Addendum 003 - Valves - Other Air Pressure Valves R0.pdf
PDF 6 MB Posted
- Attached to
- Request for Proposal - Construction Services for Project L-897, Central Plateau Water Treatment Facility
- Solicitation number
- 338214
- Issued by
-
Department of Energy
View the file
Other files
Show 40 more
Latest 50 of 88 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
COVER PAGE OF SELLER’S SUBMITTAL
City Name: Hanford, WA - MSA
Pall Project No.: 01.000287
Job Number: Project L-897, Subcontract 70816
Task Register 6 (Task 1 – VI Submittal Package)
To: (Contractor)
Mission Support Alliance, LLC (MSA)
PO Box 650
Richland, WA 99352
From: (Subcontractor)
Pall Water
A Division of Pall Corporation
839 State Route 13
Cortland, NY 13045
Patty Willis
Phone: 607-758-1699
Name of Project: Hanford, WA, Central Plateau WTF
Pall Document Number: NYCS000015440 Rev: 00
Description of Item: Other Air Pressure Control Valves
Specification Section: 43 21 00
Deviations: See document NYCS000015386
INDEX:
Page 1: Cover Page Information
Page 2: Revision History and Approvals
Page 3: Tab 01 - NYCS000015439,CSS,Other Air Pressure Control Valves,01.287
Pages 4-5: Tab 02 - NYCS000015445,Festo,MS4-LRF,0.25in,5um,WH172287
Pages 6-65: Tab 03 - NYCS000015446,Festo,MS-LFR,Technical Brochure
Date: 12/19/2019
PALL ADVANCED SEPARATIONS SYSTEMS
DIVISION OF PALL CORPORATION, CORTLAND, NY
Rev Name Date Created By
Approved By
Created By
Approved By
Created By
Approved By
Created By
Approved By
Revision Description
Title
Document # Revision griffinju Text Box These commodities, technology, or software may only be exported from the United States in accordance with the Export Administration Regulations. Diversion contrary to U.S. law is prohibited.
Doc Number: NYCS000015439R00 Doc Title: NYCS000015439,CSS,Other Air Pressure Control Valves,01.287.docx
Components Specification Sections
The following specification sections are relevant to the approval of submittal NYCS000015440, Other Air Pressure Control Valves,01.287:
L‐897, Attachment No. 2 ‐ HNF‐SPEC‐63538, Section 43 21 00, Pumping Equipment – Basic Requirements.
Any exceptions and clarifications to the specification section above can be found in submittal NYCS000015386,L‐897,Section 43 21 00,Es and Cs,01.287.
Pall has taken exceptions and clarifications relevant to the other air pressure control valves proposed.
Filter regulator
MS4-LFR-1/4-D6-CRV-AS
Part number: 529146
Data sheet
Feature Value
Size 4
For use in the food industry See supplementary material information
Type code MS4-LFR
Series MS
Actuator lock can be closed with accessories Rotary knob with detent
Mounting position Vertical +/- 5°
Grade of filtration 5 µm
Condensate drain Fully automatic
Design Filter regulator with pressure gauge
Max. condensate volume 19 ml
Controller function Outlet pressure constant With return flow function With secondary exhausting
Bowl guard Plastic bowl guard
Symbol 00991587
Pressure gauge with pressure gauge
Operating pressure 2 bar ... 12 bar
Pressure regulation range 0.3 bar ... 7 bar
Max. pressure hysteresis 0.25 bar
Standard nominal flow rate 1500 l/min
Operating medium Compressed air as per ISO 8573-1:2010 [7:4:-] Inert gas
Corrosion resistance class (CRC) 2 - Moderate corrosion stress
Storage temperature -10 °C ... 60 °C
Air quality class at the output Compressed air as per ISO 8573-1:2010 [6:4:4]
Temperature of medium 5 °C ... 60 °C
Ambient temperature 5 °C ... 60 °C
Product weight 275 g
Type of mounting Front panel mounting With accessories Line installation Optionally:
Pneumatic connection 1 G1/4
Pneumatic connection 2 G¼
Note on materials RoHS-compliant
Material of sub-base Die-cast aluminum
12/15/19 - Subject to change - Festo AG & Co. KG 1/24
LarkinD Text Box
NYCS000015445R00
LarkinD
WH172287
Feature Value
Material of operator panel PA
POM
Seals material NBR
Compressed air filter material PE
Housing material Die-cast aluminum
Diaphragm material NBR
Material of bowl PC
Separating disc material POM
12/15/19 - Subject to change - Festo AG & Co. KG 2/25
Filter regulators MS-LFR, MS series q/w Festo core product range
Covers 80% of your automation tasks
Worldwide: Always in stock
Superb: Festo quality at an attractive price
Easy: Reduces procurement and storing complexity qReady for dispatch from the Festo factory in 24 hours
Held in stock in 13 service centres worldwide
More than 2200 products wReady for dispatch in 5 days maximum from stock
Assembled for you in 4 service centres worldwide
Up to 6 x 1012 variants per product series
Look of the star!
LarkinD
NYCS000015446R00
Subject to change – 2019/052 � Internet: www.festo.com/catalog/...
MS series service unit components Key features
MS series service unit components
Solutions for every application Freely combinable function modules
With its large product range, highly functional components and a wide choice of services, the MS series from
Festo offers a complete concept for compressed air preparation. Suitable for simple standard applications as well as application-specific solutions to the highest quality standards.
Available as individual components, pre-assembled combinations ex-stock, application-specific combinations or complete turnkey solutions. The five sizes in the MS series achieve maximum flow rates with minimum space requirements.
Pressure regulators, on/off and soft-start valves with safety function, filter, pressure and flow sensors, dryers, sensors and lubricators. All these allow a suitable solution to be as sembled for every task. Their modular structure means that the components are freely combinable. A simple connection system saves time when replacing individual modules without dismantling the entire combination.
What's more, many of the components are certified to UL and ATEX.
CAD models and configurator Engineering tools
Convenient aids for planning and se lecting application-specific individual devices and combinations. The product configurator lets you config ure customised solutions quickly and transfer the order data with no hassle.
Selection tool for choosing the right service unit without oversizing, and with the right air quality class:
� www.festo.com/engineering/war tungseinheit
Integrated sensors Safety functions Energy savings
Pressure and flow sensors Soft-start/quick exhaust valves
MS6-SV/MS9-SV
Service units MSE6 Intelligent mix of sizes
� Maximum machine availability through controlled processes
� Reliable compressed air preparation and supply for systems
� Integrable or stand-alone
� Easy to connect with M8/M12 plug
� Fast and reliable exhausting of systems up to Performance Level e, certified to EN ISO 13849-1
� Integrated soft-start function
� Fully automatic monitoring and regulation of compressed air supply
� Automatic shut-off of the compressed air in stand-by mode
� Detection and notification of leakages
� Condition monitoring of relevant process data
� Optimum flow rate with up to 18% smaller size
� Excellent energy efficiency
� Cost-optimised combinations – save up to 30%!
Size differences
Size MS2 MS4 MS6 MS9 MS12
Grid dimension [mm] 25 40 62 90 124
Port sizes M5, QS-6 Gx, G¼, Gy G¼, Gy, G½, G¾ G½, G¾, G1, G1¼, G1½
G1, G1¼, G1½, G2
Standard nominal flow rate qnN1)
[l/min] 350 1800 6500 20000 22000
1) Using pressure regulator MS-LR as an example
2019/05 – Subject to change 3� Internet: www.festo.com/catalog/...
Key features
Note
Information
The next few pages provide a brief overview of the complete product range for the MS series service unit components.
You can find detailed information and all of the technical data in the documentation for the corresponding service unit component.
Accessories such as connection plates or mounting brackets can be ordered either via the configurator or separately.
Structure of a service unit
The order of the individual compon ents within a service unit is relevant for safety and functionality. It is not possible to assemble the service unit components in any order in the flow direction. There are restrictions and rules.
The configurator for service unit MSB is a reliable and convenient way of arranging individual service unit components. This ensures that the applicable rules are complied with. As a result, you get a completely assembled combination with UL or
ATEX certification if you need it.
