PALL ADVANCED SEPARATIONS SYSTEMS
SPECIFICATIONS:
UL-508A
NFPA-79
NFPA-70
1. THIS DRAWING IS SPECIFIC FOR THE CIP ACID ROOM I/O PANEL AND NUMATICS MANIFOLD.
2. SEE FIG. 37 (SHT 18) FOR SUB-BUS CABLING BETWEEN NUMATICS G3 PLC I/O AND NUMATICS ETHERNET MODULE /
NUMATICS 501 SOLENOID VALVE.
3. PANEL ASSEMBLER TO TAG BOTH ENDS OF SIGNAL AIR TUBING BETWEEN NUMATICS MANIFOLD AND BULKHEAD.
4. FIELD INSTALLER TO TAG BOTH ENDS OF ANALOG AND DIGITAL SIGNAL CABLES PER TAG # ON STATION LAYOUT
TABLES WITH MACHINE PRINTED LABELS. FOR LIMIT SWITCH CABLES WHICH HAVE
ZSO & ZSC SIGNALS SHARING ONE CABLE, USE PREFIX "ZSO/ZSC-" AND THE NUMERICAL VALUE OF THE TAG #.
01.000287
HANFORD WA, CENTRAL PLATEAU WTF
I/O STATION # ANALOG DESCRIPTIONCONN. # TAG # TYPICAL I/O STATION # DIGITAL DESCRIPTIONINPUT # TAG # TYPICAL VALVE STATION # VALVE TAG # VALVE DESCRIPTION
I/O STATION # ANALOG DESCRIPTIONCONN. # TAG # TYPICAL
I/O STATION # DIGITAL DESCRIPTIONINPUT # TAG # TYPICAL
I/O STATION # ANALOG DESCRIPTIONCONN. # TAG # TYPICAL
I/O STATION # DIGITAL DESCRIPTIONOUTPUT # TAG # TYPICAL
16 DI
PNP
I0/I1
I2/I3
I4/I5
I6/I7
I8/I9
I10/I11
I12/I13
I14/I15
NUMATICS
2 AI/2 AO
4-20mA
I0
I1
O0/I0
O1/I1
NUMATICS
16 DI
PNP
I0/I1
I2/I3
I4/I5
I6/I7
I8/I9
I10/I11
I12/I13
I14/I15
NUMATICS
I/O STATION #2
16 DIGITAL INPUTS
(2 PER CONNECTOR)
I/O STATION #6
2 ANALOG INPUTS
2 ANALOG OUTPUT
I/O STATION #1
16 DIGITAL INPUTS
(2 PER CONNECTOR)
I/O STATION #4
4 ANALOG INPUTS
SUB-BUS IN
CONNECTOR
I/O STATION #3
8 DIGITAL OUTPUTS
4 AI
4-20mA
I0
I1
I2
I3
NUMATICS
I/O STATION #5
4 ANALOG INPUTS
4 AI
4-20mA
I0
I1
I2
I3
NUMATICS
8 DO
PNP
O0
O1
O2
O3
O4
O5
O6
O7
NUMATICS
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
V -5
V -5
V -5
V -5
V -5
4B
V -5
V -5
V -5
V -5
V -5
V -1
V -1
V -1
V -5
4A
V -5
2A
V -5
2B
COMMUNICATION MODULE
DLR ETHERNET MODULE
4-PIN 12MM CONNECTOR
SUB-BUS OUT
CONNECTOR
MODULE
STATUS
ACTIVITY
LINK
NETWORK
STATUS
COMM
ETHERNET / IP
POWER
NUMATICS
SEE SHEET 1 FOR REVISIONS
SEE SHEET 1 FOR REVISIONSPANEL DEVICESFIELD DEVICES
PANEL DEVICESFIELD DEVICES
1. THE CONTROL ENCLOSURE IS CONSTRUCTED OF STAINLESS STEEL AND RATED NEMA TYPE 4X (IP66).
THE USE OF ALL CONDUIT PENETRATION HUBS OF THE SAME ENVIRONMENTAL RATING AS THE
ENCLOSURE IS REQUIRED.
