0.pdf PDF
Addendum 003 - Equipment - Centrifugal Pumps R0.pdf PDF
Addendum 003 - Equipment - Indeeco Heater General Infor R0.pdf PDF
Addendum 003 - Mechanical Drawings - Membrane Train Assy Dwg R3.pdf PDF
Addendum 003.pdf PDF
Addendum 003 - Equipment - Wilden Pump General Information R0.pdf PDF
Addendum 003 - Equipment - Water Softener R0.pdf PDF
Addendum 003 - Electrical Drawings - Interconnect Diagram Pall Comments.pdf PDF
Addendum 003 - Analytical Instrumentation - Pressure Instrumentation R1.pdf PDF
Addendum 003 - Mechanical Drawings - P and ID R4 Pall Submittal Return Comments.pdf PDF
Addendum 003 - Valves - Water Pressure Control Valves R0.pdf PDF
Addendum 003 - Equipment - Other Strainers R0.pdf PDF
Addendum 003 - Equipment - NSF PID Scope R0.pdf PDF
Show 40 more

Latest 50 of 88 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

COVER PAGE OF SELLER’S SUBMITTAL

City Name: Hanford, WA - MSA

Pall Project No.: 01.000287

Job Number: Project L-897, Subcontract 70816

Task Register 6 (Task 1 – VI Submittal Package)

To: (Contractor)

Mission Support Alliance, LLC (MSA)

PO Box 650

Richland, WA 99352

From: (Subcontractor)

Pall Water

A Division of Pall Corporation

839 State Route 13

Cortland, NY 13045

Patty Willis

Phone: 607-758-1699

Name of Project: Hanford, WA, Central Plateau WTF

Pall Document Number: NYCS000015175 Rev: 01

Description of Item: Flow Instrumentation

Specification Section: 40 73 02

Deviations: See document NYCS000015383

INDEX:

Page 1: Cover Page Information

Page 2: Revision History and Approvals

Page 3: Tab 1 - NYCS000015448,CSS,Flow Instrumentation,01.287 R01

Pages 4-15: Tab 2 - Brooks GT1600 Rotometer Cut Sheet R00

Pages 16-19: Tab 3 - Hach TU5X00 Flow Sensor Cut Sheet R00

Pages 20-23: Tab 4 - Turck Flow Switch Cut Sheet R00a

Pages 24-61: Tab 5 - 0.5 Inch Rosemount 8750W Magnetic Flow Meter Cut Sheet R00

Pages 62-101: Tab 6 - 6-Inch & 8-Inch Rosemount 8750W Magnetic Flow Meter Cuts

Pages 102-125:Tab 7 - FCI ST100L Air Flow Meter Cut Sheet R00

Date: 12/19/2019

PALL ADVANCED SEPARATIONS SYSTEMS

DIVISION OF PALL CORPORATION, CORTLAND, NY

Rev Name Date Created By

Approved By

Created By

Approved By

Created By

Approved By

Created By

Approved By

Revision Description

Title

Document # Revision griffinju Text Box These commodities, technology, or software may only be exported from the United States in accordance with the Export Administration Regulations. Diversion contrary to U.S. law is prohibited.

Doc Number: NYCS000015448R01 Doc Title: NYCS000015448,CSS,Flow Instrumentation,01.287 R01.docx

Components Specification Sections

The following specification sections are relevant to the approval of submittal NYCS000015175, Flow Instrumentation,01.287:

L‐897, Attachment No. 2 ‐ HNF‐SPEC‐63538, Section 40 73 02, Process Instrumentation Meters & Transmitters.

Any exceptions and clarifications to the specification section above can be found in submittal NYCS000015383, L‐897, Section 40 73 02, Es and Cs,01.287.

Pall has taken exceptions and clarifications relevant to the flow instrumentation proposed.

PALL CORPORATION

Membrane Filtration (MF) System

FLOW INSTRUMENTATION CUT SHEET

Rotometers (Flow Indicators):

3.5 to 35 Liters/Hour:

BROOKS P/N: 16 4 0 A G6 A 1 AA 1 3 D 1 0 A

Part Number Key:

16 Base Model, Horizonatl Inlet & Outlet 4 127mm Scale Length, 127 – Low Flow 0 Horizontal Inlet, Horizontal Outlet Connections A Always “A” (Default)

G6 R-6-127-AT Tube, ¼” Ball Float, Carboloy

3.5 to 35 LPH Range, Water

A 316 SST Fittings 1 ¼” Connection Size

AA Standard NPT(F) Connection 1 Viton O-Ring 3 Direct Reading Scale D +/- 2 Percent Full Scale Accuracy 1 Valve at Inlet 0 No Alarms A No Approvals

9 to 90 Liters/Hour:

BROOKS P/N: 16 4 0 A H6 A 1 AA 1 3 D 1 0 A

Part Number Key:

16 Base Model, Horizonatl Inlet & Outlet 4 127mm Scale Length, 127 – Low Flow 0 Horizontal Inlet, Horizontal Outlet Connections A Always “A” (Default)

H6 R-6-127-BT Tube, ¼” Ball Float, Carboloy 9 to 90 LPH Range, Water

A 316 SST Fittings 1 ¼” Connection Size

AA Standard NPT(F) Connection 1 Viton O-Ring 3 Direct Reading Scale D +/- 2 Percent Full Scale Accuracy 1 Valve at Inlet 0 No Alarms A No Approvals

Thermal Mass Flow

GT1600 Model

• Configurable to retro-fit GT10xx, GT130x and Full-View

• 360 degrees rotatable viewing angle

• High quality materials for safety, in- and outdoor durability

• 316 stainless steel frame

• Polycarbonate safety shield

• 316/316L dual certified stainless steel process fittings

• Alarms for high- and low flow (optional for all flow ranges, either at time of order, or as add-on in the field)

• Flanged or threaded connections, available horizontal and vertical

• Panel- and wall mount options

• Easy in-situ maintenance: Clean or replace tube and float without removal from the process piping

• Adjust the scale to compensate for process variation

• Optional integral needle valve

DATA SHEET- data

Variable Area

Model GT1600

1BrooksInstrument.com

Flow Accuracy Standard: ±10%, ± 5%, ±2% Full Scale, Class 2.5 acc VDI/VDE Optional: ±1% Full Scale, Class 1.6 acc VDI/VDE

Repeatability ≤ 0.5% Full Scale

Ambient Temperature Limits ‐4°F to 125°F | ‐20°C to 52°C

Scales Transparant scale. Adjustable Nominal Lengths: 75mm, 127mm and 250mm Choice of direct reading units, millimeter or percentage of maximum flow with factor tag.

Operating Fluid Temperature Limits 33 to 250°F | 1°C to 121°C

Mounting options In‐line Panel‐mount (see Dimensions) Wall‐mount (see Dimensions)

Features

View GT1600 Product Page

Industrial Glass Tube Variable Area Flow Meters

Product Specifications

Capacities and Pressure Drops See Capacities

HomR Text Box

3.5 to 35 LPH: BROOKS P/N 16 4 0 A G6 A 1 AA 1 3 D 1 0 A 9 to 90 LPH: BROOKS P/N: 16 4 0 A H6 A 1 AA 1 3 D 1 0 A psi bar psi bar 02 300 20.7 240 16.5 06 300 20.7 240 16.5 07 300 20.7 240 16.5 08 250 17.0 240 16.5 09 200 13.8 200 13.8 10 175 12.1 175 12.1

Metering Tube (wetted) Process fittings (wetted)

Float Stops (wetted) O rings (wetted) Housing Window & safety shield Hardware

Tube size 02&06 Tube size 07 10

Pressure Ratings

Float (wetted)

Materials of construction

Maximum Operating Pressure (PSIG | bar) at Fluid Temperature Tube size Threaded process connections Flanged process connections

Horizontal IN/OUT Horizontal IN/OUT

Vertical IN/ Horizontal OUT

Process connections NPT Threaded Flanged ANSI 150# RF

Vertical IN/ Horizontal OUT

Vertical IN/OUT

Polycarbonate with UV inhibitor 316 stainless steel

Valve Optional integral needle valve

Div1/Div2 (CSA) – gas/dust. Protection method I.S. / Non incendive Zone1/Zone2 (CSA/ATEX/IECex) – gas/dust. Protection method Ex m (no barrier)

Alarms Ring initiator high / low alarm

Hazardous area approvals

Material Certification to DIN 3.1 Declaration of Compliance 2.1 Oxygen Service

Reed switch high / low alarm

Vertical IN/OUT Horizontal IN/ Vertical OUT Horizontal IN/ Vertical OUT

316/316L (dual certified stainless steel)

Viton®, Buna N, Kalrez®, EPDM

Sizes 2&6: Carboloy® or 316/316L (dual certified stainless steel) Sizes 7 10: 316/316L (dual certified stainless steel) Teflon®

Borosilicate glass

Certifications International Calibration Certificate

316 stainless steel

Product Specifications

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Line

HomR Line

HomR Rectangle

Product Specifications - Capacities

±0.9% of S.P. (20-100% F.S.), ±0.18% of F.S. (2-20% F.S.)

