06 10 00 - Rough Carpentry.pdf
PDF 479 KB Posted
- Attached to
- West Pump Station Replacement Project
- Solicitation number
- Not on record
- Issued by
- Chester County, Pennsylvania
About this file
This is a technical specification document for rough carpentry work prepared by Herbert, Rowland & Grubic, Inc. for the West Pump Station Replacement Project, a construction initiative by Northwestern Chester County Municipal Authority in Pennsylvania. The specification outlines requirements for rough lumber, carpentry, and engineered wood products, including lumber framing, blocking, nailers, furring, and grounds for the pump station building and site improvements. The document references industry standards from the American Wood Preservers Association, APA - The Engineered Wood Association, ASTM International, and the National Institute of Standards and Technology. Submittals of product data and shop drawings are required per Section 01 33 00, and work must be coordinated according to Section 01 31 13 project coordination requirements. Bids for the general construction contract (WPS-1) were due online by Wednesday, May 20, 2026 at 10:00 AM local time, with public bid opening following immediately.
The specification requires lumber materials compliant with NIST PS 20 standards, with grading specifications that include Standard and better for nominal sizes up to 2x4, and #2 and better for sizes up to 2 inches thick and wider than 4 inches. Preservative-treated material must be provided for all wood used outside the building or below grade, with field treatment of cuts and holes performed per AWPA M4 standards. Installation requirements mandate hot-dipped galvanized steel fasteners for high humidity and treated wood locations, secure anchoring to support applied loading, and proper shimming and leveling. The document specifies that wood exposed to moisture must dry completely before covering, and any wood showing bowing, warping, or twisting must be corrected or replaced to provide a suitable substrate for subsequent materials.
View the file
Other files
Show 40 more
Latest 50 of 171 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SECTION 06 10 00 – ROUGH CARPENTRY
Herbert, Rowland & Grubic, Inc. 06 10 00 - 1 000483.0450
SECTION 06 10 00 – ROUGH CARPENTRY
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Rough Lumber and Carpentry
2. Engineered Wood Products – LVL’s
B. Related Requirements:
1. Section 06 17 53 – Shop-Fabricated Wood Trusses.
2. Section 06 11 20 – Framing and Sheathing.
1.2 REFERENCES
A. American Wood Preservers Association (AWPA) Book of Standards
B. American Wood Preservers Association (AWPA) Use of Category System
C. APA – The Engineered Wood Association (APA) PRP-108, Performance Standards and
Qualification Policy for Structural Use Panel
D. APA U450D, Storage and Handling of APA Trademarked Panels
E. APA Y510T, Plywood Design Specification.
F. ASTM D2559, Standard Specification for Adhesives for Bonded Structural Wood Products for Use Under Exterior Exposure Conditions.
G. ASTM D2898, Standard Testing Methods for Accelerated Weathering of Fire-Retardant-
Treated Wood for Fire Testing.
H. ASTM D4442, Standard Test Methods for Direct Moisture Content Measurement of
Wood and Wood-Base Materials
I. ASTM D4444, Standard Test Methods for Use and Calibration of Hand-Held Moisture
Meters
J. ASTM D5456, Standard Specification for Evaluation of Structural Composite Lumber
Products.
K. ASTM E84, Test Method for Surface Burning Characteristics of Building Materials.
L. Underwriters Laboratories, Inc. (UL) 723, UL Standard for Safety Test for Surface Burning
Characteristics of Building Materials.
Herbert, Rowland & Grubic, Inc. 06 10 00 - 2 000483.0450
M. U.S. Department of Commerce, National Institute of Standards and Technology (NIST):
PS 1, Construction and Industrial Plywood
N. NIST PS 2, Performance Standard for Wood-Based Structural Use Panels
O. NIST PS 20, American Softwood Lumber Standard.
1.3 SUBMITTALS
A. Product Data and Shop Drawings: Submit under provisions of Section 01 33 00 – Submittal Procedures.
1.4 QUALITY ASSURANCE
A. Manufacturer's Qualifications:
1. Wood Treatment Plant: AWPA M3.
2. Treated Wood Inspection: AWPA M2.
B. Factory Lumber Marking:
1. ldentify type, grade, moisture content, inspection service, producing mill, and other qualities specified.
2. Marking may be omitted, as allowed by Building Code, if certificate of inspection is provided for each shipment.
1.5 SEQUENCING
A. Coordinate work under provisions of Section 01 31 13 – Project Coordination.
PART 2 - PRODUCTS
2.1 MATERIALS
A. Lumber (for framing, blocking, nailers, furring, grounds and similar members):
1. NIST PS 20
2. As indicated in the appropriate AWPA Standard and as required to achieve UL rating listed herein.
3. Grade:
a. For nominal sizes up to and including 2 X 4: Standard and better.
b. For nominal sizes up to 2” thick and wider than 4”: #2 and better.
PART 3 - EXECUTION
3.1 PREPARATION
Herbert, Rowland & Grubic, Inc. 06 10 00 - 3 000483.0450
A. Verify measurements, dimensions, and shop drawing details before proceeding.
B. Coordinate location of furring, nailers, blocking, grounds and similar supports for attached work.
C. Eliminate sharp projections which would puncture roofing, flashing or underlayment material.
3.2 ERECTION AND INSTALLATION
A. General:
1. Provide treated material in accordance with appropriate AWPA standard for intended end use.
2. Provide preservative treated material for all wood used:
a. Outside building.
b. Below grade.
3. Field treat cuts and holes in preservative and fire-retardant treated material in accordance with AWPA M4.
B. Attach work securely by anchoring and fastening as indicated or required to support applied loading.
1. Provide washers under bolt heads and nuts.
2. Fasten plywood in accordance with APA recommendations.
3. Use hot-dipped galvanized steel for high humidity and treated wood locations, unfinished steel elsewhere.
4. Use common wire nails or screws for general work.
5. Use fasteners of size that will not penetrate members where opposite side will be exposed to view or receive finish materials.
6. Install fasteners without splitting of wood; predrill as required.
7. Do not drive threaded friction type fasteners.
8. Tighten bolts and lag screws at installation and retighten as required.
C. Set work to required levels and Iines, plumb, true.
1. Shim as required.
2. Cut and fit accurately.
D. Provide wood grounds, nailers, or blocking where required for attachment of other work and surface applied items. Form to shapes indicated or required
1. Grounds:
a. Dressed, key beveled lumber minimum 1-1/2” wide of thickness required to bring face of ground even with finish material.
b. Remove temporary grounds when no longer required.
2. Install roofing nailers as indicated:
a. Install per roofing manufacturer's recommendations.
b. Match height of nailers to insulation.
c. Anchor nailers to resist force of 75 PLF.
d. Use minimum of three anchors for each nailer with ½” vent spaces
Herbert, Rowland & Grubic, Inc. 06 10 00 - 4 000483.0450 between Iengths of nailers.
e. Install nailers over vapor retarder where indicated.
E. Install wood furring plumb and level with closure strips at all edges and openings.
F. When wood has been exposed to moisture allow to completely dry out prior to covering with additional wood or another material.
G. Correct or replace wood which shows bowing, warping or twisting to provide a straight, plumb and level substrate for applications of other materials.
END OF SECTION 06 10 00