Addendum 003 - Analytical Instrumentation - Level Instrumentation R1.pdf

PDF 5 MB Posted

Attached to
Request for Proposal - Construction Services for Project L-897, Central Plateau Water Treatment Facility
Solicitation number
338214
Issued by

View the file

Other files

File Type Posted
Addendum 003 - O and M Manual - Prelim Oper and Maint Manual - Template R0.pdf PDF
Addendum 003 - Equipment - Automatic Strainers R0.pdf PDF
Addendum 003 - Valves - Other Check Valves R0.pdf PDF
Addendum 003 - Recommended Electrical Spare Parts List R0.pdf PDF
Addendum 003 - Equipment - Tab 3 - Anchor Bolt List R0.pdf PDF
Addendum 003 - Valves - Butterfly Valves R0.pdf PDF
Addendum 003 - Electrical Drawings - REMOTE IO 24VDC POWER PANEL.pdf PDF
Addendum 003 - Valves - Air Release Valves R0.pdf PDF
Addendum 003 - Analytical Instrumentation Valve List R0.pdf PDF
Addendum 003 - Valves - Auto Drain Valve R0.pdf PDF
Addendum 003 - Equipment - Commissioning Plan R0.pdf PDF
Addendum 003 - Valves - Diaphragm Valves R0.pdf PDF
Addendum 003 - VDL 006-006 RFP Const Bidder Pall Documents.xlsx XLSX spreadsheet
Addendum 003 - Valves - Other Solenoid Valves R0.pdf PDF
Addendum 003 - Electrical Drawings - FEED STRAINER PLC IO PANEL.pdf PDF
Addendum 003 - Valves - Other Air Pressure Valves R0.pdf PDF
Addendum 003 - Analytical Instrumentation - Flow Instrumentation R1.pdf PDF
Addendum 003 - Valves - Solenoid Valves R0.pdf PDF
Addendum 003 - Equipment - Actuator Torque Tables R1.pdf PDF
Addendum 003 - Equipment - Filter Elements R0.pdf PDF
Addendum 003 - Valves - Dual Disc Check Valves R0.pdf PDF
Addendum 003 - Equipment - FRP Tanks R0.pdf PDF
Addendum 003 - Equipment - Equipment List R0 - Pall Comments.pdf PDF
Addendum 003 - O and M Manual - System Functional Description (SFD) R0.pdf PDF
Addendum 003 - Electrical Drawings - MAIN CONTROL PANEL.pdf PDF
Addendum 003 - Electrical Drawings - MF VALVE RACK PANEL.pdf PDF
Addendum 003 - Electrical Drawings - Main CP 24VDC Power Panel.pdf PDF
Addendum 003 - Valves - Air Pressure Control Valves R0.pdf PDF
Addendum 003 - Equipment - FRP Tanks attachment.pdf PDF
Addendum 003 - Contractual Electrical Spare Parts List R0.pdf PDF
Addendum 003 - Equipment - Air System R1.pdf PDF
Addendum 003 - Analytical Instrumentation - Temperature Instrumentation R1.pdf PDF
Addendum 003 - Valves - Ball Valves R0.pdf PDF
Addendum 003 - Valves - Chemical Pressure Control Valves R0.pdf PDF
Addendum 003 - Major Electrical Comp R0.pdf PDF
Addendum 003 - Electrical Drawings - CIP CAUSTIC ROOM PLC IO PANEL.pdf PDF
Addendum 003 - Exceptions and Clarifications - Specification Cross Reference Matrix R0.pdf PDF
Addendum 003 - Equipment - Calibration Columns R0.pdf PDF
Addendum 003 - Equipment - Centrifugal Pumps R0.pdf PDF
Addendum 003 - Equipment - Indeeco Heater General Infor R0.pdf PDF
Addendum 003 - Mechanical Drawings - Membrane Train Assy Dwg R3.pdf PDF
Addendum 003.pdf PDF
Addendum 003 - Equipment - Wilden Pump General Information R0.pdf PDF
Addendum 003 - Equipment - Water Softener R0.pdf PDF
Addendum 003 - Electrical Drawings - Interconnect Diagram Pall Comments.pdf PDF
Addendum 003 - Analytical Instrumentation - Pressure Instrumentation R1.pdf PDF
Addendum 003 - Mechanical Drawings - P and ID R4 Pall Submittal Return Comments.pdf PDF
Addendum 003 - Valves - Water Pressure Control Valves R0.pdf PDF
Addendum 003 - Equipment - Other Strainers R0.pdf PDF
Addendum 003 - Equipment - NSF PID Scope R0.pdf PDF
Show 40 more

Latest 50 of 88 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

COVER PAGE OF SELLER’S SUBMITTAL

City Name: Hanford, WA - MSA

Pall Project No.: 01.000287

Job Number: Project L-897, Subcontract 70816

Task Register 6 (Task 1 – VI Submittal Package)

To: (Contractor)

Mission Support Alliance, LLC (MSA)

PO Box 650

Richland, WA 99352

From: (Subcontractor)

Pall Water

A Division of Pall Corporation

839 State Route 13

Cortland, NY 13045

Patty Willis

Phone: 607-758-1699

Name of Project: Hanford, WA, Central Plateau WTF

Pall Document Number: NYCS000015264 Rev: 01

Description of Item: Level Instrumentation

Specification Section: 40 73 02

Deviations: See document NYCS000015383

Cover Page Information Revision History and Approvals

Tab 1 - NYCS000015449,CSS,Level Instrumentation,01.287 R01

INDEX:

Page 1:

Page 2:

Page 3:

Pages 4-7: Tab 2 - Drexelbrook Level Switch Cut Sheet R00

Pages 8-38: Tab 3 - Rosemount 3051T Hydrostatic Level Transmitter Cut Sheet R00

Date: 12/19/2019

PALL ADVANCED SEPARATIONS SYSTEMS

DIVISION OF PALL CORPORATION, CORTLAND, NY

Rev Name Date Created By

Approved By

Created By

Approved By

Created By

Approved By

Created By

Approved By

Revision Description

Title

Document # Revision griffinju Text Box These commodities, technology, or software may only be exported from the United States in accordance with the Export Administration Regulations. Diversion contrary to U.S. law is prohibited.

Doc Number: NYCS000015449R01 Doc Title: NYCS000015449,CSS,Level Instrumentation,01.287 R01.docx

Components Specification Sections

The following specification sections are relevant to the approval of submittal NYCS000015264, Level Instrumentation,01.287:

L‐897, Attachment No. 2 ‐ HNF‐SPEC‐63538, Section 40 73 02, Process Instrumentation Meters and Transmitters.

Any exceptions and clarifications to the specification section above can be found in submittal NYCS000015383, L‐897, Section 40 73 02, Es and Cs,01.287.

Pall has taken exceptions and clarifications relevant to the flow instrumentation proposed.

PALL CORPORATION

Membrane Filtration (MF) System

LEVEL INSTRUMENTATION CUT SHEET

Ultra-Sonic Gap Level Switches

12-Inch 316SS Probe, SPDT Relay, 24VDC Power:

Drexelbrook P/N: 705-0001-001-BA0304.8 & 5041100001S000900

Part Number Key:

705-0001-0001 Drexelbrook Veri-Gap Ultra-Sonic Gap Level Sensor

B 316/316L SST Wetted Parts A0 3/4" NPT Process Connection

304.8 12" (304.8mm) Switch Point

5041 Drexelbrook Veri-Gap 504-1000 Series Switch 1 24VDC Power / DPDT Relay Output 0 Integral Electronics 0 Default Always "0" 0 Default Always "0"

01 For Use With PN 705-0001-001 316SS Sensor S Single Point Electronics 0 No Time Delay 0 No Approvals 0 No Verification Circuit 9 NEMA 4X Explosion-Proof Integral Housing 0 Standard Relay 0 High Level Fail Safe (Field Configurable)

Note: Veri-Gap Sensor & Level Switch are Factory Assembled and delivered as a single instrument.