>1100 slpm F.S.:

±1.0% of F.S.

AA1:L48

127-Low Flow Pressure Drop Pressure Drop Alarm inch W.C./kPa inch W.C./kPa Type

R-2-127-AAAAT 316SS 1.9 0.11 0.7/0.17 1.0 0.11 6.7 0.8/0.19

R-2-127-AAAAT Carboloy 3.7 0.22 1.1/0.27 1.0 0.2 12 1.2/0.3

R-2-127-AAT Carboloy 7.5 0.45 1.2/0.29 1.0 0.38 23 1.5/0.37

R-2-127-DT 316SS 15 0.93 0.9/0.22 1.0 0.68 40 1.0/0.24

R-2-127-DT Carboloy 25 1.5 1.5/0.38 1.0 1 61 1.7/0.42

R-2-127-AT 316SS 39 2.3 1.1/0.27 1.0 1.4 86 1.2/0.3

R-2-127-AT Carboloy 59 3.5 1.9/0.47 1.0 2 120 2.1/0.52

R-2-127-BT 316SS 110 6.8 1.8/0.45 1.0 3.9 230 2.0/0.21

R-2-127-BT Carboloy 170 10 3.0/0.75 1.0 5.6 340 3.3/0.83 R-2-127-CT Carboloy 270 16 6.1/1.51 1.0 9 540 4.8/1.2

R-6-127-AT 316SS 410 25 6.1/1.53 1.0 14 850 6.8/1.7

R-6-127-AT Carboloy 620 37 10.5/2.61 1.0 20 1200 11.6/2..9

R-6-127-BT 316SS 1000 65 30.1/7.5 1.0 35 2100 33.3/8.3

R-6-127-BT Carboloy 1500 95 57.8/14.4 1.0 49 2900 64.2/16

250-High Flow Pressure Drop Pressure Drop inch W.C./kPa inch W.C./kPa

7-XV-11A-A 0.48 100 8/2 1.0 1.8 3.1 10/2.5

7-XS-23-A 0.77 170 16/4.0 1.0 3.3 5.6 17/4.2

8-XV-8-A 1.00 240 5/1.5 3.7 4.4 7.5 5/1.3

8-XV-14-A 1.40 320 8/2 5.4 5.8 9.9 8/2

8-XV-31-A* 2.00 460 16/4 7.0 14 24 17/4.3

9-XS-33-A 3.20 730 4/1 2.3 13 22 8/2

9-XV-87-A* 3.90 890 14/3.5 17 28 48 16/4

9-XS-87-A* 5.10 1100 18/4.5 3.5 36 62 19/4.8

10-XV-64-A 6.20 1400 12/3 15 25 43 14/3.5

10-XS-64-A 7.80 1700 16/4 3.7 32 54 18/4.5

10-XS-138-A* 10.00 2400 30/7.5 5.5 80 130 36/9

10-XJ-238-A* 21.00 4800 104/26 1.0 150 270 16/4

127-High Flow 7-XV-11A-A 0.41 93 8/2 1.0 1.8 3.1 10/2.5

7-XS-23-A 0.66 150 16/4.0 1.0 2.7 4.6 17/4.2

8-XV-8-A 0.99 220 5.0/1.25 3.7 4 6.9 6.0/1.5

8-XV-14-A 1.3 310 8.0/2 5.4 5.3 9.1 10/2.5

8-XV-31-A* 1.7 400 24/6 7.0 11 20 28/7

9-XS-33-A 3.0 690 7.0/1.7 2.3 12 21 8.0/2.0

9-XV-87-A* 3.6 830 14/3.5 17 26 44 16/4.0

9-XS-87-A* 4.5 1000 17/4.2 3.5 32 55 20/5.0

10-XV-64-A 6 1300 9/2.25 15 24 41 10/2.5

10-XS-64-A 7.4 1600 12/3 3.7 30 52 13/3.25

10-XS-138-A* 9.8 2200 29/7.25 5.5 68 110 33/8.25

10-XJ-238-A* 20 4700 104/26 1.0 140 250 16/4

075-High Flow 8-XV-8-A 0.82 180 8/2 3.3 5.6 9/2.25

8-RJ-10 1.5 340 9/2.25 6.3 10 11/2.7

8-RJ-23 2.4 540 13/3.25 9.9 16 15/3.7

8-RJ-30 3.1 710 19/4.8 13 22 22/5.5

8-RJ-39 4.7 1000 34/6

10-RJ-80 12 2700 18/4.5

10-RJ-180 21 4900 71/17.6

10-RJ-37 24 40 18/4.5

10-RJ-83 36 62 35/8.7

10-RJ-90 55 93 71/17.6

Ring Initiator

Reed Switch

Size 02

Size 06

SLPM ln/h

Size 07 R-7M-25-1FT

Size 08 R-8M-25-4FT

Size 09 R-9M-25-3FT

Size 10 R-10M-25-3FT

Full Scale - Water Full Scale - Air

Tube Float GPM l/h V.I.C.

cSt

Tube Float cc/min l/h V.I.C.

cSt

SCFM m3n/h

Size 07 R-7M-127-1FT

Size 08

Size 10 R-10M-75-3

R-8M-75-1

Size 08 R-8M-127-4FT

Size 09 R-9M-127-3FT

Size 10 R-10M-127-3FT

HomR Rectangle

HomR Rectangle

HomR Text Box

Product Specifications - Dimensions

Product Description - Dimensions inch mm inch mm inch mm inch mm inch mm inch mm

H-IN / H-OUT 1020 8.59 218.3 0.59 15.0

V-IN / V-OUT 1024 9.84 250.0 - -

H-IN / V-OUT 1026 9.22 234.1 0.59 15.0

V-IN/ H-OUT 1027 9.22 234.1 0.59 15.0

H-IN / H-OUT 1110 8.59 218.3 0.59 15.0

V-IN / V-OUT 1114 9.63 244.5 - -

H-IN / V-OU 1T 140 9.11 231.4 0.59 15.0

V-IN/ H-OUT 1144 9.11 231.4 0.59 15.0

H-IN / H-OUT 1020 8.59 218.3 3.50 75.0

V-IN / V-OUT 1024 10.63 270.0 - -

H-IN / V-OU 1T 026 9.61 244.1 2.95 75.0

V-IN/ H-OUT 1027 9.61 244.1 2.95 75.0

H-IN / H-OUT 1140 8.59 218.3

V-IN / V-OUT 1144 377.8 - -

H-IN / V-OU 1T 146 11.73

V-IN/ H-OUT 1147 11.73

H-IN / H-OU 1T 020 17.50 444.5 0.91 23.0

V-IN / V-OUT 1024 19.69 500.0 - -

H-IN / V-OU 1T 026 18.59 472.3 0.91 23.0

V-IN/ H-OUT 1027 18.59 472.3 0.91 23.0

H-IN / H-OUT #7/8 16.50 419.1

H-IN / H-OUT #9/10 17.50 444.5

V-IN / V-OUT #7/ 18 7.00 431.8

V-IN / V-OUT #9/10 17.25 438.2

H-IN / V-OUT #7/ 18 6.75 425.5

H-IN / V-OUT #9/1 10 7.38 441.3

V-IN/ H-OUT #7/ 18 6.75 425.5

V-IN/ H-OUT #9/10 17.38 441.3

V-IN / V-OUT Retrofit only(4) GT1307 1307 16.94 430.2 - -

H-IN / H-OUT #7/8 3.94 100.0

H-IN / H-OUT #9/1 40 .72 120.0

V-IN / V-OUT 1024 19.69 500.0 - -

H-IN / V-OUT #7/8 3.94 100.0

H-IN / V-OUT #9/1 40 .72 120.0

V-IN/ H-OUT #7/ 38 .94 100.0

V-IN/ H-OUT #9/10 4.72 120.0

H-IN / H-OUT #7/

22.88

8 3 .50 88.9

H-IN / H-OUT #9/10 4.00 101.6

V-IN / V-OUT #7/

7.00 419.1

V-IN / V-OUT #9/10

17.25 444.5

H-IN / V-OUT #7/8 3 .50 88.9

H-IN / V-OUT #9/10 4 .00 101.6

V-IN/ H-OUT #7/8 3 .50 88.9

V-IN/ H-OUT #9/10 4 .00 101.6

Note (3) - Standard dimension

Note (4) - Retro-fit dimensions are for replacement of GT10xx, GT130x and Full-View meters in e in new in .

