01 64 00 - Owner Furnished Products.pdf

PDF 12 MB Posted

Attached to
WCTA Meter Replacement Project
Solicitation number
US.257570
Issued by
Lancaster County, Pennsylvania

About this file

This file is a specification document for owner-furnished products related to the West Cocalico Township Authority (WCTA) Meter Replacement Project in Pennsylvania. The project involves the replacement of approximately 790 water meters with new Advanced Metering Infrastructure (AMI) meters across West Cocalico Township. The Owner will furnish Kamstrup flowIQ 2200 ultrasonic water meters, with the Contractor responsible for all other materials and equipment required for complete installation. The Contractor must transport, handle, inspect, and install the meters according to manufacturer instructions, store them in appropriate weathertight, climate-controlled enclosures with seals and labels intact, and assume responsibility for any damage once equipment leaves the Owner's storage area. Installation must be performed by approved installers only, with field quality control and testing conducted in accordance with manufacturer specifications, and photographic documentation of proper installation required. Bids are due Thursday, November 5, 2026 at 10:00 AM local time via PennBid, with bid security of not less than 10% required in the form of a certified check or bid bond.

The Kamstrup flowIQ 2200 meters feature ultrasonic technology with integrated acoustic leakage detection, temperature monitoring, low start flow of 2 liters per hour, and a battery life of up to 16 years. The meters support Wireless M-Bus and linkIQ communication protocols, operate at a maximum pressure of 250 PSI, measure water temperatures between 33°F and 120°F, and are IP68-rated for waterproof installation indoors, in pits, or underwater. Available in multiple sizes with nominal flows ranging from 1.6 to 4.0 cubic meters per hour, the meters include data logging capabilities for yearly, monthly, daily, and hourly consumption patterns, with intelligent info codes for leak detection, pipe burst notification, tampering alerts, and flow analysis. The Contractor must ensure proper meter placement, correct directional flow installation, appropriate gasket sizing, antenna mounting, and meter readability verification before project completion.

View the file

Other files

File Type Posted
00 73 73a Steel Products Procurement Certification.pdf PDF
00 01 01 LA Cover.pdf PDF
01 26 13 - Requests for Interpretation.pdf PDF
4-Bid Summary - EVP Edited .pdf PDF
00 63 36 - Field Order Form.pdf PDF
00 61 13.16 - Payment Bond.pdf PDF
00 45 19 Non Collusion Affidavit.pdf PDF
01 25 00 - Substitution Procedures.pdf PDF
00 21 13 - Instructions to Bidders.pdf PDF
00 63 63 - Change Order Form.pdf PDF
00 62 76 - App for Payment.pdf PDF
01 22 00 - Unit Prices.pdf PDF
00 65 19.16 - Affidavit of Release of Liens.pdf PDF
01 77 00 - Closeout Procedures.pdf PDF
00 73 46a - Wage Determination Schedule.pdf PDF
00 11 13 - Advertisement for Bids.pdf PDF
00 73 43-1 - Certification Form llc-25 PA Dep L&I.pdf PDF
00 73 46 - Wage Determination Schedule.pdf PDF
01 61 00 - Product Requirements.pdf PDF
01 31 19 - Project Meetings.pdf PDF
00 73 43 - Wage Rate Requirements.pdf PDF
00 45 36 EEO Certificate.pdf PDF
00 65 16 - Certificate of Substantial Completion.pdf PDF
01 35 13 - Special Project Requirements.pdf PDF
01 32 33 - Photographic Documentation.pdf PDF
00 45 33 Certification of Non-Segregated Facilities and Non-Employment of Illegal Alien Labor.pdf PDF
01 31 13 - Project Coordination.pdf PDF
00 65 19.23 - Notice of Acceptability of Work.pdf PDF
00 52 00 - Agmnt btw Own and Cntr for Const Con Stip Price.pdf PDF
00 65 19.19 - Consent of Surety to Final Payment.pdf PDF
01 33 00 - Submittal Procedures.pdf PDF
00 01 10 - Table of Contents.pdf PDF
00 72 00 - General Conditions 2018.pdf PDF
01 78 39 - Project Record Documents.pdf PDF
01 10 00 - Project Summary.pdf PDF
01 40 00 - Quality Requirements.pdf PDF
3-00 91 13 - Addenda No. 1.pdf PDF
00 45 46 Public Works Employment Verification Form.pdf PDF
00 63 49 - Work Change Directive Form.pdf PDF
01 42 00 - References.pdf PDF
01 32 16 - Construction Progress Schedule - SMALL.pdf PDF
00 60 00 - Project Forms.pdf PDF
00 73 73 - Statutory Requirements.pdf PDF
01 73 00 - Execution Requirements.pdf PDF
00 73 36 - Equal Employment Opportunity Requirements.pdf PDF
00 63 13 - RFI Form.pdf PDF
00 61 13.13 - Performance Bond.pdf PDF
01 26 00 - Contract Modifications.pdf PDF
00 43 13 - Bid Bond PENAL SUM Form.pdf PDF
01 32 26 - Construction Progress Reporting.pdf PDF
Show 40 more

Latest 50 of 51 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

01 64 00 – OWNER-FURNISHED PRODUCTS

Herbert, Rowland & Grubic, Inc. 01 64 00 - 1 25-331-07

SECTION 01 64 00 – OWNER-FURNISHED PRODUCTS

PART 1 - GENERAL

1.1 SECTION INCLUDES

A. Owner furnished products.

1.2 PRODUCT DELIVERY REQUIREMENTS

A. Owner responsibilities:

1. Coordinate delivery of Owner procured equipment with Contractor.

B. Contractor Responsibilities:

1. Transport and handle products according to manufacturer's instructions to Work area.

2. Before removing equipment from the Owner’s storage area, the Contractor is to inspect the equipment and report any damage to the products before the equipment leaves the Owner storage area. Once the equipment leaves the Owner’s storage area, the Contractor assumes responsibility for any damage to the equipment and costs associated with replacing the damaged equipment.

