Addendum 003 - Mechanical Drawings - P and ID R4 Pall Submittal Return Comments.pdf
PDF 4 MB Posted
- Attached to
- Request for Proposal - Construction Services for Project L-897, Central Plateau Water Treatment Facility
- Solicitation number
- 338214
- Issued by
-
Department of Energy
View the file
Other files
Show 40 more
Latest 50 of 88 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A
B
C
D
A
B
C
D
12345678
12345678
DRAWING NUMBER
MATERIAL MASTER
DRAWING NAME
PROJECT ID
DWG SIZE
REVISION
SHEET OF
Copyright PALL CORPORATION This document may contain confidential technical data, including trade secrets proprietary to Pall Corporation. The drawing, design rights and all other disclosures in this document are the property of Pall
Corporation. Unauthorized use, copying, distribution to third parties, manufacture, or reproduction in whole or in part is prohibited.
PALL Corporation
PROJECT ENGINEER
ENGINEER
ENGINEER
ENGINEER
CHECKER
DRAWN BY
NAME DATE
UNLESS OTHERWISE SPECIFIED, THE FOLLOWING
INFORMATION PERTAINS ONLY TO THIS SHEET
SCALE
CODE INDENTIFICATION NO.
DO NOT SCALE
FROM DRAWING
THIRD ANGLE
PROJECTION
TOLERANCE
X. ±
.X ±
.XX ±
.XXX ±
FRACTION ±
ANGLE ± DEG
DIMENSIONS ARE IN
INCHES
ONLY
MILLIMETER
ONLY
IN [mm] mm [IN]
ALL FINISHED SURFACES
µIN µm
SEE SHEET 1 FOR REVISION
17238
These commodities, technology or software may only be exported from the United States in accordance with the
Export Administration
Regulations. Diversion contrary to U.S. law is prohibited.
IMPORTANT: BEFORE ATTEMPTING TO OPERATE OR INSTALL THIS SYSTEM, IT IS ESSENTIAL TO READ AND UNDERSTAND
THIS PRODUCT'S OPERATION AND MAINTENANCE MANUAL (SHIPPED UNDER SEPARATE COVER). FAILURE TO READ THE
OPERATION AND MAINTENANCE MANUAL BEFORE ATTEMPTING TO OPERATE ANY PALL CORPORATION EQUIPMENT MAY
RESULT IN SERIOUS PERSONAL INJURY AND/OR PRODUCT DAMAGE, AND VOID ANY AND/OR ALL WARRANTIES
.XXXX ±
Pall Advanced Separation Systems
Industrial, Cortland NY
PRIMARY SYSTEM P&ID
B. HARRIS
01.000287
D
09SEP2017
D. LARKIN 19DEC2019
G. CEMPA 19DEC2019
R. HOM 19DEC2019
TEMPLATE REV: R2013.1
NO SCALE
X
* PROVIDED
BY OTHERS
IF REQUIRED
NOTE: STRAINER BACKWASH CONTROL
IS BASED ON TIME, WITH DIFFERENTIAL
PRESSURE AS A BACKUP CONTROL.
1. ON THIS SHEET, ALL TANKS, PIPING, TUBING, FLEXIBLE CONNECTORS, ASSY.
HARDWARE, AND FIELD WIRING TO BE PROVIDED AND INSTALLED BY OTHERS.
ALL VALVES, INSTRUMENTS, & PUMPS INDICATED WITH (*) TO BE FURNISHED BY PALL CORP.
FOR INSTALLATION BY OTHERS UNLESS OTHERWISE NOTED.
2. FLANGES AT ENDS OF HEADERS SHOULD BE REMOVABLE FOR CLEANOUT AND
INSPECTION.
3. STRAIGHT RUN OF 5 PIPE DIA'S UPSTREAM AND TWO PIPE DIA'S DOWN STREAM OF
FLOW METER REQUIRED.
4. SAMPLE PRESSURE : 6 bar / 87 PSIG MAX. FOR 35° - 104° F [2° - 40° C]
3 bar / 43 PSIG MAX. FOR 104° - 140° F [40° - 60° C]
5. VALVE V-3119 ISOLATES THE MF SKIDS, CLOSING SLOWLY UPON SHUTDOWN CONDITIONS.
NOTE: SEE SHEET 2 FOR
RACK PIPING DETAILS.
AVG DESIGN FLOW - 3.5 MGD
[5.0 MGD FUTURE]
MAX DESIGN FLOW - 2787 GPM
[3802 GPM FUTURE]
SAMPLE
TAP
AVG DESIGN FLOW - 0.14 MGD
[0.21 MGD FUTURE]
MAX DESIGN FLOW - 1152 GPM
[1344 GPM FUTURE]
AVG DESIGN FLOW - 3.7 MGD
[5.2 MGD FUTURE]
MAX DESIGN FLOW - 2906 GPM
[3960 GPM FUTURE]
RACK 1 RACK 2
300 MICRON, 3960 GPM WITH
1/2 HP, 460 VAC., 3PH MOTOR
N+1 DESIGN
(TYP. 2)
TO BACKWASH
WASTE TANK
I
X X
X
X X
X
X X
X X
X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X
MAG
CV
4352A
CV
4352B
M
M
1152 GPM @ 93 TDH
[1344 GPM FUTURE]
20 HP @ 3500 RPM
(TYP. 3)
I
* PROVIDED
BY OTHERS
IF REQUIRED
CLEARWELL
SAMPLE
TAP
FILTRATE VENT
FROM RACK
FLOWMETERS
SH.2 @ B5
3.5 MGD NET PRODUCTION
[5.0 MGD NET FUTURE PRODUCTION]
PALL SUPPLIED VALVE
AND MODULE RACK
AREA BY OTHERS
THROTTLE TO SET
PI-3271 TO 5 - 10 PSIG
RACK 3
X X
X
X X pH
CL2
INITIAL RELEASE
DHT
10DEC2019
DML
19DEC2019
GJC
19DEC2019
RH
19DEC2019
ACH
FROM ACH PIPING
HCL
FROM NaOCL PIPING
EW
FROM COLUMBIA
RIVER WATER
EW
FROM COLUMBIA
RIVER WATER
PCV
EW-PRV-1601
EW-PIT-1601
PCV
EW-PRV-1602
EW-PIT-1603
TO STRAINERS
PTW-PIT-3005
PTW-PIT-3009
PTW-STR-3201
SBW-AOV-3201
PTW-STR-3202
SBW-AOV-3202
SAM-AIT-3007
PTW-TIT-3008
SAM-AIT-3006
SAM-FE-3006
BCKW-PMP-4303
BCKW-PI-4303
BCKW-PMP-4302
BCKW-FIT-4305
BCKW-PI-4353
BCKW-PI-4354
BCKW-PI-4302
FT-PIT-4003
SAM-AE-4001 SAM-FE-4001
HCL
FROM NaOCL FEED
PCV
HCL-PCV-7101
SAM-AIT-4032
SAM-AE-4032
SAM-FI-4030 SAM-AE-4030
TURBIDIMETER
(SEE NOTE 4)
TURBIDIMETER (SEE NOTE 4) SAMPLE
TAP
SAM-AIT-4001
SAM-TURB-3006
PTW-AOV-3119
PTW-PRV-3071B
PTW-PIT-3070
BCKW-VFD-4302
BCKW-VFD-4303
FT-MIX-4005
pH *SAM-AIT-3007
EW-PIT-1600
PIT
EW-PIT-1602
PTW-MIX-1601
TIT
EW-TIT-1609
SAM-AIT-1613
SAM-AE-1613
SAM-AE-1612
SAM-AIT-1612
pH
SAM-FI-1611
SAM-AE-1611
SAM-AIT-1611
ALK
HV
1602*
HV
HV
PRV
HV
1603HV
HV
HV
HV
HV
HV
4355B
HV
4355A
HV
HV
SET @ 30 PSI
*SAM-AIT-4030
SAM-FI-1612
SAM-FI-1611
SAM-FI-3007
SET @ 70 PSIG
SET @ 70 PSIG
IF REQUIRED
BY OTHERS
SET @ 50 PSIG
PIT
PITPIT
ACH-PCV-7101
ACH-PCV-7401
PCV
PCV
PI
TURB
SAM-FI-4032
NOTE 5
FILTRATE HEADER MUST BE KEPT FULL AT
ALL TIMES FOR RF SUPPLY AND HAVE 2-4
PSIG MINIMUM BACK PRESSURE, MAXIMUM
BACK PRESSURE IS 15 PSIG.
*HV
X X
X X
X
X X
X
RACK 4
PTW-PRV-3071A
SET @ 50 PSIG
CV
4352C
M
BCKW-PMP-4304
BCKW-PI-4304
BCKW-PI-4355
BCKW-VFD-4304
HV
4355C
SS
SV
1600120 VAC
S
SAM-FE-1613
NKUTIL
Callout Add isolation ball valve here
NKUTIL
Pen x
NKUTIL
Callout Not required
NKUTIL
Callout PTW-AOV-3119 function is not understood. Each skid has a pair of valves (1030, 1001) with similar function to close on shut down. Provide justification for the need of this valve as it will become a single point of failure for this facility.
NKUTIL
Callout HV-3069A, HV-3069B, HV-3069C, HV-3069D, PRV-3071A, PRV-3071B function are not understood. If this is something that Pall requires in order to make membrane system function as a complete system, then Pall should provide and warrant equipment.
NKUTIL
Cloud
NKUTIL
Text Box
NKUTIL
Text Box
NKUTIL
Text Box
NKUTIL
Callout Provide justification for 3rd Backwash pump, this was not a part of original concept and has cost implications
NKUTIL
Callout Why does pump name not match tag or VFD name?