DO NOT PENETRATE THE TOP OF THE ENCLOSURE.
4. THE PANEL FABRICATOR WILL PROVIDE ALL MISCELLANEOUS MATERIALS NECESSARY TO COMPLETE
THE PANEL FABRICATION THAT ARE NOT SHOWN/INCLUDED ON THE BILL OF MATERIALS. THESE ITEMS INCLUDE WASHERS, SCREWS, WIRE TIES, ETC. ANY ITEMS EXTERNAL TO THE PANEL MUST MEET THE
NEMA RATING OF THE PANEL AND PROJECT. THE PANEL FABRICATOR WILL ALSO PROVIDE ANY
ADDITIONAL MATERIAL NECESSARY NOTED ON THE BILL OF MATERIALS IF THE QUANTITY IS INCORRECT.
2. DIMENSIONS ARE FOR REFERENCE ONLY.
3. REFER TO THE SUPPLIED INSTALLATION AND OPERATION MANUAL FOR ADDITIONAL INFORMATION.
FABRICATION NOTES - PLEASE REVIEW
5. STANDARD CONDUIT FOR 120VAC SHALL BE USED ON THE SKID.
PANEL DEVICESFIELD DEVICES
1. THE CONTROL ENCLOSURE IS CONSTRUCTED OF STAINLESS STEEL AND RATED NEMA TYPE 4X (IP66).
THE USE OF ALL CONDUIT PENETRATION HUBS OF THE SAME ENVIRONMENTAL RATING AS THE
ENCLOSURE IS REQUIRED.
DO NOT PENETRATE THE TOP OF THE ENCLOSURE.
4. THE PANEL FABRICATOR WILL PROVIDE ALL MISCELLANEOUS MATERIALS NECESSARY TO COMPLETE THE PANEL FABRICATION THAT ARE NOT SHOWN/INCLUDED ON THE BILL OF MATERIALS. THESE ITEMS
INCLUDE WASHERS, SCREWS, WIRE TIES, ETC. ANY ITEMS EXTERNAL TO THE PANEL MUST MEET THE
NEMA RATING OF THE PANEL AND PROJECT. THE PANEL FABRICATOR WILL ALSO PROVIDE ANY
ADDITIONAL MATERIAL NECESSARY NOTED ON THE BILL OF MATERIALS IF THE QUANTITY IS INCORRECT.
2. DIMENSIONS ARE FOR REFERENCE ONLY.
3. REFER TO THE SUPPLIED INSTALLATION AND OPERATION MANUAL FOR ADDITIONAL INFORMATION.
FABRICATION NOTES - PLEASE REVIEW
5. STANDARD CONDUIT FOR 120VAC SHALL BE USED ON THE SKID.
PALL ARIA™ SYSTEM
PALL CORPORATION
CORTLAND, NY, USA
HANFORD WA, CENTRAL PLATEAU; ACID ROOM PANEL
01.000287 WH104701
NYCS000015164 2020
24VDC 10A
15A
NEMA TYPE 4X
WARNING
DISCONNECT POWER
BEFORE WORKING WITHIN
W
FILTRATION. SEPARATION. SOLUTION.
PALL CORPORATION
SM
FOR SERVICE, SUPPORT, OR PARTS
PLEASE CALL SYSTEM SERVICES
GROUP: 1-866-475-0115
WHEN CALLING, PLEASE REFERENCE THE
PROJECT NUMBER ON THE SYSTEM NAMEPLATE.
V
-2
V
-2
V
-2
V
-2
V
-2
V
-2
V
-2
V
-2
S P
A R
E
S P
A R
E
S P
A R
E
S P
A R
E
S P
A R
E
S P
A R
E
S P
A R
E
S P
A R
E
S P
A R
E
S P
A R
E
V
-4
V
-4
V
-4
V
-4
V
-4
V
-4
V
-4
V
-4
S P
A R
E
S P
A R
E
S P
A R
E
S P
A R
E
S P
A R
E
S P
A R
E
16 DI
PNP
I0/I1
I2/I3
I4/I5
I6/I7
I8/I9
I10/I11
I12/I13
I14/I15
NUMATICS
2 AI/2 AO
4-20mA
I0
I1
O0/I0
O1/I1
NUMATICS
16 DI
PNP
I0/I1
I2/I3
I4/I5
I6/I7
I8/I9
I10/I11
I12/I13
I14/I15
NUMATICS
I/O STATION #2
16 DIGITAL INPUTS
(2 PER CONNECTOR)
I/O STATION #6
2 ANALOG INPUTS
2 ANALOG OUTPUT
I/O STATION #1
16 DIGITAL INPUTS
(2 PER CONNECTOR)
I/O STATION #4
4 ANALOG INPUTS
SUB-BUS IN
CONNECTOR
I/O STATION #3
8 DIGITAL OUTPUTS
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
V -5
V -5
V -5
V -5
V -5
4B
V -5
V -5
V -5
V -5
V -5
V -1
V -1
V -1
4 AI
4-20mA
I0
I1
I2
I3
NUMATICS
I/O STATION #5
4 ANALOG INPUTS
4 AI
4-20mA
I0
I1
I2
I3
NUMATICS
V -5
4A
V -5
2A
V -5
2B
COMMUNICATION MODULE
DLR ETHERNET MODULE
4-PIN 12MM CONNECTOR
SUB-BUS OUT
CONNECTOR
MODULE
STATUS
ACTIVITY
LINK
NETWORK
STATUS
COMM
ETHERNET / IP
POWER
NUMATICS
8 DO
PNP
O0
O1
O2
O3
O4
O5
O6
O7
NUMATICS
SECURE NAMEPLATE TO INSIDE OF DOOR
IN A CONSPICUOUS LOCATION USING
BLACK NEOPRENE ADHESIVE ONLY.
NAMEPLATE DETAILS
(SCALE 1:1)
NAMEPLATES ARE ENGRAVED PLASTIC LAMINATE WITH DOUBLE-SIDED,
BLACK NEOPRENE ADHESIVE, APPROX 1/32" THICK.
ADDITIONALLY, NAMEPLATES WILL BE SECURED TO THE ENCLOSURE DOOR USING SCREWS.
COLOR IS WHITE WITH BLACK LETTERING.
WARNING NAMEPLATES ARE ORANGE WITH BLACK LETTERING.
SEE SHEET 5 FOR CORRECT PLACEMENT.
BULKHEAD LABEL DETAILS
MACHINE PRINTED THERMAL WITH ADHESIVE
BACK ACCEPTABLE FOR THESE BULK HEAD
LABELS
FILTRATION. SEPARATION. SOLUTION.
PALL CORPORATION
SM
FOR SERVICE, SUPPORT, OR PARTS
PLEASE CALL SYSTEM SERVICES
GROUP: 1-866-475-0115
WHEN CALLING, PLEASE REFERENCE THE
PROJECT NUMBER ON THE SYSTEM NAMEPLATE.
PALL ARIA™ SYSTEM
PALL CORPORATION
CORTLAND, NY, USA
HANFORD WA, CENTRAL PLATEAU; ACID ROOM PANEL
01.000287 WH104701
NYCS000015164 2020
24VDC 10A
15A
NEMA TYPE 4X
WARNING
DISCONNECT POWER
BEFORE WORKING WITHIN
V5109-2
V5132-2
V5212-2
V5227-2
V5120-2
V5124-2
V5558-2
V5557-2
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
V5109-4
V5132-4
V5212-4
V5227-4
V5120-4
V5124-4
V5558-4
V5557-4
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE