PALL ADVANCED SEPARATIONS SYSTEMS
120V AC & 24V DC POWER DISTRIBUTION
TABLE OF CONTENTS
SHEET 2:
SHEET 3:
INDEXSHEET 1:
460V AC POWER DISTRIBUTION
HANFORD WA
PROJECT : 01.000287
NETWORK DIAGRAMSHEET 4:
MAIN PANEL FIELD WIRING (1 OF 3)SHEET 5:
MAIN PANEL FIELD WIRING (2 OF 3)SHEET 6:
CAUSTIC TANK ROOM & ACID TANK ROOM
SHEET 7:
SHEET 8:
REMOTE I/O PANEL FIELD WIRING
FEED STRAINER FIELD WIRING SHEET 9:
MAIN PANEL FIELD WIRING (3 OF 3)
HomR Text Box
PALL RESPONSES TO CUSTOMER REVIEW COMMENTS IN RED TEXT
460 VAC, 60HZ
3Ø POWER SUPPLY
(BY OTHERS)
AIR COMPRESSOR
M-6001A
(CA-CMP-6001)
20 HP
RF PUMP
P-4302A
(BCKW-PMP-4302)
20 HP
VFD-4302A
(BCKW-VFD-4302)
LOCAL
PANEL
FEED STRAINER
S-3201A
(PTW-STR-3201)
0.5 HP
M O
T O
R S
T A
R T E
R
O.L.
CON1
R E
V E
R S
IN
G
80 kW
CIP CAUSTIC
TANK HEATER
H-5004
(CIP-HTR-5004)
CON1
CIP CIRC PUMP
P-5204A
(CIPS-PMP-5204A)
M O
T O
R S
T A
R T E
R
O.L.
CON1
10 HP
CON2
SEE SHEET 1 FOR REVISIONS
( 33 FLA)
H E
A T E
R P
A N
E L
C A
U S
T
IC
T A
N K
CUSTOMER MOTOR CONTROL CENTER EDN-MCC-6520
(BY OTHERS)
(BY OTHERS) (BY OTHERS)(BY OTHERS)(BY OTHERS)(BY OTHERS) (BY OTHERS)
M S
-3
M S
-5
A
460 VAC, 60HZ
3Ø POWER SUPPLY
(BY OTHERS)
AIR
COMPRESSOR
M-6001B
(CA-CMP-6002)
20 HP
RF PUMP
P-4302B
(BCKW-PMP-4303)
20 HP
LOCAL
PANEL
FEED STRAINER
S-3201B
(PTW-STR-3202)
0.5 HP
M O
T O
R S
T A
R T E
R
O.L.
CON1
R E
V E
R S
IN
G
80 kW
CIP ACID
TANK HEATER
H-5104
(CIP-HTR-5104)
CON1
CIP CIRC PUMP
P-5204B
(CIPS-PMP-5204B)
M O
T O
R S
T A
R T E
R
O.L.
CON1
10 HP
CON2
( 33 FLA)
H E
A T E
R P
A N
E L
A C
ID
T
A N
K
(BY OTHERS) (BY OTHERS)(BY OTHERS)(BY OTHERS)(BY OTHERS) (BY OTHERS)
M S
-3 B
M S
-5 B
CUSTOMER MOTOR CONTROL CENTER EDN-MCC-6530
(BY OTHERS)
RF PUMP
P-4302C
(BCKW-PMP-4304)
20 HP
(BY OTHERS)
VFD-4302B
(BCKW-VFD-4303)
VFD-4302C
(BCKW-VFD-4304)
NOTES:
1. UNLESS OTHERWISE INDICATED, ALL COMPONENTS TO BE SUPPLIED
BY PALL FOR FIELD INSTALLATION BY OTHERS.
2. RF PUMP VFD'S TO BE CONTROLLED BY ETHERNET; ALL OTHER MOTOR
STARTERS AND POWER CONTACTORS TO BE HARD-WIRED SIGNALS TO PALL
MAIN CONTROL PANEL
3. EACH CIP TANK HEATER TO BE POWERED BY TWO POWER CONTACTORS IN
SERIES. "CON1" IS USED FOR CIP TANK TEMPERATURE CONTROL & "CON2" IS A
SAFETY FOR HEATER SHUTDOWN ON HEATER ELEMENT OVER TEMPERATURE.
DEBEST
Text Box
BLEND
DEBEST
PolyLine
DEBEST
Line
IRINCON
Detailed Check 63 kW in design drawing H-2-838441-1
IRINCON
Detailed Check 63 kW in design drawing H-2-838441-2
IRINCON
Detailed Check
7.5 HP in design drawing H-2-838441-1
IRINCON
Detailed Check
7.5 HP in design drawing H-2-838441-1
HomR Text Box
PALL RESPONSE:
CHANGE FROM 7.5 HP TO 10 HP DUE TO CIP PUMP LOCATION BELOW VALVE RACKS & ADDITIONAL MF MODULES ON EACH RACK.
HomR Text Box
PALL RESPONSE:
CHANGE FROM 7.5 HP TO 10 HP DUE TO CIP PUMP LOCATION BELOW VALVE RACKS & ADDITIONAL MF MODULES ON EACH RACK.
HomR Text Box
PALL RESPONSE:
ADDITIONAL MF MODULES ON EACH RACK DICTATED INCREASE OF CIP HEATER SIZE FROM 63KW TO 80KW TO MEET MINIMUM CYCLE TIME REQUIREMENTS.
HomR Text Box
PALL RESPONSE:
ADDITIONAL MF MODULES ON EACH RACK DICTATED INCREASE OF CIP HEATER SIZE FROM 63KW TO 80KW TO MEET MINIMUM CYCLE TIME REQUIREMENTS.
REMOTE I/O 24VDC POWER PANEL
PALL DWG NYCS000015169
VALVE RACK
I/O PANEL
PALL DWG
NYCS000015170
UPS BACKED
120VAC, 60HZ
1 PHASE SUPPLY
(BY OTHERS)
SEE SHEET 1 FOR REVISIONS
(BY OTHERS)(BY OTHERS)
(BY OTHERS)
VALVE RACK
I/O PANEL
PALL DWG
NYCS000015170
VALVE RACK
I/O PANEL
PALL DWG
NYCS000015170
VALVE RACK #1 VALVE RACK #2 VALVE RACK #3
FEED
STRAINER
I/O PANEL
PALL DWG
NYCS000015171
CIP CAUSTIC
TANK ROOM
PLC
I/O PANEL
PALL DWG
NYCS000015163
CIP ACID
TANK ROOM
I/O PANEL
PALL DWG
NYCS000015164
GFCI
120VAC
RECEPTACLE
UPS BACKED 120VAC POWER DISTRIBUTION (BY OTHERS)
(BY OTHERS)
20 HP
(BY OTHERS)
NON-UPS BACKED
120VAC, 60HZ
1 PHASE SUPPLY
(BY OTHERS)
120VAC UTILITY POWER DISTRIBUTION (BY OTHERS)
RF PUMP P-4302A
(BCKW-PMP-4302)
20 HP
(BY OTHERS)
AIR COMPRESSOR
M-6001A
(CA-CMP-6001)
20 HP
(BY OTHERS)
20 HP
(BY OTHERS)
10 HP
(BY OTHERS)
10 HP
(BY OTHERS)
AIR COMPRESSOR
M-6001B
(CA-CMP-6002)
CIP CIRC PUMP
P-5204A
(CIPS-PMP-5204A)
CIP CIRC PUMP
PMP-5204B
(CIPS-PMP-5204AB)
W
W
W
W
W
W
MOTOR
ANTI-CONDENSATION
SPACE HEATER
POWER
DISTRIBUTION
(BY OTHERS) (BY OTHERS) (BY OTHERS)
120VAC
GFCI
RECEPTACLE
(BY OTHERS)
120VAC
GFCI
RECEPTACLE
(BY OTHERS)
120VAC
GFCI
RECEPTACLE
(BY OTHERS)
VALVE RACK
I/O PANEL
PALL DWG
NYCS000015170
VALVE RACK #4
(BY OTHERS)
120VAC
GFCI
RECEPTACLE
(BY OTHERS)
(BY OTHERS)
RAW WATER
ALKALINITY
ANALYZER
120VAC POWER
(SEE ALSO SHT 5)
ACID CIP TANK T-5101
RECIRC PUMP P-5101
(CIPC-PMP-5101)
0.75 HP
M O
T O
R S
T A
R T E
R
O.L.
CON1
(BY OTHERS)
M S
-5
CAUSTIC CIP TANK T-5001
RECIRC PUMP P-5001
(CIPC-PMP-5001)
0.75 HP
M O
T O
R S
T A
R T E
R
O.L.
CON1
(BY OTHERS)
M S
-5
(BY OTHERS) (BY OTHERS)
RF PUMP P-4302B
(BCKW-PMP-4303)
20 HP
(BY OTHERS)
W
RF PUMP P-4302C
(BCKW-PMP-4304)
(BY OTHERS) (BY OTHERS)
ACID CIP TANK
LEAK DETECTOR
120VAC POWER
(SEE ALSO SHT 8)
CAUSTIC CIP TANK
LEAK DETECTOR
120VAC POWER
(SEE ALSO SHT 8)
DEBEST
Text Box
BLEND
DEBEST
PolyLine
DEBEST
Text Box
BLEND
IRINCON
Text Box 120 VAC power circuits to these space heaters are NOT included in Design Drawings. I do not think these heaters are needed as all these pumps are inside the building that is a conditioned space. Karl Sutton (Building HVAC systems to confirm this understanding).
HomR Text Box
SPEC 01 61 02, SECTION 2.2,E,1,2,a REQUIRES SPACE HEATERS ON MOTORS 10 HP OR LARGER. PER THIS REQUEST & SUBSEQUENT DISCUSSION, MOTOR SPACE HEATERS WILL BE REMOVED ON TNE NEXT DRAWING REVISION.
MAIN CONTROL PANEL
NUMATICS G3 I/O
(I/P ADDRESS: )
2A.
2B. ETHERNET CABLE SHALL BE CATEGORY 6 UNSHIELDED
TWISTED PAIR DATA CABLE (BELDEN CAT# 1583A OR EQUAL)
WITH RJ45 PLUGS, AND SHALL BE PROTECTED BY
INSTALLATION IN PVC CONDUIT OR A SUITABLE CABLE TRAY.
SEE SHEET 1 FOR REVISIONS
-E N
T R
MOD 0
E T H
E R
N E
T
C O
M M
M
O D
U L E
MOD 2
I/ O
M O
D U
L E
MOD 3
I/ O
M O
D U
L E
MOD 4
I/ O
M O
D U
L E
MOD 5
I/ O
M O
D U
L E
MOD 6
I/ O
M O
D U
L E
MOD 7
I/ O
M O
D U
L E
MOD 8
I/ O
M O
D U
L E
MOD 9
I/ O
M O
D U
L E
MOD 1
I/ O
M O
D U
L E
MOD 0
-L
C O
N T
R O
L O
G
IX
C P
U
MOD 2
-E N
T R
E T H
E R
N E
T
C O
M M
M
O D
U L E
MOD 1
-R M
R E
D U
N D
A N
C Y
M O
D U
L E
MOD 3
-E N
T R
E T H
E R
N E
T
C O
M M
M
O D
U L E
MOD 0
-L
C O
N T
R O
L O
G
IX
C P
U
MOD 2
-E N
T R
E T H
E R
N E
T
C O
M M
M
O D
U L E
MOD 1
-R M
R E
D U
N D
A N
C Y
M O
D U
L E
MOD 4
-E N
T R
E T H
E R
N E
T
C O
M M
M
O D
U L E
NUMATICS 501 SOLENOID MANIFOLD
1 2 3 4
MODULE
STATUS
ACTIVITY
LINK
NETWORK
STATUS
COMM
ETHERNET / IP
POWER
NUMATICS
NUMATICS G3 I/O
(I/P ADDRESS: )
NUMATICS 501 SOLENOID MANIFOLD
1 2 3 4
MODULE
STATUS
ACTIVITY
LINK
NETWORK
STATUS
COMM
ETHERNET / IP
POWER
NUMATICS
NUMATICS G3 I/O
(I/P ADDRESS: )
NUMATICS 501 SOLENOID MANIFOLD
1 2 3 4
MODULE
STATUS
ACTIVITY
LINK
NETWORK
STATUS
COMM
ETHERNET / IP
POWER
NUMATICS
NUMATICS G3 I/O
(I/P ADDRESS: )
NUMATICS 501 SOLENOID MANIFOLD
1 2 3 4
MODULE
STATUS
ACTIVITY
LINK
NETWORK
STATUS
COMM
ETHERNET / IP
POWER
NUMATICS
NUMATICS G3 I/O
(I/P ADDRESS: )
NUMATICS 501 SOLENOID MANIFOLD
1 2 3 4
MODULE
STATUS
ACTIVITY
LINK
NETWORK
STATUS
COMM
ETHERNET / IP
POWER
NUMATICS
NUMATICS G3 I/O
(I/P ADDRESS: )
NUMATICS 501 SOLENOID MANIFOLD
1 2 3 4
MODULE
STATUS
ACTIVITY
LINK
NETWORK
STATUS
COMM
ETHERNET / IP
POWER
NUMATICS
CIP CAUSTIC TANK ROOM
I/O PANEL
PALL DWG: NYCS000015165
PALL DWG.
NYCS000015163
NUMATICS G3 I/O
CIP ACID TANK ROOM PUMP I/O PANEL
(I/P ADDRESS: )
NUMATICS 501 SOLENOID MANIFOLD
1 2 3 4
MODULE
STATUS
ACTIVITY
LINK
NETWORK
STATUS
COMM
ETHERNET / IP
POWER
NUMATICS
VFD
4302A
VFD
4302B
VFD
4302C
MCC EDN-MC-6520 MCC EDN-MC-6530
(IP ADDRESS:_____________________)
E T H E R N E T
DEKSTOP PC
IP ADDRESS: )
16 DI
PNP
I0/I1
I2/I3
I4/I5
I6/I7
I8/I9
I10/I11
I12/I13
I14/I15
NUMATICS
AI
0mA
I0
I1
ATICS
2 AI
4-2
O0/I0
O1/I1
NUM
16 DI
PNP
I0/I1
I2/I3
I4/I5
I6/I7
I8/I9
I10/I11
I12/I13
I14/I15
NUMATICS
AI
0mA
I0
I1
ATICS
2 AI
4-2
O0/I0
O1/I1
NUM
16 DI
PNP
I0/I1
I2/I3
I4/I5
I6/I7
I8/I9
I10/I11
I12/I13
I14/I15
NUMATICS
AI
0mA
I0
I1
ATICS
2 AI
4-2
O0/I0
O1/I1
NUM
16 DI
PNP
I0/I1
I2/I3
I4/I5
I6/I7
I8/I9
I10/I11
I12/I13
I14/I15
NUMATICS
AI
0mA
I0
I1
ATICS
2 AI
4-2
O0/I0
O1/I1
NUM
16 DI
PNP
I0/I1
I2/I3
I4/I5
I6/I7
I8/I9
I10/I11
I12/I13
I14/I15
NUMATICS
AI
0mA
I0
I1
ATICS
2 AI
4-2
O0/I0
O1/I1
NUM
16 DI
PNP
I0/I1
I2/I3
I4/I5
I6/I7
I8/I9
I10/I11
I12/I13
I14/I15
NUMATICS
AI
0mA
I0
I1
ATICS
2 AI
4-2
O0/I0
O1/I1
NUM
16 DI
PNP
I0/I1
I2/I3
I4/I5
I6/I7
I8/I9
I10/I11
I12/I13
I14/I15
NUMATICS
AI
0mA
I0
I1
ATICS
2 AI
4-2
O0/I0
O1/I1
NUM
PALL DWG: NYCS000015164
FEED STRAINER PUMP I/O PANEL
PALL DWG: NYCS000015171
MF VALVE RACK #4 I/O PANEL
PALL DWG: NYCS000015170
MF VALVE RACK #3 I/O PANEL
PALL DWG: NYCS000015170
MF VALVE RACK #1 I/O PANEL
PALL DWG: NYCS000015170
MF VALVE RACK #2 I/O PANEL
PALL DWG: NYCS000015170
DEBEST
Highlight
DEBEST
Text Box
CAT5E (TYP) --
HDR HAD PREVIOUSLY SHOWN CAT6 CABLES, BUT MSA REQUESTED THAT CAT5E CABLES BE USED INSTEAD.
DEBEST
PolyLine
DEBEST
PolyLine
DEBEST
Text Box TO ETHERNET/IP TO PROFINET GATEWAY IN CONTROL COMMUNICATIONS PANEL WT-CPNL-1500 (BY OTHERS)
DEBEST
Text Box
CAT5E
DEBEST
PolyLine
DEBEST
Highlight Auch
DEBEST
Text Box
CAT5E
DEBEST
Highlight
DEBEST
Text Box
CAT5E
DEBEST
Highlight
DEBEST
Text Box
CAT5E
DEBEST
Highlight
DEBEST
Text Box
CAT5E
DEBEST
Highlight
DEBEST
Text Box
CAT5E
DEBEST
Highlight
DEBEST
Text Box
CAT5E
DEBEST
Highlight
DEBEST
Text Box
CAT5E
DEBEST
Highlight
DEBEST
Text Box
CAT5E
DEBEST
Highlight
HomR Text Box
PALL RESPONSE:
ETHERNET CABLES WILL BE CHANGED FROM CAT 6 TO CAT 5E ON NEXT DRAWING REVISION.
HomR Text Box
THIS ETHERNET I/P LINK WILL BE INCLUDED IN THE NEXT INTERCONNECT DWG REVISION.
SEE SHEET 1 FOR REVISIONS
SEE DWG: NYCS000015165
(BY PALL)
0.5 HP 0.5 HP
120VAC SIGNAL RELAY PANEL
SEE DWG: NYCS000015166
(BY PALL)
J-BOX (SEE SHT 9) J-BOX (SEE SHT 8)
DEBEST
Cloud
DEBEST
Text Box
DEBEST
PolyLine
DEBEST
Cloud
DEBEST
Text Box THESE TWO SIGNALS WILL BE SENT TO THE MAIN CONTROL PANEL VIA DIGITAL COMMUNICATIONS VIA ETHERNET/IP TO PROFINET GATEWAY IN CONTROL COMMUNICATIONS PANEL WT-CPNL-1500 (BY OTHERS)
DEBEST
PolyLine
DEBEST
Highlight
DEBEST
Text Box
ANALOG I/O
(1)-#16 TSP PER DEVICE (BY OTHERS)
DEBEST
PolyLine
DEBEST
Highlight in
DEBEST
PolyLine
DEBEST
Text Box
ANALOG I/O
(4)-#16 TSP PER DEVICE (BY OTHERS)
DEBEST
PolyLine
HomR Text Box
PALL RESPONSE:
LIT-4020 & LSH-4019 WILL BE REMOVED ON NEXT DRAWING REVISION.
HomR Text Box
CHANGES/CORRECTIONS SHOWN ABOVE WILL BE INCORPORATED INTO THE NEXT DRAWING REVISION.
SEE DWG: NYCS000015165
(BY PALL)
120VAC SIGNAL RELAY PANEL
SEE DWG: NYCS000015166
(BY PALL)
10 HP 10 HP
0.75
HP
0.75
HP
NOTES:
CON1 = CIP TANK HEATER TEMPERATURE CONTROL CONTACTOR
CON2 = CIP TANK SAFETY CONTROL CONTACTOR
SEE DWG: NYCS000015165
(BY PALL)
DEBEST
Rectangle
DEBEST
Text Box
ACH ROOM ALARM
BEACON
(BY OTHERS)
DEBEST
Text Box
WT-YA-0404A
DEBEST
Rectangle
DEBEST
Text Box
ACH ROOM ALARM
BEACON
(BY OTHERS)
DEBEST
Text Box
WT-YA-0404A
DEBEST
PolyLine
DEBEST
PolyLine
DEBEST
Text Box ADD INTERCONNECTIONS FOR THE ACH METERING PUMP SKIDS AND THE ACH TANK LEVEL SWITCHES
DEBEST
Cloud
DEBEST
PolyLine
DEBEST
PolyLine
DEBEST
Rectangle
DEBEST
Text Box
BACKWASH WASTE TANK LEVEL SWITCH
(BY OTHERS)
DEBEST
Text Box
BWW-LSHH-8301A
DEBEST
Rectangle
DEBEST
Text Box
BACKWASH WASTE TANK LEVEL SWITCH
(BY OTHERS)
DEBEST
Text Box
BWW-LSHH-8301B
DEBEST
PolyLine
DEBEST
Rectangle
DEBEST
Text Box
ACH ROOM ESEW FLOW SWITCH
(BY OTHERS)
DEBEST
Text Box
SHR-FSH-6625
DEBEST
PolyLine
DEBEST
Rectangle
DEBEST
Text Box
ACH ROOM ESEW FLOW SWITCH
(BY OTHERS)
DEBEST
Text Box
SHR-FSH-6626
DEBEST
Rectangle
DEBEST
Text Box
SAMPLE ROOM ESEW FLOW SWITCH
(BY OTHERS)
DEBEST
Text Box
SHR-FSH-6621
DEBEST
PolyLine
DEBEST
Rectangle
DEBEST
Text Box
HVAC CONTROL PANEL
(BY OTHERS)
DEBEST
Text Box
CPNL-6601
DEBEST
PolyLine
DEBEST
Text Box
24VDC DISCRETE I/O
(4)-#16 AWG PER DEVICE (BY OTHERS)
DEBEST
PolyLine
DEBEST
Rectangle
DEBEST
Text Box
ALARM AUTO DIALER
(BY OTHERS)
DEBEST
Text Box
WT-ADD-0400
DEBEST
PolyLine
DEBEST
Text Box
24VDC DISCRETE I/O
(16)-#16 AWG PER DEVICE (BY OTHERS)
DEBEST
PolyLine
HomR Text Box
PALL RESPONSE:
CONTROL OF ALUMINIUM CHLOROHYDRATE METERING PUMP SYSTEM & TANK LEVEL ARE OUTSIDE OF PALL'S ORIGINAL SCOPE.
HomR Text Box
PALL RESPONSE:
ADDITIONAL SIGNALS CITED ON THIS SHEET FOR ALARM BEACONS, FLOW SWITCHES AND WASTE TANK LEVELS ARE NOT IN THE ORIGINAL PALL SCOPE.
HomR Text Box
PALL RESPONSE:
THERE IS NO REQUIREMENT FOR ALARM AUTODIALER SIGNALS IN THE CUSTOMER SPECIFICATION.
HomR Text Box
THERE ARE NO SPECIFICATIONS PROVIDED FOR HVAC CONTROL PANEL SIGNALS TO THE PALL SYSTEM. PLEASE CLARIFY THEIR FUNCTION.
CIP CAUSTIC ROOM I/O PANEL
(PALL DWG NYCS000015163)
0.75
HP
CIP ACID ROOM I/O PANEL
(PALL DWG NYCS000015164)
0.75
HP
DEBEST
Rectangle
DEBEST
Text Box
CA ROOM ESEW FLOW SWITCH
(BY OTHERS)
DEBEST
Text Box
SHR-FSH-6622
DEBEST
PolyLine
DEBEST
Rectangle
DEBEST
Text Box
CAUSTIC ROOM ESEW FLOW SWITCH
(BY OTHERS)
DEBEST
Text Box
SHR-FSH-6623
DEBEST
PolyLine
DEBEST
Rectangle
DEBEST
Text Box
CAUSTIC ROOM ESEW FLOW SWITCH
(BY OTHERS)
DEBEST
Text Box
SHR-FSH-6624
DEBEST
PolyLine
HomR Text Box
ADDITIONAL FLOW SWITCH SIGNALS CITED ON THIS SHEET ARE NOT IN PALL'S ORIGINAL SCOPE.
1. ALL WIRING AND RACEWAY SHOWN TO
BE SUPPLIED AND INSTALLED BY OTHERS,
UNLESS OTHERWISE NOTED.
2. WIRE SIZES ARE PALL RECOMMENDED ONLY.
3. LIMIT SWITCHES ARE LOCATED AT EACH END OF
TRAVEL ON THE AMIAD FEED STRAINERS N.C.
CONTACT OPENS WHEN THE WIPER WITHIN THE
STRAINER REACHES THE RESPECTIVE END OF TRAVEL.
TERMINALS ARE LOCATED IN THE J-BOX ON THE STRAINER.
File details come from the government source that posted it. Updated .