When arranging a combination of individually configured and ordered service unit components, the points on the right must be adhered to under all circumstances.
� Regulators MS-LFR/LR/LRP/LRE are only permissible in the flow direc tion with the same or decreasing pressure regulation range
� Filters MS-LFR/LF/LFM/LFX are only permissible in the flow direction with an increasing grade of filtration
� Lubricators MS-LOE are not permit ted in the flow direction upstream of a filter MS-LFR/LFM/LF/LFX, water separator MS-LWS or membrane air dryer MS-LDM1
� A micro filter MS-LFM must be installed upstream of an activated carbon filter MS-LFX or membrane air dryer MS-LDM1 in the flow direction
� A flow sensor SFAM cannot be installed directly downstream of a regulator MS-LFR/LR; a branching module MS-FRM must be positioned between them
� A soft-start/quick exhaust valve
MS-SV must be the last service unit component in the flow direction
Total product range for MS series service unit components
Type Description Size Pneumatic connection
Push-in connector
Female thread Connection plate with thread
M G NPT G NPT
Combinations
Service units MSB-FRC Technical data � Internet: msb
Combinations of filter regulator and lubricator
4 – – x, ¼ – – –
6 – – ¼, y, ½ – – –
Service units MSB Technical data � Internet: msb
7 combinations, predefined 4 – – ¼ – – –
6 – – ½ – – –
Combinations freely configurable 4 – – x, ¼ – x, ¼, y x, ¼, y
6 – – ¼, y, ½ – ¼, y, ½, ¾ ¼, y, ½, ¾
9 – – ¾, 1 ¾, 1 ½, ¾, 1, 1¼, 1½ ½, ¾, 1, 1¼, 1½
Service units MSE6 Technical data � Internet: mse6
Combinations with fieldbus con nection for measuring pressure, flow rate and consumption
6 – – – – ½ –
Subject to change – 2019/054 � Internet: www.festo.com/catalog/...
Key features
Total product range for MS series service unit components
Type Description Size Pneumatic connection
Push-in connector
Female thread Connection plate with thread
M G NPT G NPT
Individual devices
Filter regulators MS-LFR Technical data � Internet: ms-lfr
Filter and pressure regulator in a single device, grade of filtration 5 or 40 μm
2 QS-6 M5 – – – –
4 – – x, ¼ – x, ¼, y x, ¼, y
6 – – ¼, y, ½ – ¼, y, ½, ¾ ¼, y, ½, ¾
9 – – ¾, 1 ¾, 1 ½, ¾, 1, 1¼, 1½ ½, ¾, 1, 1¼, 1½
12 – – – – 1, 1¼, 1½, 2 –
Filters MS-LF Technical data � Internet: ms-lf
Grade of filtration 5 or 40 μm 4 – – x, ¼ – x, ¼, y x, ¼, y
6 – – ¼, y, ½ – ¼, y, ½, ¾ ¼, y, ½, ¾
9 – – ¾, 1 ¾, 1 ½, ¾, 1, 1¼, 1½ ½, ¾, 1, 1¼, 1½
12 – – – – 1, 1¼, 1½, 2 –
Fine and micro filters MS-LFM Technical data � Internet: ms-lfm
Grade of filtration 0.01 or 1 μm 4 – – x, ¼ – x, ¼, y x, ¼, y
6 – – ¼, y, ½ – ¼, y, ½, ¾ ¼, y, ½, ¾
9 – – ¾, 1 ¾, 1 ½, ¾, 1, 1¼, 1½ ½, ¾, 1, 1¼, 1½
12 – – – – 1, 1¼, 1½, 2 –
Activated carbon filters MS-LFX Technical data � Internet: ms-lfx
For removing liquid and gaseous oil particles
4 – – x, ¼ – x, ¼, y x, ¼, y
6 – – ¼, y, ½ – ¼, y, ½, ¾ ¼, y, ½, ¾
9 – – ¾, 1 ¾, 1 ½, ¾, 1, 1¼, 1½ ½, ¾, 1, 1¼, 1½
12 – – – – 1, 1¼, 1½, 2 –
Water separators MS-LWS Technical data � Internet: ms-lws
Remove condensed water from compressed air, maintenance-free
6 – – ¼, y, ½ – ¼, y, ½, ¾ ¼, y, ½, ¾
9 – – ¾, 1 ¾, 1 ½, ¾, 1, 1¼, 1½ ½, ¾, 1, 1¼, 1½
12 – – – – 1, 1¼, 1½, 2 –
2019/05 – Subject to change 5� Internet: www.festo.com/catalog/...
Key features
Total product range for MS series service unit components
Type Description Size Pneumatic connection
Push-in connector
Female thread Connection plate with thread
M G NPT G NPT
Individual devices
Pressure regulators MS-LR Technical data � Internet: ms-lr
For setting the required operating pressure, 4 pressure regulation ranges
2 QS-6 M5 – – – –
4 – – x, ¼ – x, ¼, y x, ¼, y
6 – – ¼, y, ½ – ¼, y, ½, ¾ ¼, y, ½, ¾
9 – – ¾, 1 ¾, 1 ½, ¾, 1, 1¼, 1½ ½, ¾, 1, 1¼, 1½
12 – – – – 1, 1¼, 1½, 2 –
Pressure regulators MS-LRB Technical data � Internet: ms-lrb
For creating a regulator manifold with independent pressure regula tion ranges. Pressure output is to the front or rear.
4 – – ¼ – x, ¼, y –
6 – – ½ – ¼, y, ½, ¾ –
Precision pressure regulators MS-LRP Technical data � Internet: ms-lrp
For precise setting of the required operating pressure, 4 pressure regulation ranges, pressure hysteresis 0.02 bar
6 – – ¼, y, ½ – ¼, y, ½, ¾ ¼, y, ½, ¾
Precision pressure regulators MS-LRPB Technical data � Internet: ms-lrpb
For configuring a regulator manifold with independent pressure regulation ranges.
Pressure output is to the front or rear.
6 – – ½ – ¼, y, ½, ¾ –
Electrical pressure regulators MS-LRE Technical data � Internet: ms-lre
Electrically adjustable pressure regulator, 4 pressure regulation ranges
6 – – ¼, y, ½ – ¼, y, ½, ¾ ¼, y, ½, ¾
Lubricators MS-LOE Technical data � Internet: ms-loe
Add a precisely adjustable amount of oil to the compressed air. The oil mist component is proportional to the compressed air flow rate.
4 – – x, ¼ – x, ¼, y x, ¼, y
6 – – ¼, y, ½ – ¼, y, ½, ¾ ¼, y, ½, ¾
9 – – ¾, 1 ¾, 1 ½, ¾, 1, 1¼, 1½ ½, ¾, 1, 1¼, 1½
12 – – – – 1, 1¼, 1½, 2 –
Subject to change – 2019/056 � Internet: www.festo.com/catalog/...
Key features
Total product range for MS series service unit components
Type Description Size Pneumatic connection
Push-in connector
Female thread Connection plate with thread
M G NPT G NPT
Individual devices
On/off valves MS-EM Technical data � Internet: ms-em
Manually operated on/off valve for pressurising and exhausting pneumatic installations.
4 – – x, ¼ – x, ¼, y x, ¼, y
6 – – ¼, y, ½ – ¼, y, ½, ¾ ¼, y, ½, ¾
9 – – ¾, 1 ¾, 1 ½, ¾, 1, 1¼, 1½ ½, ¾, 1, 1¼, 1½
12 – – – – 1, 1¼, 1½, 2 –
On/off valves MS-EE Technical data � Internet: ms-ee
Solenoid actuated on/off valve for pressurising and exhausting pneumatic installations.
4 – – x, ¼ – x, ¼, y x, ¼, y
6 – – ¼, y, ½ – ¼, y, ½, ¾ ¼, y, ½, ¾
9 – – ¾, 1 ¾, 1 ½, ¾, 1, 1¼, 1½ ½, ¾, 1, 1¼, 1½
12 – – – – 1, 1¼, 1½, 2 –
Soft-start valves MS-DL Technical data � Internet: ms-dl
Pneumatically actuated soft-start valve for slowly pressurising and exhausting pneumatic installations.