6.0

Full-ViewRetrofit only(4)

Flanged 150lbs RF

Notes

Dimension A B C L M N

Meter type Tube size

Process on

Or n H(orizontal)

V(er al R) etro-fit Model

50.0 4.00 101.6 1.00 25.4

127-Low Flow 02

NPT- GF T1000Standard dimensions(3)

1.97 0.24

1110 0.91 23.0

1114 - -

70.0 8.002.76

0.91 23.0

1117 0.91

18.59 472.3

GT1000Standard dimensions(3)

Full-ViewRetrofit only(4)

250-High Flow 07

Standard dimensions(3)

Full-ViewRetrofit only(4)

Full-View 1140Retrofit only(4)

GT1000Flanged 150lbs RF

NPT- GF T1000Standard dimensions(3)

7.0203.2 1.63 41.28 0.28

23.0

17.50 444.5

18.59 472.3

P Q

3.00 101.6 14.88

298.1 298.1

3.00 101.6

3.00 101.6

1847.24 37.61.48

393.515.49 69.72.74

581.0

22.50 571.5

19.69 500.0

20.00 508.0

19.69 500.0

20.00 508.0 inch mm inch mm inch mm inch mm inch mm inch mm inch mm inch mm

H IN / H OUT 12.31 312.7 0.91 23.0

V IN / V OUT 14.50 368.2

H IN / V OUT 13.41 340.5 0.91 23.0

V IN/ H OUT 13.95 354.4 0.91 23.0

H IN / H OUT #7/8 11.50 292.1

H IN / H OUT #9/10 12.50 317.5

V IN / V OUT #7/8 12.00 304.8

V IN / V OUT #9/10 12.25 311.2

H IN / V OUT #7/8 11.75 298.5

H IN / V OUT #9/10 12.38 314.3

V IN/ H OUT #7/8 11.75 298.5

V IN/ H OUT #9/10 12.38 314.3

V IN / V OUT Retrofit only(4) GT1306 1306 11.75 298.5

H IN / H OUT #7/8 3.94 100.0

H IN / H OUT #9/10 4.72 120.0

V IN / V OUT #7/8

V IN / V OUT #9/10

H IN / V OUT #7/8 3.94 100.0

H IN / V OUT #9/10 4.72 120.0

V IN/ H OUT #7/8 3.94 100.0

V IN/ H OUT #9/10 4.72 120.0

H IN / H OUT #7/8 11.50 292.1 3.50 88.9

H IN / H OUT #9/10 12.50 317.5 4.00 101.6

V IN / V OUT #7/8 17.88 454.0

V IN / V OUT #9/10 17.50 444.5

H IN / V OUT #7/8 14.69 373.0 3.50 88.9

H IN / V OUT #9/10 15.00 381.0 4.00 101.6

V IN/ H OUT #7/8 14.69 373.0 3.50 88.9

V IN/ H OUT #9/10 15.00 381.0 4.00 101.6

H IN / H OUT 9.02 229.1 0.83 21.0

V IN / V OUT 11.20 284.6

H IN / V OUT 10.11 256.9 0.83 21.0

V IN/ H OUT 10.11 256.9 0.83 21.0

V IN / V OUT Retrofit only(4) GT1305 1305 7.75 196.9

H IN / H OUT #7/8 3.94 100.0

H IN / H OUT #9/10 4.72 120.0

V IN / V OUT #7/8

V IN / V OUT #9/10

H IN / V OUT #7/8 3.94 100.0

H IN / V OUT #9/10 4.72 120.0

V IN/ H OUT #7/8 3.94 100.0

V IN/ H OUT #9/10 4.72 120.0

Note (3) Standard dimension are for new installations

Note (4) Retro fit dimensions are for replacement of GT10xx, GT130x and Full View meters in existing installation. Not for use in new installations.

Model

Dimension A B C L M N

1110 0.91 23.0

NPT F Standard dimensions(3)

1116 0.91 23.0

1117 0.91 23.0

Retrofit only(4)

70.0 N/A2.76

10.11 256.9

10.11 256.9

13.41 340.5

13.41 340.5

Standard dimensions(3)

12.31 312.7

14.50 368.2

9.02 229.1

11.20 284.6

Retrofit only(4)

NPT F Standard dimensions(3)

127 High Flow

075 High Flow 08

Flanged 150lbs RF

Full View

GT1000

Full View

Notes

Flanged 150lbs RF

Standard dimensions(3)

Meter type Tube size

Process connection

Orientation H(orizontal) V(ertical) Retro fit

Product Specifications - Dimensions

Product Approvals Overview

M e c h a n ic a l

R e e d

S w it c h

In d u c ti v e A la rm

Declaration Declaration

CRN

ATEX

IECEX

Explosion safety "Intrinsic Safety (ia)

UL File E73889 Vol3 Sec

Explosion safety "Intrinsic Safety (ia)"

ATEX

Pepperl + Fuchs

PTB 99 ATEX 2128 X

Pepperl + Fuchs Control Draw ing:116- 0165G

TCF: 203104000-1604

Explosion safety "Intrinsic Safety

(ia)"

Inductive Ring Sensor

Non-Hazardous Locations Pow er Supply Current consumption

Ambient Temperature

Hazardous Location

ATEX

FM Approvals

Pepperl + Fuchs Model: RC10-14-N3-Y53478 Pepperl + Fuchs Model: RC15-14-N3-Y53479

Nominal Voltage 8V Operating Voltage 5...25V Active area clear : 3mA (at 8V) Active area obscured: 0.5...0.95mA (at 8V)

0°C to 40°C

II 2 G Ex ia IIC T6…T1 Gb IP67 Refer to ATEX Certif icate for: Input parameters, Max Ambient Temperature, Special conditions for use

Class I, Division 1, Group A, B, C, Class II, Division

Standards used for evaluation:

Ambient Temperature range:

Input Pow er:

Special conditions for safe

EN 60079-0 : 2012+A11: 2013, EN 60079-18 : 2015

IEC 60079-0 : 2011, IEC 60079-18 : 2014

-20 °C to +65 °C (Standard Version) -20 °C to +55 °C (With Junction box Version) 30V, 250mA, 3W Refer to IOM

Ambient Temperature ratings:

Input parameters:

Special conditions for safe use:

-20° C ≤ Tamb ≤ 65° C Vmax = 30V, Imax = 100mA, Ci = 0μF, Li = 0μH Refer to IOM

IS Class I, II, III, Div 1, Groups A, thru G

Ex mb IIC T6 Gb Ex mb IIIC T85°C Db (Standard Version)

KIWA 18ATEX0013 X

IECEx KIWA 18.0008X

Declarations Mark

Meter Options

Standards/Directives/Marking Status/Certificate

Explosion safety "Constructional safety (c)"

ATEX II2G Ex h IIC T6…T4 Gb II2D Ex h IIIC T120°C Db Special conditions for safe use:

Refer to IOM

EU Declaration of Conformity

EMC Directive (2014/30/EU) RoHS Directive (2011/65/EU)

EMC Directive (2014/30/EU)

Reed Sw itch Alarms are classif ied as “Simple Apparatus” w hen used in Intrinsically Safe circuits. They comply w ith the requirements of EN60079-11 clause 5.7 – Simple apparatus.

Pressure Equipment Directive (2014/68/EU) EMC Directive (2014/30/EU) The equipment uses a reed sw itch sensor & is outside the scope of the directive since the inherent nature of the physical characteristics of w hich is such that:

(i) it is incapable of generating or contributing to electromagnetic emissions w hich exceed a level allow ing radio and telecommunication equipment and other equipment to operate as intended; and

(ii) it operates w ithout unacceptable degradation in the presence of the electromagnetic disturbance normally consequent upon its intended use.