NKUTIL
Arrow
NKUTIL
Pen
NKUTIL
Pen
NKUTIL
Callout Not required
NKUTIL
Callout Provide isolation ball valve
DEBEST
Cloud
DEBEST
Cloud
DEBEST
Text Box FURNISH OPEN/CLOSE LIMIT SWITCHES FOR THE STRAINER VALVES AND CONNECT TO THE STRAINER I/O PANEL
DEBEST
Cloud
DEBEST
Cloud
DEBEST
Cloud
DEBEST
Cloud
DEBEST
Text Box THESE DEVICES APPEAR TO BE MISSING FROM THE SYSTEM INTERCONNECTION DETAILS. ADD TO THE STRAINER I/O PANEL
DEBEST
PolyLine
DEBEST
PolyLine
DEBEST
PolyLine
DrukeL Text Box
2. Pall Response: Pall will provide isolation valve as requested.
DrukeL Text Box
10. Pall Response: The P&ID is using Pall standard tagging convention as well as the HDR tagging.
DrukeL Text Box
1. Pall Response - these devices are not in Pall scope of supply or control. Pall can add the monitoring of these signals which will change the current scope of control/supply and can be done at added cost. Pall does not support that signals to be run to the strainer I/O panel as these are non strainer instruments. It is Pall Water practice to have these go to the Pall Master Control Panel.
DrukeL Text Box
3. Pall Response: Pall will remove as requested.
DrukeL Text Box
4. Pall Response: Pall will remove as requested.
DrukeL Text Box
5. Pall Response: Pall will remove as requested.
DrukeL Text Box
7. Pall Response: Pall will add the ball valve as requested.
DrukeL Text Box 8 & 9. Pall Response: In teleconference with HDR/MSA/Pall on 1/17/2020, HDR stated the Hydraulic profile would be updated. HDR stated the incoming raw pressure would not be 95 psi as originally designed, but would be significantly lower pressure. With that, HDR stated the PRV's 1601/1602 could be set to achieve the 45 - 50 psi required at the Membrane feed. Pall will remove the PRV's 3071A/B from P&ID and add the requirement of 45-50 psig at the Membrane feed inlet. Pall requests verification of the pressure drop over the minimum and maximum feeds flow rates, with the new hydraulic profile.
DrukeL Text Box
11. Pall Response: Per teleconference on 1/17/2020 with HDR/MSA/Pall, HDR and MSA requested Pall to review the option to provide 2 ANSI pumps in lieu of 3 SSH pumps. Per email from Tom Bell-Games on 29-Jan-2020, Pall will incorporate (2) 50 HP Goulds 3196 pumps for BCKW-PMP-4302 and BCKW-PMP-4303. RCI-058 was sent to MSA for formal confirmation. Pall will be providing a Request for Equitable cost adjustment for this change.
DrukeL Text Box
6. Pall Response: Pall agrees to provide limit switches as requested.
C
D
A
B
C
D
12345678
12345678
DRAWING NUMBER
MATERIAL MASTER
DRAWING NAME
PROJECT ID
DWG SIZE
REVISION
SHEET OF
Copyright PALL CORPORATION This document may contain confidential technical data, including trade secrets proprietary to Pall Corporation. The drawing, design rights and all other disclosures in this document are the property of Pall
Corporation. Unauthorized use, copying, distribution to third parties, manufacture, or reproduction in whole or in part is prohibited.
PALL Corporation
PROJECT ENGINEER
ENGINEER
ENGINEER
ENGINEER
CHECKER
DRAWN BY
NAME DATE
UNLESS OTHERWISE SPECIFIED, THE FOLLOWING
INFORMATION PERTAINS ONLY TO THIS SHEET
SCALE
CODE INDENTIFICATION NO.
DO NOT SCALE
FROM DRAWING
THIRD ANGLE
PROJECTION
TOLERANCE
X. ±
.X ±
.XX ±
.XXX ±
FRACTION ±
ANGLE ± DEG
DIMENSIONS ARE IN
INCHES
ONLY
MILLIMETER
ONLY
IN [mm] mm [IN]
ALL FINISHED SURFACES
µIN µm
SEE SHEET 1 FOR REVISION
17238
These commodities, technology or software may only be exported from the United States in accordance with the
Export Administration
Regulations. Diversion contrary to U.S. law is prohibited.
IMPORTANT: BEFORE ATTEMPTING TO OPERATE OR INSTALL THIS SYSTEM, IT IS ESSENTIAL TO READ AND UNDERSTAND
THIS PRODUCT'S OPERATION AND MAINTENANCE MANUAL (SHIPPED UNDER SEPARATE COVER). FAILURE TO READ THE
OPERATION AND MAINTENANCE MANUAL BEFORE ATTEMPTING TO OPERATE ANY PALL CORPORATION EQUIPMENT MAY
RESULT IN SERIOUS PERSONAL INJURY AND/OR PRODUCT DAMAGE, AND VOID ANY AND/OR ALL WARRANTIES
.XXXX ±
Pall Advanced Separation Systems
Industrial, Cortland NY
VALVE RACK DESIGN
B. HARRIS
01.000287
D
09SEP2017
D. LARKIN 19DEC2019
G. CEMPA 19DEC2019
R. HOM 19DEC2019
TEMPLATE REV: R2013.1
NO SCALE
X
CIP FEED
FILTRATE VENT
FILTRATE
AS / RF (UPPER) DRAIN
REVERSE FILTRATION SUPPLY
LOWER DRAIN (INTERCONNECT)
CIP RETURN
VALVE, IT AIR
AIR SCRUB SUPPLY
FEED CONNECTION
XXXX
(SEE NOTE 2)
72 MODULES W/
84 MOD SPACES
X
LIMIT OF PALL
RACK SCOPE
SEE NOTE 1.
RF
FEED
X XX
FROM INSTRUMENT
DRAIN (BLEED)
FROM FILTRATE
DRAIN (BLEED)
XXXX
30 PSIG
X X X
X X X
1. ALL PIPING, VALVES, AND INSTRUMENTS INSIDE BOX INDICATED ARE
PROVIDED PRE-ASSEMBLED AND FACTORY TESTED, WITH THE
EXCEPTION OF THE MODULE RACK AND FIT-1005.
2. MODULE RACK IS SHIPPED UNASSEMBLED, FOR FIELD
ASSEMBLY BY OTHERS.
3. PIPING SUPPLIED "BY OTHERS" MUST BE PLUMB, SQUARE & LEVEL.
CUSTOMER CONNECTION POINT MUST BE WITHIN 1/8" TOTAL OF THE
PALL CONNECTION (1/4" FOR EXPANSION JOINT CONNECTIONS, EXCLUDING
ANY HORIZONTAL LENGTH OF THE EXPANSION JOINT). CENTERLINE OF
CONNECTING PIPING "BY OTHERS" MUST BE PARALLEL TO THE PALL
CONNECTION CENTERLINE WITHIN ONE (1) DEGREE. EXPANSION JOINTS
SHALL BE A MINIMUM OF 12" IN LENGTH.
4. ALL FLEX CONNECTORS AND EXPANSION JOINTS TO BE PROVIDED
BY OTHERS AND CAN NOT GO DIRECTLY TO VALVES.
(ELASTOMER TO ELASTOMER JOINT NOT PERMITTED)
5. A METAL RING OR SPOOL IS REQUIRED BETWEEN FLEXIBLE CONNECTORS
AND VALVE FACES.
6. SAMPLE PRESSURE : 6 bar / 87 PSIG MAX. FOR 35° - 104° F [2° - 40° C]
3 bar / 43 PSIG MAX. FOR 104° - 140° F [40° - 60° C]
7. BLOCK AND BLEED VALVES CAN BE FURNISHED BY PALL FOR INSTALLATION
BY OTHERS. BLOCK AND BLEED SPOOL PIECES ARE BY OTHERS UNLESS
OTHER WISE NOTED.
TO COMMON
DRAIN
SEE AIR SCHEMATIC SHEET
FOR SOLENOID BANK DETAILS
COMPRESSED
AIR TO SOLENOID
BANK
X X
TO FLOW
TOTALIZER
@ SH. 1
A
A
A1
A2
C1
C2
D1
D2
D3
F1
F2
C1
A1
A2
F2
F1
D2
C2
D1
D3
MAG
I P
C2
CV
NOTE 4
NOTE 4
NOTE 4
NOTE 4
8" TRAN
SVERSE
X X X X X X X X X
COMPRESSED AIR
TO AIR SCRUB
X
SAMPLE
TAP
100 MESH
CONE STRAINER
XXXXX
TURBIDIMETER
HACH 5300
1/2" NPT CONNECTION
TO COMMON
DRAIN (GRAVITY)
6"
8"
8"
8"
2"
4"
4"
8"
1/2"
3"
2"
FILTRATE CIP
RETURN (BLEED)
CIP FILTRATE RETURN BLEEDC3
C3
I P
CA-PCV-1098
CA-PI-1099
CA-AOV-1096
BCKW-AOV-1013
FT-PCV-1018
SAM-AOV-1052
SAM-AE-1016
SAM-AIT-1019
SAM-FE-1016
FT-PIT-1021
VT-AOV-1017
DR-AOV-1024
FT-AOV-1025
CIPR-AOV-1029
CIPR-AOV-1012 CIPR-FCV-1015
FWW-AOV-1010
CA-AOV-1006
CA-STR-1009
CA-PI-1007
PTW-PIT-1004
PTW-FIT-1005
CIPS-AOV-1003
DR-AOV-1022
CIPS-AOV-1023
RW-AOV-1030
PTW-FCV-1001
DR-AOV-1031
DR-AOV-1014
SS
120 VAC
SS
120 VAC
FWW-AOV-1002
I P
NKUTIL
Pen
NKUTIL
Callout Shall
DEBEST
Highlight
DEBEST
Callout
PALL
DEBEST
Cloud
DEBEST
Text Box THE LIMIT SWITCH FOR THESE VALVES APPEAR TO BE MISSING FROM THE SYSTEM INTERCONNECTION DETAILS. PLEASE VERIFY WIRING REQUIREMENTS
DrukeL Text Box
13. Pall Response: Pall response. Limit switch will be added to electrical drawings as requested.
DrukeL Text Box
15. Pall response. Pall shall provide the block and block valves. P&ID note will be updated.
DrukeL Text Box
14. Pall response. Pall will provide the spool pieces. P&ID comment will be updated. Pall Water will ensure that pricing adjusted accordingly for these valves.
DrukeL Text Box
12. Pall Response: Pall is considering making V1030 a spring return fail closed valve for shutdown protection. It would require a slow closing mechanism. See #12, page 10 for further shutdown comments.
