33 05 53 - Identification For Utilities Piping And Equipment.pdf

PDF 469 KB Posted

Attached to
Water Main Replacement Project Phase 4 Contract No. WR-4
Solicitation number
Not on record
Issued by
Lancaster County, Pennsylvania

About this file

This is a technical specification document for identification and marking of utilities piping and equipment prepared by Herbert, Rowland & Grubic, Inc., applicable to the Elizabethtown Area Water Authority's Water Main Replacement Project Phase 4 (Contract No. WR-4). The specification establishes requirements for plastic ribbon tape identification systems used to mark direct-buried water utility lines and restrained joints. The primary products required include APWA Color-Code standard identification tape, minimum 6 inches wide by 5 mils thick with aluminum core for detectability, imprinted with "CAUTION BURIED WATER LINE BELOW," and restrained joint marking tape, minimum 2.5 inches wide by 4 mils thick with adhesive backing imprinted with "RESTRAINED JOINT." Installation requirements mandate that identification tape be placed continuously 24 inches below finish grade, above piping, with separate tape for each pipe in common trenches. Restrained joint marking tape must be adhered directly to pipe surfaces and applied along the entire length of pipe, including around the circumference of bells on all fittings and valves, with pipe surfaces free of frost and moisture prior to application.

The specification references ASME A13.1 standards for piping system identification color schemes and requires contractor submittals including manufacturer's catalog literature, shop drawings detailing wording, symbols, letter sizes, color-coding, and valve charts with tag numbers, locations, functions, and manufacturer information. Project record documents must document actual locations of tagged valves upon project closeout. All identification materials must be manufactured for direct burial service and conform to APWA Color-Code standards. No pricing information, set-asides, incumbent vendors, or funding sources are specified in this technical specification document.

View the file

Other files

File Type Posted
03 30 00 - Cast-in-Place Concrete.pdf PDF
01 78 39 - Tap Card - Project Record Documents.pdf PDF
32 12 16 - Asphalt Paving.pdf PDF
00 45 19 Non Collusion Affidavit.pdf PDF
01 41 26 - Permit Requirements.pdf PDF
03 39 00 - Concrete Curing.pdf PDF
01 33 00 - Submittal Procedures.pdf PDF
01 77 00 - Closeout Procedures.pdf PDF
00 65 19.19 - Consent of Surety to Final Payment.pdf PDF
01 26 13 - Request for Interpretation.pdf PDF
32 11 23 - Aggregate Base Courses.pdf PDF
00 21 13 - Instructions to Bidders.pdf PDF
00 73 73 - Statutory Requirements.pdf PDF
02 31 00 Subsurface Utility Engineering.pdf PDF
00 01 10 - Table of Contents.pdf PDF
00 65 19.16 - Affidavit of Release of Liens.pdf PDF
01 22 00 - Unit Prices.pdf PDF
00 63 36 - Field Order Form.pdf PDF
01 73 00 - Execution Requirements.pdf PDF
00 73 46 - Wage Rate Determination.pdf PDF
00 63 49 - Work Change Directive Form.pdf PDF
01 10 00 - Project Summary.pdf PDF
03 20 00 - Concrete Reinforcing.pdf PDF
00 43 13 - Bid Bond PENAL SUM Form.pdf PDF
00 31 46 - Permits_01 - Phase 4 HOP Application - Sealed.pdf PDF
01 42 00 - References.pdf PDF
32 13 13 - Concrete Paving.pdf PDF
00 11 13 - Advertisement for Bids.pdf PDF
01 74 19 - Construction Waste Management and Disposal.pdf PDF
00 65 19.23 - Notice of Acceptability of Work.pdf PDF
01 32 33 - Photographic Documentation.pdf PDF
31 23 19 - Dewatering.pdf PDF
02 82 33 Removal and Disposal of ACM.pdf PDF
32 91 13 - Soil Preparation.pdf PDF
33 14 17 - Site Water Service Utility Laterals.pdf PDF
01 61 00 - Product Requirements.pdf PDF
00 72 00 - General Conditions 2018.pdf PDF
32 91 19 - Landscape Grading.pdf PDF
00 52 00 - Owner_Contractor Agreement.pdf PDF
33 14 19 - Valves And Hydrants For Water Utility Service.pdf PDF
00 61 13.13 - Performance Bond.pdf PDF
31 23 16.26 - Rock Removal.pdf PDF
01 32 36 - Video Monitoring and Documentation.pdf PDF
01 26 00 - Contract Modifications.pdf PDF
01 40 00 - Quality Requirements.pdf PDF
31 23 23.33 - Flowable Fill.pdf PDF
01 50 00 - Temporary Facilities and Controls.pdf PDF
00 45 36 EEO Certificate.pdf PDF
33 14 13 - Public Water Utility Distribution Piping.pdf PDF
00 73 43 - Wage Rate Requirements.pdf PDF
Show 40 more

Latest 50 of 91 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

33 05 53 – IDENTIFICATION FOR UTILITIES PIPING AND EQUIPMENT

Herbert, Rowland & Grubic, Inc. 33 05 53 - 1 009280.0426

SECTION 33 05 53 – IDENTIFICATION FOR UTILITIES PIPING AND EQUIPMENT

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Plastic ribbon tape for placement above direct-buried utility.

B. Related Requirements:

1. Section 33 14 13 – Public Water Utility Distribution Piping: Materials and methods for piping, valves, and appurtenances.

1.2 REFERENCE STANDARDS

A. ASME A13.1 - Scheme for the Identification of Piping Systems.

1.3 SUBMITTALS

A. Section 01 33 00 – Submittal Procedures: Requirements for submittals.

B. Product Data: Submit manufacturer's catalog literature for each product required.

C. Shop Drawings: Submit list of wording, symbols, letter size, and color-coding for mechanical identification and valve chart and schedule, including valve tag number, location, function, and valve manufacturer's name and model number.

1.4 CLOSEOUT SUBMITTALS

A. Section 01 77 00 – Closeout Procedures: Requirements for closeout procedures.

B. Project Record Documents: Record actual locations of tagged valves; include valve tag numbers.

1.5 QUALITY ASSURANCE

A. Conform to ASME A13.1 for color scheme for identification of piping systems and accessories.

PART 2 - PRODUCTS

2.1 RIBBON TAPE

A. Identification Tape:

1. Description:

a. APWA Color-Code standard, continuously printed.

b. Minimum Size: 6 inches wide by 5 mils thick.

c. Manufactured with aluminum core to allow for detection.

d. Manufactured for direct burial service.

33 05 53 – IDENTIFICATION FOR UTILITIES PIPING AND EQUIPMENT

Herbert, Rowland & Grubic, Inc. 33 05 53 - 2 009280.0426

e. Imprint for water lines: “CAUTION BURIED WATER LINE BELOW” in large letters.

B. Restrained Joint Marking Tape:

1. Description:

a. APWA Color-Code standard, continuously printed.

b. Minimum Size: 2-1/2 inches wide by 4 mils thick.

c. Manufactured for direct burial service.

d. Imprint: “RESTRAINED JOINT” in large letters.

e. Adhesive backer.

PART 3 - EXECUTION

3.1 PREPARATION

A. Section 01 73 00 – Execution Requirements: Requirements for installation preparation.

B. Degrease and clean surfaces to receive adhesive for identification materials.

3.2 INSTALLATION

A. Identification Tape:

1. Continuous buried 24 inches below finish grade, above piping.

2. If multiple pipes occur in common trench, locate tape above each pipe.

3. Coordinate with trench Work as specified in Section 31 23 33 – Trenching and

Backfilling for Utilities.

B. Restrained Joint Marking Tape:

1. According to manufacturer’s installation instructions and as specified below.

2. Install the joint marking tape by adhering directly to the pipe.

3. The marking tape shall be installed along the entire length of pipe, including around the circumference of the bells of all fittings and valves.

4. The pipe must be free of frost and moisture along the surface of the pipe receiving the tape.

5. Coordinate with trench Work as specified in Section 31 23 33 – Trenching and

Backfilling for Utilities.

END OF SECTION 33 05 53