4 – – x, ¼ – x, ¼, y x, ¼, y
6 – – ¼, y, ½ – ¼, y, ½, ¾ ¼, y, ½, ¾
12 – – – – 1, 1¼, 1½, 2 –
Soft-start valves MS-DE Technical data � Internet: ms-de
Solenoid actuated soft-start valve for slowly pressurising and exhausting pneumatic installations.
4 – – x, ¼ – x, ¼, y x, ¼, y
6 – – ¼, y, ½ – ¼, y, ½, ¾ ¼, y, ½, ¾
12 – – – – 1, 1¼, 1½, 2 –
Soft-start/quick exhaust valves MS-SV Technical data � Internet: ms-sv
For building up pressure gradually and reducing pressure quickly and safely in pneumatic piping systems.
Up to category 1, PL c.
6 – – ½ – ¼, y, ½, ¾ ¼, y, ½, ¾
9 – – ¾, 1 ¾, 1 ½, ¾, 1, 1¼, 1½ ½, ¾, 1, 1¼, 1½
Up to category 3, PL d.
Up to category 4, PL e in the case of optional extension.
6 – – ½ – ¼, y, ½, ¾ ¼, y, ½, ¾
Up to category 4, PL e. 6 – – ½ – ¼, y, ½, ¾ –
2019/05 – Subject to change 7� Internet: www.festo.com/catalog/...
Key features
Total product range for MS series service unit components
Type Description Size Pneumatic connection
Push-in connector
Female thread Connection plate with thread
M G NPT G NPT
Individual devices
Membrane air dryers MS-LDM1 Technical data � Internet: ms-ldm
Wear-free membrane dryer with internal air consumption
4 – – x, ¼ – x, ¼, y x, ¼, y
6 – – ¼, y, ½ – ¼, y, ½, ¾ ¼, y, ½, ¾
Branching modules MS-FRM Technical data � Internet: ms-frm
Compressed air distributor with
4 connections
4 – – x, ¼ – x, ¼, y –
6 – – ¼, y, ½ – ¼, y, ½, ¾ –
9 – – ¾, 1 ¾, 1 ½, ¾, 1, 1¼, 1½ ½, ¾, 1, 1¼, 1½
12 – – – – 1, 1¼, 1½, 2 –
Distributor blocks MS-FRM-FRZ Technical data � Internet: ms-frm-frz
Compressed air distributor with
4 connections and half the grid dimension width
4 – – – – – –
6 – – – – – –
Flow sensors SFAM Technical data � Internet: sfam
For absolute flow rate information and accumulated air consumption measurement
6 – – – – ½ ½
9 – – – – 1, 1½ 1, 1½
Subject to change – 2019/058 � Internet: www.festo.com/catalog/...
Filter regulators MS2-LFR, MS series Peripherals overview
Mounting components and accessories
� Page/Internet
1 Pressure gauge
PAGN
2 Mounting bracket
MS2-WR
For wall mounting, knurled nut included in scope of delivery 56
3 Nut
MS2-WRS
For front panel mounting 56
4 Plug screw
MS2-G18S
– Filter cartridge
LFP
-V- New
2019/05 – Subject to change 9� Internet: www.festo.com/catalog/...
Type codes
MS 2 – LFR – M5 – D6 – AR – BAR – C – M – B
Series
MS Standard service unit
Size
2 Grid dimension 25 mm
Service function
LFR Filter regulator
Pneumatic connection
M5 Female thread M5
QS6 Push-in connector for tubing O.D. 6 mm
Pressure regulation range
D6 Pressure regulation range 0.5 … 7 bar
Pressure gauge/adapter
AR Pressure gauge
A8 Adapter for EN pressure gauge x, without pressure gauge
Pressure gauge scale
None
BAR Display unit [bar/psi]
MPA Display unit [MPa]
Grade of filtration
C 5 μm
Condensate drain
M Manual rotary
Version
B Basic
Subject to change – 2019/0510 � Internet: www.festo.com/catalog/...
Technical data
With pressure gauge
Without pressure gauge
-M- Flow rate
140 … 310 l/min
-Q- Temperature range
–5 … +50 °C
-L- Operating pressure
1 … 10 bar
General technical data
With pressure gauge With adapter for EN pressure gauge x, without pressure gauge
Pneumatic connection 1, 2 M5
QS-6
Design Filter regulator with pressure gauge Filter regulator without pressure gauge
Regulating function Output pressure constant, with return flow action, with secondary venting
Type of mounting With accessories
In-line installation
Front panel mounting
Mounting position Vertical ±5°
Grade of filtration [μm] 5
Air quality class at the outlet Compressed air to ISO 85731:2010 [6:4:4]
Condensate drain Manual rotary
Actuator lock Rotary knob with detent
Pressure regulation range [bar] 0.5 … 7
Max. pressure hysteresis [bar] 0.25
Pressure indicator With pressure gauge Gx prepared
Max. condensate volume [ml] 3
Characteristic flow rate values
Pneumatic connection 1, 2 M5 QS-6
Standard nominal flow rate qnN1)
[l/min] 140 310
1) Measured at p1 = 10 bar and p2 = 6 bar, Δp = 1 bar
2019/05 – Subject to change 11� Internet: www.festo.com/catalog/...
Technical data
Operating and environmental conditions
Pneumatic connection 1, 2 M5 QS-6
Operating pressure [bar] 1 … 10 1 … 8
Operating medium Compressed air to ISO 8573-1:2010 [7:4:4]
Inert gases
Ambient temperature [°C] –5 … +50
Temperature of medium [°C] –5 … +50
Storage temperature [°C] –5 … +50
Corrosion resistance class CRC1) 1
1) Corrosion resistance class CRC 1 to Festo standard FN 940070
Low corrosion stress. For dry indoor applications or transport and storage protection. Also applies to parts behind covers, in the non-visible interior area, and parts which are covered in the application (e.g. drive trunnions).
Weights [g]
Pneumatic connection 1, 2 M5 QS-6
With pressure gauge 47.1 43.9
Without pressure gauge 38.1 34.9
Materials
Housing PA
Rotary knob POM
Bowl PC
Filter PE
Separating disc POM
Valve tappet Wrought aluminium alloy, NBR
Diaphragm NBR
Spring High-alloy steel
Seals NBR
Note on materials RoHS-compliant
Subject to change – 2019/0512 � Internet: www.festo.com/catalog/...
Technical data
Dimensions Download CAD data � www.festo.com
With pressure gauge AR
MS2-LFR-M5-…-AR MS2-LFR-QS6-…-AR
Barbed fitting for plastic tubing
PUN(-H)-8x1.25
1 Pneumatic connection QS-6
� Flow direction
Type B1 B2 B3 B4 B5 B7 D1 D2
D3
D4 D5
L1 L2 L3 L4 L5
MS2-LFR-M5-…-AR 28
16.7 49 25 14 15.5
M5 21 M23x1 13.8 23 74.9 14.4 34.1 32 17.9
MS2-LFR-QS6-…-AR 33.1 QS-6
2019/05 – Subject to change 13� Internet: www.festo.com/catalog/...
Technical data
Dimensions Download CAD data � www.festo.com
With adapter A8 for EN pressure gauge x, without pressure gauge With pressure gauge AR
Type B2 B3 B7 D1 D5
D6
MS2-LFR-M5-…-A8
16.7 33.4 –
M5
– Gx
MS2-LFR-QS6-…-A8 QS-6
MS2-LFR-M5-…-AR
16.7 49 15.5
M5 23 –
MS2-LFR-QS6-…-AR QS-6
Ordering data
Pressure regulation range 0.5 … 7 bar, rotary knob with detent
Size Pneumatic connection 1, 2 Condensate drain Part No. Type
Pressure gauge, display unit [bar/psi]
MS2 M5 Manual rotary 8086641 MS2-LFR-M5-D6-AR-BAR-C-M-B
QS-6 Manual rotary 8086644 MS2-LFR-QS6-D6-AR-BAR-C-M-B
Pressure gauge, display unit [MPa]
MS2 M5 Manual rotary 8086642 MS2-LFR-M5-D6-AR-MPA-C-M-B
QS-6 Manual rotary 8086645 MS2-LFR-QS6-D6-AR-MPA-C-M-B
Adapter for EN pressure gauge x, without pressure gauge
MS2 M5 Manual rotary 8086643 MS2-LFR-M5-D6-A8-C-M-B
QS-6 Manual rotary 8086646 MS2-LFR-QS6-D6-A8-C-M-B
Subject to change – 2019/0514 � Internet: www.festo.com/catalog/...
Filter regulators MS4/MS6-LFR, MS series Peripherals overview
Filter regulator MS4/MS6-LFR aJ aA aB aF
-H- Note
Additional accessories:
– Module connector for combina tion with size MS4/MS6 or size
MS9 � Internet: amv, rmv, armv
– Adapter plate for mounting on profiles � Internet: ipm-80, ipm-40-80, ipm-80-80 aC aD aE
2019/05 – Subject to change 15� Internet: www.festo.com/catalog/...
Peripherals overview
Mounting attachments and accessories
Individual device Combination � Page/
InternetWithout connecting plate
With connecting plate
Without connecting plate
With connecting plate
1 Cover cap
MS4/6-END
ms4-end, ms6-end
2 Connecting plate-SET
MS4/6-AG…
ms4-ag, ms6-ag
Connecting plate-SET
MS4/6-AQ…
ms4-aq, ms6-aq
3 Module connector
MS4/6-MV
ms4-mv, ms6-mv
4 Mounting bracket
MS4/6-WB
ms4-wb, ms6-wb
5 Mounting bracket
MS4-WBM
ms4-wbm
6 Mounting bracket
MS4/6-WR
ms4-wr, ms6-wr
7 Hex nut
MS4/6-WRS
ms4-wrs, ms6-wrs
8 Cover plate
VS
9 Adapter plate for EN pressure gauge x/¼
A8/A4 aJ Pressure gauge
MA
aA Pressure sensor without display
AD7 … AD10
aB Connecting cable
NEBU-M8…-LE3
aC Pressure sensor with display
AD1 … AD4
aD Connecting cable
NEBU-M8…-LE3/NEBU-M12…-LE4
aE Fully automatic condensate drain, electrically actuated E2/E3/E4 aF Padlock
LRVS-D
– Mounting bracket
MS4/6-WP/WPB/WPE/WPM
ms4-wp, ms6-wp
Subject to change – 2019/0516 � Internet: www.festo.com/catalog/...
Type codes
MS 6 – LFR – ½ – D7 – E R M – AS
Series
MS Standard service unit
Size
4 Grid dimension 40 mm
6 Grid dimension 62 mm
Service function
LFR Filter regulator
Pneumatic connection
MS4
x Female thread Gx
¼ Female thread G¼
MS6
¼ Female thread G¼ y Female thread Gy
½ Female thread G½
Pressure regulation range
D6 Pressure regulation range 0.3 … 7 bar
D7 Pressure regulation range 0.5 … 12 bar
Grade of filtration
C 5 μm
E 40 μm
Bowl guard
R Plastic bowl guard
U Integrated as metal bowl
Condensate drain
M Manual rotary
V Fully automatic
Security
AS Rotary knob with detent, lockable via accessories
Additional variants can be ordered using the modular system � 30
� Pneumatic connection
� Pressure regulation range
� Condensate drain
� Pressure gauge alternatives
� Alternative pressure gauge scale
� Secondary venting
� Rotary knob
� Security
� Type of mounting
� EU certification
� UL certification
2019/05 – Subject to change 17� Internet: www.festo.com/catalog/...
Technical data
Manual rotary condensate drain, with pressure gauge
Semi or fully automatic condensate drain, with pressure gauge
With this device, the filter and pressure regulator are combined into a single unit. The sintered filter with water separator removes contamina tion, pipe sinter, rust and condensate from the compressed air.
-M- Flow rate
850 … 7,200 l/min
-Q- Temperature range
–10 … +60 °C
-L- Operating pressure
0.8 … 20 bar
-W- www.festo.com
� Good regulation characteristics with low hysteresis and primary pressure compensation
� Good particle and condensate separation
� Available with or without secondary venting
� High flow rate
� Directly-actuated diaphragm regulator
� Four pressure regulation ranges:
0.3 … 4 bar, 0.3 … 7 bar,
0.5 … 12 bar and 0.5 … 16 bar
� Regulator lock for protecting the values against adjustment
� Two pressure gauge connections for different fitting options
� Return flow option for exhausting from output 2 to output 1 already integrated
� Optional pressure sensor
� Optional device variant EX4 for use in potentially explosive areas in zones 1, 2, 21 and 22
� Choice of filter cartridges:
5 μm or 40 μm
� New filter cartridges � 58
General technical data
Size MS4 MS6
Pneumatic connection 1, 2
Female thread Gx or G¼ G¼, Gy or G½
Connecting plate AG… Gx, G¼ or Gy G¼, Gy, G½ or G¾
Connecting plate AQ… NPTx, NPT¼ or NPTy NPT¼, NPTy, NPT½ or NPT¾
Constructional design Filter regulator with/without pressure display
Regulating function Output pressure constant, with return flow action, with/without secondary venting
Type of mounting Via accessories
In-line installation
Front panel mounting
Mounting position Vertical ±5°
Grade of filtration [μm] 5
Air purity class at the output Compressed air in accordance with ISO 85731:2010 [6:4:4] (Grade of filtration 5 μm)
Compressed air in accordance with ISO 85731:2010 [7:4:4] (Grade of filtration 40 μm)
Bowl guard Plastic bowl guard
Integrated as metal bowl
Condensate drain Manual rotary
Semi-automatic
Fully automatic
– Fully automatic, electrically actuated
Regulator lock Rotary knob with detent, lockable via accessories
Rotary knob with integrated lock
-H- Note: This product conforms to ISO 1179-1 and to ISO 228-1
Subject to change – 2019/0518 � Internet: www.festo.com/catalog/...
Technical data
General technical data
Size MS4 MS6
Pressure regulation range
D5 [bar] 0.3 … 4
D6 [bar] 0.3 … 7
D7 [bar] 0.5 … 12 (0.5 … 10 with pressure sensor variant AD… or with UL certification)
D8 [bar] – 0.5 … 16 (0.5 … 10 with UL certification)
Max. hysteresis [bar] 0.25
Pressure display Via pressure sensor for displaying output pressure via LCD display and electrical output
Via pressure sensor for displaying output pressure via operational status indicator and electrical output
Via pressure gauge for displaying output pressure
Via pressure gauge with red/green scale for displaying output pressure
Gx prepared –
G¼ prepared
Max. condensate volume [cm3] 19 (with plastic bowl guard)
25 (with metal bowl)
Standard nominal flow rate qnN1) [l/min]
Size MS4 MS6
Pneumatic connection Gx G¼ G¼ Gy G½
D5 – Pressure regulation range 0.3 … 4 bar
Grade of filtration 5 μm 9002) 1,8002) 2,0002) 5,5002) 6,9002)
40 μm 1,1002) 1,9002) 2,2002) 6,0002) 7,2002)
D6 – Pressure regulation range 0.3 … 7 bar
Grade of filtration 5 μm 900 1,500 2,700 5,000 5,600
40 μm 1,000 1,700 2,800 5,700 6,200
D7 – Pressure regulation range 0.5 … 12 bar
Grade of filtration 5 μm 850 1,200 2,200 3,500 4,000
40 μm 900 1,500 2,500 4,000 4,500
D8 – Pressure regulation range 0.5 … 16 bar
Grade of filtration 5 μm – – 2,000 3,300 3,800
40 μm – – 2,300 3,500 4,000
1) Measured at p1 = 10 bar and p2 = 6 bar, Δp = 1 bar
2) Measured at p1 = 10 bar and p2 = 3 bar, Δp = 1 bar
-H- 125 l/min must be available for the fully automatic condensate drain to close correctly.
2019/05 – Subject to change 19� Internet: www.festo.com/catalog/...
Technical data
Operating and environmental conditions
Condensate drain Manual rotary Semi-automatic Fully automatic Fully automatic, electrical
M H V E2/E3/E4
Size MS4 MS6 MS4 MS6 MS4 MS6 MS6
Operating pressure [bar] 0.8 … 14
(0.8 … 10)1)
0.8 … 20
(0.8 … 10)1)
1.5 … 12
(1.5 … 10)1)
1.5 … 12
(1.5 … 10)1)
2 … 12
(2 … 10)1)
2 … 12
(2 … 10)1)
0.8 … 16
(0.8 … 10)1)
Operating medium Compressed air in accord ance with ISO 85731:2010
[–:4:–]
Compressed air in accord ance with ISO 85731:2010
[–:4:–]
Compressed air in accord ance with ISO 85731:2010
[7:4:–]
Compressed air in accord ance with ISO 85731:2010
[–:4:–]
Inert gases
Ambient temperature [°C] –10 … +60 (0 … +50)2) +5 … +60 (+5 … +50)2) +5 … +60 (+5 … +50)2) +1 … +60 (+1 … +50)2)
Temperature of medium [°C] –10 … +60 (0 … +50)2) +5 … +60 (+5 … +50)2) +5 … +60 (+5 … +50)2) +1 … +60 (+1 … +50)2)
Storage temperature [°C] –10 … +60 –10 … +60 –10 … +60 +1 … +60
Corrosion resistance class CRC3) 2
Food-safe4) See supplementary material information –
UL certification4) cULus recognized (OL)
1) Value in brackets applies to MS4/MS6-LFR with UL certification.
2) Value in brackets applies to MS4/MS6-LFR with pressure sensor AD… .
3) Corrosion resistance class CRC 2 to Festo standard FN 940070
Moderate corrosion stress. Indoor applications in which condensation may occur. External visible parts with primarily decorative requirements for the surface and which are in direct contact with the ambient atmo sphere typical for industrial applications.
4) Additional information www.festo.com/sp � Certificates.
ATEX
EU certification EX4
ATEX category gas II 2G
Ex-ignition protection type gas Ex h IIC T6 Gb X
ATEX category dust II 2D
EX-ignition protection type dust Ex h IIIC T60°C Db X
ATEX ambient temperature +5 °C Ta +60 °C
CE mark (see declaration of conformity)1) To EU Explosion Protection Directive (ATEX)
1) Additional information www.festo.com/sp � Certificates.
Weight [g]
Size MS4 MS6
Rotary knob Without integrated lock E11 With integrated lock E11 Without integrated lock E11 With integrated lock E11
Filter regulator with plastic bowl guard
R
275 400 875 1,145
Filter regulator with metal bowl U 475 600 1,087 1,627
Filter regulator with metal bowl U and fully automatic condensate drain, electrically actuated E2/E3/E4
– – 1,800 2,070
Subject to change – 2019/0520 � Internet: www.festo.com/catalog/...
Technical data
Materials
Sectional view
Filter regulator
1 Housing Die-cast aluminium
2 Rotary knob PA/POM
Rotary knob with integrated lock
E11
Aluminium
3 Plastic bowl guard PC
4 Metal bowl Wrought aluminium alloy, die-cast aluminium
Inspection window PA
5 Filter element PE
6 Spin disc POM
7 Filter holder POM
8 Separating plate POM
9 Stabilising disc POM aJ Diaphragm NBR aA Spring Steel
– Seals NBR
Note on materials RoHS-compliant
Free of copper and PTFE only with cover plate VS
Standard flow rate qn as a function of output pressure p2
Pressure regulation range D6 or D7 Grade of filtration 5 μm Grade of filtration 40 μm
MS4-LFR-x
Input pressure p1 = 10 bar p2 [b ar qn [l/min] qn [l/min] p2 [b ar
D6: 0.3 … 7 bar
D7: 0.5 … 12 bar
MS4-LFR-¼
Input pressure p1 = 10 bar p2 [b ar qn [l/min] qn [l/min] p2 [b ar
D6: 0.3 … 7 bar
D7: 0.5 … 12 bar aJ aA
2019/05 – Subject to change 21� Internet: www.festo.com/catalog/...
Technical data
Standard flow rate qn as a function of output pressure p2
Pressure regulation range D6 or D7 Grade of filtration 5 μm Grade of filtration 40 μm
MS6-LFR-¼
Input pressure p1 = 10 bar qn [l/min] p2 [b ar qn [l/min] p2 [b ar
D6: 0.3 … 7 bar
D7: 0.5 … 12 bar
MS6-LFR-y
Input pressure p1 = 10 bar qn [l/min] p2 [b ar qn [l/min] p2 [b ar
D6: 0.3 … 7 bar
D7: 0.5 … 12 bar
MS6-LFR-½
Input pressure p1 = 10 bar p2 [b ar qn [l/min] qn [l/min] p2 [b ar
D6: 0.3 … 7 bar
D7: 0.5 … 12 bar
Subject to change – 2019/0522 � Internet: www.festo.com/catalog/...
Technical data
Dimensions – Basic version MS4-LFR Download CAD data � www.festo.com
Integrated MS pressure gauge with standard scale, manual rotary condensate drain, rotary knob with detent, lockable via accessories
With plastic bowl guard R With metal bowl U
1 Installation dimensions � Flow direction
Type B1 B2 B3 D1 D2 L1 L2 L3 L4 L5 L6
Plastic bowl guard
Metal bowl
MS4-LFR-x 40 21 57
Gx
37.2 140.6 158 27 60.2 58.5 25 17.7
MS4-LFR-¼ G¼
2019/05 – Subject to change 23� Internet: www.festo.com/catalog/...
Technical data
Dimensions – Basic version MS6-LFR Download CAD data � www.festo.com
Integrated MS pressure gauge with standard scale, manual rotary condensate drain, rotary knob with detent, lockable via accessories
With plastic bowl guard R With metal bowl U
1 Installation dimensions � Flow direction
Type B1 B2 B3 D1 D2 L1 L2 L3 L4 L5 L6
Plastic bowl guard
Metal bowl
MS6-LFR-¼
62 31 77
G¼
51.2 190 218 39 95.1 85 68 15.8MS6-LFR-y Gy
MS6-LFR-½ G½
Subject to change – 2019/0524 � Internet: www.festo.com/catalog/...
Technical data
Dimensions – Pressure gauge alternatives Download CAD data � www.festo.com
Cover plate VS Adapter plate A8/A4 for EN pressure gauge x/¼, without pressure gauge
� Flow direction
Type B2 B3 D1 D4
MS4-LFR-x-…-VS 21 54
Gx
MS4-LFR-¼-…-VS G¼
MS4-LFR-x-…-A8 21 58.5
Gx Gx
MS4-LFR-¼-…-A8 G¼
MS4-LFR-x-…-A4 21 58.5
Gx G¼
MS4-LFR-¼-…-A4 G¼
MS6-LFR-¼-…-VS
31 76
G¼
–MS6-LFR-y-…-VS Gy
MS6-LFR-½-…-VS G½
MS6-LFR-¼-…-A4
31 78.5
G¼
G¼MS6-LFR-y-…-A4 Gy
MS6-LFR-½-…-A4 G½
2019/05 – Subject to change 25� Internet: www.festo.com/catalog/...
Technical data
Dimensions – Pressure gauge alternatives Download CAD data � www.festo.com
Integrated MS pressure gauge with red/green scale RG
� Flow direction
Type B2 B3 D1
MS4-LFR-x-…-RG 21 58.5
Gx
MS4-LFR-¼-…-RG G¼
MS6-LFR-¼-…-RG
31 78.5
G¼
MS6-LFR-y-…-RG Gy
MS6-LFR-½-…-RG G½
Subject to change – 2019/0526 � Internet: www.festo.com/catalog/...
Technical data
Dimensions – Pressure gauge alternatives Download CAD data � www.festo.com
Pressure sensor with LCD display AD1 … AD4 Technical data � Internet: sde1
Variant AD1:
SDE1-D10-G2-MS-L-P1-M8 with
3-pin plug M8x1, 1 switching output PNP
Variant AD2:
SDE1-D10-G2-MS-L-N1-M8 with
3-pin plug M8x1, 1 switching output NPN
Variant AD3:
SDE1-D10-G2-MS-L-PI-M12 with
4-pin plug M12x1, 1 switching output PNP and 4 … 20 mA analogue
Variant AD4:
SDE1-D10-G2-MS-L-NI-M12 with
4-pin plug M12x1, 1 switching output NPN and 4 … 20 mA analogue
� Flow direction
Pressure sensor without LCD display (operational status indicator only) AD7 … AD10 Technical data � Internet: sde5
Variant AD7:
SDE5-D10-O-…-P-M8 with 3-pin plug M8x1, threshold value comparator, 1 switching output
PNP, N/O contact
Variant AD8:
SDE5-D10-C-…-P-M8 with 3-pin plug M8x1, threshold value comparator, 1 switching output
PNP, N/C contact
Variant AD9:
SDE5-D10-O3-…-P-M8 with 3-pin plug M8x1, window comparator, 1 switching output PNP, N/O con tact
Variant AD10:
SDE5-D10-C3-…-P-M8 with 3-pin plug M8x1, window comparator, 1 switching output PNP, N/C contact
� Flow direction
Type B2 B3 D1 D6 L5 L6
MS4-LFR-x-…-AD1/AD2 21 82.6
Gx M8x1 35.1 46.7
MS4-LFR-¼-…-AD1/AD2 G¼
MS4-LFR-x-…-AD3/AD4 21 82.6
Gx M12x1 35.1 55.8
MS4-LFR-¼-…-AD3/AD4 G¼
MS4-LFR-x-…-AD7/AD8/AD9/AD10 21 59.1
Gx M8x1 – –
MS4-LFR-¼-…-AD7/AD8/AD9/AD10 G¼
MS6-LFR-¼-…-AD1/AD2
31 103
G¼
M8x1 35.1 46.7MS6-LFR-y-…-AD1/AD2 Gy
MS6-LFR-½-…-AD1/AD2 G½
MS6-LFR-¼-…-AD3/AD4
31 103
G¼
M12x1 35.1 55.8MS6-LFR-y-…-AD3/AD4 Gy
MS6-LFR-½-…-AD3/AD4 G½
MS6-LFR-¼-…-AD7/AD8/AD9/AD10
31 79
G¼
M8x1 – –MS6-LFR-y-…-AD7/AD8/AD9/AD10 Gy
MS6-LFR-½-…-AD7/AD8/AD9/AD10 G½
2019/05 – Subject to change 27� Internet: www.festo.com/catalog/...
Technical data
Dimensions – Rotary knob Download CAD data � www.festo.com
For installation into control panel or attaching with hex nut MS4/6-WRS (not included in the scope of delivery)
Rotary knob with detent Rotary knob with detent, lockable via accessories AS
Rotary knob with integrated lock
E11
2 Installation dimensions
Long rotary knob with detent LD Long rotary knob with detent, lockable via accessories LD-AS
3 For pressure adjustment: pull out telescopic rotary knob fully
Type B4 B5 D2 D3 L3 L8 L9 L10 L11 ß 1
MS4-LFR-… – –
37.2
M30x1.5
51.1 13 5
6 36MS4-LFR-…-AS 48.6 30 60.2 13 5
MS4-LFR-…-E11 – – 76 14 6 60
MS4-LFR-…-LD – –
51.1
76.8
MS4-LFR-…-LD-AS 48.6 30 60 85.7
MS6-LFR-… – –
51.2
M44x1
86 21 14
7 55MS6-LFR-…-AS 64.4 38.8 95.1 12 5
MS6-LFR-…-E11 – – 110 21 14 60
MS6-LFR-…-LD – –
MS6-LFR-…-LD-AS 64.4 38,8 95.5 148.5
Subject to change – 2019/0528 � Internet: www.festo.com/catalog/...
Technical data
Dimensions – Condensate drain Download CAD data � www.festo.com
Manual rotary M Semi-automatic H Fully automatic V
Barbed connector for plastic tubing PUN(-H)-8x1,25
MS4-…-R/U-M
MS6-…-R-M MS6-…-U-M
Push-in connector for plastic tubing PUN-6/PAN-6
MS4-…-R/U-H
MS6-…-R-H MS6-…-U-H
Barbed connector for plastic tubing PUN(-H)-8x1,25
MS4-…-R/U-V
MS6-…-R-V MS6-…-U-V
Type D6 L6 Type D6 L6 Type D6 L6
Plastic bowl guard R Plastic bowl guard R Plastic bowl guard R
MS4-LFR-…-M
5.6
17.7 MS4-LFR-…-H
6.2
22.1 MS4-LFR-…-V
5.6
20.4
MS6-LFR-…-M 15.8 MS6-LFR-…-H 20.4 MS6-LFR-…-V 18.5
Metal bowl U Metal bowl U Metal bowl U
MS4-LFR-…-M
5.6
17.7 MS4-LFR-…-H
6.2
22.1 MS4-LFR-…-V
5.6
20.4
MS6-LFR-…-M – MS6-LFR-…-H – MS6-LFR-…-V –
Fully automatic, electrically actuated E2/E3/E4 Technical data � Internet: pwea
Condensate drain PWEA:
2 Electrical connection: Screw terminal PG9
3 Connection 360° rotatable for plastic tubing PUN-H-12x2
Type B6 B7 B8 B9 L12
MS6-LFR-…-E2/E3/E4 72 140 108 15 174.5
2019/05 – Subject to change 29� Internet: www.festo.com/catalog/...
Technical data qCore product range
Ordering data
Size Connection Condensate drain Grade of filtration 5 μm Grade of filtration 40 μm
Part No. Type Part No. Type
Pressure regulation range 0.3 … 7 bar, plastic bowl guard, integrated MS pressure gauge with standard scale, display unit [bar], rotary knob with detent, lockable via accessories
MS4 G¼ Manual rotary q529144 MS4-LFR-¼-D6-CRM-AS q529148 MS4-LFR-¼-D6-ERM-AS
Fully automatic q529146 MS4-LFR-¼-D6-CRV-AS q529150 MS4-LFR-¼-D6-ERV-AS
MS6 G½ Manual rotary q529176 MS6-LFR-½-D6-CRM-AS q529180 MS6-LFR-½-D6-ERM-AS
Fully automatic q529178 MS6-LFR-½-D6-CRV-AS q529182 MS6-LFR-½-D6-ERV-AS
Pressure regulation range 0.5 … 12 bar, plastic bowl guard, integrated MS pressure gauge with standard scale, display unit [bar], rotary knob with detent, lockable via accessories
MS4 G¼ Manual rotary q529152 MS4-LFR-¼-D7-CRM-AS q529156 MS4-LFR-¼-D7-ERM-AS
Fully automatic q529154 MS4-LFR-¼-D7-CRV-AS q529158 MS4-LFR-¼-D7-ERV-AS
MS6 G½ Manual rotary q529184 MS6-LFR-½-D7-CRM-AS q529188 MS6-LFR-½-D7-ERM-AS
Fully automatic q529186 MS6-LFR-½-D7-CRV-AS q529190 MS6-LFR-½-D7-ERV-AS
Pressure regulation range 0.5 … 12 bar, integrated as metal bowl, integrated MS pressure gauge with standard scale, display unit [bar], rotary knob with detent, lockable via accessories
MS4 G¼ Manual rotary – – q535724 MS4-LFR-¼-D7-EUM-AS
Fully automatic q535720 MS4-LFR-¼-D7-CUV-AS q535722 MS4-LFR-¼-D7-EUV-AS
MS6 G½ Manual rotary q530338 MS6-LFR-½-D7-CUM-AS q529192 MS6-LFR-½-D7-EUM-AS
Fully automatic q530340 MS6-LFR-½-D7-CUV-AS q529194 MS6-LFR-½-D7-EUV-AS
Ordering data
Size Connection Condensate drain Grade of filtration 5 μm Grade of filtration 40 μm
Part No. Type Part No. Type
Pressure regulation range 0.3 … 7 bar, plastic bowl guard, integrated MS pressure gauge with standard scale, display unit [bar], rotary knob with detent, lockable via accessories
MS4 Gx Manual rotary 529160 MS4-LFR-x-D6-CRM-AS 529164 MS4-LFR-x-D6-ERM-AS
Fully automatic 529162 MS4-LFR-x-D6-CRV-AS 529166 MS4-LFR-x-D6-ERV-AS
MS6 G¼ Manual rotary 529196 MS6-LFR-¼-D6-CRM-AS 529200 MS6-LFR-¼-D6-ERM-AS
Fully automatic – – 529202 MS6-LFR-¼-D6-ERV-AS
Gy Manual rotary 529216 MS6-LFR-y-D6-CRM-AS 529220 MS6-LFR-y-D6-ERM-AS
Fully automatic 529218 MS6-LFR-y-D6-CRV-AS 529222 MS6-LFR-y-D6-ERV-AS
Pressure regulation range 0.5 … 12 bar, plastic bowl guard, integrated MS pressure gauge with standard scale, display unit [bar], rotary knob with detent, lockable via accessories
MS4 Gx Manual rotary 529168 MS4-LFR-x-D7-CRM-AS 529172 MS4-LFR-x-D7-ERM-AS
Fully automatic 529170 MS4-LFR-x-D7-CRV-AS 529174 MS4-LFR-x-D7-ERV-AS
MS6 G¼ Manual rotary 529204 MS6-LFR-¼-D7-CRM-AS 529208 MS6-LFR-¼-D7-ERM-AS
Fully automatic 529206 MS6-LFR-¼-D7-CRV-AS 529210 MS6-LFR-¼-D7-ERV-AS
Gy Manual rotary 529224 MS6-LFR-y-D7-CRM-AS 529228 MS6-LFR-y-D7-ERM-AS
Fully automatic 529226 MS6-LFR-y-D7-CRV-AS 529230 MS6-LFR-y-D7-ERV-AS
Pressure regulation range 0.5 … 12 bar, integrated as metal bowl, integrated MS pressure gauge with standard scale, display unit [bar], rotary knob with detent, lockable via accessories
MS6 Gy Manual rotary – – 529232 MS6-LFR-y-D7-EUM-AS
Fully automatic 530348 MS6-LFR-y-D7-CUV-AS 529234 MS6-LFR-y-D7-EUV-AS
Festo core product range qGenerally ready for shipping ex works in 24 hours wGenerally ready for shipping ex works in 5 days
Subject to change – 2019/0530 � Internet: www.festo.com/catalog/...
Ordering data – Modular products
Ordering table
Grid dimension [mm] 40 62 Condi tions
Code Enter code
0M Module No. 526489 526490
Series Standard MS MS
Size 4 6 …
Function Filter regulator -LFR -LFR
Pneumatic connection Female thread Gx – 1 -x
Female thread G¼ Female thread G¼ 1 w-¼
– Female thread Gy 1 -y
– Female thread G½ 1 w-½
Connecting plate Gx – -AGA
Connecting plate G¼ Connecting plate G¼ w-AGB
Connecting plate Gy Connecting plate Gy -AGC
– Connecting plate G½ w-AGD
– Connecting plate G¾ -AGE
Connecting plate NPTx – 1 -AQK
Connecting plate NPT¼ Connecting plate NPT¼ 1 -AQN
Connecting plate NPTy Connecting plate NPTy 1 -AQP
– Connecting plate NPT½ 1 -AQR
– Connecting plate NPT¾ 1 -AQS
Pressure regulation range 0.3 … 4 bar w-D5
0.3 … 7 bar w-D6
0.5 … 12 bar w-D7
– 0.5 … 16 bar 1 -D8
Grade of filtration 40 μm w-E
5 μm w-C
Bowl Plastic bowl with plastic bowl guard w-R
Metal bowl -U
Condensate drain
Manual w-M
Semi-automatic (P1 max. 12 bar) 2 -H
Fully automatic (P1 max. 12 bar) 2 w-V
External, fully automatic, electrical
– 115 V AC, terminals 1 3 -E2
– 230 V AC, terminals 1 3 -E3
– 24 V DC, terminals 1 3 -E4
1 x, ¼, y, ½, AQK, AQN, AQP, AQR, AQS, D8, E2, E3, E4, AD1 … AD4, AD7 … AD10, E11, WPM
Not with EU certification EX4
2 H, V Not with pressure regulation range D8
3 E2, E3, E4 Only with metal bowl U
Transfer order code
MS – LFR – – – – –
Festo core product range qGenerally ready for shipping ex works in 24 hours wGenerally ready for shipping ex works in 5 days
Mandatory data
Options
M
O
2019/05 – Subject to change 31� Internet: www.festo.com/catalog/...
Ordering data – Modular products
Ordering table
Grid dimension [mm] 40 62 Condi tions
Code Enter code
0O Pressure gauge alternatives Cover plate w-VS
Adapter plate for EN pressure gauge x, without pressure gauge
-A8
Adapter plate for EN pressure gauge ¼, without pressure gauge -A4
Integrated pressure gauge, red-green scale 4 -RG
Pressure sensor with LCD display, plug M8, 1 switching output PNP, 3-pin 1 5 -AD1
Pressure sensor with LCD display, plug M8, 1 switching output NPN, 3-pin 1 5 -AD2
Pressure sensor with LCD display, plug M12, 1 switching output PNP, 4-pin, analogue output 4 … 20 mA
1 5 -AD3
Pressure sensor with LCD display, plug M12, 1 switching output NPN, 4-pin, analogue output 4 … 20 mA
1 5 -AD4
Pressure sensor with operational status indicator, plug M8, threshold value comparator, PNP, N/O contact
1 5 -AD7
Pressure sensor with operational status indicator, plug M8, threshold value comparator, PNP, N/C contact
1 5 -AD8
Pressure sensor with operational status indicator, plug M8, window comparator, PNP, N/O contact
1 5 -AD9
Pressure sensor with operational status indicator, plug M8, window comparator, PNP, N/C contact
1 5 -AD10
Alternative pressure gauge scale psi 6 -PSI
MPa 6 -MPA
Secondary venting Without secondary venting -OS
Rotary knob Long rotary knob 7 -LD
0M Security Without
Lockable via accessories w-AS
With integrated lock 1 -E11
0O Type of mounting Mounting bracket with knurled nut for regulator head 8 w-WR
Mounting bracket standard design 9 -WP
Mounting bracket for attaching the service units 1 9 -WPM
Mounting bracket centrally at rear (wall mounting top and bottom), connecting plates not required w-WB
Mounting bracket centrally at rear (wall mounting top), connecting plates not required
-WBM
EU certification II 2GD to EU Explosion Protection Directive (ATEX) -EX4
UL certification cULus, ordinary location for Canada and USA -UL1
Flow direction Flow direction from right to left -Z
4 RG Alternative pressure gauge scale PSI serves only as an auxiliary scale
5 AD1 … AD4, AD7 … AD10
Measuring range max. 10 bar
Not with pressure regulation range D8
6 PSI, MPA Not with pressure gauge alternatives VS, A8, A4, AD1 … AD4, AD7 … AD10
7 LD Not with security E11
8 WR Not with long rotary knob LD
9 WP, WPM Only with connecting plate AGA, AGB, AGC, AGD, AGE, AQK, AQN, AQP, AQR or AQS
Transfer order code
Festo core product range qGenerally ready for shipping ex works in 24 hours wGenerally ready for shipping ex works in 5 days
Mandatory data
Options
M
Subject to change – 2019/0532 � Internet: www.festo.com/catalog/...
Filter regulators MS9-LFR, MS series Peripherals overview
-H- Note
Additional accessories:
– Module connector for combina tions with size MS6, MS9 or MS12
� Internet: rmv, armv
2/3/4/5
2/3/4/5 aC aB aJ aA
2019/05 – Subject to change 33� Internet: www.festo.com/catalog/...