Canadian Registration Number (CRN) Explosion safety "encapsulation (m)"

II 2 G Ex mb IIC T6 Gb II 2 D Ex mb IIIC T85°C Db (Standard Version)

Ex mb IIC T5 Gb Ex mb IIIC T100°C Db (With Junction box Version)

II 2 G Ex mb IIC T5 Gb II 2 D Ex mb IIIC T100°C Db (With Junction box Version) use:

1, Group E, F, G, Class III, Division 1 Class I, Zone 0, Group IIC T6

Product Approvals Overview

Model Code

Code Description Code Option Option Description1

Request a Quote

¹

I.-II. Base Model Number 16 Horizontal Inlet and Outlet

III. Body - Flow/Scale Length Body Flow Scale Length 1 250-High Flow 250mm 2 127-High Flow 127mm 3 075-High Flow 75mm 4 127-Low Flow 127mm

IV. Connection Orientation 0 Horizontal Inlet - Horizontal Outlet 4 Vertical Inlet - Vertical Outlet 6 Horizontal Inlet - Vertical Outlet 7 Vertical Inlet - Horizontal Outlet

V. Model Revision A Initial release of global model code

VI.-VII. Maximum Flowrate 250 - High Flow Water Air Code GPM l/h SCFM m3n/h Tube Float

JC 0.48 100 1.8 3.1 J R-7M-25-1FT C 7-XV-11A-A

JF 0.77 170 3.3 5.6 J R-7M-25-1FT F 7-XS-23-A

KC 1.00 240 4.4 7.5 K R-8M-25-4FT C 8-XV-8-A

KF 1.40 320 5.8 9.9 K R-8M-25-4FT F 8-XV-14-A

KJ 2.00 460 14* 24* K R-8M-25-4FT J 8-XV-31-A*

LC 3.20 730 13 22 L R-9M-25-3FT C 9-XS-33-A

LF 3.90 890 28* 48* L R-9M-25-3FT F 9-XV-87-A*

LJ 5.10 1100 36* 62* L R-9M-25-3FT J 9-XS-87-A*

MC 6.20 1400 25 43 M R-10M-25-3FT C 10-XV-64-A

MF 7.80 1700 32 54 M R-10M-25-3FT F 10-XS-64-A

MJ 10.00 2400 80* 130* M R-10M-25-3FT J 10-XS-138-A*

MM 21.00 4800 150* 270* M R-10M-25-3FT M 10-XJ-238-A*

* These codes require a back pressure of 30 psig /2 bar

127 - High Flow Water Air Code GPM l/h SCFM m3n/h Tube Float

SC 0.41 93 1.8 3.1 S R-7M-127-1FT C 7-XV-11A-A

SF 0.66 150 2.7 4.6 S R-7M-127-1FT F 7-XS-23-A

TC 0.99 220 4 6.9 T R-8M-127-4FT C 8-XV-8-A

TF 1.3 310 5.3 9.1 T R-8M-127-4FT F 8-XV-14-A

TJ 1.7 400 11* 20* T R-8M-127-4FT J 8-XV-31-A*

UC 3 690 12 21 U R-9M-127-4FT C 9-XS-33-A

UF 3.6 830 26* 44* U R-9M-127-4FT F 9-XV-87-A*

UJ 4.5 1000 32* 55* U R-9M-127-4FT J 9-XS-87-A*

VC 6 1300 24 41 V R-10M-127-3FT C 10-XV-64-A

VF 7.4 1600 30 52 V R-10M-127-3FT F 10-XS-64-A

VJ 9.8 2200 68* 110* V R-10M-127-3FT J 10-XS-138-A*

VM 20 4700 140* 250* V R-10M-127-3FT M 10-XJ-238-A*

* These codes require a back pressure of 30 psig/2 bar

075 - High Flow Water Air Code GPM l/h SCFM m3n/h Tube Float

PC 0.82 180 3.3 5.6 P R-8M-75-1 C 8-XV-8-A

PF 1.5 340 6.3 10 P R-8M-75-1 F 8-RJ-10

PJ 2.4 540 9.9 16 P R-8M-75-1 J 8-RJ-23

PM 3.1 710 13 22 P R-8M-75-1 M 8-RJ-30

PQ 4.7 1000 N/A N/A P R-8M-75-1 Q 8-RJ-39

RC 12 2700 N/A N/A R R-10M-75-3 C 10-RJ-80

RF 21 4900 N/A N/A R R-10M-75-3 F 10-RJ-180

RJ N/A N/A 24 40 R R-10M-75-3 J 10-RJ-37

RM N/A N/A 36 62 R R-10M-75-3 M 10-RJ-83

RQ N/A N/A 55 93 R R-10M-75-3 Q 10-RJ-90

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Text Box

Model Code

Code Description Code Option Option Description1¹

VI.-VII. Maximum Flowrate (continued) 127 - Low Flow Water Air Code GPH l/h SLPM In/h Tube Float

A3 1.9 0.11 0.11 6.7 A R-2-127-AAAAT 3 316SS

A6 3.7 0.22 0.2 12 A R-2-127-AAAAT 6 CARBOLOY

B6 7.5 0.45 0.38 23 B R-2-127-AAT 6 CARBOLOY

C3 15 0.93 0.68 40 C R-2-127-DT 3 316SS

C6 25 1.5 1 61 C R-2-127-DT 6 CARBOLOY

D3 39 2.3 1.4 86 D R-2-127-AT 3 316SS

D6 59 3.5 2 120 D R-2-127-AT 6 CARBOLOY

E3 110 6.8 3.9 230 E R-2-127-BT 3 316SS

E6 170 10 5.6 340 E R-2-127-BT 6 CARBOLOY

F6 270 16 9 540 F R-2-127-CT 6 CARBOLOY

G3 410 25 14 850 G R-6-127-AT 3 316SS

G6 620 37 20 1200 G R-6-127-AT 6 CARBOLOY

H3 1000 65 35 2100 H R-6-127-BT 3 316SS

H6 1500 95 49 2900 H R-6-127-BT 6 CARBOLOY

VIII. Fitting Material A 316 Stainless Steel B 316 Stainless Steel w/ CRN

IX. Connection Size 1 1/4” Low Flow 2 1/2” High Flow 3 3/4” High Flow 4 1” High Flow 5 1” Vertical / 3/4” Horizontal. Size 10 only.

X. - XI. Connection Type AA Standard / GT1000 Retrofit NPT - Female AB Standard / GT1000 Retrofit ANSI #150 RF Flange BA Retrofit GT130x NPT - Female CA Retrofit Full-View 11xx NPT - Female CB Retrofit Full-View 11xx ANSI 150# RF Flange DC Retrofit GT1000 Rc - Female\

XII. O-Ring Material 1 Viton® fluoroelastomer 2 Buna 3 Kalrez®

4 EPDM

XIII. Scale Inscription 1 MM Scale 2 Percent Scale 3 Direct Reading Scale 4 Dual Scale

XIV. Meter Accuracy A ±10% B ±5% Full Scale C ±5% w/calibration D ±2% Full Scale E ±2% Full Scale w/calibration F ±1% Full Scale w/calibration G 2.5 VDI/VDE w/calibration H 1.6 VDI/VDE w/calibration

XV. Valve Type/Location 0 None 1 Valve at Inlet 2 Valve at Outlet

XVI. Alarm 0 None 1 1 Switch/Sensor 2 2 Switches/Sensors

XVII. Approvals A None B ATEX - Zone 1 & Zone 2, non-Electrical C UL / FM - Hazardous location D ATEX - Zone 1 & Zone 2, Electrical

Sample Standard Model Code

I-II III IV V VI-VII VIII IX X-XI XII XIII XIV XV XVI XVII

16 1 4 A D0 A 2 AA 1 3 D 0 0 A

Rectangle

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Text Box

Additional Services Available

· CONDULET JUNCTION BOX ASSEMBLY

Op�on Code Descrip�on

0 None 1 1 Switch/Sensor 203Z023AAA 2 2 Switches/Sensor 203Z023AAA from 16xxG Model Code, posi�on 16 Part Numbers for Relays Alarm

· RELAY

Op�on Code Descrip�on

110VAC

1 or 2 relay

220VAC

1 or 2 relay

24VAC

1 or 2 relay

0 None 1 1 Switch/Sensor 029G008ZZZ or 029G010ZZZ or 029G012ZZZ 2 2 Switches/Sensor 029G008ZZZ or 029G010ZZZ or 029G012ZZZ

Alarm from 16xxG Model Code, posi�on 16 Part Numbers for Relays

· FRONT PANEL MOUNTING KIT

#2-6 778Z018AAA 127mm

#7-10 778Z019AAA 250mm

· BACK PANEL MOUNTING KIT

#2-6 778Z020AAA 127mm

#7-10 778Z021AAA 250mm

· 3.1 Material Cert

· International Calibration Certificate (ICC)

· NACE MR0175 MR0103

· PMI

· Clean for Oxygen Service 2.1

· Declaration of Compliance 2.1

· Pressure Test Certificate 2.2

· Commercial Cleaning

Brooks is committed to assuring all of our customers receive the ideal flow solution for their application, along with outstanding service and support to back it up. We operate first class repair facilities located around the world to provide rapid response and support. Each location utilizes primary standard calibration equipment to ensure accuracy and reli-ability for repairs and recalibration and is certified by our local Weights and Measures Authorities and traceable to the relevant International Standards.

Visit www.BrooksInstrument.com to locate the service location nearest to you.

START-UP SERVICE AND IN-SITU CALIBRATION

Brooks Instrument can provide start-up service prior to operation when required. For some process applications, where ISO-9001 Quality Certification is important, it is mandatory to verify and/or (re)calibrate the products periodically. In many cases this service can be provided under in-situ conditions, and the results will be traceable to the relevant international quality standards.

CUSTOMER SEMINARS AND TRAINING

Brooks Instrument can provide customer seminars and dedicated training to engineers, end users, and maintenance per-sons. Please contact your nearest sales representative for more details. Due to Brooks Instrument’s commitment to continuous improvement of our products, all specifications are subject to change without notice.

TRADEMARKS

Brooks ......................................................................Brooks Instrument, LLC All other trademarks are the property of their respective owners.

DS-VA-GT1600-eng/2019-9

Service and Support

Hach TU5X00sc Series Turbidimeter Flow Sensor:

Hach P/N: LQV160.99.00002

USAGE:

In-Line paddle-wheel type flow sensor to provide local measurement of Hach TU5X00sc Turbidimeter (ie, TU5300sc & TU5400sc) sample water flow rate on Hach SC200 controller

Integral 25-Inch signal cable plugs into port on Hach TU5X00sc series Turbidimeters.

Flow Sensor for TU5300 sc and TU5400 sc Laser Turbidimeter Product #: LQV160.99.00002

USD Price: $152.00 Available

Adding a flow measurement along with your TU5300 sc or TU5400 sc turbidity measurement provides critical information about the status of your drinking water process. A TU5 series turbidimeter's flow sensor accessory can provide alerts to flow issues, giving you important information to resolve problems and get your plant running smoothly.

Product details pdf footer17

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Line

HomR Text Box

SAMPLE

WATER INLET

HomR Oval

HomR Text Box

FE-*

HomR Oval

HomR Text Box

AE-*

HomR Oval

HomR Text Box

AIT

HomR Polygonal Line

HomR Line

HomR Text Box

SAMPLE WATER

TO DRAIN

HomR Line

HomR Text Box

HACH FLOW

SENSOR

HomR Text Box

HACH TU5X00 TURBIDIMETER

SENSOR

HomR Text Box

HACH SC200 CONTROLLER

HomR Oval

HomR Line

HomR Text Box

25" FLOW SENSOR CABLE

HomR Oval

HomR Line

HomR Oval

HomR Line

HomR Text Box

1/4" OD SAMPLE WATER TUBING

HomR Polygonal Line

HomR Text Box

(MANUAL)

FLOW REGULATOR VALVE

HomR Line

HomR Text Box

5.25' TURBIDIMETER

SENSOR CABLE

Polygon

Figure 3 Installation overview with accessories

1 Service bracket 6 Flow sensor (accessory)

2 Automatic cleaning module (accessory) 7 Bubble trap overflow

3 SC controller 8 Sample outlet

4 Bubble trap (accessory) 9 Sample inlet

5 Flow regulator5 10 TU5300 sc or TU5400 sc

5 Not used with the bubble trap.

12 English

HomR Oval

HomR Text Box

HACH TU5X00

FLOW SENSOR

(FE-)

HomR Line

HomR Line

HomR Line

HomR Line

HomR Line

HomR Line

HomR Line

HomR Text Box

HACH SC200

(AIT-)

HomR Text Box

HACH TU5X00

(AE-)

HomR Rectangle

HomR Line

HomR Line

HomR Text Box

(NOT USED)

HomR Line

HomR Line

HomR Text Box

(NOT USED)

HomR Text Box

(NOT USED)

HomR Text Box

(NOT USED)

HomR

(NOT USED)

Text Box

HACH TU5X00 FLOW SENSOR

HomR Line

HomR Text Box

HACH TU5X00

TURBIDIMETER

SENSOR

HomR Line

HomR Text Box

HACH FLOW SENSOR INTEGRAL SIGNAL CABLE

(PLUGS INTO HACH TU5X00 TURB. SENSOR)

HomR Line

HomR Text Box

SAMPLE WATER

INLET LINE

Line

Flow Switch (Insertion Type):

FLOW SWITCH:

TURCK P/N: FCS-N1/2 A4P-AP8X-H1141/L100

THERMAL FLOW SWITCH: 4-INCH (100mm) PROBE w/ ½” NPT PROCESS

CONNECTION, 316 SS WETTED PARTS, PNP SIGNAL OUTPUT, 24VDC

POWER, 4-PIN M12 (MALE) SIGNAL PORT

CABLE PLUG:

MENCOM P/N: MDC-4FP-FW11

PLUG CONNECTOR: 4-PIN M12 (FEMALE) FIELD-WIRING CONNECTOR,

POLYAMIDE BODY w/ NICKEL-PLATED BRASS NUT, COPPER CONTACTS w/ GOLD PLATING, ACCEPTS #18-#22 AWG CONDUCTORS / 5-10mm (0.20”-

0.40”) OD CABLE

TURCK

DC Self-Contained Flow Monitors

19 TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com

FCS-N1/2 A4P-AP8X-H1141

• DC PNP/NPN transistor output, short-circuit protected

• Flow monitor and signal processor in one compact housing

• Dynamic pressure resistance up to 870 psi

• Simple adjustment by means of potentiometer

This DC self-contained flow device has a flow monitor and signal processor incorporated into one compact housing. It is ideal for monitoring liquid flow speeds in the 2 to 295 ft/min range.

The flow monitor is designed for installation directly into the pipeline by means of a pipe-tee or welded pipe socket. It is suitable for use in a 1/2 inch pipe diameter or larger.

The flow monitor probe is made of 316TI stainless steel and the housing is made of plastic. The flow monitor is rated for dynamic pressures up to 870 psi. The outputs of the monitors feature a short-circuit protected PNP transistor.

Setpoint adjustments, in reference to flow speed, are achieved by means of an adjuster located under the protective screw cap on the front of the device.

The output is de-energized when the flow speed is below the setpoint; the output is energized when flow speed is above the setpoint. Each of the six LEDs display the difference the actual flow speed in comparison to the flow speed that the setpoint is adjusted to. The LEDs operate as follows:

Red LED: flow is below set point Yellow LED: flow is at or above set point Green LEDs: each LED indicates a percentage of flow above the setpoint

Notes: Available with relay output. Consult factory.

homr homr

TURCK FLOW SWITCH (100mm / 4-INCH PROBE LENGTH):

P/N FCS-N1/2 A4P-AP8X-H1141/L100

TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com 20

Flow Monitors DC Self Contained

FCS-N1/2 A4P-AP8X-H1141

Type FCS-N1/2 A4P-AP8X-H1141 ID Number M6871032

Operating Voltage 19.2 - 28.8 VDC (including ripple) Power / Current consumption ≤65 mA

Output PNP transistor, short-circuit and reverse polarity protected

Switching current ≤400 mA Voltage drop ≤1.5 V at 400 mA

Temperature Range (flow) -25° to +80°C (-13° to +176°F) cont.

up to +100°C (+212° F) for approx.10 min.

Operating Range (flow rate) Water 1-150 cm/s (2-295 ft/min) Oil 3-300 cm/s (6-590 ft/min)

Time Delay Before Availability 2-15 s (8 s typical) Switch ON time (above setpoint) 1-13 s (2 s typical) Switch OFF time (below setpoint) 1-15 s (2 s typical) Temperature gradient max. 250°C/min. (450°F/min.)

Pressure Rating 1450 psi (100 bar)

LED Indications Below setpoint, output de-energized red At setpoint, output energized yellow Above setpoint, output energized green (4), in addition to yellow LED)

Probe Material (DIN 2 462/17 440) 316TI stainless steel (1.4571) Enclosure (DIN 40 050) IP 67, NEMA 1,3,4,4x,12,13 Temperature rating -25° to +80°C (-13° to +176°F) Torque 100 Nm (73.7 ft-lb)

Housing Material PBT Enclosure (DIN 40 050) IP 67, NEMA 1, 3, 4, 4x, 12, 13 Operating temperature -25° to +80°C (-13° to +176°F)

Connection 3-wire eurofast quick disconnects RK 4T-* or WK 4T-* (Page 59)

* = Length in meters

FCS-N1/2 A4P-AP8X-H1141

homr Rectangle homr

NOTE: PIN 2 NOT USED

H-20 Mencom Corporation TEL: 770-534-4585 www.mencom.com

MDC Series (Micro-DC) Cordsets

Micro-DC Series (M12) Field Wireable Plugs PG 11 Threads 18-24 AWG

Face View of Male

# of Poles

Wire AWG Rating PG Size Cable Range Female Straight Male Straight

18-24

250V 4A

PG 11

PG 11*

PG 11*

PG 11*

PG 11*

5.0 - 10 mm

4.5 - 5.5 mm x 2

4.0 - 5.0 mm x 2

3.5 - 4.5 mm x 2

2.5 - 3.5 mm x 2

MDC-4FP-FW11

MDC-4FP-FW11-2x5 MDC-4FP-FW11-2x4.5 MDC-4FP-FW11-2x4 MDC-4FP-FW11-2x3

MDC-4MP-FW11

MDC-4MP-FW11-2x5 MDC-4MP-FW11-2x4.5 MDC-4MP-FW11-2x4 MDC-4MP-FW11-2x3

18-24

50V 4A

PG 11

PG 11*

PG 11*

PG 11*

PG 11*

5.0 - 10 mm

4.5 - 5.5 mm x 2

4.0 - 5.0 mm x 2

3.5 - 4.5 mm x 2

2.5 - 3.5 mm x 2

MDC-5FP-FW11

MDC-5FP-FW11-2x5 MDC-5FP-FW11-2x4.5 MDC-5FP-FW11-2x4 MDC-5FP-FW11-2x3

MDC-5MP-FW11

MDC-5MP-FW11-2x5 MDC-5MP-FW11-2x4.5 MDC-5MP-FW11-2x4 MDC-5MP-FW11-2x3

20-24

50V 4A

PG 11

PG 11*

PG 11*

PG 11*

PG 11*

5.0 - 10 mm

4.5 - 5.5 mm x 2

4.0 - 5.0 mm x 2

3.5 - 4.5 mm x 2

2.5 - 3.5 mm x 2

MDC-8FP-FW11

MDC-8FP-FW11-2x5 MDC-8FP-FW11-2x4.5 MDC-8FP-FW11-2x4 MDC-8FP-FW11-2x3

MDC-8MP-FW11

MDC-8MP-FW11-2x5 MDC-8MP-FW11-2x4.5 MDC-8MP-FW11-2x4 MDC-8MP-FW11-2x3

PG 11 Male StraightPG 11 Female Straight

These connectors are easily wired by inserting the individual wires into the screw terminal contacts. The connectors are water tight to IP 67 and are fully mate-able with other “Micro DC” style connectors. Other multi-hole grommets are available for the PG11 version, please consult the factory for part number and availability.

* These part numbers have a two hole grommet that allows two different cables to be installed into one fi eld wireable connector.

Specifi cations:

Body: Black Polyamide Insulator: Black Polyamide Contacts: Copper Alloy with Gold Plating Coupling Nut: Nickel Plated Brass Seal: NBR Temperature: -25ºC to +85ºC (-13ºF to +185ºF) Protection: IP67 - Single opening grommet IP65 - Two hole grommet Approvals: U.S.: UL Pending Canada: C-UL Pending

2.6

.8

2.7

.8

HomR Polygonal Line

HomR Text Box

4-PIN MICRO-DC (FEMALE) PLUG: MEMCON P/N MDC-4FP-FW11

HomR Rectangle

HomR Line

HomR Line

HomR Oval

HomR Line

HomR Line

FLOW INSTRUMENTATION CUT SHEET

½-Inch Flanged Mag. Flow Meter w/ 316L SS Electrodes/GND Rings:

Rosemount P/N: 8750W D M R 2 A 4 F T S A 005 C A1 DA1 M4 G1 AX Q4

Part Number Key:

8750W Model: Rosemount 8750W Utility Magnetic Flow Meter D Sensor Design Revision: Revision "D"

M Transmitter Class: Revision 4 Electronics R Transmitter Mount: Remote Field Mount (Order Cable Separately)

2 Transmitter Power: DC Power Supply (12 to 42VDC) A Transmitter Outputs: 4-20mA; Digital HART; Scalable Pulse

4 Conduit Entries: 1/2-14 NPT, Additional Entry F Sensor Style: Flanged T Lining Material: PTFE

S Electrode Material: 316L Stainless-Steel A Electrode Type: 2 Measurement Electrodes – Standard

005 Line Size: ½ Inch (DN15) C Flange Type and Material: Slip-On, Raised-Face, Carbon Steel

A1 Flange Rating: ASME B16.5, Class 150 DA1 Adv. Diagnostics Suite 1: Process Diagnostics HPN, Grounding/Wiring, Electrode Coating

M4 Transmitter Display: Local Operator Interface G1 Ground Ring: 316L Stainless-Steel (Qty 2) AX Discrete I/O: Two Discrete Channels (DI/DO 1, DO 2) Q4 Quality Cert: Calibration Certificate per ISO 10474 3.1B

Remote Flow Transmitter Signal Cable:

Rosemount P/N: 08732-0065-2001 (order by FT)

FLOW INSTRUMENTATION CUT SHEET

½-Inch Flanged Mag. Flow Meter w/ Hastalloy Electrodes/GND Rings:

Rosemount P/N: 8750W D M R 2 A 4 F T H A 005 C A1 DA1 M4 G2 AX Q4

Part Number Key:

8750W Model: Rosemount 8750W Utility Magnetic Flow Meter D Sensor Design Revision: Revision "D"

M Transmitter Class: Revision 4 Electronics R Transmitter Mount: Remote Field Mount (Order Cable Separately)

2 Transmitter Power: DC Power Supply (12 to 42VDC) A Transmitter Outputs: 4-20mA; Digital HART; Scalable Pulse

4 Conduit Entries: 1/2-14 NPT, Additional Entry F Sensor Style: Flanged T Lining Material: PTFE

H Electrode Material: Hastalloy C-276 A Electrode Type: 2 Measurement Electrodes – Standard

005 Line Size: ½ Inch (DN15) C Flange Type and Material: Slip-On, Raised-Face, Carbon Steel

A1 Flange Rating: ASME B16.5, Class 150 DA1 Adv. Diagnostics Suite 1: Process Diagnostics HPN, Grounding/Wiring, Electrode Coating

M4 Transmitter Display: Local Operator Interface G2 Ground Ring: Hastalloy C-276 (Qty 2) AX Discrete I/O: Two Discrete Channels (DI/DO 1, DO 2) Q4 Quality Cert: Calibration Certificate per ISO 10474 3.1B

Remote Flow Transmitter Signal Cable:

Rosemount P/N: 08732-0065-2001 (order by FT)

Product Data Sheet 00813-0300-4750, Rev CB

May 2019

Rosemount® 8750W Magnetic Flowmeter System for Utility, Water, and Wastewater Applications

■ Best in class value with performance, reliability, and diagnostics suited for monitoring applications

■ Reliable all welded coil housing and lightweight sensor design rated to IP68

■ Available in 4–20mA with HART®, FOUNDATION™ Fieldbus, Modbus® RS-485, Process Diagnostics, and SMART™ Meter Verification to improve reliability and performance

■ Available with drinking water certifications

HomR Text Box

ROSEMOUNT P/N: 8750W D M R 2 A 4 F T S A 005 C A1 DA1 M4 G1 AX Q4

8750W D M R 2 A 4 F T H A 005 C A1 DA1 M4 G2 AX Q4

HomR Text Box

316 SS ELECTRODES &

GROUNDING RINGS

HomR Text Box 1/2-Inch FLANGED MAG. FLOW METER WITH REMOTE TRANSMITTER (24VDC POWER):

HomR Line

HomR Line

HomR Line

HomR Line

HomR Line

HomR Line

HomR Line

HomR Line

HomR Text Box

HASTALLOY ELECTRODES &

GROUNDING RINGS

Product Selection Guide The Rosemount 8750W Magnetic Flowmetersensor is available in a flanged style and transmitter is available in remote and integral transmitter configurations to ensure compatibility with all utility, water, and wastewater applications.

Transmitter selection

Transmitter General characteristics

Field mount ■ Integral and remote configurations available

■ HART/Analog and Pulse outputs available

■ FOUNDATION™ Fieldbus and pulse output available

■ Modbus RS-485 and Pulse output available

■ Advanced Diagnostics available

■ LCD display (optional)

— With optional optical switch local operator interface(1)

■ Two discrete channels (optional)

Wall mount ■ Wall mount configuration

■ HART/Analog and Pulse outputs available

■ Modbus RS-485 and Pulse output available

■ FOUNDATION™ Fieldbus and pulse output available

■ Advanced Diagnostics available

■ Local LCD display (optional)

— With optional 15 button tactile key pad(1)

■ Two discrete channels (optional)

(1) HART or Modbus protocol only.