Ultra-Sonic Gap Level Switches

12-Inch Hastalloy Probe, SPDT Relay, 24VDC Power:

Drexelbrook P/N: 705-0001-001-BA0304.8 & 5041100001S000900

705-0001-0001 Drexelbrook Veri-Gap Ultra-Sonic Gap Level Sensor

C Hastalloy-C Wetted Parts A0 3/4" NPT Process Connection

304.8 12" (304.8mm) Switch Point

5041 Drexelbrook Veri-Gap 504-1000 Series Switch 1 24VDC Power / DPDT Relay Output 0 Integral Electronics 0 Default Always "0" 0 Default Always "0"

05 For Use With PN 705-0001-051 Hastalloy Sensor S Single Point Electronics 0 No Time Delay 0 No Approvals 0 No Verification Circuit 9 NEMA 4X Explosion-Proof Integral Housing 0 Standard Relay 0 High Level Fail Safe (Field Configurable)

Note: Veri-Gap Sensor & Level Switch are Factory Assembled and delivered as a single instrument.

Guaranteed Safety Verify™ circuitry checks that the complete system (crystals, crystal bonding, electronics and relay) is functioning correctly.

No Calibration Required No opportunity for error in calibration or adjustments in gain controls.

Local Control This line-powered version of the 504 Series gap switch has its 5A DPDT relay where you need it...built into the unit and close to pumps, valves, horns and other final control elements.

Wide Range of Applications Performance is unaffected by changes in liquid density, pressure, or electrical properties.

Major Breakthrough The VeriGAP level switch is the only safe gap switch available for high level alarming or indication. All other gap switches are inherently low level fail safe only. With most low-level fail-safe devices, either an absence of material or a component failure will indicate a low level alarm. With most high level fail-safe devices, the presence of material will only trigger an alarm if the system is functioning properly. A component failure, such as separation of the crystals, will cause the device to indicate an absence of material. This will result in a normal condition, even if the tank is over filling.

Outperforms Generic Gap Switches VeriGAP overcomes the problems inherent in genric gap switches by testing the entire system (crystals, crystal bonding,electronics and relay) on demand, eliminating the possibility of a spill.

Unlike other gap switches with so-called self-testing features, the VeriGAP requires no calibration. This eliminates the potential for error or spills during installation and setup.

Ideal for Liquid Measurement The VeriGAP is ideal for high and low point level measurements in liquids. It is not affected by variations in viscosity, density, pressure, temperature, or electrical properties.

VeriGAP™ 504-1000 Series Line Powered Ultrasonic Gap Switch

DREXELBROOK®

DATA SHEET

www.Drexelbrook.com6

Electronics Model # 404-1000-9

Input Power:

120Vac +/- 20% (240Vac or 24Vdc +/-6V opt.)

Level Output:

DPDT relay

Contact Ratings:

120Vac: 6A resistive, 4.4A inductive, 1/6HP 240Vac: 6A resistive, 4.9A inductive, 1/3HP 30Vdc: 6A resistive Min. Rating 100mA / 12VDC

Max. Cont. Carrying Current 7A

Operating Temperature*:

-40ºF to 160ºF (-40ºC to 70ºC)

Fail-Safe:

High or low level (field-selectable)

Repeatability:

1/16 inch (1.59 mm)

Response Time:

2 seconds

Housing:

Nema 1-4X, 5 and 12

Dimensions in inches (mm).

Mounting Dimensions

Area Classifications:

Groups A,B,C,D, Class I, Div. 1 or 2. Groups E,F,G, Class II, Div. 1 or 2

RFI Effect:

No effect on operating point from a 5 watt field @ 27, 150, or 450 MHz

Sensor Model # 705-1-1

Material:

316 SS

Mounting:

3/4 inch NPT

Process Temperature:

Standard: -40ºF to 250ºF (-40ºC to 121ºC) Optional: -40ºF to 350ºF (-40ºC to 177ºC)

Process Pressure:

1000 psi (69 BAR)

Operating Point:

3/8 inch (9.523 mm) from tip

Approvals:

EDO#3-28-03-251

Specifications www.Drexelbrook.com

Phone: +1 215-674-1234 • Fax: +1 215-674-2731

E-mail: drexelbrook.info@ametek.com

205 Keith Valley Road | Horsham PA 19044 U.S.A.

VeriGAP™ 504-1000 Series

HomR Rectangle

HomR Rectangle

HomR Line

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Rectangle

(Hydrostatic) Level Transmitters

0 – 30 PSI Range, 316L-SS Wetted Parts:

Rosemount P/N: 3051T G 1 A 2B 2 1 A C6 Q4 M5

3051T Model: In-Line Pressure Transmitter G TYPE: Gauge Pressure 1 RANGE: -14.7 to 30 PSI (831 Inch WC) A TRANSMITTER OUTPUT: 4-20mA with digital based HART

2B PROCESS CONNECTION: ½”-14 FNPT

2 ISO. DIAPHRAGM & PROCESS CONNECTION: 316L-SS

1 SENSOR FILL: Silicone A HOUSING MATERIAL & CONDUIT ENTRY: Aluminum, ½”-14 NPT

C6 PRODUCT CERTS: CSA Explosion-Proof, Dust, Ignition-Proof, I.S. and Division 2 Q4 CALIBRATION CERT: Factory Calibration Certification M5 DISPLAY OPTION: LCD Display Only

0 – 30 PSI Range, Hastalloy Wetted Parts:

Rosemount P/N: 3051T G 1 A 2B 3 1 A C6 Q4 M5

3051T Model: In-Line Pressure Transmitter G TYPE: Gauge Pressure 1 RANGE: -14.7 to 30 PSI (831 Inch WC) A TRANSMITTER OUTPUT: 4-20mA with digital based HART

2B PROCESS CONNECTION: ½”-14 FNPT

3 ISO. DIAPHRAGM & PROCESS CONNECTION: Hastalloy C-276 1 SENSOR FILL: Silicone A HOUSING MATERIAL & CONDUIT ENTRY: Aluminum, ½”-14 NPT

C6 PRODUCT CERTS: CSA Explosion-Proof, Dust, Ignition-Proof, I.S. and Division 2 Q4 CALIBRATION CERT: Factory Calibration Certification M5 DISPLAY OPTION: LCD Display Only

Product Data Sheet 00813-0100-4001, Rev TE

July 2019

Rosemount™ 3051 Pressure Transmitter

With the Rosemount 3051 Pressure Transmitter, you'll gain more control over your plant. You'll be able to reduce product variation and complexity as well as your total cost of ownership by leveraging one device across a number of pressure, level, and flow applications. You'll have access to information you can use to diagnose, correct, and even prevent issues. And with unparalleled reliability and experience, the Rosemount 3051 is the industry standard that will help you perform at higher levels of efficiency and safety so you can remain globally competitive.

HomR Text Box

316L-SS: ROSEMOUNT P/N: 3051TG1A2B21AC6Q4M5

Hastalloy: ROSEMOUNT P/N: 3051TG1A2B31AC6Q4M5

Setting the standard for pressure measurement

Proven best-in-class performance, reliability, and safety

■ More than seven million installed

■ Reference accuracy 0.04 percent of span

■ Installed total performance of 0.14 percent of span

■ 10-year stability of 0.2 percent of URL

■ SIL2/3 certified (IEC 61508)

Maximize installation and application flexibility with the coplanar platform

■ Improve reliability and performance with integrated DP Flow meters, DP Level solutions, and integral manifolds.

■ Easy installation with all solutions fully assembled, leak-tested, and calibrated.

■ Meet your application needs with an unsurpassed offering.

Contents Setting the standard for pressure measurement

Rosemount

3051C Coplanar

Pressure Transmitter

Rosemount

3051T In-Line Pressure Transmitter

Rosemount

3051CF Flow meter selection guide

Rosemount

3051CFA Annubar Flow Meter

Rosemount

3051CFC Compact Flow Meter

Rosemount

3051CFP Integral Orifice Flow Meter

Rosemount

3051L Level Transmitter

Specifications

Rosemount

3051 product certifications

Rosemount 3051 Wireless product certifications

Dimensional drawings

Options

July 2019

2 Rosemount 3051

Advanced functionality

Loop Integrity diagnostics

■ Detect on-scale failures caused by electrical loop issues before they impact your process operation.