Peripherals overview
Mounting attachments and accessories
Individual unit Combination � Page/
InternetWith female thread
¾/1/N¾/N1
With connecting plate AG…/AQ… Module without connect ing thread, without connecting plate G/NG
Without EU certification EX4
With EU certification EX4
1 Connecting plate-SET
MS9-AG…
ms9-ag
Connecting plate-SET
MS9-AQ…
ms9-aq
2 Module connector
MS9-MV
ms9-mv
3 Mounting bracket
MS9-WP
ms9-wp
4 Mounting bracket
MS9-WPB
ms9-wp
5 Mounting bracket
MS9-WPM
ms9-wp
6 MS pressure gauge
AG
7 Cover plate
VS
8 Pressure sensor without display
AD7 … AD10
9 Connecting cable
NEBU-M8…-LE3
aJ Adapter plate for EN pressure gauge ¼
A4 aA Pressure gauge
MA
aB Padlock
LRVS-D
aC Condensate drain, fully automatic, electrically actuated E2/E3/E4
Subject to change – 2019/0534 � Internet: www.festo.com/catalog/...
Type codes
MS 9 – LFR – G – D6 – E U M – DI – AG – BAR – AS
Series
MS Standard service unit
Size
9 Grid dimension 90 mm
Service function
LFR Filter regulator
Pneumatic connection
G Module without connecting thread, without connecting plate
NG Module without connecting thread, without connecting plate (inch)
Pressure regulation range/operation mode
D6 0.5 … 7 bar, manually operated
D7 0.5 … 12 bar, manually operated
Grade of filtration
C 5 μm
E 40 μm
Bowl guard
U Integrated as metal bowl
Condensate drain
M Manual rotary
V Fully automatic
Regulator type
Piloted
DI Directly actuated
Pressure gauge
AG MS pressure gauge
Pressure gauge scale
BAR bar
PSI psi
Security
AS Rotary knob with detent, can be locked using accessories
Additional variants can be ordered using the modular system � 44
� Pneumatic connection
� Pressure regulation range
� Condensate drain
� Pressure gauge alternatives
� Alternative pressure gauge scale
� Secondary venting
� Security lock
� Type of mounting
� EU certification
� UL certification
2019/05 – Subject to change 35� Internet: www.festo.com/catalog/...
Technical data
Manual rotary condensate drain, with pressure gauge
Semi or fully automatic condensate drain, with pressure gauge
With this component, the filter and pressure regulator are combined into a single unit. The sintered filter with water separator removes contamina tion, pipe sinter, rust and condensate from the compressed air.
-M- Flow rate
10,000 … 23,000 l/min
-Q- Temperature range
–10 … +60 °C
-L- Supply pressure
1 … 20 bar
-W- www.festo.com
� Good regulation characteristics with low hysteresis and primary pressure compensation
� Good particle and condensate separation
� Piloted or directly actuated filter-diaphragm regulator
� High flow rates
� Available with or without secondary venting
� Four pressure regulation ranges:
0.5 … 4 bar, 0.5 … 7 bar,
0.5 … 12 bar and 0.5 … 16 bar
� Pressure gauge connection for different fitting options
� Available with manual, semi-auto matic, fully automatic or fully auto matic, electrically actuated condensate drain
� Actuator lock to protect set values against adjustment
� Optional pressure sensor
� Choice of filter cartridges: 5 μm or
40 μm
� New filter cartridges � 58
� Optional device variant EX4 for use in potentially explosive areas in zones 1, 2, 21 and 22
General technical data
Pneumatic connection 1, 2
Female thread G¾, G1, NPT¾ or NPT1
Connecting plate AG… G½, G¾, G1, G1¼ or G1½
Connecting plate AQ… NPT½, NPT¾, NPT1, NPT1¼ or NPT1½
Module without connecting thread/plate G/NG
Design Piloted filter-diaphragm regulator
Directly actuated filter-diaphragm regulator
Regula tor type
Piloted Output pressure constant, with return flow action, with primary pressure compensation, with secondary venting
Directly actuated Output pressure constant, with return flow action, with/without secondary venting
Type of mounting Via accessories
In-line installation
Mounting position Vertical ±5°
Grade of filtration [μm] 5 (air purity class at the output: compressed air in accordance with ISO 85731:2010 [6:4:4])
40 (air purity class at the output: compressed air in accordance with ISO 85731:2010 [7:4:4])
Bowl guard Integrated as metal bowl
Condensate drain Manual rotary
Semi-automatic
Fully automatic
Fully automatic, electrically actuated
Security Rotary knob with detent, lockable via accessories
Rotary knob with integrated lock
Pressure regulation range/operation mode
D5 [bar] 0.5 … 4, manually operated
D6 [bar] 0.5 … 7, manually operated
D7 [bar] 0.5 … 12, manually operated (0.5 … 10 with pressure sensor variant AD…)
D8 [bar] 0.5 … 16, manually operated (0.5 … 10 with pressure sensor variant AD…)
Subject to change – 2019/0536 � Internet: www.festo.com/catalog/...
Technical data
General technical data
Max. pressure hysteresis [bar] 0.4
Pressure display Via pressure sensor for displaying output pressure via operational status indicator and electrical output
Via pressure gauge for displaying output pressure
Via pressure gauge with red/green scale for displaying output pressure
G¼ prepared
Max. condensate volume [ml] 220
Standard nominal flow rate qnN1)2) [l/min]
Design Piloted filter-diaphragm regulator Directly actuated filter-diaphragm regulator DI
Pneumatic connection G¾/NPT¾ G1/NPT1 G¾/NPT¾ G1/NPT1
D5 – Pressure regulation range 0.5 … 4 bar
Grade of filtration 5 μm 17,0003) 20,0003) 16,0003) 18,0003)
40 μm 18,0003) 23,0003) 16,0003) 20,0003)
D6 – Pressure regulation range 0.5 … 7 bar
Grade of filtration 5 μm 15,000 18,000 12,000 10,000
40 μm 16,000 20,000 12,000 10,000
D7 – Pressure regulation range 0.5 … 12 bar
Grade of filtration 5 μm 15,000 18,000 – –
40 μm 16,000 20,000 – –
D8 – Pressure regulation range 0.5 … 16 bar
Grade of filtration 5 μm 15,000 18,000 – –
40 μm 16,000 20,000 – –
1) All values ±15%
2) Measured at p1 = 10 bar and p2 = 6 bar, Δp = 1 bar
3) Measured at p1 = 10 bar and p2 = 4 bar, Δp = 1 bar
-H- 125 l/min must be available for the fully automatic condensate drain to close correctly.
Operating and environmental conditions
Condensate drain Manual rotary
M
Semi-automatic
H
Fully automatic
V
Fully automatic, electrically actuated
E2/E3/E4
Operating pressure [bar] 1 … 20 1.5 … 12 2 … 12 1 … 16
Operating medium Compressed air in accord ance with ISO 85731:2010
[–:4:–]
Compressed air in accord ance with ISO 85731:2010
[–:4:–]
Compressed air in accord ance with ISO 85731:2010
[7:4:–]
Compressed air in accord ance with ISO 85731:2010
[–:4:–]
Ambient temperature [°C] –10 … +60 +5 … +60 +5 … +60 +1 … +60
Ambient temperature with pressure sensor AD
[°C] 0 … +50 +5 … +50 +5 … +50 +1 … +50
Temperature of medium [°C] –10 … +60 +5 … +60 +5 … +60 +1 … +60
Temperature of medium with pressure sensor AD
[°C] 0 … +50 +5 … +50 +5 … +50 +1 … +50
Storage temperature [°C] –10 … +60 +5 … +60 +5 … +60 +1 … +60
Corrosion resistance class CRC1) 2
UL certification2) cULus recognized (OL)
1) Corrosion resistance class CRC 2 to Festo standard FN 940070
Moderate corrosion stress. Indoor applications in which condensation may occur. External visible parts with primarily decorative requirements for the surface and which are in direct contact with the ambient atmo sphere typical for industrial applications.
2) Additional information www.festo.com/sp � Certificates.
2019/05 – Subject to change 37� Internet: www.festo.com/catalog/...
Technical data
ATEX
EU certification EX4
ATEX category gas II 2G
Ex-ignition protection type gas Ex h IIC T6 Gb X
ATEX category dust II 2D
EX-ignition protection type dust Ex h IIIC T60°C Db X
ATEX ambient temperature +5 °C Ta +60 °C
CE mark (see declaration of conformity)1) To EU Explosion…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .