COVER PAGE OF SELLER’S SUBMITTAL
City Name: Hanford, WA - MSA
Pall Project No.: 01.000287
Job Number: Project L-897, Subcontract 70816
Task Register 6 (Task 1 – VI Submittal Package)
To: (Contractor)
Mission Support Alliance, LLC (MSA)
PO Box 650
Richland, WA 99352
From: (Subcontractor)
Pall Water
A Division of Pall Corporation
839 State Route 13
Cortland, NY 13045
Patty Willis
Phone: 607-758-1699
Name of Project: Hanford, WA, Central Plateau WTF
Pall Document Number: NYCS000015577 Rev: 00
Description of Item: Anchor Bolt List
Specification Section: HNF-SPEC-63538, 05 13 00
Deviations: None
INDEX:
Page 1: Cover Page Information
Page 2: Revision History and Approvals
Page 3: Tab 3 - NYCS000015577, Anchor Bolt List
Date: 3/4/2020
PALL ADVANCED SEPARATIONS SYSTEMS
DIVISION OF PALL CORPORATION, CORTLAND, NY
Rev Name Date Created By
Approved By
Created By
Approved By
Created By
Approved By
Created By
Approved By
Revision Description
Title
Document # Revision griffinju Text Box These commodities, technology, or software may only be exported from the United States in accordance with the Export Administration Regulations. Diversion contrary to U.S. law is prohibited.
Document:
NYCS000015577 Project #: 01.289
Revision: 00 Project: Hanford, WA.
ID Description Comment Anchor Bolt
Diameter (inches)
Epoxy Anchor Bolt Material Anchor Bolt Embedment (Minimum) inches
Approximate length to order
(inches)
Number of Sub-
Systems
Bolts Per Sub-
System
Bolts Total Sub-System
Sub-Total Approx inches
Comment
1 8 inch Transverse Valve Rack Per ATI seismic report, Phase A 7/8 SET-3G A320 Grade B8M (316SS) 5.5 12 4 4 16 192 2 Module Rack Per ATI seismic report, Phase A 1/2 SET-3G A320 Grade B8M (316SS) 4 10 24 4 96 960 3 3117 gallon acid tank Per ATI seismic report, Phase A 3/4 SET-3G A320 Grade B8M (316SS) 7.5 12 4 4 16 192 for angle stops --- 3117 gallon acid tank Per Tank Fabricator seismic report TBD TBD A320 Grade B8M (316SS) TBD TBD TBD TBD TBD TBD Needs addition anchorage, design by Tank Fabricator 4 5201 gallon caustic tank Per ATI seismic report, Phase A 3/4 SET-3G A320 Grade B8M (316SS) 7.5 12 4 4 16 192 for angle stops --- 5201 gallon caustic tank Per Tank Fabricator seismic report TBD TBD A320 Grade B8M (316SS) TBD TBD TBD TBD TBD TBD Needs addition anchorage, design by Tank Fabricator 5 RF pumps Per ATI seismic report, Phase A 3/8 AT-XP A320 Grade B8M (316SS) 3 9 3 4 12 108 6 CIP pumps Per ATI seismic report, Phase A 3/8 AT-XP A320 Grade B8M (316SS) 3 9 2 4 8 72 7 Culligen water softeners Per ATI seismic report, Phase A 5/8 SET-3G A320 Grade B8M (316SS) 4.75 9 2 3 6 54 8 Culligen brine tank Per ATI seismic report, Phase A 1/2 AT-XP A320 Grade B8M (316SS) 3 6 1 4 4 24 9 Air compressors Per ATI seismic report, Phase B 1/2 AT-XP A320 Grade B8M (316SS) 3 8 2 8 16 128
10 Air receivers Per ATI seismic report, Phase B 5/8 AT-XP A320 Grade B8M (316SS) 5 9 2 4 8 72 11 Main Panel Per ATI seismic report, Phase B 3/8 AT-XP A320 Grade B8M (316SS) 3 7 1 6 6 42
13, 14 Acid and Caustic panels Per ATI seismic report, Phase B --- --- --- --- 2 --- --- --- No anchor bolts, hardware by Others 15 Feed strainer panel Per ATI seismic report, Phase B --- --- --- --- --- 1 --- --- --- No anchor bolts, hardware by Others 16 Remore I/O power panel Per ATI seismic report, Phase B --- --- --- --- --- 1 --- --- --- No anchor bolts, hardware by Others
12, 17 Power Supply for Main panel, 120VAC Relay panel Per ATI seismic report, Phase B --- --- --- --- --- 2 --- --- --- No anchor bolts, hardware by Others
Diameter Total Approximate Inches calc'd # of lengths 6 foot lengths 7/8 192 2.7 3 3/4 384 5.3 6 5/8 126 1.8 2 1/2 1112 15.4 17 3/8 222 3.1 4
Refer to ATI Seismic Reports. The summary information here has been transposed.
Anchor Bolts will be supplied in six foot lengths of threaded rod, to be cut in the field by Contractor.
| Cover page |
| Revision History & Approvals |
| Tab 3 - NYCS000015577,rev00 - Anchor Bolt List |
| Title: Anchor Bolt List, 01.287 |
| Document: NYCS000015577 |
| Revision: 00 |
| RevRow1: 0 |
| NameCreated By: DMLarkin |
| DateCreated By: 02-MAR-2020 |
| NameApproved By: SWatson |
| DateApproved By: 02-MAR-2020 |
| Revision DescriptionRow1: Initial Issue |
| RevRow2: |
| NameCreated By_2: |
| DateCreated By_2: |
| NameApproved By_2: |
| DateApproved By_2: |
| Revision DescriptionRow2: |
| RevRow3: |
| NameCreated By_3: |
| DateCreated By_3: |
| NameApproved By_3: |
| DateApproved By_3: |
| Revision DescriptionRow3: |
| RevRow4: |
| NameCreated By_4: |
| DateCreated By_4: |
| NameApproved By_4: |
| DateApproved By_4: |
| Revision DescriptionRow4: |
File details come from the government source that posted it. Updated .