01.000287
PALL ADVANCED SEPARATIONS SYSTEMS
HANFORD, WA
UL-508A
NFPA-79
NFPA-70 (NEC)
PASS ELECTRICAL ENCLOSURE
FABRICATION SPECIFICATION
NYCS000010006
SPECIFICATIONS:
PROVIDE ANY ADDITIONAL MATERIAL NECESSARY NOTED ON THE BILL OF MATERIALS IF THE QUANTITY IS INCORRECT.
EXTERNAL TO THE PANEL MUST MEET THE NEMA RATING OF THE PANEL AND PROJECT. THE PANEL FABRICATOR WILL ALSO
10. THE PANEL FABRICATOR WILL PROVIDE ALL MISCELLANEOUS MATERIALS NECESSARY TO COMPLETE THE PANEL FABRICATION THAT IS NOT SHOWN IN THE BILL OF MATERIALS. THESE ITEMS INCLUDE WASHERS, SCREWS, WIRE TIES, ETC. ANY ITEMS
1. THE CONTROL ENCLOSURE IS CONSTRUCTED OF 316 STAINLESS STEEL, AND RATED NEMA TYPE 4X.
8. REFER TO THE SUPPLIED INSTALLATION AND MAINTENANCE MANUAL FOR ADDITIONAL INFORMATION.
2. TERMINAL BLOCKS ARE ALLEN BRADLEY 1492 SERIES IDENTIFIED WITH AN APPROPRIATE MARKING SYSTEM. ALL WIRING
MARKING COLLARS).
WILL BE TERMINATED WITH APPROPRIATELY SIZED FERRULES WITH INSULATING COLLARS. (IDENTIFIED WITH WRAP STYLE
7. DIMENSIONS ARE FOR REFERENCE ONLY.
6. WIRING EXTERNAL TO PANEL SHOWN AS .
NOTES - PLEASE REVIEW
BLACK LETTERING. WARNING LABELS WILL BE ORANGE WITH BLACK LETTERING.
5. NAMEPLATES ARE ENGRAVED PLASTIC LAMINATE WITH DOUBLE-SIDED, BLACK NEOPRENE ADHESIVE, APPROX 1/32" THICK.
ADDITIONALLY, NAMEPLATES WILL BE SECURED TO THE ENCLOSURE DOOR USING SCREWS. COLOR IS WHITE WITH
THE USE OF ALL CONDUIT PENETRATION HUBS OF THE SAME ENVIRONMENTAL RATING AS THE ENCLOSURE IS REQUIRED.
4. WIRING EXTERNAL TO PANEL SHALL BE AS PER ELECTRICAL STANDARD REQUIREMENT.
9. CORROSION INHIBITOR, BOM ITEM #603.
20-22 Lb.-In. / (2.3-2.5 Nm) 5-5.6 Lb.-In. / (0.6 Nm)
CIRCUIT BREAKER:
TERMINAL BLOCKS:
5-5.6 Lb.-In. / (0.6 Nm) 30 Lb.-In. / (3.4 Nm)
FUSE BLOCKS :
GROUND BAR:
BLUE
WHITE/BLUE
GREEN
+24 VDC POWER
24 VDC COMMON
GROUND
BLACK
WHITE
120 VAC POWER
120 VAC NEUTRAL
3. POWER WIRING INTERNAL TO THE ENCLOSURE, EXCLUSIVE OF INSTRUMENT SIGNALS, WILL BE A MINIMUM OF #14 AWG
(UNLESS OTHERWISE NOTED) WITH TYPE MTW (105°C) OR EQUAL INSULATION. CONTROL WIRING WILL BE #16 AWG
(UNLESS OTHERWISE NOTED) WITH TYPE MTW (105°C) OR EQUAL INSULATION. ALL ANALOG INSTRUMENT CABLES SHALL
BE TSP CABLE, OR EQUIVALENT, WITH 600 VAC RATING (80°C).
THIS PANEL CONTAINS CLASS 1 AND 2 CONTROL CIRCUITS. ONLY CLASS 1 AND 2 COPPER CONDUCTORS WILL BE USED.
+24VDC/SIGNAL WIRING SHALL BE SEGREGATED FROM POWER WIRING TO THE FULLEST EXTENT PRACTICAL.
INTERSECTION OF DISSIMILAR VOLTAGES SHALL BE AT RIGHT ANGLES, WHEN POSSIBLE.
THE FOLLOWING COLORS WILL BE USED TO IDENTIFY THE VARIOUS VOLTAGE LEVELS:
CONTRACTOR SHOULD REFER TO THE FOLLOWING TABLE FOR FIELD WIRING TERMINATION TORQUE SPECS:
DO NOT PENETRATE TOP OF ENCLOSURE. CONDUIT INSTALLATION ONLY
THROUGH ENCLOSURE SIDES AND BOTTOM ARE PERMITTED.
SEE SHEET 1 FOR REVISIONS
WARNING
DISCONNECT POWER
BEFORE WORKING WITHIN
LT1403
W x
W W
(2
V D
C x
W W
(2
V D
C x
W W
(1 V
A C x
W W
(1 V
A C
120VAC, 60 Hz, 1Ø UPS BACK
POWER FROM CUSTOMER
POWER SUPPLY
POWER SUPPLY
POWER SUPPLY
POWER SUPPLY
POWER SUPPLY
POWER SUPPLY
POWER SUPPLY
WARNING
DISCONNECT POWER
BEFORE WORKING WITHIN
NAMEPLATE DETAILS