LarkinD Line
C
D
A
B
C
D
12345678
12345678
DRAWING NUMBER
MATERIAL MASTER
DRAWING NAME
PROJECT ID
DWG SIZE
REVISION
SHEET OF
Copyright PALL CORPORATION This document may contain confidential technical data, including trade secrets proprietary to Pall Corporation. The drawing, design rights and all other disclosures in this document are the property of Pall
Corporation. Unauthorized use, copying, distribution to third parties, manufacture, or reproduction in whole or in part is prohibited.
PALL Corporation
PROJECT ENGINEER
ENGINEER
ENGINEER
ENGINEER
CHECKER
DRAWN BY
NAME DATE
UNLESS OTHERWISE SPECIFIED, THE FOLLOWING
INFORMATION PERTAINS ONLY TO THIS SHEET
SCALE
CODE INDENTIFICATION NO.
DO NOT SCALE
FROM DRAWING
THIRD ANGLE
PROJECTION
TOLERANCE
X. ±
.X ±
.XX ±
.XXX ±
FRACTION ±
ANGLE ± DEG
DIMENSIONS ARE IN
INCHES
ONLY
MILLIMETER
ONLY
IN [mm] mm [IN]
ALL FINISHED SURFACES
µIN µm
SEE SHEET 1 FOR REVISION
17238
These commodities, technology or software may only be exported from the United States in accordance with the
Export Administration
Regulations. Diversion contrary to U.S. law is prohibited.
IMPORTANT: BEFORE ATTEMPTING TO OPERATE OR INSTALL THIS SYSTEM, IT IS ESSENTIAL TO READ AND UNDERSTAND
THIS PRODUCT'S OPERATION AND MAINTENANCE MANUAL (SHIPPED UNDER SEPARATE COVER). FAILURE TO READ THE
OPERATION AND MAINTENANCE MANUAL BEFORE ATTEMPTING TO OPERATE ANY PALL CORPORATION EQUIPMENT MAY
RESULT IN SERIOUS PERSONAL INJURY AND/OR PRODUCT DAMAGE, AND VOID ANY AND/OR ALL WARRANTIES
.XXXX ±
Pall Advanced Separation Systems
Industrial, Cortland NY
CLEAN-IN-PLACE (CIP) DESIGN
B. HARRIS
01.000287
D
09SEP2017
D. LARKIN 19DEC2019
G. CEMPA 19DEC2019
R. HOM 19DEC2019
TEMPLATE REV: R2013.1
NO SCALE
X
1. ALL PIPING, TUBING, HARDWARE, FLEXIBLE CONNECTORS, AND FIELD WIRING ON THIS SHEET TO BE PROVIDED
AND INSTALLED BY OTHERS. ALL TANKS, VALVES, INSTRUMENTS & EQUIPMENT MARKED WITH (*) ON THIS
SHEET FURNISHED BY PALL FOR INSTALLATION BY OTHERS UNLESS OTHERWISE NOTED.
2. POWER CONTRACTORS LOCATED IN HEATER PANELS.
3. SOME LINE SIZES MAY CHANGE DEPENDING ON MODULE COUNT.
4. SEE AIR SUPPLY SCHEMATIC SHEET FOR TRANSFER PUMP AND VALVE.
5. VENT THROUGH ROOF.
6. CIP-TK-5101 AND CIP-TK-5001 ARE DOUBLE WALL TANKS. ALL INSTRUMENT, PIPE, ETC. PENETRATE TO INNER
TANK, EXCEPT THE LEAK DETECTION SENSORS: CIP-LD-5101 AND CIP-LD-5001.
CIP RETURN
SAMPLE TAP
TO 4' A.F.F.
PITCH PIPING BACK TO
RACKS WITH NO TRAPS
CIP FEED RETURN
VENT THROUGH
ROOF
RINSE (TANK FILL)
BACKFLOW
PREVENTER
RUN TO 4' A.F.F.
TO FLOOR DRAIN
BY OTHERS IF REQ'D
AIR VENT CAN BE ROUTED THROUGH THE
ROOF OR TO A FLOOR DRAIN WITH AIR GAP
PIPING HIGH
POINT
IF POTABLE WATER HARDNESS IS >180PPM
CaCO3 WATER SOFTENER IS REQUIRED
MUST BE REGULATED IF PRESSURE IS
GREATER THAN 70 PSI
ACID
CIP TANK
2500 GAL.
MAXIMUM
WORKING
VOLUME
OVERFLOW
80kW
EXPANSION JOINTS AS
REQUIRED BY OTHERS
SEE
NOTE 2
CAUSTIC
CIP/EFM TANK
4400 GAL.
MAXIMUM
WORKING
VOLUME
OVERFLOW
SAMPLE
TAP
80kW
EXPANSION JOINTS AS
REQUIRED BY OTHERS
SEE
NOTE 2
CIP RECLAMATION
SAMPLE
TAP
I
I
I
I
I
I
I
I
I
I
PCV
PCV
PCV
CIP-TK-5001
CIP-LIT-5006
CIP-LSLL-5003
CIP-LSHH-5002
* STW-AOV-6103
NA-PCV-5004
* NPW-AOV-5109
HCL-PCV-7104
CIP-HTR-5004*
PCV
PCV
CTA-PCV-5120
CTS-PCV-5501
CIP-TIT-5007
CIP-LIT-5106
CIP-LSLL-5103
CIP-LSHH-5102
CIP-TK-5101
CIP-HTR-5104*
CIP-TIT-5107
CIP-PCV-5121
CIP-AOV-5212
CIP-AOV-5132
CIP-AOV-5025
CIP-AOV-5227
CIP-PCV-5558
RUN SAMPLE TAP
TO 4' A.F.F.
TIE INTO DRAIN
PUMP SUCTION AT
SYSTEM LOW POINT
30 MESH
Y-STRAINER
30 MESH
Y-STRAINER
30 MESH
Y-STRAINER
TO DRAIN
BY OTHERS
TO DRAIN
BY OTHERS
CIP CIRCULATION PUMPS
300 GPM @ 70 FT.
10 HP @ 3500 RPM
(TYP. 2)
CIPS-STR-5207A
CIPS-STR-5207B
CIPS-PMP-5204A
CIPS-PMP-5204B
CIPS-PI-5239A
CIPS-PE-5239A
CIPS-FSL-5203A
CIPS-FSL-5203B
CIPS-PI-5239B
CIPS-PE-5239B
CIPS-AOV-5282A
CIPS-AOV-5282B
CIPS-AOV-5244B
CIPS-AOV-5244A
CIPS-AOV-5289
CIPS-AOV-5288*
CIPR-AIT-5619 CIPR-AIT-5605
ORP pH
CIPW-AOV-5217
CIPS-AOV-5218
CIPS-PI-5281A
CIPS-PE-5281A
CIPS-PI-5281B
CIPS-PE-5281B
CIPR-AOV-5216
CIP-AOV-5213
FROM
NEUT SYSTEM
THIS SHEET @ A6
HV
5281A
HV
5280A
HV
5281B
HV
5280B
HV
5255B
HV
5255A
HV
5239A
HV
5240A
HV
5239B
HV
5240B
HV
HV
HV
PCV
HV
CS
LG
LG
SET @ 50 PSIG
SET @ 5 PSIG
SET @ 5 PSIG
SET @ 5 PSIG
SET @
5 PSIG
SET @ 5 PSIG
CV
6"
4"
CIPR-FI-5619 CIPR-FI-5605
CIPR-AE-5619 CIPR-AE-5605
RECLAIM / DRAIN
CIP-LD-5101*
CIP-LD-5001
NOTE 5
NOTE 6
NOTE 6
NOTE 5
HV
CIP RECLAMATION
TANK CIRCULATION PUMP
50 GPM @ 25 FT.
0.75 HP @ 3500 RPM
CIPC-PMP-5101
HV
5124A
HV
HV
5123B
HV
5123A
HV
5124B
TANK CIRCULATION PUMP
50 GPM @ 25 FT.
0.75 HP @ 3500 RPM
CIPC-PMP-5001
HV
5024A
HV
HV
5023B
HV
5023A
HV
5024B
MAN
WAY
MAN
WAY
NKUTIL
Pen I
NKUTIL
Pen I
NKUTIL
Pen Too
NKUTIL
Text Box
NKUTIL
Pen I
NKUTIL
Pen I
NKUTIL
Pen Too
NKUTIL
Text Box
NKUTIL
Callout Add manual isolation valve here
NKUTIL
Arrow
NKUTIL
Text Box
NKUTIL
Text Box
NKUTIL
Pen x
NKUTIL
Cloud
NKUTIL
Callout Provide justification for tank recirculation pump
NKUTIL
Callout Provide justification for tank recirculation pump
NKUTIL
Cloud
NKUTIL
Cloud
NKUTIL
Callout This section of piping is not understood, please provide explanation.
NKUTIL
Cloud
NKUTIL
Callout What is the purpose of this valve? Please provide explanation.
NKUTIL
Callout Why increase to 1-inch?
NKUTIL
Callout Is 3/4" really necessary, seems 1/2" would be more than enough for the amount of chemical needed
NKUTIL
Callout Please change to 1/2"
NKUTIL
Callout 3/4"
NKUTIL
Pen
NKUTIL
Pen
NKUTIL
Callout 1/2"
NKUTIL
Arrow
NKUTIL
Pen
NKUTIL
Pen
NKUTIL
Arrow
NKUTIL
Arrow
NKUTIL
Callout 3/4" on SH.4
NKUTIL
Callout what is purpose of this valve
NKUTIL
Cloud
NKUTIL
Callout Softener is being provided by Pall
NKUTIL
Pen
NKUTIL
Pen
DEBEST
Cloud
DEBEST
Text Box PROVIDE OPEN/CLOSED LIMIT SWITCHES FOR THIS VAVLE AND CONNECT TO THE CIP CAUSTIC ROOM I/O PANEL
DEBEST
Cloud
DEBEST
Cloud
DEBEST
Text Box THESE DEVICES APPEAR TO BE MISSING FROM THE SYSTEM INTERCONNECTION DETAILS. ADD TO THE PALL MAIN CONTROL PANEL.
DEBEST
PolyLine
DrukeL Text Box
16. Pall response: Agreed. Softened water supply is shown at D1
DrukeL Text Box
17. Pall response: This sample valve may be deleted. The purpose is for WQ sampling and is not needed on the potable water line.
DrukeL Text Box
18. Pall response. Post CIP or EFM rack rinse will flow through V5242 direct to the Backwash Waste Tank
DrukeL Text Box Pall response: Pall currently does not have limit switches on vent valves. What is the purpose of providing this addition signal?
DrukeL Text Box
20. Pall response: Pall will add these valves as requested.
DrukeL Text Box
24. Pall response: RCI-057 was submitted to address this comment.
DrukeL Text Box Pall Response: AIT-5605 and AIT-5619 will be added to the next revision of the Interconnect Drawing.
DrukeL Text Box
21. Pall agrees this section of piping needs to be removed.
DrukeL Text Box
23. Pall Response: As discussed in the 1/17/2020 call with HDR/MSA/Pall, the recirculation pumps on Caustic and Acid tanks will be removed. They were added as required in the specification Pall will seek adjustment in pricing as considerable effort was spent meeting this specification requirement for the submittal of subject pumps.
DrukeL Text Box
22. Pall Response: Pall will add check valves downstream of each CIP recirc pump to prevent by-pass during several of rinse sequence steps. The exact check valve to use is undetermined as of 12-MAR-2020.
DrukeL Text Box Pall Response: LG5001 will be added using mechanical float type Level Indicator recommended by the tank manufacturer.
DrukeL Text Box Pall response. Pall will remove the comment from the P&ID as requested.
DrukeL Text Box Pall Response: Pall will add the asterisk to LG5101, the device will be provided by Pall. Pall will adjust pricing accordingly for added LG's on this sheet.
DrukeL Text Box
23. Pall response: As discussed in the 1/17/2020 call with HDR/MSA/Pall, the recirculation pumps on Caustic and Acid tanks will be removed. They were added as required in the specification.
DrukeL Text Box Pall Response: Pall is proposing 3/4 inch lines and valves for 6 gpm flows, all chemical except Calcium thiosulfate. refer to valve List responses.
DrukeL Text Box Pall Response: Pall is proposing 3/4 inch lines and valves for 6 gpm flows, all chemical except Calcium thiosulfate. Refer to valve list rsponses.
DrukeL Text Box
19. Pall response: Pall will change to 1/2". Refer to Valve List responses.
DrukeL Text Box
19. Pall response: Pall will change to 1/2". Refer to Valve List responses.
DrukeL
Pall Response: Pall is proposing 3/4 inch lines and valves for 6 gpm flows, all chemical except Calcium thiosulfate. refer to valve List responses.
C
D
A
B
C
D
12345678
12345678
DRAWING NUMBER
MATERIAL MASTER
DRAWING NAME
PROJECT ID
DWG SIZE
REVISION
SHEET OF
Copyright PALL CORPORATION This document may contain confidential technical data, including trade secrets proprietary to Pall Corporation. The drawing, design rights and all other disclosures in this document are the property of Pall
Corporation. Unauthorized use, copying, distribution to third parties, manufacture, or reproduction in whole or in part is prohibited.
PALL Corporation
PROJECT ENGINEER
ENGINEER
ENGINEER
ENGINEER
CHECKER
DRAWN BY
NAME DATE
UNLESS OTHERWISE SPECIFIED, THE FOLLOWING
INFORMATION PERTAINS ONLY TO THIS SHEET
SCALE
CODE INDENTIFICATION NO.
DO NOT SCALE
FROM DRAWING
THIRD ANGLE
PROJECTION
TOLERANCE
X. ±
.X ±
.XX ±
.XXX ±
FRACTION ±
ANGLE ± DEG
DIMENSIONS ARE IN
INCHES
ONLY
MILLIMETER
ONLY
IN [mm] mm [IN]
ALL FINISHED SURFACES
µIN µm
SEE SHEET 1 FOR REVISION
17238
These commodities, technology or software may only be exported from the United States in accordance with the
Export Administration
Regulations. Diversion contrary to U.S. law is prohibited.
IMPORTANT: BEFORE ATTEMPTING TO OPERATE OR INSTALL THIS SYSTEM, IT IS ESSENTIAL TO READ AND UNDERSTAND
THIS PRODUCT'S OPERATION AND MAINTENANCE MANUAL (SHIPPED UNDER SEPARATE COVER). FAILURE TO READ THE
OPERATION AND MAINTENANCE MANUAL BEFORE ATTEMPTING TO OPERATE ANY PALL CORPORATION EQUIPMENT MAY
RESULT IN SERIOUS PERSONAL INJURY AND/OR PRODUCT DAMAGE, AND VOID ANY AND/OR ALL WARRANTIES
.XXXX ±
Pall Advanced Separation Systems
Industrial, Cortland NY
CHEMICAL TRANSFER DESIGN
B. HARRIS
01.000287
D
09SEP2017
D. LARKIN 19DEC2019
G. CEMPA 19DEC2019
R. HOM 19DEC2019
TEMPLATE REV: R2013.1
NO SCALE
X
ACID TRANSFER PUMP
6 GPM @ 60 FT.
60 PSIG AIR.
1/2 X 1/2
BLENDED ACID
TANK
1. ALL PIPING, TUBING, HARDWARE, FLEXIBLE CONNECTORS, AND FIELD WIRING ON THIS
SHEET TO BE PROVIDED AND INSTALLED BY OTHERS. ALL TANKS, VALVES, INSTRUMENTS,
& EQUIPMENT MARKED WITH (*) ON THIS SHEET FURNISHED BY PALL FOR INSTALLATION
BY OTHERS UNLESS OTHERWISE NOTED.
2. SOME LINE SIZES MAY CHANGE DEPENDING ON MODULE COUNT.
30 MESH
MAG
HV
HV
HV
PISH
TOTE CONTAINMENT AND STAND
BY OTHERS
VENT
(TO OUTSIDE)
CTA-TK-7300 CC
CTA-STR-5114
CTA-CC-5110
CTA-PMP-5115
PSV
CTA-PSV-5100 *
CTA-PISH-5115
CTA-FIT-5121
CTA-PE-5115
CTA-AOV-5120
CTA-AOV-5124
CTA-FE-5121
LIT
5100 *
CTA-LIT-5100
HV
* HV
HV
20 L
SET @ 80 PSI
23-32% SULFURIC ACID
10-15% CITRIC ACID
DP
HV
X
PRV
X
SS
SV
*24 VDC
X X
X
XXX
CV
PI
* FI
XX
X X
X X
X X
XX
X
NKUTIL
Callout Does a valve on a vent line meet code?
NKUTIL
Pen
NKUTIL
Pen I
NKUTIL
Pen I
NKUTIL
Pen
NKUTIL
Pen
NKUTIL
Text Box Please use Diaphragm valve for reliability
NKUTIL
Arrow
NKUTIL
Arrow
NKUTIL
Arrow
NKUTIL
Arrow
NKUTIL
Arrow
NKUTIL
Arrow
NKUTIL
Arrow
NKUTIL
Callout Why not 1/2"? The pipe feeding it is 1/2". Please explain because it changes the current design
NKUTIL
Arrow
NKUTIL
Text Box
DrukeL Text Box
27. Pall Response: No comment, this piping is not in Pall's scope of design. Pall is proving a valve to be installed by Others. Please advise if calibration column vent line valves will be removed, then Pall will update the PID to reflect.
DrukeL Text Box
28. Pall response. The sizing of the chemical transfer lines are by Others. Pall increased the line sizes based on experience with pressure spikes that have occurred in other plants. This will be substantially mitigated with the pressure dampeners. Further discussion is required. Refer to Valve List comments, Pall is proposing 3/4" for 6 gpm flows, 1/2" for 2 gpm flows.
DrukeL
26. Pall Response: Pall shall adjust to diaphragm valves in locations requested. Following up discussions required to ensure proper ends supplied. Do you want flanged diaphragm valves as specified for NaOH service or are true union ends preferred? Pall suggests using the same valves throughout, why is there a need to mix diaphragm and ball valves?
C
D
A
B
C
D
12345678
12345678
DRAWING NUMBER
MATERIAL MASTER
DRAWING NAME
PROJECT ID
DWG SIZE
REVISION
SHEET OF
Copyright PALL CORPORATION This document may contain confidential technical data, including trade secrets proprietary to Pall Corporation. The drawing, design rights and all other disclosures in this document are the property of Pall
Corporation. Unauthorized use, copying, distribution to third parties, manufacture, or reproduction in whole or in part is prohibited.
PALL Corporation
PROJECT ENGINEER
ENGINEER
ENGINEER
ENGINEER
CHECKER
DRAWN BY
NAME DATE
UNLESS OTHERWISE SPECIFIED, THE FOLLOWING
INFORMATION PERTAINS ONLY TO THIS SHEET
SCALE
CODE INDENTIFICATION NO.
DO NOT SCALE
FROM DRAWING
THIRD ANGLE
PROJECTION
TOLERANCE
X. ±
.X ±
.XX ±
.XXX ±
FRACTION ±
ANGLE ± DEG
DIMENSIONS ARE IN
INCHES
ONLY
MILLIMETER
ONLY
IN [mm] mm [IN]
ALL FINISHED SURFACES
µIN µm
SEE SHEET 1 FOR REVISION
17238
These commodities, technology or software may only be exported from the United States in accordance with the
Export Administration
Regulations. Diversion contrary to U.S. law is prohibited.
IMPORTANT: BEFORE ATTEMPTING TO OPERATE OR INSTALL THIS SYSTEM, IT IS ESSENTIAL TO READ AND UNDERSTAND
THIS PRODUCT'S OPERATION AND MAINTENANCE MANUAL (SHIPPED UNDER SEPARATE COVER). FAILURE TO READ THE
OPERATION AND MAINTENANCE MANUAL BEFORE ATTEMPTING TO OPERATE ANY PALL CORPORATION EQUIPMENT MAY
RESULT IN SERIOUS PERSONAL INJURY AND/OR PRODUCT DAMAGE, AND VOID ANY AND/OR ALL WARRANTIES
.XXXX ±
Pall Advanced Separation Systems
Industrial, Cortland NY
CHEMICAL TRANSFER DESIGN
B. HARRIS
01.000287
D
09SEP2017
D. LARKIN 19DEC2019
G. CEMPA 19DEC2019
R. HOM 19DEC2019
TEMPLATE REV: R2013.1
NO SCALE
X
CALCIUM THIOSULFATE
TRANSFER PUMP
2 GPM @ 120 FT.
80 PSIG AIR.
1/4 X 1/4
40 MESH
MAG
HV
HV
PISH
HV
NC
1. ALL PIPING, TUBING, HARDWARE, FLEXIBLE CONNECTORS, AND FIELD WIRING ON THIS
SHEET TO BE PROVIDED AND INSTALLED BY OTHERS. ALL TANKS, VALVES, INSTRUMENTS,
& EQUIPMENT MARKED WITH (*) ON THIS SHEET FURNISHED BY PALL FOR INSTALLATION
BY OTHERS UNLESS OTHERWISE NOTED.
2. SOME LINE SIZES MAY CHANGE DEPENDING ON MODULE COUNT.
30% CALCIUM
THIOSULFATE
TANK
TOTE CONTAINMENT AND STAND
BY OTHERS
VENT
(TO OUTSIDE)
CTS-TK-5501
CTS-STR-5511
CTS-CC-5501
CTS-PMP-5502
CC
5501 PSV
CTS-PSV-5501
CTS-PE-5502CTS-PISH-5502
CTS-FIT-5505
CTS-FE-5505
PISH
PISH
AIT
AE
AIT
AE
SO₂ SO₂
CTS-AAH-5500B
CTS-AIT-5500A
CTS-AE-5500A
CTS-AIT-5500B
CTS-AE-5500B
CTS-AAH-5500A
SO₂ GAS ALARM HORN
SO₂ GAS ALARM BEACON
SO₂ GAS
DETECTOR #2
SO₂ GAS
DETECTOR #1
BY OTHERS
CTS-AOV-5558
CTS-AOV-5557
LIT
NC *
CTS-LIT-5502
HV
HV
HV
HV
10 L
SET @
80 PSI
HV
DP
HV
X
PRV
X
SS
SV
*24 VDC
X X
X
XXX
CV
XX
X X
X X
X X
XX
X
PI
* FI
NKUTIL
Callout This arrangement does not seem consistent with the pulsation dampener proposed. The submittal for the Wilden instrument implies that it would be inline. Revise PID or equipment offering. Typical all Pulsation Dampeners this project.
NKUTIL
Pen
NKUTIL
Pen
NKUTIL
Callout Not a part of this project
NKUTIL
Arrow
NKUTIL
Text Box Please use ball valve for ease of operation
NKUTIL
Callout Does a valve on a vent line meet code?
NKUTIL
Text Box
DrukeL Text Box
30. Pall response: Pall will correct the PID and show in-line pulsation dampener.
DrukeL Text Box
29. Pall Response: No comment, this piping is not in Pall's scope of design. Pall is proving a valve to be installed by Others. Please advise if calibration column vent line valves will be removed, then Pall will update the PID to reflect.
DrukeL Text Box
31. Pall Response: Pall will remove as requested.
DrukeL Text Box
32. Pall would prefer to provide the same type of valve throughout each chemical service, this will reduce spare parts. Discussion required.
DrukeL
Pall response. Pall will add the asterisk to this valve indicating Pall's scope of supply.
C
D
A
B
C
D
12345678
12345678
DRAWING NUMBER
MATERIAL MASTER
DRAWING NAME
PROJECT ID
DWG SIZE
REVISION
SHEET OF
Copyright PALL CORPORATION This document may contain confidential technical data, including trade secrets proprietary to Pall Corporation. The drawing, design rights and all other disclosures in this document are the property of Pall
Corporation. Unauthorized use, copying, distribution to third parties, manufacture, or reproduction in whole or in part is prohibited.
PALL Corporation
PROJECT ENGINEER
ENGINEER
ENGINEER
ENGINEER
CHECKER
DRAWN BY
NAME DATE
UNLESS OTHERWISE SPECIFIED, THE FOLLOWING
INFORMATION PERTAINS ONLY TO THIS SHEET
SCALE
CODE INDENTIFICATION NO.
DO NOT SCALE
FROM DRAWING
THIRD ANGLE
PROJECTION
TOLERANCE
X. ±
.X ±
.XX ±
.XXX ±
FRACTION ±
ANGLE ± DEG
DIMENSIONS ARE IN
INCHES
ONLY
MILLIMETER
ONLY
IN [mm] mm [IN]
ALL FINISHED SURFACES
µIN µm
SEE SHEET 1 FOR REVISION
17238
These commodities, technology or software may only be exported from the United States in accordance with the
Export Administration
Regulations. Diversion contrary to U.S. law is prohibited.
IMPORTANT: BEFORE ATTEMPTING TO OPERATE OR INSTALL THIS SYSTEM, IT IS ESSENTIAL TO READ AND UNDERSTAND
THIS PRODUCT'S OPERATION AND MAINTENANCE MANUAL (SHIPPED UNDER SEPARATE COVER). FAILURE TO READ THE
OPERATION AND MAINTENANCE MANUAL BEFORE ATTEMPTING TO OPERATE ANY PALL CORPORATION EQUIPMENT MAY
RESULT IN SERIOUS PERSONAL INJURY AND/OR PRODUCT DAMAGE, AND VOID ANY AND/OR ALL WARRANTIES
.XXXX ±
Pall Advanced Separation Systems
Industrial, Cortland NY
CHEMICAL TRANSFER DESIGN
B. HARRIS
01.000287
D
09SEP2017
D. LARKIN 19DEC2019
G. CEMPA 19DEC2019
R. HOM 19DEC2019
TEMPLATE REV: R2013.1
NO SCALE
X
NaOH TRANSFER PUMP
6 GPM @ 60 FT.
60 PSIG AIR.
1/2 X 1/2
30 MESH
MAG
PISH
NC
25% NaOH
TANK
TOTE CONTAINMENT AND STAND
BY OTHERS
VENT
(TO OUTSIDE)
NA-TK-5010 CC
* NA-CC-5010
NA-STR-5032 NA-PMP-5015
PSV
NA-PSV-5015
NA-PE-5015
1. ALL PIPING, TUBING, HARDWARE, FLEXIBLE CONNECTORS, AND FIELD WIRING ON THIS
SHEET TO BE PROVIDED AND INSTALLED BY OTHERS. ALL TANKS, VALVES, INSTRUMENTS,
& EQUIPMENT MARKED WITH (*) ON THIS SHEET FURNISHED BY PALL FOR INSTALLATION
BY OTHERS UNLESS OTHERWISE NOTED.
2. SOME LINE SIZES MAY CHANGE DEPENDING ON MODULE COUNT.
NA-PISH-5015
NA-FIT-5017
NA-FE-5017 NA-AOV-5018*
LIT
NC
NA-LIT-5010
HV
HV
HV
HV
HV
HV
20 L
SET @
80 PSI
DP
HV
X
PRV
X
SS
SV
*24 VDC
X X
X
XXX
CV
XX
X X
X X
X X
XXX
X
PI
* FI
NKUTIL
Callout Does a valve on a vent line meet code?
NKUTIL
Text Box Please use ball valve for ease of operation
NKUTIL
Arrow
NKUTIL
Text Box
DrukeL Text Box Pall Response: No comment, this piping is not in Pall's scope of design. Pall is proving a valve to be installed by Others. Please advise if calibration column vent line valves will be removed, then Pall will update the PID to reflect.
DrukeL Text Box Pall response. Pall will correct the PID and show in-line pulsation dampener.
DrukeL
33. Pall Response: Pall would prefer to provide the same type of valve throughout each chemical service, this will reduce spare parts. Discussion required. Refer to Valve List responses.
C
D
A
B
C
D
12345678
12345678
DRAWING NUMBER
MATERIAL MASTER
DRAWING NAME
PROJECT ID
DWG SIZE
REVISION
SHEET OF
Copyright PALL CORPORATION This document may contain confidential technical data, including trade secrets proprietary to Pall Corporation. The drawing, design rights and all other disclosures in this document are the property of Pall
Corporation. Unauthorized use, copying, distribution to third parties, manufacture, or reproduction in whole or in part is prohibited.
PALL Corporation
PROJECT ENGINEER
ENGINEER
ENGINEER
ENGINEER
CHECKER
DRAWN BY
NAME DATE
UNLESS OTHERWISE SPECIFIED, THE FOLLOWING
INFORMATION PERTAINS ONLY TO THIS SHEET
SCALE
CODE INDENTIFICATION NO.
DO NOT SCALE
FROM DRAWING
THIRD ANGLE
PROJECTION
TOLERANCE
X. ±
.X ±
.XX ±
.XXX ±
FRACTION ±
ANGLE ± DEG
DIMENSIONS ARE IN
INCHES
ONLY
MILLIMETER
ONLY
IN [mm] mm [IN]
ALL FINISHED SURFACES
µIN µm
SEE SHEET 1 FOR REVISION
17238
These commodities, technology or software may only be exported from the United States in accordance with the
Export Administration
Regulations. Diversion contrary to U.S. law is prohibited.
IMPORTANT: BEFORE ATTEMPTING TO OPERATE OR INSTALL THIS SYSTEM, IT IS ESSENTIAL TO READ AND UNDERSTAND
THIS PRODUCT'S OPERATION AND MAINTENANCE MANUAL (SHIPPED UNDER SEPARATE COVER). FAILURE TO READ THE
OPERATION AND MAINTENANCE MANUAL BEFORE ATTEMPTING TO OPERATE ANY PALL CORPORATION EQUIPMENT MAY
RESULT IN SERIOUS PERSONAL INJURY AND/OR PRODUCT DAMAGE, AND VOID ANY AND/OR ALL WARRANTIES
.XXXX ±
Pall Advanced Separation Systems
Industrial, Cortland NY
CHEMICAL TRANSFER DESIGN
B. HARRIS
01.000287
D
09SEP2017
D. LARKIN 19DEC2019
G. CEMPA 19DEC2019
R. HOM 19DEC2019
TEMPLATE REV: R2013.1
NO SCALE
X
1. ALL PIPING, TUBING, HARDWARE, FLEXIBLE CONNECTORS, AND FIELD WIRING ON THIS
SHEET TO BE PROVIDED AND INSTALLED BY OTHERS. ALL TANKS, VALVES, INSTRUMENTS,
& EQUIPMENT MARKED WITH (*) ON THIS SHEET FURNISHED BY PALL FOR INSTALLATION
BY OTHERS UNLESS OTHERWISE NOTED.
2. SOME LINE SIZES MAY CHANGE DEPENDING ON MODULE COUNT
3. SEE AIR SUPPLY SCHEMATIC SHEET FOR TRANSFER PUMP AND VALVES.
4. MAGNETIC SIGHT GLASS TO INDICATE TANK LEVEL
LI
LSHH
LSLL
12.5%
NaOCL
TANK #1
[HCL-TK-7101]
12.5%
NaOCL
TANK #2
[HCL-TK-7102]
HCL-LI-7101
HCL-LSHH-7101
HCL-LSLL-7101
LE
LIT
HCL-LIT-7101
HCL-LE-7101
LE
LIT
HCL-LIT-7102
HCL-LE-7102ZSOZSC
STW-MOV-7111
ZSCZSO
STW-MOV-7101
ZSCZSO
STW-MOV-7102
ZSOZSC
STW-MOV-7111
LI
HCL-LI-7102
LSHH
LSLL
HCL-LSHH-7102
HCL-LSLL-7102
30 MESH
HCL-STR-5415
VENT TO OUTSIDE
PI
HCL-PMP-7100
HCL RECIRC PUMP
NaOCL CONTAINMENT SUMP AREA
LSH
HCL-LI-7103
SODIUM HYPOCHLORITE
CHEMICAL FEED STATION
HCL-CPNL-7100 NaOCI TRANSFER PUMP
6 GPM @ 60 FT.
80 PSIG AIR.
1/2 X 1/2
(SEE NOTE 3)
MAG
HV
PISH
NC*
PSV
5402 *
HCL-PSV-5402 *
HCL-PISH-5402 HCL-PE-5402
HCL-FIT-5405
HCL-FE-5405
HCL METERING PUMP #1
[HCL-PMP-7101]
1/2 X 1/2
(BY OTHERS)
PISH
NC
HCL-PSV-7101
HCL-PISH-7101 HCL-PE-7101
HCL-PMP-5402
HCL METERING PUMP #2
[HCL-PMP-7102]
1/2 X 1/2
(BY OTHERS)
PISH
NC
HCL-PSV-7102
HCL-PISH-7102 HCL-PE-7102
HCL-CC-7102
(NOTE 4) (NOTE 4)
FILL STATION
HV
*DP
HV
HV
HV
HV
PRV
SS
SV
24 VDC
X X
X
XXX X X X
HV
CV
5402 *
XX
X X
X X
X X
XXX
X
PI
F
NKUTIL
Pen
NKUTIL
Pen
NKUTIL
Pen
NKUTIL
Text Box 6%
NKUTIL
Text Box 6%
DEBEST
Cloud
DEBEST
Cloud
DEBEST
Cloud
DEBEST
Cloud
DEBEST
PolyLine
DEBEST
PolyLine
DEBEST
Cloud
DEBEST
Cloud
DEBEST
Cloud
DEBEST
Cloud
DEBEST
Text Box THESE DEVICES APPEAR TO BE MISSING FROM THE SYSTEM INTERCONNECTION DETAILS; ADD TO THE CIP CAUSTIC ROOM I/O PANEL
DEBEST
Text Box THESE DEVICES APPEAR TO BE MISSING FROM THE SYSTEM INTERCONNECTION DETAILS; ADD TO THE CIP CAUSTIC ROOM I/O PANEL
DEBEST
PolyLine
DEBEST
PolyLine
DEBEST
Cloud
DEBEST
Text Box THE RECIRC PUMP APPEARS TO BE MISSING FROM THE SYSTEM INTERCONNECTION DETAILS; ADD TO THE PALL MAIN CONTROL PANEL
DEBEST
Line
DEBEST
Cloud
DEBEST
Text Box
CHANGE HCL TO BE NAOCL (TYP ALL)
DrukeL Text Box
34. Pall response: Pall will change to 6% NaOCl for solution used in the MF CIP.
DrukeL Text Box
35. Pall Response: Pall scope only includes metering of NaOCl solution to support MF CIP operations and does not include generation of 6% NaOCl, metering to Filtrate Water or Export, therefore the nine (9) devices cited above are not under control by the Pall system. If this scope of control / supply is being requested of Pall Water this will need to be defined as there are question on how this process is to be controlled and had not been considered within the current contract.
DrukeL Text Box Pall Response. Pall will correct the PID and show in-line pulsation dampener.
DrukeL
Pall response. Pall will remove HV7100 from it's scope of supply.
C
D
A
B
C
D
12345678
12345678
DRAWING NUMBER
MATERIAL MASTER
DRAWING NAME
PROJECT ID
DWG SIZE
REVISION
SHEET OF
Copyright PALL CORPORATION This document may contain confidential technical data, including trade secrets proprietary to Pall Corporation. The drawing, design rights and all other disclosures in this document are the property of Pall
Corporation. Unauthorized use, copying, distribution to third parties, manufacture, or reproduction in whole or in part is prohibited.
PALL Corporation
PROJECT ENGINEER
ENGINEER
ENGINEER
ENGINEER
CHECKER
DRAWN BY
NAME DATE
UNLESS OTHERWISE SPECIFIED, THE FOLLOWING
INFORMATION PERTAINS ONLY TO THIS SHEET
SCALE
CODE INDENTIFICATION NO.
DO NOT SCALE
FROM DRAWING
THIRD ANGLE
PROJECTION
TOLERANCE
X. ±
.X ±
.XX ±
.XXX ±
FRACTION ±
ANGLE ± DEG
DIMENSIONS ARE IN
INCHES
ONLY
MILLIMETER
ONLY
IN [mm] mm [IN]
ALL FINISHED SURFACES
µIN µm
SEE SHEET 1 FOR REVISION
17238
These commodities, technology or software may only be exported from the United States in accordance with the
Export Administration
Regulations. Diversion contrary to U.S. law is prohibited.
IMPORTANT: BEFORE ATTEMPTING TO OPERATE OR INSTALL THIS SYSTEM, IT IS ESSENTIAL TO READ AND UNDERSTAND
THIS PRODUCT'S OPERATION AND MAINTENANCE MANUAL (SHIPPED UNDER SEPARATE COVER). FAILURE TO READ THE
OPERATION AND MAINTENANCE MANUAL BEFORE ATTEMPTING TO OPERATE ANY PALL CORPORATION EQUIPMENT MAY
RESULT IN SERIOUS PERSONAL INJURY AND/OR PRODUCT DAMAGE, AND VOID ANY AND/OR ALL WARRANTIES
.XXXX ±
Pall Advanced Separation Systems
Industrial, Cortland NY
COMPRESSED AIR DESIGN
B. HARRIS
01.000287
D
09SEP2017
D. LARKIN 19DEC2019
G. CEMPA 19DEC2019
R. HOM 19DEC2019
TEMPLATE REV: R2013.1
NO SCALE
X
1. ALL EQUIPMENT, VALVES, AND INSTRUMENTS ON THIS SHEET
FURNISHED BY PALL. ALL PIPING, WIRING, TUBING, HARDWARE,
AND INSTALLATION BY OTHERS.
2. BLEED SLIGHT FLOW THROUGH SIDE PORT OF VALVE TO INSURE
DEW POINT SENSOR HAS CONTINUOUSLY REFRESHED SAMPLE AIR.
X XX
1040 GAL.
200 PSIG
RATED
X XX
COMPRESSOR ASSEMBLY WITH
INTERNAL DRYER & FILTERS
20 H.P. 81 SCFM @ 150 PSIG.
460 VAC, 3 PH
(TYP. 2) - N+1 DESIGN
PSIG
SET
PSIG
SET
PSIG
SET
PSIG
SET
216 SCFM
[252 SCFM FUTURE]X
X
X X
X X
X X
X X
X X
X X
X X
X X
XXXXXXXXXXXX
XXX
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X
XX
XX XXX
XXX
X XXXXXX
X XXXXXX
X X X X X X X X X X X X X X X X X X X X X X
X X
X X
X X
X X
X
X X X X X X X X X X X X X X X X
XXXX
XXXX XX
X X
X X
X X
X X
XXX XX
X
X
X X
X
NC
CV
I P
I P
VENT
SEE NOTE 2
[FIT-6035 A & B] ARE NPT CONNECTIONS
BUT CUSTOMER NEEDS TO INSTALL
FLANGES FOR MAINTENANCE
CA-CMP-6001
CA-CMP-6002
CA-PI-6018
CA-PSL-6001
CA-PIT-6011
CA-PSV-6012
CA-PCV-6019
CA-PI-6020
CA-FIT-6035
CA-AOV-6034
CA-PCV-6020
CA-PI-6021
CA-FIT-6036
CA-AOV-6035
CA-PCV-6016
CA-PI-6016
CA-PCV-6017
CA-PCI-6017
ADV
DR-SOV-6010
T120 VAC
CA-RCVR-6010
0.2
MICRON
X
X
X
0.2
MICRON
X
X
X
0.2
MICRON
0.2
MICRON
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X
X 1040 GAL.
200 PSIG
RATED
XXXXXX
XX
X
CA-PI-6018
CA-PSL-6041
CA-PIT-6041
CA-PSV-6042
ADV
DR-SOV-6040
T120 VAC
CA-RCVR-6040
X X
X X
NKUTIL
Callout Please describe this, symbol not on legend, is this a solenoid valve?
DEBEST
Cloud
DEBEST
Text Box
APPEARS TO BE MISSING FROM THE INSTRUMENT LIST
DEBEST
Cloud
DEBEST
Text Box
APPEARS TO BE MISSING FROM THE INSTRUMENT LIST
DrukeL Text Box
37. Pall Response: Pall will add these pressure gages to the next revision of the Instrument List.
DrukeL Text Box
36. Pall response. Added to legend. This in an automatic condensate drain valve, refer to submittal NYCS000015358.
DrukeL
37. Pall Response: Pall will add these pressure gages to the next revision of the Instrument List.
C
D
A
B
C
D
12345678
12345678
DRAWING NUMBER
MATERIAL MASTER
DRAWING NAME
PROJECT ID
DWG SIZE
REVISION
SHEET OF
Copyright PALL CORPORATION This document may contain confidential technical data, including trade secrets proprietary to Pall Corporation. The drawing, design rights and all other disclosures in this document are the property of Pall
Corporation. Unauthorized use, copying, distribution to third parties, manufacture, or reproduction in whole or in part is prohibited.
PALL Corporation
PROJECT ENGINEER
ENGINEER
ENGINEER
ENGINEER
CHECKER
DRAWN BY
NAME DATE
UNLESS OTHERWISE SPECIFIED, THE FOLLOWING
INFORMATION PERTAINS ONLY TO THIS SHEET
SCALE
CODE INDENTIFICATION NO.
DO NOT SCALE
FROM DRAWING
THIRD ANGLE
PROJECTION
TOLERANCE
X. ±
.X ±
.XX ±
.XXX ±
FRACTION ±
ANGLE ± DEG
DIMENSIONS ARE IN
INCHES
ONLY
MILLIMETER
ONLY
IN [mm] mm [IN]
ALL FINISHED SURFACES
µIN µm
SEE SHEET 1 FOR REVISION
17238
These commodities, technology or software may only be exported from the United States in accordance with the
Export Administration
Regulations. Diversion contrary to U.S. law is prohibited.
IMPORTANT: BEFORE ATTEMPTING TO OPERATE OR INSTALL THIS SYSTEM, IT IS ESSENTIAL TO READ AND UNDERSTAND
THIS PRODUCT'S OPERATION AND MAINTENANCE MANUAL (SHIPPED UNDER SEPARATE COVER). FAILURE TO READ THE
OPERATION AND MAINTENANCE MANUAL BEFORE ATTEMPTING TO OPERATE ANY PALL CORPORATION EQUIPMENT MAY
RESULT IN SERIOUS PERSONAL INJURY AND/OR PRODUCT DAMAGE, AND VOID ANY AND/OR ALL WARRANTIES
.XXXX ±
Pall Advanced Separation Systems
Industrial, Cortland NY
WATER SOFTENERS OVERVIEW
B. HARRIS
01.000287
D
09SEP2017
D. LARKIN 19DEC2019
G. CEMPA 19DEC2019
R. HOM 19DEC2019
TEMPLATE REV: R2013.1
NO SCALE
X
TO CAUSTIC
CIP
BRINE TANK
150 GAL
WATER
SOFTENER
#1
WATER
SOFTENER
#2
TO HOSE BIBBS
TRUCK LOADOUT
STATION
PI
6901*
BY-PASS
SVW-PRV-6900
NPW-WS-6901 NPW-WS-6902
STW-PI-6901
NPW-T-6902
CONTROLCONTROL
1. ALL PIPING, TUBING, HARDWARE, FLEXIBLE CONNECTORS, AND FIELD WIRING ON THIS
SHEET TO BE PROVIDED AND INSTALLED BY OTHERS. ALL TANKS, VALVES, INSTRUMENTS,
& EQUIPMENT MARKED WITH (*) ON THIS SHEET FURNISHED BY PALL FOR INSTALLATION
BY OTHERS UNLESS OTHERWISE NOTED.
2. WATER SOFTENER DOES NOT COME WITH ANY INTERCONNECT PIPING.
HV
HV
HV
HV
HV
HV
HV
6901 HV
SET @ 80 PSIG
FM
NOTE 2
20 GPM
120 GPM @ 50 PSIG
N+1 DESIGN
FM
STW-FM-6900
C
D
A
B
C
D
12345678
12345678
DRAWING NUMBER
MATERIAL MASTER
DRAWING NAME
PROJECT ID
DWG SIZE
REVISION
SHEET OF
Copyright PALL CORPORATION This document may contain confidential technical data, including trade secrets proprietary to Pall Corporation. The drawing, design rights and all other disclosures in this document are the property of Pall
Corporation. Unauthorized use, copying, distribution to third parties, manufacture, or reproduction in whole or in part is prohibited.
PALL Corporation
PROJECT ENGINEER
ENGINEER
ENGINEER
ENGINEER
CHECKER
DRAWN BY
NAME DATE
UNLESS OTHERWISE SPECIFIED, THE FOLLOWING
INFORMATION PERTAINS ONLY TO THIS SHEET
SCALE
CODE INDENTIFICATION NO.
DO NOT SCALE
FROM DRAWING
THIRD ANGLE
PROJECTION
TOLERANCE
X. ±
.X ±
.XX ±
.XXX ±
FRACTION ±
ANGLE ± DEG
DIMENSIONS ARE IN
INCHES
ONLY
MILLIMETER
ONLY
IN [mm] mm [IN]
ALL FINISHED SURFACES
µIN µm
SEE SHEET 1 FOR REVISION
17238
These commodities, technology or software may only be exported from the United States in accordance with the
Export Administration
Regulations. Diversion contrary to U.S. law is prohibited.
IMPORTANT: BEFORE ATTEMPTING TO OPERATE OR INSTALL THIS SYSTEM, IT IS ESSENTIAL TO READ AND UNDERSTAND
THIS PRODUCT'S OPERATION AND MAINTENANCE MANUAL (SHIPPED UNDER SEPARATE COVER). FAILURE TO READ THE
OPERATION AND MAINTENANCE MANUAL BEFORE ATTEMPTING TO OPERATE ANY PALL CORPORATION EQUIPMENT MAY
RESULT IN SERIOUS PERSONAL INJURY AND/OR PRODUCT DAMAGE, AND VOID ANY AND/OR ALL WARRANTIES
.XXXX ±
Pall Advanced Separation Systems
Industrial, Cortland NY
AIR SCHEMATIC DESIGN
B. HARRIS
01.000287
D
09SEP2017
D. LARKIN 19DEC2019
G. CEMPA 19DEC2019
R. HOM 19DEC2019
TEMPLATE REV: R2013.1
NO SCALE
X
V5132
CONTINUED
@ ZONE D5
1 2 3 4 5 76
TYPE ``B''V5109
VALVE SOLENOID BANK8 9
COMPRESSED AIR AREA
COMPRESSED AIR SUPPLY
TYPE ``B''
TYPE ``B''
VALVE SOLENOID BANK
V5120
V5227
V5212
CIP ACID TANK ROOM
OFF SKID CIP PUMP &
CIP SYSTEM VALVES
(FIELD TUBED)
1 2 3 4 5 76
FEED AREA
V3203A
V3203B
OFF SKID FEED STRAINER VALVES
(FIELD TUBED)
1 2 3 4 65
VALVE SOLENOID BANK8
SPRING RETURN
VALVE RACK #2
ALL VALVES ARE TYPE "A" UNLESS OTHERWISE NOTED.
2. SOLENOID BANKS, VALVES, AND SKIDS SUPPLIED BY PALL.
3. ISOLATION VALVES TO BE INSTALLED AS REQUIRED BY OTHERS.
4. FIELD TUBING TO BE SST, POLY OR COPPER.
5. REFER TO THE PROJECT SPECIFIC ELECTRICAL DRAWINGS FOR FOR THE
ACTUAL ORIENTATION OF VALVES IN RELATION TO THE SOLENOID BANKS.
6. FOR V-5018 & V-5019 ADJUST SPEED CONTROLS ON PORTS 3 & 5 TO BE
1/4 OF A TURN FROM BEING CLOSED.
(B)
SEE NOTE 6
(A)
VALVE SOLENOID BANK
X X
X X
X X
X X
X
V1010
SPARE
TYPE ``B''
61 2 3 4 5
X X
X X
X
X X
X X X
X X X
X X
X
X X X X
FCV1001
X X
X X
X X
X X
X X
X
X X
X X
X X
X
V1003
X X
X
V1013
FCV1018
V1017
2216 17 18 19 20 2111 12 13 14 157 8 9 10
V1025
V1022
V1023
V1024
V1030
V1031
OFF SKID BLOCK & BLEED VALVES
(FIELD TUBED)
X X
X X
X X
X X
X X
X X
X X
X
V1006
MF VALVE RACK #1 (TYP. MF VALVE RACK)AIR SUPPLY
CONTINUED FROM
ZONE A7
TYPE ``B'' SPARE
(B)
(A)
2 4
(B)
DOUBLE ACTING
(A)
142 4
FCV6034A
FCV6034B
V5558
XXX
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X X X
X X X X
X X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X
X X
X X
X
X X
X
X X
X X
X X
X X X
X X
X X
X X
X
X X
X X
X X
X X
X X
X X
X X
X X
X
X X
X X
9 10
T Y P E `B
X X
X X
X X
X X
X X
TYPE ``B'' SPARE
X X
X X
X X
X X
X X
X
V5242
PI
X
ON RACK VALVES
FACTORY TUBED
AIR SUPPLY
3 5
3 5
X X
X X
TO ACTUATED
VALVE CYLINDER
X X
TO ACTUATED
VALVE CYLINDER
2 4X X
TO PUMP
P-XXXX
11 12
X X
AIR SUPPLY
X X
AIR SUPPLY
TYPE ``B'' V3119
X X
X
VALVE RACK #3X X
X X
X X
X X
X X
X X
X
V1012
V1014
V1029
X X
X X
X X
X X
X X
X X
X X
X X
X
X X
V5124
X X
X
SPARE
X
SPARE
V5557
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
13 14 15 16
X
X
X X
X X
X
X X
X
SPARE
X X
X X
X X
X X
X X
X X
X
X X
X X
X
X X
X X
ELECTRICAL ENCLOSURE
CIP-CPNL-5201
ELECTRICAL ENCLOSURE
CIP-CPNL-5001
CIP CAUSTIC TANK ROOM
CIP TRANSFER VALVES
(FIELD TUBED)
ELECTRICAL ENCLOSURE
CIP-CPNL-5101
ELECTRICAL ENCLOSURE
WT-CPNL-1000A
X X X
VALVE RACK #4
ELECTRICAL ENCLOSURE
WT-CPNL-1000B
ELECTRICAL ENCLOSURE
WT-CPNL-1000C
ELECTRICAL ENCLOSURE
WT-CPNL-1000D
16 17 18 19 2013 14 15
TYPE ``A''
X X
X X
X X
X X
X X
V5216
X X
X X
X X
X X
X
V5213
X X
X X
X X
X X
V5025
X X
X X
X X
X X
V5244A
X X
X X
X X
X
V5244B
X X
X X
X X
V5217
X X
X X
X
V5282A
X X
X X
V5282B
X X
X
V5289
X X
X
V5218
X X
V5288
X
V5018
SPARE
X X
SPARE
X X
SPARE
X X
X
SPARE
X X
X X
SPARE
X X
X X
X
V5009
X X
X X
X X
X X
X
X X
X X
X SPARE
SPARE
SPARE
SPARE
SPARE
TYPE ``A''
TYPE ``A''
TYPE ``B''
TYPE ``A''
TYPE ``A''
TYPE ``A''
TYPE ``A''
TYPE ``A''
TYPE ``A''
TYPE ``A''
TYPE ``A''
TYPE ``A''
TYPE ``A''
TYPE ``A''
TYPE ``A''
TYPE ``A''
TYPE ``A''
TYPE ``A''
TYPE ``A''
TYPE ``B''
X X
FCV1015
DrukeL
12. Pall to add pneumatic air signal interlock to slowdown closure of control valves FCV-1001 and FCV-1018 on a rapid system shutdown.
C
D
A
B
C
D
12345678
12345678
DRAWING NUMBER
MATERIAL MASTER
DRAWING NAME
PROJECT ID
DWG SIZE
REVISION
SHEET OF
Copyright PALL CORPORATION This document may contain confidential technical data, including trade secrets proprietary to Pall Corporation. The drawing, design rights and all other disclosures in this document are the property of Pall
Corporation. Unauthorized use, copying, distribution to third parties, manufacture, or reproduction in whole or in part is prohibited.
PALL Corporation
PROJECT ENGINEER
ENGINEER
ENGINEER
ENGINEER
CHECKER
DRAWN BY
NAME DATE
UNLESS OTHERWISE SPECIFIED, THE FOLLOWING
INFORMATION PERTAINS ONLY TO THIS SHEET
SCALE
CODE INDENTIFICATION NO.
DO NOT SCALE
FROM DRAWING
THIRD ANGLE
PROJECTION
TOLERANCE
X. ±
.X ±
.XX ±
.XXX ±
FRACTION ±
ANGLE ± DEG
DIMENSIONS ARE IN
INCHES
ONLY
MILLIMETER
ONLY
IN [mm] mm [IN]
ALL FINISHED SURFACES
µIN µm
SEE SHEET 1 FOR REVISION
17238
These commodities, technology or software may only be exported from the United States in accordance with the
Export Administration
Regulations. Diversion contrary to U.S. law is prohibited.
IMPORTANT: BEFORE ATTEMPTING TO OPERATE OR INSTALL THIS SYSTEM, IT IS ESSENTIAL TO READ AND UNDERSTAND
THIS PRODUCT'S OPERATION AND MAINTENANCE MANUAL (SHIPPED UNDER SEPARATE COVER). FAILURE TO READ THE
OPERATION AND MAINTENANCE MANUAL BEFORE ATTEMPTING TO OPERATE ANY PALL CORPORATION EQUIPMENT MAY
RESULT IN SERIOUS PERSONAL INJURY AND/OR PRODUCT DAMAGE, AND VOID ANY AND/OR ALL WARRANTIES
.XXXX ±
Pall Advanced Separation Systems
Industrial, Cortland NY
LEGEND
B. HARRIS
01.000287
D
09SEP2017
D. LARKIN 19DEC2019
G. CEMPA 19DEC2019
R. HOM 19DEC2019
TEMPLATE REV: R2013.1
NO SCALE
X
VALVE SYMBOLS
(PALL)(CUSTOMER)
PUMP SYMBOLS STRAINER SYMBOLS
PRESSURE CALIBRATION
MANIFOLD (2 VALVE UNIT)
FLOWMETER-
GEAR DISPLACEMENT
TEMPERATURE TRANSMITTER
TEMPERATURE SWITCH LOW LOW
TEMPERATURE SWITCH LOW
TEMPERATURE SWITCH HIGH HIGH
TEMPERATURE SWITCH HIGH
TEMPERATURE RECORDER CONTROLLER
TEMPERATURE LIMIT HIGH
TEMPERATURE INDICATING TRANSMITTER
TEMPERATURE INDICATING CONTROLLER
TEMPERATURE INDICATOR
TEMPERATURE ELEMENT
TEMPERATURE CONTROL VALVE
TEMPERATURE CONTROLLER (BLIND)
LEVEL TRANSMITTER (BLIND)
LEVEL SWITCH LOW LOW
LEVEL SWITCH HIGH HIGH
LEVEL RECORDING CONTROLLER
LEVEL INDICATING TRANSMITTER
LEVEL INDICATING CONTROLLER
LEVEL CONTROL VALVE
LEVEL CONTROLLER (BLIND)
TEMPERATURE INSTRUMENTS
LEVEL INSTRUMENTS
TSLL
TT
TI
TRC
TSHH
TSL
TSH
TLH
TIT
TIC
TE
TCV
TC
LT
LEVEL SWITCH MID
LEVEL SWITCH LOW
LEVEL SWITCH HIGH
LEVEL RECORDER
LSLL
LSHH
LSM
LSL
LSH
LRC
LR
LIT
LEVEL INDICATOR
LEVEL GAGE GLASS
LEVEL ELEMENT
LCV
LIC
LI
LG
LE
LC
PRESSURE DIFFERENTIAL
PRESSURE TRANSMITTER (BLIND)
PRESSURE SWITCH LOW LOW
PRESSURE SWITCH LOW
PRESSURE SWITCH HIGH HIGH
PRESSURE SWITCH HIGH
PRESSURE RECORDER CONTROLLER
PRESSURE INDICATING TRANSMITTER
PRESSURE INDICATING SWITCH
PRESSURE INDICATING CONTROLLER
PRESSURE HAND CONTROL (REGULATOR)
DIFFERENTIAL PRESSURE SWITCH
DIFFERENTIAL PRESSURE INDICATOR
DIFFERENTIAL PRESSURE HIGH HIGH
DIFFERENTIAL PRESSURE HIGH
PRESSURE DIFFERENTIAL CONTROLLER
PRESSURE CONTROLLER (BLIND)
DIFFERENTIAL SET POINT INDICATOR
FLOW SWITCH LOW LOW
FLOW SWITCH HIGH HIGH
FLOW RECORDER CONTROLLER
FLOW TOTALIZER CONTROLLER
FLOW INDICATOR TRANSMITTER
FLOW INDICATOR CONTROLLER
FLOW RATIO CONTROLLER
FLOW CONTROLLER (BLIND)
FLOW INSTRUMENTS
PRESSURE INSTRUMENTS
PRESSURE RECORDER
PSL
PSLL
PT
PSHH
PSH
PRC
PR
PRESSURE LIMIT HIGH
PRESSURE INDICATOR
PLH
PIT
PIS
PIC
PDIC
PHC
PDS
PI
PDHH
PDH
PDC
PDI
DSPI
PC
FLOW INTEGRATOR
FLOW SWITCH LOW
FLOW SWITCH HIGH
FSLL
FX
FSHH
FSL
FSH
FRC
FLOW RECORDER
FLOW TOTALIZER
FLOW METER
FLOW INDICATOR
FR
FQC
FQ
FM
FIT
FIC
FI
FLOW ELEMENT
FLOW CONTROL VALVE
FFC
FE
FCV
FC
ZSRC
ZS
ZSC
XR
Y
WIT
VFD
VFC
V
UA
TW
LIMIT SWITCH OPEN & CLOSED
LIMIT SWITCH CLOSED
LIMIT SWITCH REVERSE CLOSED
EXCESS RECIRCULATION
CONVERTER
WEIGHT INDICATING TRANSMITTER
VARIABLE FREQUENCY DRIVE
VOLT FREE CONTACT
VALVE (ACTUATED)
MULTIVARIABLE ALARM
TREATED WATER
S
SG
SST
T
SW
SS
RF
SC
REV
PS
PVC
SIGHT GLASS / GAUGE
STAINLESS STEEL
SELECTOR SWITCH
SETTLED WATER
TANK
SPEED CONTROL
REVERSE FILTRATION
POLYVINYL CHLORIDE
STRAINER
REVERSING
PUMP SPEED
PNEUMATIC TO CURRENT TRANSDUCER
MECHANICAL DEVICE / MOTOR
CURRENT TO PNEUMATIC TRANSDUCER
O/C/A
PRD
P/I
PRV
PD
P/A
PA
P
ORP
NO
NEUT
NC
MX
MEM
M
PRESSURE RUPTURE DISK
PRESSURE RELIEF VALVE
PROCESS DRAIN
PULSE TO ANALOG
OXIDATION REDUCTION POTENTIAL
PLANT AIR
PUMP
OPEN-CLOSE-AUTO
NORMALLY OPEN
NORMALLY CLOSED
NEUTRALIZATION
MIXER
MEMBRANE
EX
H
I/P
HV
FW
CV
EN
DPI
DE
CIPS
CIPR
CIP
EXHAUST
HAND VALVE (MANUAL)
FINISHED WATER
HEATER
DIFFERENTIAL PRESSURE INDICATOR
CLEAN-IN-PLACE SUPPLY
CLEAN-IN-PLACE RETURN
CLEAN-IN-PLACE
CHECK VALVE
ENERGIZE
DE-ENERGIZE
ANALYTICAL INSTRUMENT TRANSMITTER
MISCELLANEOUS
BS
BD
ATO
ATC
ATA
AS
AIT
AE
A
BACK…