Addendum 003 - Analytical Instrumentation - Temperature Instrumentation R1.pdf

PDF 13 MB Posted

Attached to
Request for Proposal - Construction Services for Project L-897, Central Plateau Water Treatment Facility
Solicitation number
338214
Issued by

View the file

Other files

File Type Posted
Addendum 003 - O and M Manual - Prelim Oper and Maint Manual - Template R0.pdf PDF
Addendum 003 - Equipment - Automatic Strainers R0.pdf PDF
Addendum 003 - Valves - Other Check Valves R0.pdf PDF
Addendum 003 - Recommended Electrical Spare Parts List R0.pdf PDF
Addendum 003 - Equipment - Tab 3 - Anchor Bolt List R0.pdf PDF
Addendum 003 - Valves - Butterfly Valves R0.pdf PDF
Addendum 003 - Electrical Drawings - REMOTE IO 24VDC POWER PANEL.pdf PDF
Addendum 003 - Valves - Air Release Valves R0.pdf PDF
Addendum 003 - Analytical Instrumentation Valve List R0.pdf PDF
Addendum 003 - Valves - Auto Drain Valve R0.pdf PDF
Addendum 003 - Equipment - Commissioning Plan R0.pdf PDF
Addendum 003 - Valves - Diaphragm Valves R0.pdf PDF
Addendum 003 - VDL 006-006 RFP Const Bidder Pall Documents.xlsx XLSX spreadsheet
Addendum 003 - Valves - Other Solenoid Valves R0.pdf PDF
Addendum 003 - Electrical Drawings - FEED STRAINER PLC IO PANEL.pdf PDF
Addendum 003 - Valves - Other Air Pressure Valves R0.pdf PDF
Addendum 003 - Analytical Instrumentation - Flow Instrumentation R1.pdf PDF
Addendum 003 - Valves - Solenoid Valves R0.pdf PDF
Addendum 003 - Equipment - Actuator Torque Tables R1.pdf PDF
Addendum 003 - Equipment - Filter Elements R0.pdf PDF
Addendum 003 - Valves - Dual Disc Check Valves R0.pdf PDF
Addendum 003 - Equipment - FRP Tanks R0.pdf PDF
Addendum 003 - Equipment - Equipment List R0 - Pall Comments.pdf PDF
Addendum 003 - O and M Manual - System Functional Description (SFD) R0.pdf PDF
Addendum 003 - Electrical Drawings - MAIN CONTROL PANEL.pdf PDF
Addendum 003 - Electrical Drawings - MF VALVE RACK PANEL.pdf PDF
Addendum 003 - Electrical Drawings - Main CP 24VDC Power Panel.pdf PDF
Addendum 003 - Analytical Instrumentation - Level Instrumentation R1.pdf PDF
Addendum 003 - Valves - Air Pressure Control Valves R0.pdf PDF
Addendum 003 - Equipment - FRP Tanks attachment.pdf PDF
Addendum 003 - Contractual Electrical Spare Parts List R0.pdf PDF
Addendum 003 - Equipment - Air System R1.pdf PDF
Addendum 003 - Valves - Ball Valves R0.pdf PDF
Addendum 003 - Valves - Chemical Pressure Control Valves R0.pdf PDF
Addendum 003 - Major Electrical Comp R0.pdf PDF
Addendum 003 - Electrical Drawings - CIP CAUSTIC ROOM PLC IO PANEL.pdf PDF
Addendum 003 - Exceptions and Clarifications - Specification Cross Reference Matrix R0.pdf PDF
Addendum 003 - Equipment - Calibration Columns R0.pdf PDF
Addendum 003 - Equipment - Centrifugal Pumps R0.pdf PDF
Addendum 003 - Equipment - Indeeco Heater General Infor R0.pdf PDF
Addendum 003 - Mechanical Drawings - Membrane Train Assy Dwg R3.pdf PDF
Addendum 003.pdf PDF
Addendum 003 - Equipment - Wilden Pump General Information R0.pdf PDF
Addendum 003 - Equipment - Water Softener R0.pdf PDF
Addendum 003 - Electrical Drawings - Interconnect Diagram Pall Comments.pdf PDF
Addendum 003 - Analytical Instrumentation - Pressure Instrumentation R1.pdf PDF
Addendum 003 - Mechanical Drawings - P and ID R4 Pall Submittal Return Comments.pdf PDF
Addendum 003 - Valves - Water Pressure Control Valves R0.pdf PDF
Addendum 003 - Equipment - Other Strainers R0.pdf PDF
Addendum 003 - Equipment - NSF PID Scope R0.pdf PDF
Show 40 more

Latest 50 of 88 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

COVER PAGE OF SELLER’S SUBMITTAL

City Name: Hanford, WA - MSA

Pall Project No.: 01.000287

Job Number: Project L-897, Subcontract 70816

Task Register 6 (Task 1 – VI Submittal Package)

To: (Contractor)

Mission Support Alliance, LLC (MSA)

PO Box 650

Richland, WA 99352

From: (Subcontractor)

Pall Water

A Division of Pall Corporation

839 State Route 13

Cortland, NY 13045

Patty Willis

Phone: 607-758-1699

Name of Project: Hanford, WA, Central Plateau WTF

Pall Document Number: NYCS000015266 Rev: 01

Description of Item: Temperature Instrumentation

Specification Section: 40 73 02

Deviations: See document NYCS000015383

Cover Page Information Revision History and Approvals

Tab 1- NYCS000015451,CSS,Temperature Instrumentation,01.287 R01

INDEX:

Page 1:

Page 2:

Page 3:

Pages 4-21: Tab 2 - Rosemount 12-Inch SS Thermowelled RTD & Integral Transmitter Cuts

Pages 22-95: Tab 3 - Rosemount 18-Inch SS Thermowelled RTD & Integral Transmitter Cuts

Pages 96-169: Tab 4 - Rosemount 18-Inch Hast.Thermowelled RTD&Integral Transmitter Cuts

Date: 12/19/2019

PALL ADVANCED SEPARATIONS SYSTEMS

DIVISION OF PALL CORPORATION, CORTLAND, NY

Rev Name Date Created By

Approved By

Created By

Approved By

Created By

Approved By

Created By

Approved By

Revision Description

Title

Document # Revision griffinju Text Box These commodities, technology, or software may only be exported from the United States in accordance with the Export Administration Regulations. Diversion contrary to U.S. law is prohibited.

Doc Number: NYCS000015451R01 Doc Title: NYCS000015451,CSS,Temperature Instrumentation,01.287 R01.docx

Components Specification Sections

The following specification sections are relevant to the approval of submittal NYCS000015266, Temperature Instrumentation,01.287:

L‐897, Attachment No. 2 ‐ HNF‐SPEC‐63538, Section 40 73 02, Process Instrumentation Meters and Transmitters.

Any exceptions and clarifications to the specification section above can be found in submittal NYCS000015383, L‐897, Section 40 73 02, Es and Cs,01.287.

Pall has taken exceptions and clarifications relevant to the temperature instrumentation proposed.

Pall Corporation Membrane Filtration (MF) System Instrumentation Submittal

12” 316 SS Thermowelled RTD w/ Local Transmitter Assembly Thermowell: Rosemount P/N: 114CE0120TAA3SC032BXW Spring-Loaded RTD: Rosemount P/N: 214CRTSMB1S4E0152SLE6XWXA Local Transmitter: Rosemount P/N: 3144P D1 A 1 K6 M5 Q4 XA

12”-Stainless Steel Thermowell: Rosemount P/N: 114C E 0120 T AA 3 SC 032 B XW

Part Number Key:

114C Model: ROSEMOUNT 114C THERMOWELL E Dimension Units: ENGLISH

0120 Immersion Length: 12.0 INCHES T Mounting Style: THREADED

AA Process Connections: ½-14 ANPT 3 Stem Style: STEPPED

SC Thermowell Material: 316 / 316L SS DUAL RATED 032 Head Length: 3.2 INCHES

B Instrument Connection: ½”-14 NPSM

XW

Sensor / Thermowell Assemble: FACTORY ASSEMBLY OF SENSOR AND THERMOWELL

Spring-Loaded RTD: Rosemount P/N: 214C RT SM B1 S4 E 0152 SL E6 XW XA

Part Number Key:

214C Model: ROSEMOUNT 214C TEMPERATURE SENSOR RT Sensor Type: RTD THIN-FILM, PT100, α = 0.00385, -50 TO 450 DEG-C SM Sensor Sheath Material: 321 SST B1 Sensor Accuracy: CLASS-B PER IEC 60751 S4 Sensor Wiring Configuration: SINGLE, 4-WIRE E Dimension Units: US CUSTOMARY / ENGLISH / INCHES

0152 Sensor Insertion Length (L): 15.2 INCHES SL Sensor Mounting Style: SPRING LOADED ADAPTER E6 Product Certifications: CANADA EXPLOSION-PROOF

XW Transmitter Assembled to Sensor: FACTORY ASSEMBLED TO TRANSMITTER XA Thermowell Assembled to Sensor: FACTORY ASSEMBLED TO THERMOWELL

3144P Model: ROSEMOUNT 3144P D1 Housing Style: Field-Mount (Local), Dual-Compartment Housing, Aluminum, ½-14 NPT Ports A Transmitter Output: 4-20mA WITH DIGITAL SIGNAL BASED ON HART PROTOCOL 1 Measurement Configuration: SINGLE SENSOR K6 Product Certifications: CSA IS, FISCO DIVISION 2 AND EXPLOSION-PROOF COMBO M5 Display Option: Liquid-Crystal-Display (LCD) Q4 Calibration Certificate: 3-POINT CALIBRATION XA Assembly Options: SEPARATELY SPECIFIED SENSOR FACTORY ASSEMBLED

Product Data Sheet January 2017

00813-0500-2654, Rev BB

Rosemount™ 214C Temperature Sensors Primary product benefits

High accuracy resistance temperature detectors (RTD) and various thermocouple types offered in a variety of element configurations

Calibration capabilities for increased measurement accuracy for RTDs

HomR

12" SENSOR: ROSEMOUNT P/N: 214CRTSMB1S4E0152SLXWXA

Rosemount 214C January 2017 Rosemount 214C Temperature Sensors

Optimize plant efficiency and increase measurement reliability with industry-proven design and specifications All sensor styles and lengths available as standard in 6mm (1/4-in.) nominal diameter

State of the art manufacturing processes providing robust element packaging, increasing reliability

Industry-leading calibration capabilities allowing for Callendar-Van Dusen values giving increased RTD accuracy when paired with Rosemount transmitters

Optional Class A accuracy RTDs or Class 1/Special Tolerances thermocouples for critical temperature measurement points

Explore the benefits of a Complete Point Solution™ from Emerson™ Process Management “Transmitter assembled to sensor” and “Thermowell assembled to sensor” options enable Emerson Process Management to provide a complete point temperature solution, delivering process-ready or hand-tight transmitter, sensor, and/or thermowell assemblies

Complete portfolio of Single Point and Multi-Input Temperature Measurement solutions, allowing effective measurement and processes control with the trusted reliability from Rosemount products

Experience global consistency and local support from numerous worldwide Emerson manufacturing sites World-class manufacturing provides globally consistent product from every factory and capacity to fulfill needs of any project, large or small

Experienced Instrumentation Consultants help select right product for any temperature application and offer advice on best installation practices

Extensive global network of Emerson service and support personnel can be on-site when and where they are needed

Contents

Rosemount 214C Sensor

RTD ordering information

Thermocouple ordering information

Ordering information detail

Product certifications

Additional RTD specifications

Additional thermocouple specifications 2 Emerson.com/Rosemount6

Rosemount 214CJanuary 2017 Rosemount 214C Sensor

The Rosemount 214C Sensors are designed to provide flexible and reliable temperature measurements in process monitoring and control environments.

Features include:

Temperature ranges of -196 to 600 °C (-321 to 1112 °F) for RTDs and -196 to 1200 °C (-321 to 2192 °F) for thermocouples

Industry-standard sensor types: PT100 RTDs; thermocouple Type J, Type K, and Type T

Spring-loaded and compact spring-loaded sensor mounting styles

Hazardous location product approvals and certification

Calibration services to give insight to sensor performance

Calibration certificate to accompany sensor

Specification and selection of product materials, options, or components must be made by the purchaser of the equipment.

Figure 1. Model Number Ordering Example

The numbers below the model string example in Figure 1 correlate to the character place numbers in the ordering table.

Ensure sensor fits thermowell

Rosemount 114C Head length (H) + Immersion length (U) = Rosemount 214C Sensor insertion length (L).

Model Sensor type Sheath material Sensor accuracy Number of elements

Units Sensor insertion length

Sensor mounting style Options

2 1 4 C R W S M A 1 S 4 E 0 1 5 0 S L WR5, E5...

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 X X X X X

UH

L

3Emerson.com/Rosemount7

HomR Text Box

2 1 4 C R T S M B 1 S 4 E 0 1 5 2 S L XWXA

HomR e e

RTD ordering information Table 1. Rosemount 214C RTD Quick Order Table

Table 2. Rosemount 214C RTD Ordering Information The starred offerings (H) represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.

Place #s 1-4 Model

H 214C Temperature sensor core base model (made with standard outside diameter of 6mm [1/4--in.])

Place #s 5-6 Sensor type Details

Ref pag

H RT

RTD, PT100; = 0.00385; -50 to 450 °C (-58 to 842 °F)

Thin-film element is better in vibration and physical shock. 21

H RW

RTD, PT100; = 0.00385; -196

to 600 °C (-321 to 1112 °F)

Wire wound element allows for a wider temperature range, better for low temperature applications

Place #s 7-8 Sensor sheath material Details

Ref pag

H SM 321 SST Maximum operating temperature limit of 816 °C (1500 °F) 23

Sheath material

321 SSTSM

Number of elements

Single, 4-wire

Dual, 3-wire

S4

D3

Sensor insertion length

2 to 78.5 inches;

¼-in. increments;

w/ English units

Example

3.5 in = 0035;

50 in = 0500;

xxxx

50 to 2000 mm;

5mm increments;

w/ Metric units

Example 125 mm = 0125;

1300 mm = 1300 xxxx

Sensor type

Thin- lm; PT100;

-50 to 450 °C (-58 to 842 °F)

Wire wound; PT100;

-196 to 600 °C (-321 to 1112 °F)

T

W

Sensor accuracy

Class A

Class B

A1

B1 units

English/U.S.

customary units (inches)

Metric units (mm)

E

M

Sensor mounting style

Spring loaded adapter

Adjustable spring loa ng

SL

SA

Welded adapterWA

316 SST material options

316 SST ComponentsM2

Product certification

USA Explosionproof

Canada Explosionproof

E5

E6

See more options in the full ordering table xx

Connection heads

Rosemount Aluminum connection head with 1/2-in. NPT condult entry and instrument connection

AR1

C1B1

Extensions types

Union StyleUA

Extension length xx.x inches, 2.5 to 20 inches in ½-in.

increments; w/ English xxx mm, 65 to 500 mm

Exxx

C

R 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20...

Dimension

Units in 5-mm increments;

w/ Metric Units

4 Emerson.com/Rosemount8

HomR Text Box

2 1 4 C R T S M B 1 S 4 E 0 1 5 2 S L XW XA

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Text Box

XW = THERMOWELL ASSEMBLED

TO SENSOR

XA = TRANSMITTER ASSEMBLED

TO SENSOR

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR e e e

Place #s 9-10 Sensor accuracy Details Image

Ref pag

H A1 Class A per IEC 60751 over -50 to 450 °C (-58 to 842 °F)

Class A accuracy is only available with wire-wound element Option Code:

RW

H B1 Class B per IEC 60751 24

Place #s 11-12 Number of elements Details Image

Ref pag

H S3 Single, 3-wire Good measurement results 25

H S4 Single, 4-wire Excellent measurement results 25

H D3 Dual, 3-wire Added measurement redundancy 25

Place # 13 Dimension units Details

Ref pag

H E English/U.S. customary units (inches) Only applies to lengths

H M Metric units (mm) 26

Table 2. Rosemount 214C RTD Ordering Information The starred offerings (H) represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.

White

Red

Red

White 5Emerson.com/Rosemount9

HomR Polygonal Line

HomR Rectangle

HomR Rectangle

HomR e e

Place #s 14-17 Sensor insertion length (L)

Ref pag

H xxxx xxx.x inches, 2 to 78.5 inches in 1/4-in. increments (when ordered with Dimension units code E)

Example of a 6.25-in. length where the second decimal is dropped off: 0062

H xxxx xxxx mm, 50 to 2000 mm in 5-mm increments (when ordered with Dimension units code M)

Example of a 50 mm length: 0050

Place #s 18-19 Sensor mounting style Details Image

Ref pag

H SL Spring loaded adapter Ensures sensor contact with thermowell tip

H SC Compact spring loaded adapter

Non-explosionproof adaper that is 29.72mm (1.17 inches) shorter than standard spring loaded adapter (currently not available with Division 2/Zone 2 approvals)

H SW

Spring loaded adapter with thermowell contact indication

Spring loaded adapter with a small opening on the side of the adapter for visual indication of sensor contact with the tip of a thermowell

H WA Welded adapter

Welded joint between sensor capsule and adapter allows for direct immersion of sensor into the process.

If thermowell is used, this welded joint acts as a secondary process seal.

H WC Compact welded adapter

Non-explosionproof adapter that is 29.72mm (1.17 inches) shorter than standard welded adapter (currently not available with Division 2/Zone 2 approvals)

H SA Adjustable spring loaded fitting

Adjustable fitting that allows for installation along sensor capsule body. The spring loaded fitting ensures sensor contact to thermowell tip.

H CA Compression fitting 1/8-in. NPT

Adjustable fitting that allows for installation along the sensor capsule body

H CB Compression fitting 1/4-in. NPT

H CC Compression fitting 1/2-in. NPT

H CD Compression fitting 3/4-in. NPT

H SO Sensor only Sensor capsule without any fittings or adapters for mounting

Table 2. Rosemount 214C RTD Ordering Information The starred offerings (H) represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.

6 Emerson.com/Rosemount10

HomR Text Box

HomR Line

HomR Rectangle

HomR e e e e

Low temperature housing Ref pag

H LT Low temperature connection head option down to -51 °C (-60 °F) 40

Transmitter assembled to sensor Details Ref pag

H XA

Process-ready assembly of transmitter and sensor

Ensures sensor is threaded into connection head with transmitter and torqued for process-ready installation; sensor is wired to the transmitter

H XC

Hand-tight assembly of transmitter and sensor

Ensures sensor is threaded into connection head with transmitter but only hand tightened; manual wiring is required

Thermowell assembled to sensor Details Ref pag

H XW

Process-ready assembly of sensor and thermowell

Ensures sensor is threaded into thermowell and torqued for process-ready installation

H XT

Hand-tight assembly of sensor and thermowell

Ensures sensor is threaded into thermowell but only hand tightened 40

Extended product warranty Details Ref pag

H WR3 3-year limited warranty This warranty option is to extend your manufacturers warranty to three or five years for manufacturer related defects

H WR5 5-year limited warranty 40

Table 2. Rosemount 214C RTD Ordering Information The starred offerings (H) represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.

11Emerson.com/Rosemount11

HomR Rectangle

HomR Rectangle

HomR

Ordering information detail

Sensor type Back to RTD ordering table

Back to Thermocouple ordering table

RTD

RTDs are based on the principle that the electrical resistance of a metal increases as temperature increases – a phenomenon known as thermal resistivity. Thus, a temperature measurement can be inferred by measuring the resistance of the RTD element.

RTDs are constructed of a resistive material with leads attached and usually placed into a protective sheath (see “Sheath material” on page 23 for details). The resistive material can be a variety of materials. Emerson however, standardizes on platinum materials for all RTDs because of its high accuracy, excellent repeatability, and exceptional linearity over a wide temperature range. Platinum RTDs also exhibit a large resistance change per degree of temperature change.

The relationship between the resistance change of an RTD vs. temperature is called its Temperature Coefficient of Resistance (TCR) and is often referred to as the RTD's alpha curve. Emerson's PT100 RTDs all have a standard alpha coefficient of

= 0.00385 which is the most popular option that is recognized nationally and internationally. Reference Figure 2 for typical behavior of the resistance of a platinum RTD over a range of temperature.

Figure 2. Resistance Change vs. Temperature for Platinum RTD (PT100)

Emerson offers the two most common styles of RTD sensors: thin-film and wire-wound. Wire-wound RTDs are manufactured by winding the resistive wire in a helical shape supported in a ceramic sheath – hence the name wire-wound. Thin-film RTDs are manufactured with a thin resistive coating that is deposited on a flat, usually rectangular ceramic substrate.

20 Emerson.com/Rosemount12

Thin-film RTD (RT)

Thin-film elements are generally better in vibration and physical shock. With a platinum construction (PT100) and a temperature coefficient =0.00385, this sensor element is rated for use between -50 to 450 °C (-58 to 842 °F).

Wire-wound RTD (RW)

When a wider temperature range is required for an RTD, the wire-wound element is a better choice. The RW option code is for wire-wound RTDs which are for -196 to 600 °C (-321 to 1112 °F). Similar to the thin-film element, this element has a platinum construction (PT100) and an alpha value of =0.00385. Due to its wider temperature range, this option should be chosen for low temperature applications (below -50 °C [-58 °F]) and high temperature applications (above 450 °C [842 °F]).

Table 5. RTD Comparison

Figure 3. RTD Elements

Thin-film Wire-wound

Option code RT RW

Element type Thin-film Wire-wound

Temperature range -50 to 450 °C (-58 to 842 °F)

-196 to 600 °C (-321 to 1112 °F)

Good for Higher vibration and physical shock

Higher accuracy and low temperature applications

Accuracy Class B Class A; Class B

21Emerson.com/Rosemount13 elkinsj Rectangle elkinsj Line elkinsj Line elkinsj Rectangle elkinsj Rectangle elkinsj Line

Line

Sensor accuracy

Back to RTD ordering table

Back to Thermocouple ordering table

(A1, B1)

The thin-film option code RT is available in Class B accuracy only.

The wire-wound option code RW is intended for applications that require high accuracy and/or subjected to high and low temperatures. Option code RW is available with both Class A and Class B accuracy. Class A is only available over -50 to 450 °C (-58 to 842 °F).

Table 7 shows the interchangeability of RTD sensors. It explains the tolerance for Class A and Class B accuracy RTDs over a specific temperature range. The performance of the option codes RT and RW sensors conform to the standard set by IEC 60751. Figure 8 is a graphical representation that demonstrates the Class A and Class B accuracy curve over temperature per IEC 60751. For maximum system accuracy, Emerson can provide sensor calibration and optional sensor-to-transmitter matching obtainable through the use of Callendar-Van Dusen Constants. See “Calibration” on page 37 for additional calibration offering.

Table 7. Interchangeability Error for RTD per IEC 60751

Figure 8. Sensor Accuracy Curve

(T1, T2, SP, ST)

Similar to RTDs, thermocouples also can have tolerances as defined by national standards. According to IEC 60584, thermocouples can have a narrower tolerance (or higher accuracy) of Class 1. Class 1 thermocouples are manufactured with higher grade wire which increases their accuracy reading. Class 2, on the other hand, has a wider accuracy error margin since they are manufactured with standard thermocouple grade wires.

Emerson also provides thermocouples that meet tolerances per ASTM E230 standards. Special Tolerances are approximately half of accuracy error margin than Standard Tolerances since they are made with higher grade wire.

°C (°F) Tolerance in °C (°F)

Class B for RTD Model Option RT Class B for RTD Model Option RW Class A for RTD Model Option RW

-196 (-321) N/A ±1.28 (2.30) N/A

-100 (-148) N/A ±0.8 (1.44) N/A

-50 (-58) ±0.55 (0.99) ±0.55 (0.99) ±0.25 (0.45)

0 (32 ) ±0.3 (0.54) ±0.3 (0.54) ±0.15 (0.27)

100 (212) ±0.8 (1.44) ±0.8 (1.44) ±0.35 (0.63)

200 (392) ±1.3 (2.34) ±1.3 (2.34) ±0.55 (0.99)

300 (572) ±1.8 (3.24) ±1.8 (3.24) ±0.75 (1.35)

450 (842) ±2.55 (4.59) ±2.55 (4.59) ±1.05 (1.89)

500 (932) N/A ±2.8 (5.04) N/A

600 (1112) N/A ±3.3 (5.94) N/A 24 Emerson.com/Rosemount14 elkinsj Rectangle

Rectangle

Number of elements

Back to RTD ordering table

Back to Thermocouple ordering table

(S3, S4, D3)

For applications where a generic RTD temperature measurement is sufficient, select option S3 for a single, 3-wire measurement. For better results, select option S4 for a single, 4-wire measurement. For added measurement reassurance, select option D3 for a dual, 3-wire measurement.

Since the lead wires are part of the RTD circuit, the lead wire resistance needs to be compensated for to achieve the best accuracy.

This becomes especially critical in applications where long sensor and/or lead wires are used. Emerson provides two lead wire configurations that are commonly available: 3-wire and 4-wire.

In a 4-wire configuration, the lead wire resistance is inconsequential to the measurement. It uses a measurement technique where a very small constant current of about 150 μA is applied to the sensor through two leads and the voltage developed across the sensor is measured over the other two wires with a high-impedance and high resolution measuring circuit. In accordance with Ohm’s Law the high impedance virtually eliminates any current flow in the voltage measurement leads and therefore the resistance of the leads is not a factor.

In a 3-wire configuration, compensation is accomplished using a third wire with the assumption that it will be the same resistance as the other two wires and the same compensation is applied to all three wires.

Lead wire configurations can be programmed in Emerson's Rosemount Temperature Transmitters since they are capable of compensating for the various configurations.

All of the available lead wire configurations conform to IEC 60751. As a result, the wire colors for the sensor match what is defined by the standard.

A 4-wire sensor can also be used in a 2- or 3- wire configuration. To properly wire the 4-wire RTD for use in a 2-, 3-, or 4-wire configuration, refer to the Rosemount 214C Quick Start Guide.

Figure 9. RTD Lead Wire Configurations

Single element, 3-wire (S3) Single element, 4-wire (S4) Dual element, 3-wire (D3)

White

Red

Red

White 25Emerson.com/Rosemount15 http://www2.emersonprocess.com/siteadmincenter/PM%20Rosemount%20Documents/00825-0400-2654.pdf http://www2.emersonprocess.com/siteadmincenter/PM%20Rosemount%20Documents/00825-0400-2654.pdf

When ordering in millimeters, the length can be ordered in 5 mm increments. Here are some examples:

50 mm = 0050

325 mm = 0325

Determining the length (L) of a replacement spring-loaded sensor in existing installation

To replace only the sensor

1. Remove the existing sensor from the installation.

2. Measure the sensor length with the spring in the relaxed state from the tip of the sensor to the thread engagement point of 13 mm (0.5-in.) into the adapter threads.

3. Subtract 6 mm (0.25-in.) from your measurement. The resulting length is (L). Use this length to specify the sensor insertion length in the ordering table.

To replace the sensor and extension

1. Remove the existing sensor and extension from the installed thermowell.

2. Measure the sensor length with the spring in the relaxed state from the tip of the sensor to the thread engagement point of 13 mm (0.5-in.) into the extension threads

3. Subtract 6 mm (0.25-in.) from your measurement. The resulting length is (L). Use this length to specify the sensor insertion length in the ordering table.

4. Measure the extension length from thermowell connection to the adapter/fitting connection accounting for 13 mm (0.5-in.)

thread engagement. The resulting length is (E). Use this length to specify the extension length in the ordering table (see “Extension length” on page 36).

Note Emerson standardizes on a spring compression of 13 mm (0.5-in.) for all spring loaded and compact spring loaded mounting styles for sensors. The thermowell tip thickness is assumed to be 6 mm (0.25-in.) and the sensors are built 6 mm (0.25-in.) longer than the ordered length to ensure contact to the thermowell tip.

To ensure sensor fits the Rosemount 114C Thermowell, refer to “Ensure sensor fits thermowell” on page 3.

27Emerson.com/Rosemount16

Sensor mounting style

Back to RTD ordering table

Back to Thermocouple ordering table

Emerson offers a variety of mounting style options for every sensor. Depending on the application needs and constraints, a certain type of mounting style may be preferred. See description of each style and their dimensions below.

Threaded style mounting adapters

The threaded style is a sensor with a threaded adapter to provide a connection to the process and connection head. The benefit of the threaded style is the ability to install it directly into a process or thermowell without any additional mounting fittings. Emerson currently offers two different threaded mounting styles: Spring loaded adapter and Compact spring loaded adapter.

Spring loaded adapter (SL)

A spring located in the threaded adapter allows the sensor to travel, ensuring contact with the bottom of a thermowell. This helps ensure better sensor accuracy, improved sensor response time and aids in providing better performance while under vibration.

Compact spring loaded adapter (SC)

When space is limited, Emerson provides a compact spring loaded adapter. This adapter has a length of

29.21 mm (1.15-in.) as shown in Figure 12. It is also an excellent option for when explosionproof approvals are not a concern yet continuous contact to the thermowell tip is required.

Spring loaded adapter with thermowell contact indication (SW)

This spring loaded adapter contains a small opening on the side of the adapter giving this design an added advantage of a visual indication of the sensor contact to the tip of the thermowell. This design is slightly larger with a length of 66.04 mm (2.60-in.).

Figure 11. Dimensions

Figure 12. Dimensions

Figure 13. Dimensions 28 Emerson.com/Rosemount17

Low temperature housing (LT)

Back to RTD ordering table

Back to Thermocouple ordering table

Selecting this option allows the connection head to be compatible to -51 °C (-60 °F).

Transmitter assembled to sensor (XA, XC)

Back to RTD ordering table

Back to Thermocouple ordering table

XA

This option is selected when a sensor is ordered with a transmitter. This option code ensures the sensor is threaded into the connection head and torqued for a process-ready installation, with the sensor wired to the terminal.

XC

This option is selected when a sensor is ordered with a transmitter. This option code ensures the sensor is threaded into the connection head, but only hand tightened, and manual wiring of the sensor to the terminal is required.

Note XC code does not meet hazardous location approval requirements. Refer to Rosemount 214C Quick Start Guide for proper installation.

Thermowell assembled to sensor (XW, XT)

Back to RTD ordering table

Back to Thermocouple ordering table

XW

This option is selected when a sensor is ordered with the Rosemount 114C Thermowell. It ensures the sensor is threaded into the thermowell and torqued for a process-ready installation.

XT

This option is selected when a sensor is ordered with the Rosemount 114C Thermowell. It ensures the sensor is threaded into the thermowell, but only hand tightened.

Note XT code does not meet hazardous location approval requirements. Refer to Rosemount 214C Quick Start Guide for proper installation.

Extended product warranty (WR3, WR5)

Back to RTD ordering table

Back to Thermocouple ordering table

The extended product warranty options are available in three or five year coverage plans. In the model string, order option codes WR3 for a three year extended warranty or WR5 for a five year warranty. This coverage is an extension of the manufacturer's limited warranty and states that the goods manufactured or services provided by seller will be free from defects in materials or workmanship under normal use and care until the expiration of the applicable warranty period.

40 Emerson.com/Rosemount18 http://www2.emersonprocess.com/siteadmincenter/PM%20Rosemount%20Documents/00825-0400-2654.pdf http://www2.emersonprocess.com/siteadmincenter/PM%20Rosemount%20Documents/00825-0400-2654.pdf elkinsj Rectangle

Additional RTD specifications Note All specifications in this section apply to all RTD unless noted otherwise.

Insulation resistance

1000 M minimum insulation resistance when measured at 500VDC at room temperature.

Insulation resistance at elevated temperature

400 M minimum insulation resistance when measured at 500 VDC at maximum temperature.

Time response

10.8 seconds maximum required to reach 50% sensor response when tested in flowing water according to IEC 60751:2008

Stability

±0.15 °C (0.059 ) maximum ice-point resistance shift following 1,000 hours at maximum specified temperature when measured per methods defined in IEC 60751:2008.

Effects of temperature cycling

±0.15 °C (0.059 ) maximum ice-point resistance shift following 10 cycles over the maximum specified temperature range when measured per methods defined in IEC 60751:2008.

Hysteresis

±0.50 °C (0.185 ) maximum ice-point resistance shift over the maximum specified temperature range when measured per methods defined in IEC 60751:2008.

Self heating

An average of 0.32 °C/mW is found when measured per method defined in IEC 60751:2008.

Process immersion

Thin film element, single

Max Minimum Immersion Depth = 30 mm measured in 100 °C water according to IEC 60751:2008

Thin film element, dual

Max Minimum Immersion Depth = 45 mm measured in 100 °C water according to IEC 60751:2008

Wire wound element

Max Minimum Immersion Depth = 50 mm measured in 100 °C water according to IEC 60751:2008

41Emerson.com/Rosemount19

Vibration limits

Thin film element

0.05 °C (0.020 ) maximum ice-point resistance shift after 3g vibration between 20 and 500 Hz for 150 hours according to IEC 60751:2008.

Wire-wound element

0.05 °C (0.020 ) maximum ice-point resistance shift after 1g vibration between 20 and 500 Hz for 150 hours according to IEC 60751:2008.

Lead wires

Lead wires -24 AWG wire, FEP insulated; color coded per IEC 60751.

42 Emerson.com/Rosemount20

Additional thermocouple specifications Note All specifications in this section apply to all thermocouple types unless noted otherwise.

Insulation resistance

1000 M minimum insulation resistance when measured at 500VDC at room temperature.

Time response

Grounded thermocouples

2.2 seconds maximum required to reach 50% sensor response when tested in flowing water according to IEC 61515:2016.

Ungrounded thermocouples

3.2 seconds maximum required to reach 50% sensor response when tested in flowing water according to IEC 61515:2016.

Process immersion

Grounded thermocouples

Max Minimum Immersion Depth = 5 mm measured in 100 °C water according to IEC 61515:2016.

Ungrounded thermocouples

Max Minimum Immersion Depth = 10 mm measured in 100 °C water according to IEC 61515:2016.

Continuity

Electrical continuity of each conductor pair is verified. For a grounded junction thermocouple, electrical continuity of each pair of conductors to sheath are verified.

Lead wires

Lead wires -24 AWG wire, FEP insulated; color coded per IEC 60584 or ASTM E230.

43Emerson.com/Rosemount21

Pall Corporation Membrane Filtration (MF) System Instrumentation Submittal

18” 316 SS Thermowelled RTD w/ Local Transmitter Thermowell: Rosemount P/N: 114C E 0180 T AA 3 SC 032 B XW Temperature Sensor: Rosemount P/N: 214C RT SM B1 S4 E 0212 SL E6 XW XA

18”- 316 SS Thermowell: 114C E 0180 T AA 3 SC 032 B XW

114C Model: ROSEMOUNT 114C THERMOWELL E Dimension Units: ENGLISH 0180 Immersion Length: 18.0 INCHES T Mounting Style: THREADED AA Process Connections: ½-14 ANPT 3 Stem Style: STEPPED SC Thermowell Material: 316 / 316L SS DUAL RATED 032 Head Length: 3.2 INCHES B Instrument Connection: ½”-14 NPSM XW Sensor / Thermowell Assemble: FACTORY ASSEMBLY OF SENSOR AND THERMOWELL

Spring-Loaded RTD: Rosemount P/N: 214C RT SM B1 S4 E 0212 SL E6 XW XA

214C Model: ROSEMOUNT 214C TEMPERATURE SENSOR

RT Sensor Type: RTD THIN-FILM, PT100, α = 0.00385, -50 TO 450 DEG-C SM Sensor Sheath Material: 321 SST B1 Sensor Accuracy: CLASS-B PER IEC 60751 S4 Sensor Wiring Configuration: SINGLE, 4-WIRE E Dimension Units: US CUSTOMARY / ENGLISH / INCHES

0212 Sensor Insertion Length (L): 21.2 INCHES SL Sensor Mounting Style: SPRING LOADED ADAPTER E6 Product Certifications: CANADA EXPLOSION-PROOF

XW Transmitter Assembled to Sensor: FACTORY ASSEMBLED TO TRANSMITTER XA Thermowell Assembled to Sensor: FACTORY ASSEMBLED TO THERMOWELL

3144P Model: ROSEMOUNT 3144P D1 Housing Style: Field-Mount (Local), Dual-Compartment Housing, Aluminum, ½-14 NPT Ports A Transmitter Output: 4-20mA WITH DIGITAL SIGNAL BASED ON HART PROTOCOL 1 Measurement Configuration: SINGLE SENSOR K6 Product Certifications: CSA IS, FISCO DIVISION 2 AND EXPLOSION-PROOF COMBO M5 Display Option: Liquid-Crystal-Display (LCD)

Q4 Calibration Certificate: 3-POINT CALIBRATION XA Assembly Options: SEPARATELY SPECIFIED SENSOR FACTORY ASSEMBLED

Rosemount 114C May 2016

EmersonProcess.com/Rosemount

Rosemount 114C Threaded Thermowells

Rosemount 114CMay 2016

EmersonProcess.com/Rosemount

Threaded thermowell overview

Threaded thermowells are threaded into a process pipe or tank, allowing for easy installation and removal when necessary. While this is the most common mounting method, it has the lowest pressure rating of the mounting configuration options.

Figure 1. Standard Offering–Threaded

The common options shown in Figure 1 represent a partial offering; reference the Ordering Table for a full list of available options.

Figure 2. Threaded Thermowell Components

A. Instrument connection

B. Process connection

H. Head length

U. Immersion length

Note Wetted surface includes engaged threads and immersion length (U).

Use the form below to record your model code.

Tapered threads Parallel threads

Model Instrument connection threads

Head length (H)

Thermowell material

Stem style

Process connection

Mounting style

Immersion length (U)

Units

1 1 4 C X XXXXXXXXXTXXXX

161514131211987654321 10 191817

(5) Units

English (E)

Metric (M)

(6-9) Immersion length (U)

25mm to 1165mm (M) Example: 25mm=0025, 1165mm=1165

1in to 42in (E) Example: 0.5in=0005, 42in=0420

XXXX

XXXX

(10) Mounting style

Threaded (T)

(11-12) Process connections

AA ½-14 NPT

AB

AC

¾-14 NPT

1-11.5 NPT

(13) Stem style

1 Straight stem

Tapered stem

Stepped stem

(14-15) Thermowell material

SC 316/316L SST

SF

CS

304/304L SST

Carbon steel

(16-18) Head length (H)

40mm to 225mm (M) Example: 40mm=040, 225mm=225

1.75in to 11.25in (E) Example: 1.75in=017, 10in=100

XXX

XXX

(19) Instrument connection

A ½-14 NPT

B ½-14 NPSM

Options

XX, XXX, XX

Common options

External pressure testQ5

R21

Q35

Q8

NACE approval

Wake frequency calculation

Material certification

DA M20 x 1.5p

DB

DE

M24 x 1.5p

½-in. BSPF (G½)

D M18 x 1.5p

E M20 x 1.5p

F M24 x 1.5p

UH

A

B

H U

A

B

Model Units Immersion length (U)

Mounting style

Process connection

Stem style

Thermowell material Head length (H)

Instrument connection Options

1 1 4 C T

1 2 3 4 5 6 through 9 10 11 and 12 13 14 and 15 16 through 18 19 X X X X X

EmersonProcess.com/Rosemount

Threaded ordering information

Figure 3. Model Number Ordering Example

The numbers below the model number ordering example correlate to the character place numbers in the second column of the ordering table.

Model Units Immersion length (U)

Mounting style

Process connection

Stem style

Thermowell material Head length (H)

Instrument connection Options

1 1 4 C E 0 0 6 0 T A A 1 S C 0 5 0 A

WR5,

Q76...

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 X X X X X

Table 1. Rosemount 114C Threaded Ordering Information

H The Standard offering represents the most common options. The starred options (H) should be selected for best delivery lead time.

The Expanded offering is subject to additional delivery lead time.

Place #s 1-4

Model Details

H 114C Barstock temperature thermowell Made with a standard bore diameter of 0.26-in. (6.5mm) and tip wall thickness of 0.25-in. (6.4 mm)

Place #

Dimension units Details Ref.

page

H E English units (inches) Specifies whether length units will be in inches (in) or millimeters (mm)

H M Metric units (mm) 53

Place # 6-9

Immersion length (U)

Tapered threads Parallel threads

Ref.

page

H xxxx xxx.x inches, 1.25 to 60 inches in 1/4-in. increments (when ordered with dimension units code E)

Example of a 6.25-in. length where the second decimal is dropped off: 0062

H xxxx xxxx mm, 30 to 1300 mm in 5-mm increments (when ordered with dimension units code M)

Example of a 50 mm length: 0050

Place #

Mounting style Ref.

page

H T Threaded N/A

Place #s 11-12

Process connection Details Ref.

page

H AA 1/2–14 NPT Tapered threads N/A

H AB 3/4–14 NPT Tapered threads N/A

H AC 1–11.5 NPT Tapered threads N/A

H AD 11/2–11.5 NPT Tapered threads N/A

H AE 1/2-in. BSPT Tapered threads N/A

U U

EmersonProcess.com/Rosemount

H AF 3/4-in. BSPT Tapered threads N/A

H AG 1-in. BSPT Tapered threads N/A

H DA M20 x 1.5p Parallel threads N/A

H DB M24 x 1.5p Parallel threads N/A

H DC M27 x 2p Parallel threads N/A

DD M33 x 2p Parallel threads N/A

H DE 1/2-in. BSPF (G1/2) Parallel threads N/A

H DF 3/4-in. BSPF (G3/4) Parallel threads N/A

H DG 1-in. BSPF (G1) Parallel threads N/A

Place #

Stem style Details Image Ref.

page

H 1 Straight Minimum immersion length = 1 in (25mm)

H 2 Tapered Minimum immersion length = 1 in (25mm)

H 3 Stepped Minimum immersion length = 3 in (75mm)

Place #s 14-15

Thermowell material Ref.

page

H SC 316/316L dual rated 54

SD 316/316L dual rated (NORSOK) 54

H SF 304/304L dual rated 54

H CS Carbon steel (A-105) 54

SG 316Ti SST 54

SL 310 SST 54

SM 321 SST 54

AB Alloy B3 54

AC Alloy C-276 54

AD Alloy C-4 (w/ 304/304L SST flange) 54

AE Alloy C-22 (w/ 304/304L SST flange) 54

AF Alloy C-22 (w/ 316/316L SST flange) 54

AG Alloy 20 54

AH Alloy 400 54

AJ Alloy 400 (w/ 304/304L SST flange) 54

Table 1. Rosemount 114C Threaded Ordering Information

H The Standard offering represents the most common options. The starred options (H) should be selected for best delivery lead time.

The Expanded offering is subject to additional delivery lead time.

EmersonProcess.com/Rosemount

AK Alloy 600 54

AL Alloy 600 (w/ 304/304L SST flange) 54

MO Molybdenum 54

CA Chrome-Moly Grade B-11/F-11 Class II 54

CB Chrome-Moly Grade B-22/ F-22 Class III 54

CC Chrome-Moly Grade F-91 54

NK Nickel 200 54

TT Titanium Grade 2 54

DS Super duplex SST Grade F-53 54

DT Super duplex SST Grade F-53 – NORSOK 54

DU Duplex 2205 Grade F51 54

DV Duplex 2205 Grade F51 – NORSOK 54

Place #s 16-18

Head length (H)

Tapered threads Parallel threads

Ref.

page

H xxx xxx.x inches, 1.75 to 11.25 inches in 1/4-in. increments (when ordered with Dimension Units Code E)

Example of a 6.25-in. length where the second decimal is dropped off: 062 (Default head length = 1.75 inch)

H xxx xxxx mm, 40 to 225 mm in 5-mm increments (when ordered with Dimension Units Code M)

Example of a 50 mm length: 050 (Default head length = 45 mm)

Place #

Instrument connection Details Image Ref.

page

H A 1/2–14 NPT

Female threads

H B 1/2–14 NPSM 57

C 3/4–14 NPT 57

D M18 x 1.5p 57

E M20 x 1.5p 57

F M24 x 1.5p 57

G G 1/2-in. (BSPF) 57

H G 3/4-in. (BSPF) 57

J M27 x 2p 57

K M14 x 1.5p 57

Table 1. Rosemount 114C Threaded Ordering Information

H The Standard offering represents the most common options. The starred options (H) should be selected for best delivery lead time.

The Expanded offering is subject to additional delivery lead time.

H H

EmersonProcess.com/Rosemount

Options (include with selected model number)

Sensor/thermowell assemble to options Details Ref.

page

H XT

Hand tight assembly of sensor and thermowell

Ensures sensor is threaded into thermowell but only hand tightened 57

H XW

Process-ready assembly of sensor and thermowell

Ensures sensor is threaded into thermowell and torqued for process-ready installation

Extended product warranty Details Ref.

page

H WR3 3-year limited warranty This warranty option extends manufacturer’s warranty to three or five years for manufacturer related defects

H WR5 5-year limited warranty 58

Wake frequency calculation Details Ref.

page

H R21 Wake frequency calculation Set of calculations to ensure thermowells are safe in certain process conditions

NACE approval Details Ref.

page

H Q35 NACE approval Meets MR0175/ISO 15156 and MR0103 requirements 59

PMI testing Details Ref.

page

Q76 PMI testing Verifies chemical composition of material 59

Material certification Details Ref.

page

H Q8 Material certification Certificate for material conformance and traceability in accordance with EN 10204 type 3.1

Material tests Details Ref.

page

M01 Low temperature Charpy Test Measures the low temperature ductility of the material 60

M02 Ultrasonic material test Examination of steel forgings for flaws and inclusions 60

Surface finish Details Ref.

page

Q16 Certification Certificate showing measured surface finish values 60

R14 Finish < Ra 0.3µm (12µin) Improves surface roughness of thermowell 61

Electropolish Details Ref.

page

R20 Electropolish Improve smoothness and surface quality 61

Hydrostatic pressure test Details Ref.

page

H Q5 External pressure test Verifies structural quality and checks for leaks at thermowell process connection and stem

H Q85 Internal pressure test Verifies internal structural integrity of thermowell 62

Table 1. Rosemount 114C Threaded Ordering Information

H The Standard offering represents the most common options. The starred options (H) should be selected for best delivery lead time.

The Expanded offering is subject to additional delivery lead time.

EmersonProcess.com/Rosemount

Threaded thermowell drawings

Figure 5. Thread Mount Thermowell Drawings (Tapered Thread)(1)

H. Head length

F. Hex size U. Immersion length

J. Thread allowance

N. Instrument connection (1/2-in. NPT)

P. Process connection (3/4-in. NPT)

d. Bore diameter

t. Tip thickness

B. Tip diameter

A. Root diameter

Straight Tapered Stepped

1. Total length = U+H.

H

A t

N

B d

P

U

B B

A

J

F

Table 2. Thread Mount Thermowells (Tapered Thread)(1)

Code

Code T, threaded mounting style

Hex size “F” Root diameter stepped stem

“ As”

Root diameter tapered stem

“ At”

Tip diameter “ Bt”

Tip diameter straight stem “ Bs”

Thread specificationProcess connection “P” Metric units in mm

(code M) English units in inches (code E)

AA 1/2-14 NPT 30 11/8 0.67 (17) 0.67 (17) 0.50 (12.7) 0.67 (17)

NPT per SAE -AS 71051

(reference PS-71)

AB 3/4-14 NPT 30 11/8 0.75 (19) 0.89 (22.5) 0.63 (16) 0.71 (18)

AC 1-11.5 NPT 34 11/4 0.85 (21.5) 1.04 (26.5) 0.71 (18) 0.71 (18)

AD 11/2-11.5 NPT 48 13/4 0.85 (21.5) 1.04 (26.5) 0.71 (18) 0.71 (18)

AE 1/2-in. BSPT 30 11/8 0.67 (17) 0.67 (17) 0.50 (12.7) 0.67 (17)

THD per ISO 7/1

(BS 21)

AF 3/4-in. BSPT 30 11/8 0.75 (19) 0.89 (22.5) 0.63 (16) 0.71 (18)

AG 1-in. BSPT 34 11/4 0.85 (21.5) 1.04 (26.5) 0.71 (18) 0.71 (18)

1. Dimensions are in inches (millimeters).

EmersonProcess.com/Rosemount

Ordering information detail

Dimension units Back to Threaded ordering table

Back to Flanged ordering table

Back to Van Stone ordering table

Back to Welded ordering table

The Rosemount 114C Thermowell has the flexibility to be specified in either inches (E) or millimeters (M).

English units (inches)

If English is selected, all lengths will be in inches.

Metric

If metric is selected, all lengths will be in millimeters.

Immersion length (U) Back to Threaded ordering table

Back to Flanged ordering table

Back to Van Stone ordering table

Back to Welded ordering table

The immersion length normally refers to the length of the thermowell stem beginning underneath the process connection to the tip of the thermowell. This length is typically specified by the process designer but the general rule is at least one-third or one-half the pipe diameter.

Table 16. Minimum Immersion Length by Profile Style

Note Long-length thermowells are those longer than 42 inches (1065 mm) and may be manufactured from two or three pieces of barstock.

Profile Minimum length

Straight 1 in (25mm)

Tapered 1 in (25mm)

Stepped 3 in (75mm)

U

EmersonProcess.com/Rosemount

Stem style Back to Threaded ordering table

Back to Flanged ordering table

Back to Van Stone ordering table

Back to Welded ordering table

Straight style thermowells (1)

Straight style thermowells have the same diameter along the entire immersion length. They present the largest profile to the process medium and have the highest drag force compared to other styles with the same root diameter. Because of the large tip diameter, there is more mass to heat which slows the thermal response of the measurement assembly. The minimum immersion length (U) allowed with this profile is 1 in (25mm).

Tapered style thermowells (2)

Tapered style thermowells have an outside diameter that decreases uniformly from root to tip. For the same root diameter, this design represents a good compromise between straight and stepped thermowells. It’s drag will be less than a straight style, but greater than a stepped style. The response time will be faster than a straight style and slower than a stepped style. The two general forms of a tapered stem are uniform

(tapered from root to tip) and non-uniform (straight portion followed by tapered portion). Because of its profile shape, it is a good compromise for strength between the two other styles. It is the common choice for high velocity flow applications where the flow forces typically are too great to use a stepped well. The tapered design has faster response than the straight style offering an optimal balance of strength and response time factors. The minimum immersion length (U) allowed with this profile is 1 in (25mm).

Stepped style thermowells (3)

Stepped style thermowells have two straight sections with the smaller diameter straight section at the tip. For the same root diameter as a straight profile thermowell, this design has less profile exposure to the flowing process and exhibits less drag force and quicker response time due to the smaller mass at the tip. In general, stepped thermowells will have thinner walls. By the geometry of its design, the stepped well has a higher natural frequency than the other styles with the same root diameter, and is less susceptible to vibration induced failure. Since this design has less material at the tip, its considered the best thermowell for fast time response. The minimum immersion length (U) allowed with this profile is 3 in (75mm).

Thermowell material Back to Threaded ordering table

Back to Flanged ordering table

Back to Van Stone ordering table

Back to Welded ordering table

The material of construction is typically the first consideration in choosing a thermowell for any given application. Three factors affect the choice of material:

1. Chemical compatibility with the process media to which the thermowell will be exposed

2. Temperature limits of the material

3. Compatibility with the process piping material to ensure solid, non-corroding welds and junctions

It is important the thermowell conforms to the design specs of the pipe or vessel it will be inserted into to ensure structural and material compatibility. The original process design most likely included temperature, pressure, and corrosive considerations as well as cleaning procedures, agency approvals required, and conformance with codes or standards. Since an installed thermowell essentially becomes part of the process, these original design considerations also apply to the thermowell and will drive the thermowell material of construction and mounting type selection. International pressure vessel codes are explicit about the types of materials and methods of construction allowed.

EmersonProcess.com/Rosemount

Table 17. Thermowell Materials

Code Thermowell material Flange material Code Thermowell material Flange material

SC

316/316L SST

UNS S31600/S31603

ASTM A479

316/316L SST

UNS S31600/S31603

ASTM A182 or A240

AB

Alloy B3

UNS N10001

ASTM B335

Alloy B3

UNS N10001

ASTM B333

SD

316/316L SST dual rated (NORSOK)(1)

UNS S31600/S31603

ASTM A479 NORSOK M-630 MDS D57

1. Material supplier qualified per NORSOK M-650; material qualified per NORSOK M-630.

316/316L SST dual rated (NORSOK)(1)

UNS S31600/S31603

ASTM A182 NORSOK M-630 MDS D54

AC

Alloy C-276

UNS N10276

ASTM B574

Alloy C-276

UNS N10276

ASTM B462 or B575

SF

304/304L SST

UNS S30400/S30403

ASTM A479

304/304L SST

UNS S30400/S30403

ASTM A182 or A240

AD

Alloy C-4

UNS N06455

ASTM B574

304/304L SST

UNS S30400/S30403

ASTM A182 or A240

SG

316T i SST

UNS S31635

ASTM A479

316T i SST

UNS S31635

ASTM A182

AE

Alloy C-22

UNS N06022

ASTM B574

304/304L SST

UNS S30400/S30403

ASTM A182 or A240

SH

316/316L SST w/ Tantalum sheath(2)

UNS S31600/S31603

ASTM A479

2. Sheath thickness = 0.01-in. (0.38 mm).

316/316L SST w/ Tantalum sheath

UNS S31600/S31603

ASTM A182 or A240

AF

Alloy C-22

UNS N06022

ASTM B574

316/316L SST

UNS S31600/S31603

ASTM A182 or A240

Tantalum sheath UNS R05252 AG Alloy 20

UNS N08020

ASTM B473

Alloy 20

UNS N08020

ASTM B462 or B463

SJ

316/316L SST w / PFA coating

UNS S31600/S31603

ASTM A479

316/ 316L SST w / PFA coating

UNS S31600/S31603

ASTM A182 or A240

AH

Alloy 400

UNS N04400

ASTM B164

Alloy 400

UNS N04400

ASTM B564 or B127

SK

304/304L SST w/ PTFE coating

UNS S30400/S30403

ASTM A479

304/304L SST w/ PTFE coating

UNS S30400/S30403

ASTM A182 or A240

AJ

Alloy 400

UNS N04400

ASTM B164

304/304L SST

UNS S30400/S30403

ASTM A182 or A240

SL

310 SST

UNS S31008

ASTM A479

310 SST

UNS S31008

ASTM A182 or A240

AK

Alloy 600

UNS N06600

ASTM B166

Alloy 600

UNS N06600

ASTM B564 or B168

SM

321 SST

UNS S32100

ASTM A479

321 SST

UNS S32100

ASTM A182 or A240

AL

Alloy 600

UNS N06600

ASTM B166

304/304L SST

UNS S30400/S30403

ASTM A182 or A240

CS

Carbon steel

UNS K03504

ASTM A105

Carbon steel

UNS K03504

ASTM A105, A216 GR WCB, or A515 GR

MD

Molybdenum

UNS R03600

ASTM B387

Molybdenum

UNS R03630

ASTM A204 or B386

TT

Titanium grade 2

UNS R50400

ASTM B348 GR 2

Titanium grade 2

UNS R50400

ASTM B381 GR 2

CA

Chrome-Moly Grade B-11

UNS K11797

ASTM A739 GR B-11

Chrome-Moly Grade F-11

UNS K11572

ASTM A182 GR F-11 CL2 or A387

GR11 CL2

DS

Super duplex

UNS 32750

ASTM A479 GR F53

Super duplex

UNS 32750

ASTM A182 GR F53 or A240

CB

Chrome-Moly Grade B-22

UNS K21390

ASTM A739 GR B-22

Chrome-Moly Grade F-22

UNS K21590

ASTM A182 GR F-22 CL3, A217 GR

WC9, or A387 GR22 CL2

DU

Duplex 2205

UNS 31803

ASTM A479 GR F51

Duplex 2205

UNS 31803

ASTM A182 GR F51or A240

DT

Super duplex (NORSOK)(1)

UNS 32750

ASTM A479 GR F53 NORSOK

M-630 MDS D57

Duplex 2205 (NORSOK)(1)

UNS 31803

ASTM A182 GR F53 NORSOK M-630

MDS D54

CC

Chrome-Moly Grade F-91

UNS K90901

ASTM A182

Chrome-Moly Grade F-91

UNS K90901

ASTM A182 GR F-9, A217 GR C12A, or

A387 GR 91 CL2

DV

Duplex 2205 (NORSOK)(1)

UNS 31803

ASTM A479 GR F51 NORSOK

M-630 MDS D47

Duplex 2205 (NORSOK)(1)

UNS 31803

ASTM A182 GR F51 NORSOK M-630

MDS D44

NK

Nickel 200

UNS N02200

ASTM B160

Nickel 200

UNS N02200

ASTM B162 or B564

EmersonProcess.com/Rosemount

Head length (H) Back to Threaded ordering table

Back to Flanged ordering table

Back to Van Stone ordering table

Back to Welded ordering table

Head length is the distance from the bottom of the process connection to the top of the thermowell. Each style has a minimum head length; the length specified must meet or exceed that minimum. It is shown below for all process connection styles.

Note The industry standard minimum head length for flanged and Van Stone thermowells with connections under Class 900 (ASME B16.5) or PN 100 (EN 1092-1) is 2.25 inches (60 mm).

Table 18. Recommended Minimum Head Length(1)

1. Dimensions are in inches (millimeters).

Process connection Minimum head length (H)

Threaded

1.75 (45)

Welded

H

Table 19. Recommended Minimum Head Length by…

This is the start of the file's text. The full file is on GovTribe.