■ This capability is safety certified for your most critical applications.

Local operator interface (LOI)

■ Straightforward menus and built-in configuration buttons allow you commission the device in less than a minute.

■ Configure in hazardous-area locations without removing the transmitter cover using external buttons.

Industry Leading Capabilities Extended to IEC 62591 (WirelessHART®)

■ Cost effectively implement wireless on the industry's most proven platform.

■ Optimize safety with the industry's only intrinsically safe power module.

■ Eliminate wiring design and construction complexities to lower costs by 40 to 60 percent.

■ Quickly deploy new pressure, level, and flow measurements in 70 percent less time.

Innovative, integrated DP flow meters

■ Fully assembled, configured, and leak tested for out-of-the-box installation.

■ Reduce straight pipe requirements, lower permanent pressure loss, and achieve accurate measurement in small line sizes.

■ Up to 1.65 percent volumetric flow accuracy at 8:1 turndown.

July 2019

Product Data Sheet 3

Proven, reliable, and innovative DP Level technologies

■ Connect to virtually any process with a comprehensive offering of process connections, fill fluids, direct mount, or capillary connections and materials.

■ Quantify and optimize total system performance with QZ option.

■ Operate at higher temperature and in vacuum applications.

■ Optimize level measurement with cost efficient Rosemount™ Tuned-System™ assemblies.

Instrument manifolds – quality, convenient, and easy

■ Designed and engineered for optimal performance with

Rosemount transmitters.

■ Save installation time and money with factory assembly.

■ Offers a variety of styles, materials, and configurations.

July 2019

4 Rosemount 3051

Rosemount™ 3051T In-Line Pressure Transmitter

Rosemount 3051T In-Line Pressure Transmitters are the industry standard for gage and absolute pressure measurement. The in-line, compact design allows the transmitter to be connected directly to a process for quick, easy and cost effective installation. Capabilities include:

■ The Loop Integrity Diagnostic continuously monitors the electrical loop to detect changes that compromise the integrity of the transmitted 4-20 mA output signal (Option Code DA0).

■ LOI with straightforward menus and built-in configuration buttons (option code M4).

■ Safety certification (option code QT).

See Specifications and options for more details on each configuration. Specification and selection of product materials, options, or components must be made by the purchaser of the equipment. See Material selection for more information on material selection.

Table 2: Rosemount 3051T In-Line Pressure Transmitter Ordering Information

The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.

Model Transmitter type

3051T In-line pressure transmitter

Pressure type

G Gage ★

A(1) Absolute ★

Pressure range

Gage (Rosemount 3051TG)(2) Absolute (Rosemount 3051TA)

1 –14.7 to 30 psi (–1,01 to 2,06 bar) 0 to 30 psia (0 to 2,06 bar) ★

2 –14.7 to 150 psi (–1,01 to 10,34 bar) 0 to 150 psia (0 to 10,34 bar) ★

3 –14.7 to 800 psi (–1,01 to 55,15 bar) 0 to 800 psia (0 to 55,15 bar) ★

4 –14.7 to 4000 psi (–1,01 to 275,79 bar) 0 to 4000 psia (0 to 275,79 bar) ★

5 –14.7 to 10000 psi (–1,01 to 689,47 bar) 0 to 10000 psia (0 to 689,47 bar) ★

6(3) –14.7 to 20000 psi (–1,01 to 1378,95 bar) 0 to 20000 psia (0 to 1378,95 bar)

Transmitter output

A(4) 4–20 mA with digital signal based on HART® Protocol ★

F FOUNDATION™ Fieldbus Protocol ★

W(5) PROFIBUS® PA Protocol ★

July 2019

Product Data Sheet 13 https://www.emerson.com/catalog/ConfiguratorDisplayView?redirectURL=https%3A%2F%2Fwww.emerson.com%2Fen-us%2Fcatalog%2Frosemount-sku-3051-in-line-pressure-transmitter&catalogId=20051&qty=1&productId=726914&storeId=20151&utm_source=rmt_us-tech_doc-pds&utm_medium=pdfe&utm_content=3051_ilpt_cfg&utm_campaign=19grmtp-305181 https://www.emerson.com/en-us/catalog/rosemount-sku-3051-in-line-pressure-transmitter?utm_source=rmt_us-tech_doc-pds&utm_medium=pdfe&utm_content=3051_ilpt&utm_campaign=19grmtp-305187 HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Text Box

316L-SS: ROSEMOUNT P/N: 3051TG1A2B21AC6Q4M5

Hastalloy: ROSEMOUNT P/N: 3051TG1A2B31AC6Q4M5

HomR Line

Line

Table 2: Rosemount 3051T In-Line Pressure Transmitter Ordering Information (continued)

X(6) Wireless (requires wireless options and engineered polymer housing) ★

M(7) Low-power 1–5 Vdc with digital signal based on HART Protocol

Process connection style

2B ½–14 NPT female (range 1–5 only) ★

2C(8) G½ A EN837-1 male (range 1–4 only) ★

2F(9) Coned and threaded, compatible with autoclave Type F-250-C (range 5–6 only)

61(10)(11) Non-threaded Instrument flange (range 1–4 only)

Isolating diaphragm(12) Process connection wetted parts material

2 316L SST 316L SST ★

3 Alloy C-276 Alloy C-276 ★

7 Gold-plated 316 SST 316L SST

Sensor fill fluid

1 Silicone ★

2(10) Inert ★

Housing material Conduit entry size

A Aluminum ½–14 NPT ★

B Aluminum M20 x 1.5 ★

E Aluminum, ultra low copper ½–14 NPT

F Aluminum, ultra low copper M20 x 1.5

J SST ½–14 NPT ★

K SST M20 x 1.5 ★

P(13) Engineered polymer No conduit entries ★

D(14) Aluminum G½

M(14) SST G½

Wireless options (requires wireless output code X and engineered polymer housing code P)

Wireless transmit rate, operating frequency, and protocol

WA3 User configurable transmit rate, 2.4GHz WirelessHART ★

Antenna and SmartPower

WP5 Internal antenna, compatible with Green Power Module (I.S. Power Module sold separately) ★

Options (include with selected model number)

Extended product warranty

WR3 3-year limited warranty ★

WR5 5-year limited warranty ★

Plantweb™ control functionality

A01 FOUNDATION Fieldbus control function block suite ★

July 2019

14 Rosemount 3051

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Rectangle

HomR Text Box

316L-SS: ROSEMOUNT P/N: 3051TG1A2B21AC6Q4M5

Hastalloy: ROSEMOUNT P/N: 3051TG1A2B31AC6Q4M5

HomR Rectangle

HomR Line

Plantweb diagnostic functionality

DA0 Loop Integrity HART diagnostic ★

D01 FOUNDATION Fieldbus diagnostics suite ★

Integral assembly(15)

S5 Assemble to Rosemount 306 integral manifold ★

Diaphragm seal assemblies(15)

S1 Assemble to one Rosemount 1199 seal ★

Mounting bracket(16)

B4 Bracket for 2-in. pipe or panel mounting, all SST ★

Product certifications

E8 ATEX Flameproof and Dust Certification ★

I1(17) ATEX Intrinsic Safety and Dust ★

IA ATEX Intrinsic Safety for FISCO; for FOUNDATION Fieldbus or PROFIBUS PA Protocols only ★

N1 ATEX Type n Certification and Dust ★

K8 ATEX Flame-proof, Intrinsic Safety, Type n, Dust (combination of E8, I1 and N1) ★

E4(18) TIIS Flameproof ★

E5 FM Explosion-proof, Dust Ignition-proof ★

I5(19) FM Intrinsically Safe, Nonincendive ★

IE FM FISCO Intrinsically Safe; for FOUNDATION Fieldbus or PROFIBUS PA Protocols only ★

K5 FM Explosion-proof, Dust Ignition-proof, Intrinsically Safe, and Division 2 ★

C6 CSA Explosion-proof, Dust Ignition-proof, Intrinsically Safe, and Division 2 ★

E6 CSA Explosion-proof, Dust Ignition-proof, Division 2 ★

I6(13) CSA Intrinsic Safety ★

K6 CSA and ATEX Explosion-proof, Intrinsically Safe, and Division 2 (combination of C6, E8, and I1) ★

E7 IECEx Flameproof, Dust Ignition-proof ★

I7 IECEx Intrinsic Safety ★

N7 IECEx Type n Certification ★

K7 IECEx Flameproof, Dust Ignition-proof, Intrinsic Safety, and Type n (combination of I7, N7, and E7) ★

E2 INMETRO Flameproof ★

I2 INMETRO Intrinsic Safety ★

IB INMETRO FISCO intrinsically safe; for FOUNDATION Fieldbus or PROFIBUS PA Protocols only ★

K2 INMETRO Flameproof, Intrinsic Safety ★

E3 China Flameproof ★

I3 China Intrinsic Safety ★

N3 China Type n ★

EM Technical Regulations Customs Union (EAC) Flameproof ★

July 2019

Product Data Sheet 15

HomR Rectangle

HomR Text Box

316L-SS: ROSEMOUNT P/N: 3051TG1A2B21AC6Q4M5

Hastalloy: ROSEMOUNT P/N: 3051TG1A2B31AC6Q4M5

HomR Line

IM Technical Regulations Customs Union (EAC) Intrinsic Safety ★

KM Technical Regulations Customs Union (EAC) Flameproof and Intrinsic Safety ★

KB FM and CSA Explosion-proof, Dust Ignition-proof, Intrinsically Safe, and Division 2 (combination of K5 and C6) ★

KD FM, CSA, and ATEX Explosion-proof, Intrinsically Safe (combination of K5, C6, I1, and E8) ★

EP(20) Republic of Korea Flameproof

IP(21) Republic of Korea Intrinsic Safety

KP(22) Republic of Korea Flameproof, Intrinsic Safety

Drinking water approval(23)

DW NSF drinking water approval ★

Shipboard approvals(10)

SBS American Bureau of Shipping ★

SBV(24) Bureau Veritas (BV) ★

SDN Det Norske Veritas ★

SLL(24) Lloyds Register (LR) ★

Custody transfer

C5 Measurement Canada Accuracy Approval (limited availability depending on transmitter type and range.

Contact an Emerson representative.)

Calibration certification

Q4 Calibration certificate ★

QG Calibration certificate and GOST verification certificate ★

QP Calibration certification and tamper evident seal ★

Material traceability certification

Q8 Material traceability certification per EN 10204 3.1 ★

Quality certification for safety(25)

QS Prior-use certificate of FMEDA Data ★

QT Safety certified to IEC 61508 with certificate of FMEDA ★

Configuration buttons

D4(25) Analog zero and span ★

DZ(26) Digital zero trim ★

Display and interface options

M4(27) LCD display with LOI ★

M5 LCD display ★

Wireless stainless steel sensor module(13)

WSM Wireless SST sensor module ★

Conduit plug(10)(28)

DO 316 SST conduit plug ★

July 2019

16 Rosemount 3051

HomR Rectangle

HomR Rectangle

HomR Text Box

316L-SS: ROSEMOUNT P/N: 3051TG1A2B21AC6Q4M5

Hastalloy: ROSEMOUNT P/N: 3051TG1A2B31AC6Q4M5

HomR Line

Transient terminal block(10)(29)

T1 Transient protection terminal block ★

Software configuration(26)

C1 Custom Software Configuration (For wired, see the Rosemount 3051 Configuration Data Sheet. For wireless, see the Rosemount 3051 Wireless Configuration Data Sheet.)

Low power output

C2 0.8–3.2 Vdc output with digital signal based on HART Protocol (available with output code M only)

Alarm levels(25)

C4(30) Analog output levels compliant with NAMUR recommendation NE 43, alarm high ★

CN(30) Analog output levels compliant with NAMUR recommendation NE 43, low alarm ★

CR Custom alarm and saturation signal levels, high alarm (requires C1 and Rosemount 3051 Configuration Data Sheet)

CS Custom alarm and saturation signal levels, low alarm (requires C1 and Rosemount 3051 Configuration Data Sheet)

CT Rosemount standard low alarm ★

Pressure testing

P1 Hydrostatic testing with certificate

Cleaning process area(31)

P2 Cleaning for special service

P3 Cleaning for <1 ppm chlorine/fluorine

Ground screw(10)(32)

V5 External ground screw assembly ★

Surface finish

Q16 Surface finish certification for sanitary remote seals ★

Toolkit total system performance reports

QZ Remote seal system performance calculation report ★

Conduit electrical connector(10)

GE M12, 4-pin, male connector (eurofast) ★

GM A size mini, 4-pin, male connector (minifast) ★

NACE certificate(33)

Q15 Certificate of Compliance to NACE MR0175/ISO15156 for wetted materials ★

Q25 Certificate of Compliance to NACE MR0103 for wetted materials ★

Cold temperature(34)

BR5(35) –58 °F (–50 °C) cold temperature ★

BR6(36) –76 °F (–60 °C) cold temperature ★

HART Revision configuration (requires HART output code A)(4)

HR5 Configured for HART Revision 5 ★

July 2019

Product Data Sheet 17 https://www.emerson.com/documents/automation/configuration-data-sheet-rosemount-3051-en-89456.pdf https://www.emerson.com/documents/automation/configuration-data-sheet-rosemount-3051-wireless-series-en-89758.pdf http://www2.emersonprocess.com/siteadmincenter/PM%20Rosemount%20Documents/00806-0100-4007.pdf http://www2.emersonprocess.com/siteadmincenter/PM%20Rosemount%20Documents/00806-0100-4007.pdf http://www2.emersonprocess.com/siteadmincenter/PM%20Rosemount%20Documents/00806-0100-4007.pdf http://www2.emersonprocess.com/siteadmincenter/PM%20Rosemount%20Documents/00806-0100-4007.pdf HomR Text Box

316L-SS: ROSEMOUNT P/N: 3051TG1A2B21AC6Q4M5

Hastalloy: ROSEMOUNT P/N: 3051TG1A2B31AC6Q4M5

HR7 Configured for HART Revision 7 ★

Typical model number: 3051T G 5 F 2A 2 1 A B4

(1) Wireless output (code X) only available in absolute measurement type (code A) in range 1–5 with ½–14 NPT process connection (code 2B), and polymer housing (code P). Wireless output and range 6 is only available with coned and threaded process connection (code 2F) and polymer housing.

(2) Rosemount 3051TG lower range limit assumes atmospheric pressure of 14.7 psig.

(3) Not available with PROFIBUS PA or Low Power 1–5 Vdc transmitter output (option code W or M), inert sensor fill fluid (option code 2), NSW drinking water approval (option code DW), or assemble to manifolds (option code S5).

(4) Option HR5 configures the HART output to HART Revision 5. Option HR7 configures the HART output to HART Revision 7. The device can be field configured to HART Revision 5 or 7 if desired. HART Revision 5 is the default HART output.

(5) For local addressing and configuration, M4 (LOI) is required.

(6) Available approvals are FM Intrinsically Safe, (option code I5), CSA Intrinsically Safe (option code I6), ATEX Intrinsic Safety (option code I1), IECEx

Intrinsic Safety (option code I7), and EAC Intrinsic Safety (option code IM).

(7) Only available with C6, E2, E5, I5, K5, KB, and E8 product certifications. Not available with GE, GM, SBS, DA0, M4, D4, DZ, QT, HR5, HR7, CR, CS, CT.

(8) Wireless output (code X), not available with Absolute pressure type or C-276 diaphragm. Not available with S1, S5, or WSM. Only available in G½

A EN837-1 male process connection (code 2C) with range 1–4, 316 SST isolating diaphragm (code 2), silicone fill fluid (code 1), and housing (code P).

(9) Not available with wireless output for range 5.

(10) Not available with wireless output.

(11) Only available with 316L SST isolating diaphragm.

(12) Materials of construction comply with recommendations per NACE MR0175/ISO 15156 for sour oil field production environments. Environmental limits apply to certain materials. Consult latest standard for details. Selected materials also conform to NACE MR0103 for sour refining environments.

(13) Only available with wireless output. Not available with Absolute pressure type, range 1-4.

(14) Transmitter conduit entry will be ½ NPT and a ½ NPT to G½ thread adapter will be provided. Not available with Product certifications options E8, K8, E5, K5, C6, K6, E7, K7, E2, K2, E3, KB, and KD.

(15) “Assemble-to” items are specified separately and require a completed model number.

(16) Panel mounting bolts are not supplied.

(17) Dust approval not applicable to output code X. See C5 Custody Transfer - Measurement Canada Accuracy Approval for wireless approvals.

(18) Only available with output codes A - 4–20mA HART, F - FOUNDATION Fieldbus, and W - PROFIBUS PA. Also only available with G1/2 housing thread types.

(19) Nonincendive certification not provided with wireless output option code (X).

(20) Only available with HART 4-20 mA output (code A), FOUNDATION Fieldbus output (code F), and Low Power output (code M). Available with process connection codes 2A, 2B, 2C, 2F, and 61. Available with housing material codes A, B, E, F, J, and K. Not available with codes DZ, V5, GE, GM, or BR6.

(21) Only available with HART 4-20 mA output (code A), FOUNDATION Fieldbus output (code F), Wireless output (code X), and PROFIBUS-PA output (code W). Option IP is not available with 3051T Range 6 ordered with Wireless output. Available with process connection codes 2A, 2B, 2C, 2F, and 61. Available with housing material codes A, B, E, F, J, K, and P. Not available with code M4, V5, GE, or GM.

(22) Only available with HART 4-20 mA output (code A) and FOUNDATION Fieldbus output (code F). Available with process connection codes 2A, 2B, 2C, 2F, and 61. Available with housing material codes A, B, E, F, J, and K. Not available with codes DA0, DZ, M4, V5, GE, GM, or BR6.

(23) Not available with Alloy C-276 isolator (option code 3), assemble-to manifolds (option code S5), assemble-to seals (option code S1), surface finish certification (option code Q16), and remote seal system report (option code QZ).

(24) Only available with product certifications E7, E8, I1, I7, IA, K7, K8, KD, N1, and N7.

(25) Only available with HART 4–20 mA output code A.

(26) Only available with HART 4–20 mA output code A and wireless output code X.

(27) Only available with 4-20 mA HART output (code A) and PROFIBUS-PA output (code W).

(28) Transmitter is shipped with 316 SST conduit plug (uninstalled) in place of standard CS conduit plug.

(29) The T1 option is not needed with FISCO Product Certifications; transient protection is included in the FISCO product certification codes IA, IB, and

IE.

(30) NAMUR-compliant operation is pre-set at the factory and can be changed to standard operation in the field for the standard Rosemount 3051.

(31) Not valid with alternate process connection code S5.

(32) The V5 option is not needed with T1 option; external ground screw assembly is included with the T1 option.

(33) NACE compliant wetted materials are identified by footnote (12).

(34) Only available on pressure ranges 1–5, 4-20mA HART protocol, and silicone sensor fill fluid. Available with process connection style 2B and 2C.

BR5 and BR6 are not available with the following options: QS, DF, D7, D9, P9, Q16, GE, and GM. See factory for available approvals.

(35) BR5 option is only available with approval codes E2, E5, EM, I2, I5, I7, IM, IP, K5, KM, and KP.

(36) BR6 option is only available with approval codes EM, I2, I7, IM, IP, and KM.

July 2019

18 Rosemount 3051

Specifications

Performance specifications This product data sheet covers HART®, WirelessHART, FOUNDATION™ Fieldbus, and PROFIBUS® PA Protocols unless specified otherwise.

For zero-based spans, reference conditions, silicone oil fill, glass-filled PTFE O-rings, SST materials, coplanar flange, or ½–14 NPT process connections, digital trim values set to equal range points.

Conformance to specifications (±3σ [Sigma]) Technology leadership, advanced manufacturing techniques, and statistical process control ensure specification conformance to at least ±3σ.

Reference accuracy Stated reference accuracy equations include terminal based linearity, hysteresis, and repeatability. For wireless, FOUNDATION™

Fieldbus, and PROFIBUS® PA devices, use calibrated range in place of span.

Models Rosemount™ 3051 and WirelessHART®

Rosemount 3051C(1)

Range 5 ±0.065% of span

For spans less than 10:1, accuracy =

Ranges 2–4 ± 0.04% of span (2)

For spans less than 10:1(3), accuracy =

Range 1 ± 0.10% of span

For spans less than 15:1, accuracy =

Range 0 (CD) ± 0.10% of span

For spans less than 2:1, accuracy = ± 0.05% of URL

Rosemount 3051CA

Ranges 1–4 ± 0.04% of span(2)

July 2019

Product Data Sheet 51

HomR Rectangle

HomR Text Box

316L-SS: ROSEMOUNT P/N: 3051TG1A2B21AC6Q4M5

Hastalloy: ROSEMOUNT P/N: 3051TG1A2B31AC6Q4M5

Rosemount 3051T (4)

Ranges 1–4 ± 0.04% of span(2)

Range 5–6 ± 0.075% of span For spans less than 10:1, accuracy =

Rosemount 3051L

Ranges 2-4 ± 0.075% of span

(1) For Rosemount 3051C and 3051T with 1199 assemble to code S1, use 3051L specification.

(2) For output code W and M, ±0.065% span.

(3) For output code F, for span less than 5:1.

(4) For Rosemount 3051C and 3051T with 1199 assemble to code S1, use Rosemount 3051L specification.

Flow Performance - Flow Reference Accuracy

Note Accuracy over range of use is always application dependent. Range 1 flow meters may experience an additional uncertainty up to

0.9 percent. Consult your Emerson representative for exact specifications.

Rosemount 3051CFA Annubar Flow Meter

Ranges 2–3 ±1.80% of flow rate at 8:1 flow turndown

Rosemount 3051CFC_A Compact Annubar Flow Meter – Rosemount Annubar Option A

Ranges 2–3 Uncalibrated ±2.10% of flow rate at 8:1 flow turndown

Calibrated ±1.80% of Flow Rate at 8:1 flow turndown

Rosemount 3051CFC_C Compact Orifice Flow Meter – Conditioning Option C

Ranges 2–3 β = 0.4 ±1.75% of flow rate at 8:1 flow turndown β = 0.50, 0.65 ±1.95% of flow rate at 8:1 flow turndown

Rosemount 3051CFC_P Compact Orifice Flow Meter – Orifice Type Option P(1)

Ranges 2–3 β= 0.4 ±2.00% of flow rate at 8:1 flow turndown β= 0.65 ±2.00% of flow rate at 8:1 flow turndown

Rosemount 3051CFP Integral Orifice Flow Meter

Ranges 2–3 β<0.1 ±3.00% of flow rate at 8:1 flow turndown

0.1< β<0.2 ±1.95% of flow rate at 8:1 flow turndown

July 2019

52 Rosemount 3051

0.2< β<0.6 ±1.75% of flow rate at 8:1 flow turndown

0.6< β<0.8 ±2.15% of flow rate at 8:1 flow turndown

(1) Applicable to 2- to 12-in. line sizes. For smaller line sizes, see the Rosemount DP Flow Meters and Primary Elements Product Data Sheet.

Total performance Total performance is based on combined errors of reference accuracy, ambient temperature effect, and static pressure effect at normal operating conditions (70 percent of span typical reading, 740 psi (51,02 bar) line pressure).

For ±50 °F (28 °C) temperature changes; 0–100% relative humidity, from 1:1 to 5:1 rangedown

Models Total performance(1)

Rosemount™ 3051C

Ranges 2–5

± 0.14% of span

Rosemount 3051T

Ranges 1–4

± 0.14% of span

Rosemount 3051L

Ranges 2–4

Use Instrument Toolkit™ or the QZ option to quantify the total performance of a remote seal assembly under operating conditions.

(1) For output code W, F, and M, total performance is ±0.15% of span.

Long term stability

Models Long term stability

Rosemount™ 3051C

Ranges 2–5

±0.2% of URL for 10 years ±50 °F (28 °C) temperature changes, and up to 1000 psi (68,95 bar) line pressure.

Rosemount 3051CD, 3051CG Low/ Draft Range

Ranges 0–1

±0.2% of URL for 1 year

Rosemount 3051CA Low Range

Range 1

±0.2% of URL for 10 years ±50 °F (28 °C) temperature changes, and up to 1000 psi (68,95 bar) line pressure.

Rosemount 3051T

Ranges 1–4

±0.2% of URL for 10 years ±50 °F (28 °C) temperature changes, and up to 1000 psi (68,95 bar) line pressure.

Rosemount 3051L

Ranges 2–3

Ranges 4–5

±0.1% of URL for 1 year

±0.2% of URL for 1 year

Dynamic performance

4 - 20 mA HART®(1) FOUNDATION™ Fieldbus and PROFIBUS® PA Protocols(2)

Typical HART transmitter response time

Total Response Time (T d + T c)(3):

Rosemount 3051C

Ranges 2-5 100 ms 152 ms

Range 1 255 ms 307 ms

July 2019

Product Data Sheet 53 http://www2.emersonprocess.com/siteadmincenter/PM%20Rosemount%20Documents/00813-0100-4485.pdf HomR Rectangle

4 - 20 mA HART®(1) FOUNDATION™ Fieldbus and PROFIBUS® PA Protocols(2)

Typical HART transmitter response time

Range 0 700 ms N/A

Rosemount 3051T 100 ms 152 ms

Rosemount 3051L See Instrument Toolkit. See Instrument Toolkit.

Dead time (Td) 45 ms (nominal) 97 ms

Update rate(4) 22 times per second 22 times per second

(1) Dead time and update rate apply to all models and ranges; analog output only.

(2) Transducer block response time, Analog Input block execution time not included.

(3) Nominal total response time at 75 °F (24 °C) reference conditions.

(4) Does not apply to wireless (output code X). See Wireless (output code X) for wireless update rate.

Line pressure effect per 1000 psi (68,95 bar) For line pressures above 2000 psi (137,90 bar) and Ranges 4–5, see the following documents. For HART®, see the Rosemount™

3051 Reference Manual. For WirelessHART, see the Rosemount 3051 Wireless Reference Manual.

For FOUNDATION™ Fieldbus, see the Rosemount 3051 Reference Manual. For PROFIBUS® PA, see the Rosemount 3051 Reference Manual.

Table 7: Rosemount 3051CD and 3051CF Line Pressure Effect

Range Line pressure effect

Zero error

Ranges 2–3 ±0.05% of URL/1000 psi (68,95 bar) for line pressures from 0 to 2000 psi (0 to 137,90 bar)

Range 1 ±0.25% of URL/1000 psi (68,95 bar) for line pressures from 0 to 2000 psi (0 to 137,90 bar)

Range 0 ±0.125% of URL/100 psi (6,89 bar) for line pressures from 0 to 750 psi (0 to 51,71 bar)

Span error

Ranges 2–3 ±0.1% of reading/1000 psi (68,95 bar)

Range 1 ±0.4% of reading/1000 psi (68,95 bar)

Range 0 ±0.15% of reading/100 psi (6,895 bar)

Ambient temperature effect per 50 °F (28 °C)

Models Ambient temperature effect

Rosemount™ 3051C

Ranges 2–5 ±(0.0125% URL + 0.0625% span) from 1:1 to 5:1

±(0.025% URL + 0.125% span) from 5:1 to 150:1

Range 1 ±(0.1% URL + 0.25% span) from 1:1 to 30:1 ±(0.14% URL + 0.15% span) from 30:1 to 50:1

Range 0 ±(0.25% URL + 0.05% span) from 1:1 to 30:1

July 2019

54 Rosemount 3051 http://www2.emersonprocess.com/siteadmincenter/PM%20Rosemount%20Documents/00809-0100-4007.pdf http://www2.emersonprocess.com/siteadmincenter/PM%20Rosemount%20Documents/00809-0100-4100.pdf http://www2.emersonprocess.com/siteadmincenter/PM%20Rosemount%20Documents/00809-0100-4774.pdf http://www2.emersonprocess.com/siteadmincenter/PM%20Rosemount%20Documents/00809-0100-4797.pdf http://www2.emersonprocess.com/siteadmincenter/PM%20Rosemount%20Documents/00809-0100-4797.pdf HomR Rectangle

Models Ambient temperature effect

Rosemount 3051CA

Ranges 1–4 ±(0.025% URL + 0.125% span) from 1:1 to 30:1

±(0.035% URL + 0.125% span) from 30:1 to 150:1

Rosemount 3051T

Range 2–4 ±(0.025% URL + 0.125% span) from 1:1 to 30:1

±(0.035% URL + 0.125% span) from 30:1 to 150:1

Range 1 ±(0.025% URL + 0.125% span) from 1:1 to 10:1

±(0.05% URL + 0.125% span) from 10:1 to 100:1

Range 5–6 ±(0.1% URL + 0.15% span) from 1:1 to 5:1

Rosemount 3051L See Instrument toolkit software.

Mounting position effects

Models Mounting position effects

Rosemount™ 3051C Zero shifts up to ±1.25 in H2O (3,11 mbar), which can be calibrated out. No span effect.

Rosemount 3051CA, 3051T Zero shifts up to ±2.5 in H2O (6,22 mbar), which can be calibrated out. No span effect.

Rosemount 3051L With liquid level diaphragm in vertical plane, zero shift of up to ±1 in H2O (2,49 mbar). With diaphragm in horizontal plane, zero shift of up to ±5 in H2O (12,43 mbar) plus extension length on extended units. All zero shifts can be calibrated out. No span effect.

Vibration effect Less than ±0.1% of URL when tested per the requirements of IEC60770-1: 1999 field or pipeline with high vibration level (10–60 Hz

0.21 mm displacement peak amplitude/60–2000 Hz 3g).

Power supply effect Less than ±0.005% of calibrated span per volt change.

Electromagnetic compatibility (EMC) Meets all industrial environment requirements of EN61326 and NAMUR NE-21. Maximum deviation <1% Span during EMC disturbance.

Note NAMUR NE-21 does not apply to Low-Power (Transmitter output option code M) or Wireless (Transmitter output code X).

Note During surge event, device with 4-20mA (Transmitter output option code A) may exceed maximum EMC deviation limit or reset;

however, device will self-recover and return to normal operation within specified start-up time.

Transient protection (option code T1) Tested in accordance with IEEE C62.41.2-2002, location category B

■ 6 kV crest (0.5 µs - 100 kHz)

■ 3 kA crest (8 x 20 µs)

July 2019

Product Data Sheet 55

HomR Rectangle

■ 6 kV crest (1.2 x 50 µs)

Functional specifications

Range and sensor limits Table 8: Rosemount™ 3051CD, 3051CG, 3051CF, and 3051L Range and Sensor Limits

Range(1) Minimum span Range and sensor limits

Rosemount

3051CD,

3051CG,

3051CF, 3051L(2)

Upper (URL) Lower (LRL)

Rosemount

3051CD

Differential, 3051CF Flow Meters

Rosemount 3051CG Gage(3)

Rosemount 3051L Differential

Rosemount 3051L Gage(3)

0 0.10 inH2O (0,24 mbar)

3.00 inH2O (7,45 mbar)

–3.00 inH2O (–7,45 mbar)

N/A N/A N/A

1 0.50 inH2O (1,24 mbar)

25.00 inH2O (62,16 mbar)

–25.00 inH2O (–62,16 mbar)

–25.00 inH2O (– 62,16 mbar)

N/A N/A

2 1.67 inH2O (4,15 mbar)

250.00 inH2O (621,60 mbar)

–250.00 inH2O (–621,60 mbar)

–250.00 inH2O (– 621,60 mbar)

–250.00 inH2O (– 621,60 mbar)

–250.00 inH2O (– 621,60 mbar)

3 6.67 inH2O (16,58 mbar)

1000.00 inH2O (2,48 bar)

–1000.00 inH2O (–2,48 bar)

0.50 psia (34,47 mbar)

–1000.00 inH2O (–2,48 bar)

0.50 psia (34,47 mbar)

4 2.00 psi (137,89 mbar)

300.00 psi (20,68 bar)

–300.00 psi (–20,68 bar)

0.50 psia (34,47 mbar)

–300.00 psi (–20,68 bar)

0.50 psia (34,47 mbar)

5 13.33 psi (919,01 mbar)

2000.00 psi (137,89 bar)

– 2000.00 psi (–137,89 bar)

0.50 psia (34,47 mbar)

N/A N/A

(1) Range 0 only available with Rosemount 3051CD. Range 1 only available with 3051CD, 3051CG, or 3051CF. inH2O referenced at 68 °F (20 °C).

(2) For outputs options W and M, minimum span are: range 1 - 0.50 inH2O (1,24 mbar), range 2 - 2.50 inH2O (6,21 mbar), range 3 - 10.00 inH2O

(24,86 mbar), range 4 - 3.00 psi (0,21 bar), range 5 - 20.00 psi (1,38 bar).

(3) Assumes atmospheric pressure of 14.7 psig.

Table 9: Rosemount 3051CA and 3051T Range and Sensor Limits

Range Rosemount 3051CA Range Rosemount 3051T

Minimum span(1)

Range and sensor limits Minimum span(1)

Range and sensor limits Lower(2)

(LRL) (gage)

Upper (URL) Lower

(LRL)

Upper (URL) Lower (LRL) (absolute)

1 0.30 psi (20,68 mbar)

30 psia (2,06 bar)

0 psia (0 bar)

1 0.30 psi (20,68 mbar)

30.00 psi

(2,06 bar)

0 psia (0 bar) –14.70 psig (–1,01 bar)

2 1.00 psi (68,94 mbar)

150 psia (10,34 bar)

0 psia (0 bar)

2 1.00 psi

(68,94 mbar)

150.00 psi

(10,34 bar)

0 psia (0 bar) –14.70 psig (–1,01 bar)

3 5.33 psi (367,49 mbar)

800 psia (55,15 bar)

0 psia (0 bar)

3 5.33 psi

(367,49 mbar)

800.00 psi

(55,15 bar)

0 psia (0 bar) –14.70 psig (–1,01 bar)

4 26.67 psi (1,83 bar)

4000 psia (275,79 bar)

0 psia (0 bar)

4 26.67 psi

(1,83 bar)

4000.00 psi

(275,79 bar)

0 psia (0 bar) –14.70 psig (–1,01 bar)

July 2019

56 Rosemount 3051

Table 9: Rosemount 3051CA and 3051T Range and Sensor Limits (continued)

Range Rosemount 3051CA Range Rosemount 3051T

Minimum span(1)

Range and sensor limits Minimum span(1)

Range and sensor limits Lower(2)

(LRL) (gage)

Upper (URL) Lower

(LRL)

Upper (URL) Lower (LRL) (absolute)

5 N/A N/A N/A 5 2000.00 psi (137,89 bar)

10000.00 psi (689,47 bar)

0 psia (0 bar) –14.70 psig (–1,01 bar)

6 N/A N/A N/A 6 4000.00 psi

(275,79 bar)

20000.00 psi

(1378,95 bar)

0 psia

(0 bar)

–14.70 psig (–1,01 bar)

(1) For output options W and M, minimum span are: range 2 – 1.50 psi (0,10 bar), range 3 – 8.00 psi (0,55 bar), range 4 – 40.00 psi (2,75 bar), range 5 for 3051T – 2000.00 psi (137,89 bar).

(2) Assumes atmospheric pressure of 14.7 psig.

Service

Liquid, gas, and vapor applications.

4–20 mA HART® (output code A)

Power supply

External power supply required. Standard transmitter (4–20 mA) operates on 10.5–42.4 Vdc with no load.

Load limitations

Maximum loop resistance is determined by the voltage level of the external power supply described by:

Max. loop resistance = 43.5 (power supply voltage - 10.5)

Communication requires a minimum loop resistance of 250 ohms.

10.5 20 30 42.4

C

A

B

A. Load (Ωs) B. Operating region C. Voltage (Vdc)

Note For CSA approval, power supply must not exceed 42.4 V.

Indication

Optional 2-line LCD/LOI Display

July 2019

Product Data Sheet 57

Optional configuration buttons

Configuration buttons need to be specified:

■ Digital Zero trim (option code DZ) changes digital value of the transmitter and is used for performing a sensor zero trim.

■ Analog Zero Span (option code D4) changes analog value and can be used to rerange the transmitter with an applied pressure.

Output Two-wire 4–20mA, user selectable for linear or square root output. Digital process variable superimposed on 4–20 mA signal, available to any host that conforms to HART® Protocol. The Rosemount™ 3051 comes with Selectable HART Revisions. Digital communications based on HART Revision 5 (default) or Revision 7 (option code HR7) protocol can be selected. The HART revision can be switched in the field using any HART based configuration tool or the optional LOI (M4).

Loop Integrity diagnostics

The Loop Integrity diagnostic continuously monitors the electrical loop to detect changes that compromise the integrity of the transmitter 4-20 mA output signal. The diagnostics can detect loop problems such as water in the terminal compartment, corrosion of terminals, improper grounding, and unstable power supplies.

The device dashboard presents the diagnostics in a graphical, task-based interface that provides single-click access to critical process/device information and descriptive graphical troubleshooting.

LOI

The LOI uses a two button menu with internal and external configuration buttons. Internal buttons are always configured for LOI.

External buttons can be configured for either LOI (option code M4), analog zero and span (option code D4), or digital zero trim (option code DZ). See Rosemount 3051 Reference Manual for LOI configuration menu.

FOUNDATION™ Fieldbus (output code F)

Power supply

External power supply required; transmitters operate on 9.0 to 32.0 Vdc transmitter terminal voltage. FISCO transmitters operate on 9.0 to 17.5 Vdc.

Current draw

17.5 mA for all configurations (including LCD display option)

Indication

Optional two-line LCD display

FOUNDATION Fieldbus block execution times

Block Execution time

Resource N/A

Sensor and SPM Transducer N/A

LCD Display N/A

Analog Input 1, 2 20 milliseconds

PID 25 milliseconds

Input Selector 20 milliseconds

Arithmetic 20 milliseconds

Signal Characterizer 20 milliseconds

Integrator 20 milliseconds

July 2019

58 Rosemount 3051 http://www2.emersonprocess.com/siteadmincenter/PM%20Rosemount%20Documents/00809-0100-4007.pdf

Digital zero trim

Digital zero trim (option DZ) is an offset adjustment to compensate for mounting position effects, up to 5% of URL.

Update rate

User selectable 1 sec. to 60 min.

Wireless sensor module for in-line transmitters

The Rosemount™ 3051 Wireless Transmitter requires the engineered polymer housing to be selected. The standard sensor module will come with aluminum material. If SST is required, you must select the option WSM.

Power module

Field replaceable, keyed connection eliminates the risk of incorrect installation, Intrinsically Safe Lithium-thionyl chloride Power Module with PBT/PC enclosure. Ten-year life at one minute update rate. (1)

Note Continuous exposure to ambient temperature limits of -40 °F or 185 °F (–40 °C or 85 °C) may reduce specified life by less than 20 percent.

Low power output

1–5 Vdc HART® low power (output code M)

Output

The default three-wire 1–5 Vdc is a user-selectable output. Also user selectable for linear or square root output configuration.

Digital process variable superimposed on voltage signal, available to any host conforming to the HART Protocol. Low-power transmitter operates on 6–12 Vdc with no load. Option code C2 changes the output from 1–5 Vdc to 0.8–3.2 Vdc.

Power consumption

3.0 mA, 18–36 mW

Minimum load impedance

100 kΩ (Vout wiring)

Indication

Optional five-digit LCD display

Overpressure limits

Rosemount 3051CD/CG/CF

■ Range 0: 750 psi (51,71 bar)

■ Range 1: 2000 psig (137,90 bar)

■ Ranges 2–5: 3626 psig (250,00 bar), 4500 psig (310,26 bar) for option code P9

Rosemount 3051CA

■ Range 1: 750 psia (51,71 bar)

■ Range 2: 1500 psia (103,42 bar)

■ Range 3: 1600 psia (110,32 bar)

■ Range 4: 6000 psia (413,69 bar)

(1) Reference conditions are 70 °F (21 °C), and routing data for three additional network devices.

July 2019

Product Data Sheet 61

Rosemount 3051TG/TA

■ Range 1: 750 psi (51,71 bar)

■ Range 2: 1500 psi (103,42 bar)

■ Range 3: 1600 psi (110,32 bar)

■ Range 4: 6000 psi (413,69 bar)

■ Range 5: 15000 psi (1034,21 bar)

■ Range 6: 24000 psi (1654,74 bar)

For Rosemount 3051L or level flange option codes FA, FB, FC, FD, FP, and FQ, limit is 0 psia to the flange rating or sensor rating, whichever is lower.

Table 10: Rosemount 3051L and Level Flange Rating Limits

Standard Type CS Rating SST Rating

ANSI/ASME Class 150 285 psig 275 psig

ANSI/ASME Class 300 740 psig 720 psig

ANSI/ASME Class 600 1480 psig 1440 psig

At 100 °F (38 °C), the rating decreases with increasing temperature, per ANSI/ASME B16.5.

DIN PN 10–40 40 bar 40 bar

DIN PN 10/16 16 bar 16 bar

DIN PN 25/40 40 bar 40 bar

At 248 °F (120 °C), the rating decreases with increasing temperature, per DIN 2401.

Static pressure limit

Rosemount™ 3051CD only

Operates within specifications between static line pressures of 0.5 psia and 3626 psig (4500 psig (310, 26 bar) for option code P9).

Range 0: 0.5 psia and 750 psig (0,03 bar and 51,71 bar)

Range 1: 0.5 psia and 2000 psig (0,03 bar and 137, 90 bar)

Burst pressure limits

Rosemount™ 3051C, 3051CF coplanar or traditional process flange

10081 psig (695,06 bar)

Rosemount 3051T in-line

■ Ranges 1–4: 11016 psi (759,53 bar)

■ Range 5: 26016 psig (1793,74 bar)

■ Range 6: 46092 psi (3177,93 bar)

Failure mode alarm

HART® 4–20 mA (output option code A)

If self-diagnostics detect a sensor or microprocessor failure, the analog signal is driven either high or low to alert the user. High or low failure mode is user-selectable with a jumper/switch on the transmitter. The values to which the transmitter drives its output in

July 2019

62 Rosemount 3051

HomR Rectangle failure mode depend on whether it is configured to standard, NAMUR-compliant, or custom levels (see alarm configuration below).

The values for each are as follows:

High alarm Low alarm

Default ≥ 21.75 mA ≤ 3.75 mA

NAMUR compliant (1) ≥ 22.5 mA ≤ 3.6 mA

Custom levels (2) 20.2 – 23.0 mA 3.4 – 3.8 mA

(1) Analog output levels are compliant with NAMUR recommendation NE 43; see option codes C4 or C5.

(2) Low alarm must be 0.1 mA less than low saturation and high alarm must be 0.1 mA greater than high saturation.

Output code M

If self-diagnostics detect a gross transmitter failure, the analog signal will be driven either below 0.94 V or above 5.4 V to alert the user (below 0.75 V or above 4.4 V for Option C2). High or low alarm signal is user-selectable by internal jumper.

Output code F, W, and X

If self-diagnostics detect a gross transmitter failure, that information gets passed as an alert and a status along with the process variable.

Temperature limits

Ambient

■ –40 to 185 °F (–40 to 85 °C)

■ With LCD display(1)(2): –40 to 176 °F (–40 to 80 °C)

■ With option code BR5: –58 to 185 °F (–50 to 85 °C)

■ With option code BR6: –76 to 185 °F (–60 to 85 °C)

(1) For the output code M and W, LCD display may not be readable, and LCD display updates will be slower at temperatures below –22 °F (–30 °C).

(2) Wireless LCD display may not be readable, and LCD display updates will be slower at temperature below –4 °F (–20 °C).

Storage

Note If storage temperature is above 185 °F (85 °C), perform a sensor trim prior to installation.

■ –76 to 230 °F (–60 to 110 °C)

■ With LCD display: –76 to 185 °F (–60 to 85 °C)

■ With wireless output: –40 °F to 185 °F (–40 °C to 85 °C)

Process

At atmospheric pressures and above. See Table 11.

Table 11: Rosemount ™3051 Process Connection Temperature Limits

Rosemount 3051CD, 3051CG, 3051CF, 3051CA

Silicone fill sensor(1)

With coplanar flange –40 to 250 °F (–40 to 121 °C)(2)

With traditional flange –40 to 300 °F (–40 to 149 °C)(2)(3)

With level flange –40 to 300 °F (–40 to 149 °C)(2)

With Rosemount 305 Integral Manifold –40 to 300 °F (–40 to 149 °C)(2)

July 2019

Product Data Sheet 63

Table 11: Rosemount ™3051 Process Connection Temperature Limits (continued)

Inert fill sensor(1)(4) –40 to 185 °F (–40 to 85 °C) (5)(6)

With Option Code BR6, coplanar flange -76 to 250 °F (-60 to 121 °C)(2)

With Option Code BR6, traditional flange -75 to 300 °F (-60 to 149 °C)(2)

Rosemount 3051T (process fill fluid)

Silicone fill sensor(1) –40 to 250 °F (–40 to 121 °C)(2)

With Option Code BR6 -76 to 250 °F (-60 to 121 °C)(2)

Inert fill sensor(1) –22 to 250 °F (–30 to 121 °C)(2)

Rosemount 3051L low-side temperature limits

Silicone fill sensor(1) –40 to 250 °F (–40 to 121 °C)(2)

Inert fill sensor(1) –40 to 185 °F (–40 to 85 °C)(5)

Rosemount 3051L high-side temperature limits (process fill fluid)

SYLTHERM™ XLT –102 to 293 °F (–75 to 145 °C)

D.C. Silicone 704 32 to 401 °F (0 to 205 °C)

D.C. Silicone 200 –49 to 401 °F (–45 to 205 °C)

Inert –49 to 320 °F (–45 to 160 °C)

Glycerin and water 5 to 203 °F (–15 to 95 °C)

Neobee® M-20 5 to 401 °F (–15 to 205 °C)

Propylene glycol and water 5 to 203 °F (–15 to 95 °C)

(1) Process temperatures above 185 °F (85 °C) require derating the ambient limits by a 1.5:1 ratio.

(2) 220 °F (104 °C) limit in vacuum service; 130 °F (54 °C) for pressures below 0.5 psia.

(3) Rosemount 3051CD0 process temperature limits are –40 to 212 °F (–40 to 100 °C).

(4) Inert fill with traditional flange on Range 0: limits are 32 to 185 °F (0 to 85 °C).

(5) 160 °F (71 °C) limit in vacuum service.

(6) Not available for Rosemount 3051CA.

Humidity limits 0–100 percent relative humidity

Turn-on time Performance within specifications less than 2.0 seconds (20.0 seconds for PROFIBUS® PA and FOUNDATION™ Fieldbus Protocols) after power is applied to the transmitter.

Note Does not apply to wireless option code X.

Volumetric displacement Less than 0.005-in3 (0,08 cm3)

July 2019

64 Rosemount 3051

Damping

4–20 mA HART®

Analog output response to a step input change is user-enterable from 0.0 to 60 seconds for one time constant. This software damping is in addition to sensor module response time.

FOUNDATION™ Fieldbus

■ Transducer block: User…

This is the start of the file's text. The full file is on GovTribe.