Contents Product Selection Guide

Magmeter Diagnostics

Magnetic Flowmeter Sizing

Ordering Information

Product Specifications

Product Certifications

Dimensional drawings

May 2019

2 www.rosemount.com

Sensor selection Table 1: Sensor Selection

Sensor General characteristics

Flanged ■ Flanged process connections Welded coil housing

■ ½-in. (15 mm) to 48-in. (1200 mm)

■ Standard, reference, and bullet-nose electrodes available

Selecting materials For guidance on selecting materials, refer to the Rosemount™ Magnetic Flowmeter Material Selection Guide (00816-0100-3033) , available at www.emerson.com/rosemount.

Magmeter Diagnostics

Rosemount diagnostics reduce cost & improve output by enabling new practices

Rosemount Magnetic Flowmeters provide device diagnostics that detect and warn of abnormal situations throughout the life of the meter - from installation to maintenance and meter verification. With Rosemount Magnetic Flowmeter diagnostics enabled, plant availability and throughput can be improved, and costs through simplified installation, maintenance and troubleshooting can be reduced.

Table 2: Magnetic flowmeter diagnostics

Diagnostic name Diagnostic category Product capability

Basic diagnostics

Tunable Empty Pipe Process Standard

Electronics Temperature Meter Health Standard

Coil Fault Meter Health Standard

Transmitter Fault Meter Health Standard

Reverse Flow Process Standard

Coil current Maintenance Standard

Electrode saturation Process/Maintenance Standard

Advanced diagnostics

High Process Noise Process Suite 1 (DA1)

Grounding and Wiring Fault Installation Suite 1 (DA1)

Coated Electrode Detection Process Suite 1 (DA1)

Commanded Smart Meter Verification Meter Health Suite 2 (DA2)

Continuous Smart Meter Verification Meter Health Suite 2 (DA2)

May 2019 www.rosemount.com 3 http://www.emerson.com/rosemount HomR Rectangle

Table 2: Magnetic flowmeter diagnostics (continued)

Diagnostic name Diagnostic category Product capability

4-20 mA Loop Verification(1) Installation Suite 2 (DA2)

(1) Available with HART output only.

Options for accessing diagnostics

Rosemount Magmeter Diagnostics can be accessed through the Local Operator Interface (LOI), ProLink® III v3.1, a HART Field Communicator(1), and AMS® Suite: Intelligent Device Manager(1). Contact your local Rosemount representative to activate diagnostics or for diagnostic availability on existing transmitters.

Access diagnostics through the LOI for quicker installation, maintenance, and meter verification

Rosemount Magnetic Flowmeter Diagnostics are available through the LOI to simplify maintenance.

Access diagnostics through ProLink III v. 3.0 (HART)/ProLink III v. 3.1 (HART, Modbus)

Simplify maintenance and troubleshooting practices by utilizing ProLink III v3.0/v3.1 to access diagnostics and troubleshooting information, log variable data, run SMART Meter Verification, and print verification reports.

Access diagnostics through AMS Intelligent Device Manager(1) for the ultimate value

The value of the diagnostics increases significantly when AMS Intelligent Device Manager is used. AMS Intelligent Device Manager provides a simplified screen flow and procedures for how to respond to the diagnostic messages.

Magnetic Flowmeter Sizing Selecting the appropriate sensor size is an important step when considering a magnetic flowmeter. The physical properties of the process fluid, as well as the fluid velocity should be considered. It may be necessary to select a flow sensor that is larger or smaller than the adjacent piping to ensure the fluid velocity is in the recommended flow range for the application.

■ Operation outside these guidelines may also give acceptable performance.

Table 3: Sizing guidelines

Application Velocity range (ft/s) Velocity range (m/s)

Normal Service 0–39 0–12

Preferred Service 2–20 0.6–6.1

Note Operation outside these guidelines may also give acceptable performance.

To convert flow rate to velocity, use the appropriate factor listed in Table 4 and the following equation:

Velocity = Flow Rate

Factor

(1) Available with HART output only.

May 2019

4 www.rosemount.com

Example: English units Example: SI units

Magmeter Size: 4 in. (factor from Table 4 = 39.679) Normal Flow Rate: 300 GPM

Velocity = 300 (gpm)

39.679

Velocity = 7.56 ft/s

Magmeter Size: 100 mm (factor from Table 4 = 492.78)Normal Flow Rate: 800 L/min

Velocity = 800 (L/min)

492.78

Velocity = 1.62 m/s

Table 4: Line size vs. conversion factor

Nominal line size—Inches (mm) Gallons per minute factor Liters per minute factor

½ (15) 0.947 11.762

1 (25) 2.694 33.455

1½ (40) 6.345 78.806

2 (50) 10.459 129.89

2 ½ (65) 14.923 185.33

3 (80) 23.042 286.17

4 (100) 39.679 492.78

5 (125) 62.356 774.42

6 (150) 90.048 1,118.3

8 (200) 155.93 1,936.5

10 (250) 245.78 3,052.4

12 (300) 352.51 4,378.0

14 (350) 421.70 5,237.3

16 (400) 550.80 6,840.6

18 (450) 697.19 8,658.6

20 (500) 866.51 10,761

24 (600) 1,253.2 15,564

30 (750) 2006.0 24,913

36 (900) 2,935.0 36,451

40 (1000) 3,652.1 45,357

42 (1050) 4,115.1 51,107

48 (1200) 5,407.6 67,159

May 2019 www.rosemount.com 5

HomR Rectangle

HomR Text Box

ROSEMOUNT P/N: 8750W D M R 2 A 4 F T S A 005 C A1 DA1 M4 G1 AX Q4

8750W D M R 2 A 4 F T H A 005 C A1 DA1 M4 G2 AX Q4

HomR Line

Table 5: Line size vs. velocity/rate

Nominal line size in inches (mm)

Minimum/maximum flow rate

Gallons per minute Liters per minute at 0.04 ft/s

(low-flow cutoff) at 1 ft/s

(min range setting) at 3 ft/s at 39.37 ft/s

(max range setting) at 0.012 m/s

(low-flow cutoff) at 0.3 m/s

(min range setting) at 1 m/s at 12 m/s

(max range setting)

½ (15) 0.038 0.947 2.841 37.287 0.141 3.529 11.76 141.15

1 (25) 0.108 2.694 8.081 106.05 0.401 10.04 33.45 401.46

1½ (40) 0.254 6.345 19.04 249.82 0.946 23.64 78.81 945.67

2 (50) 0.418 10.459 31.38 411.77 1.559 38.97 129.89 1,558.7

2½ (65) 0.597 14.923 44.77 587.51 2.224 55.60 185.33 2,224.0

3 (80) 0.922 23.042 69.13 907.17 3.434 85.85 286.17 3,434.0

4 (100) 1.587 39.679 119.04 1,562.2 5.913 147.84 492.78 5,913.4

5 (125) 2.494 62.356 187.07 2,454.9 9.293 232.33 774.42 9,293.0

6 (150) 3.602 90.048 270.14 3,545.2 13.42 335.50 1,118.3 13,420

8 (200) 6.237 155.93 467.79 6,138.9 23.24 580.96 1,936.5 23,238

10 (250) 9.831 245.78 737.34 9,676.3 36.63 915.73 3,052.4 36,629

12 (300) 14.10 352.51 1,057.5 13,878 52.54 1,313.4 4,378.0 52,535

14 (350) 16.87 421.71 1,265.1 16,603 62.85 1,571.2 5,237.3 62,848

16 (400) 22.03 550.80 1,652.4 21,685 82.09 2,052.2 6,840.6 82,087

18 (450) 27.89 697.19 2,091.6 27,448 103.90 2,597.6 8,658.6 103,903

20 (500) 34.66 866.51 2,599.5 34,114 129.14 3,228.4 10,761 129,137

24 (600) 50.13 1,253.2 3,759.6 49,339 186.77 4,669.2 15,564 186,769

30 (750) 80.24 2,006.0 6,018.0 78,976 298.96 7,474.0 24,913 298,959

36 (900) 117.40 2,935.0 8,805.1 115,553 437.42 10,935 36,451 437,416

40 (1000) 146.09 3,652.1 10,956 143,785 544.29 13,607 45,357 544,286

42 (1050) 164.60 4,115.1 12,345 162,011 613.28 15,332 51,107 613,278

48 (1200) 216.30 5,407.6 16,223 212.898 805.91 20,148 67,159 805,908

Upstream and downstream piping To ensure specified accuracy over widely varying process conditions, install the sensor with a minimum of five straight pipe diameters upstream and two pipe diameters downstream from the electrode plane.

May 2019

6 www.rosemount.com

HomR Rectangle

HomR Text Box

ROSEMOUNT P/N: 8750W D M R 2 A 4 F T S A 005 C A1 DA1 M4 G1 AX Q4

8750W D M R 2 A 4 F T H A 005 C A1 DA1 M4 G2 AX Q4

HomR Line

Figure 1: Upstream and downstream straight pipe diameters

A. Five pipe diameters (upstream) B. Two pipe diameters (downstream) C. Flow direction

Installations with reduced upstream and downstream straight runs are possible. In reduced straight run installations, the meter may not meet accuracy specifications. Reported flow rates will still be highly repeatable.

Sensor grounding

A reliable ground path is required between the sensor and the process fluid. Optional grounding rings or process reference electrodes are available with the sensor to ensure proper grounding. See Table 5 and Table 6.

Ordering Information

Rosemount 8750W Magnetic Flowmeter Platform

The Rosemount 8750W Magnetic Flowmeter is available in a flanged sensor design. The sensors are fabricated from stainless and carbon steel and welded to provide a sealed coil housing that protects against moisture or other contaminants. Sizes range from 1/2-in. (15 mm) to 48-in. (1200 mm). The field mount transmitter has a die cast aluminum housing for excellent reliability. The wall mount transmitter features an easy to use operator interface. Both transmitter styles are available with advanced diagnostics to provide the best insight into the process and the meter's health.

Note The starred (★) offerings represent the most common options, and should be selected for best delivery.

Model code structure

Example model code with one selection out of each category:

8750W D M T 1 A 1 F P S A 010 C A1 Z5 DA2 AX M4 BD G5 B6 R15 V1 Q4 HR7 WG YF

Table 6: Requirements - select one from each available choice

Example code Category

8750W Base model—Magnetic Flowmeter System (utility, water, and wastewater)

D Sensor design revision—Revision "D"

M Transmitter class (Table 8)

T Transmitter mount (Table 9)

1 Transmitter power (Table 10)

May 2019 www.rosemount.com 7

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Text Box

HomR Line

HomR Text Box

ROSEMOUNT P/N: 8750W D M R 2 A 4 F T S A 005 C A1 DA1 M4 G1 AX Q4

8750W D M R 2 A 4 F T H A 005 C A1 DA1 M4 G2 AX Q4

HomR Line

HomR Line

HomR Text Box R

Table 6: Requirements - select one from each available choice (continued)

Example code Category

A Transmitter outputs (Table 11)

1 Conduit entries (Table 12)

F Sensor style (Table 13)

P Lining material (Table 14)

S Electrode material (Table 15)

A Electrode type (Table 16)

010 Line size (Table 17)

C Flange type and material (Table 18)

A1 Flange rating (Table 19)

Table 7: Options - select only as needed

Example code Category

Z5 Hazardous area certifications (Table 20)

DA2 Advanced diagnostics (Table 21)

AX Discrete input/output (Table 22)

M4 Display (Table 23)

BD Certifications (Table 24)

G5 Grounding rings (Table 25)

B6 Miscellaneous (Table 26)

R15 Submergence protection (Table 27)

V1 Special paint (Table 28)

Q4 Quality certificates (Table 29)

HR7 Revision configuration (Table 30)

WG Witness inspection (Table 31)

Yx Quick Start Guide language (Table 32)

Requirements

Table 8: Rosemount 8750W transmitter class

Code Description

M Revision 4 electronics ★

0 Spare sensor, no transmitter

Table 9: Rosemount 8750W transmitter mount

Code Description

T Integral field mount ★

R Remote field mount ★

May 2019

8 www.rosemount.com

HomR Text Box

HomR Text Box T

HomR Text Box

HomR Text Box

DA1

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Text Box

ROSEMOUNT P/N: 8750W D M R 2 A 4 F T S A 005 C A1 DA1 M4 G1 AX Q4

8750W D M R 2 A 4 F T H A 005 C A1 DA1 M4 G2 AX Q4

HomR Text Box S, H

HomR Rectangle

HomR Line

HomR Line

HomR Line

HomR Line

HomR Text Box

8750W D M R 2 A 4 F T S A 005 C A1 DA1 M4 G1 AX Q4

8750W D M R 2 A 4 F T H A 005 C A1 DA1 M4 G2 AX Q4

HomR Rectangle

HomR Rectangle

HomR Rectangle

Table 9: Rosemount 8750W transmitter mount (continued)

Code Description

W Remote wall mount ★

Table 10: Rosemount 8750W transmitter power

Code Description

1 AC Power Supply (90 -250VAC, 50/60Hz) ★

2 DC Power Supply (12 - 42VDC) ★

0 Spare sensor, no transmitter

Table 11: Rosemount 8750W transmitter outputs

Code Description

A 4-20mA output with digital HART protocol & scalable pulse output ★

F FOUNDATION™ Fieldbus & scalable pulse output ★

M Modbus RS-485 electronics, scalable pulse ★

0 Spare sensor, no transmitter

Table 12: Rosemount 8750W conduit entries

Code Description Integral mount quantity Remote mount quantity

1 ½–14 NPT 2 4 ★

2 M20–1.5 adapters 2 4 ★

4(1) ½–14 NPT, additional entry 3 5

5(1) M20–1.5, additional entry 3 5

0 Spare sensor, integral mount only, no transmitter

N/A N/A

(1) Not available with the wall mount transmitter.

Table 13: Rosemount 8750W sensor style

Code Description

F Flanged ★

0 Spare transmitter, no sensor

Table 14: Rosemount 8750W lining material

Code Description

T(1) PTFE ★

P(2) Polyurethane ★

N(3) Neoprene ★

0 Spare transmitter, no sensor

(1) Available in ½ - to 36-in. (15 mm to 900 mm) line sizes.

(2) Available in line sizes 1- to 36-in., 42-in., and 48-in. (25 mm to 900 mm, 1050 mm, and 1200 mm) line sizes.

(3) Available in line sizes 1- to 48-in. (25 mm to 1200 mm) line sizes.

May 2019 www.rosemount.com 9

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Text Box

8750W D M R 2 A 4 F T S A 005 C A1 DA1 M4 G1 AX Q4

8750W D M R 2 A 4 F T H A 005 C A1 DA1 M4 G2 AX Q4

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Rectangle

Table 15: Rosemount 8750W electrode material

S 316L stainless steel ★

H Nickel alloy 276 (UNS N 10276) ★

0 Spare transmitter, no sensor

Table 16: Rosemount 8750W electrode type

Code Description

A 2 Measurement electrodes – standard ★

B(1) 2 Measurement electrodes – bulletnose ★

E 2 Measurement electrodes plus 1 reference electrode – standard ★

F(1) 2 Measurment electrodes plus 1 reference electrode – bulletnose ★

0 Spare transmitter, no sensor

(1) Not available in ½-in. (15mm).

Table 17: Rosemount 8750W line size

Code Line size Liner availability

In this table, the starred (★) offerings represent available liner based on line size. Consult factory for additional Flange Type/Rating sensor availability

PTFE code T Poly code P Neoprene code N

005 ½-in. (15 mm) ★

010 1-in. (25 mm) ★ ★ ★

015 1½-in. (40 mm) ★ ★ ★

020 2-in. (50 mm) ★ ★ ★

025 2½-in. (65 mm) ★ ★

030 3-in. (80 mm) ★ ★ ★

040 4-in. (100 mm) ★ ★ ★

050 5-in. (125 mm) ★ ★

060 6-in. (150 mm) ★ ★ ★

080 8-in. (200 mm) ★ ★ ★

100 10-in. (250 mm) ★ ★ ★

120 12-in. (300 mm) ★ ★ ★

140 14-in. (350 mm) ★ ★ ★

160 16-in. (400 mm) ★ ★ ★

180 18-in. (450 mm) ★ ★ ★

200 20-in. (500 mm) ★ ★ ★

240 24-in. (600 mm) ★ ★ ★

300 30-in. (750 mm) ★ ★ ★

May 2019

10 www.rosemount.com

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Text Box

8750W D M R 2 A 4 F T S A 005 C A1 DA1 M4 G1 AX Q4

8750W D M R 2 A 4 F T H A 005 C A1 DA1 M4 G2 AX Q4

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Rectangle

Table 17: Rosemount 8750W line size (continued)

Code Line size Liner availability

In this table, the starred (★) offerings represent available liner based on line size. Consult factory for additional Flange Type/Rating sensor availability

PTFE code T Poly code P Neoprene code N

360 36-in. (900 mm) ★ ★ ★

400 40-in. (1000 mm) ★

420 42-in. (1050 mm) ★ ★

480 48-in. (1200 mm) ★ ★

000 Spare transmitter, no sensor

Table 18: Rosemount 8750W flange type and material

Code…