3. Provide equipment and personnel to handle products in accordance with manufacturer recommendations; use methods to prevent soiling, disfigurement, or damage.

1.3 PRODUCT STORAGE AND HANDLING REQUIREMENTS

A. Store and protect products according to manufacturer's instructions.

B. Store products with seals and labels intact and legible.

C. Store sensitive products in weathertight, climate-controlled enclosures in an environment suitable to product.

PART 2 - PRODUCTS

2.1 OWNER FURNISHED PRODUCTS

A. The following attached documents list all of the components that will be furnished by the Owner:

1. Kamstrup flowIQ 220 Data Sheet and Installation Guides.

B. All materials and equipment not specifically listed in the above, or shown as provided by others, are to be supplied by the Contractor.

2.2 CONTRACTOR FURNISHED COMPONENTS FOR OWNER-FURNISHED PRODUCTS

A. All material and equipment required for a complete installation shall be provided and installed by the Contractor.

01 64 00 – OWNER-FURNISHED PRODUCTS

Herbert, Rowland & Grubic, Inc. 01 64 00 - 2 25-331-07

PART 3 - EXECUTION

3.1 EXAMINATION

A. Section 01 73 00 - Execution Requirements: Requirements for installation examination.

B. Verify that dwelling or establishment, piping, and property owner are ready for the installation before entering the property.

3.2 INSTALLATION

A. According to manufacturer instructions:

1. Refer to attached documents.

2. Coordinate with manufacturer as necessary for additional information.

3.3 FIELD QUALITY CONTROL

A. Section 01 40 00 - Quality Requirements: Requirements for inspecting and testing.

B. Testing, Adjustment & Acceptance: In accordance with manufacturer instructions.

C. Demonstrate functionality for all Owner furnished products. Provide photographic evidence of proper installation as specified in Section 01 32 33 – Photographic Documentation.

END OF SECTION

Data Sheet flowIQ® 2200

• Acoustic leakage detection in service connections

• Pinpoint accuracy

• Integrated communication

• Wireless M-Bus and linkIQ®

• Intelligent info codes assists you with your operations, asset management and customer service

• Temperature measurement

2 Kamstrup A/S • 58101922_A1_EN_08.2022

Contents

Taking smart metering to the next level 3

Approved meter data 4

Material 4

Technical data 4

Pressure loss 5

Meter sizes 5

Customer logo 5

Display and info codes 6

Sensor information 7

Data registers 8

Integrated communication 9

Ordering details 10

Configuration 11

Accessories 12

3Kamstrup A/S • 58101922_A1_EN_08.2022

Taking smart metering to the next level flowIQ® 2200 raises the bar for what you can expect from a static ultrasonic water meter.

Founded on our more than 25 years of experience, the meter provides modern water utilites with the knowledge needed to make informed decisions and prioritise daily efforts.

flowIQ® 2200 introduces integrated acoustic leakage detection. Acting like a fine-meshed network of noise-loggers, the meters listen to the surrounding pipes and detect noise patterns and acoustic changes that indicate potential leaks.

Thanks to low start flow of 2 l/hour, flowIQ® 2200 measures even the smallest consumption. The meter is highly stable throughout the entire dynamic range with a very low error margin – and as a static meter with no moving parts, it maintains the same high accuracy throughout its lifetime of up to 16 years.

Other key features include intelligent alarms and info codes as well as a configurable log to match your data needs.

All of this ensures fair and accurate billing, improves the data quality and helps to reduce the non-revenue water.

Hygiene Security and hygiene are high priority areas in both the development and production.

Our water meters are approved for use with drinking water and are disinfected, dried and packed in airtight packaging so they are not subject to environmental influences before their application. Moreover, we continuously test for disinfection effectiveness through frequent audits both internally and by external accredited laboratories.

All these steps are carried out to ensure that only water meters of the highest quality leave our production facilities.

4 Kamstrup A/S • 58101922_A1_EN_08.2022

Approved meter data

MID classifications Approval DK-0200-MI001-022

Mechanical environment Class M1

Electromagnetic environment Class E1 and E2 for Wireless M-Bus and linkIQ® version

Climatic environment 5...55 °C, condensing humidity (indoors mounted in utility rooms and outdoors in meter pits – mounting in direct prolonged sunligt must be avoided)

OIML R49 designations Accuracy class 2

Sensitivity class U0/D0

Ambient class Fulfils OIML R49 class B and O (building/outdoor)

Medium temperature, cold water 0.1...30 °C (T30) or 0.1...50 °C (T50)

Meter types Q3 = 1.6 m³/h, 2.5 m³/h and 4.0 m³/h

Drinking water approvals KTW/W270

Material

Wetted parts Meter housing and meter pipe PPS with 40 % fibreglass and PSU

Reflectors Stainless steel

Strainer PES

Technical data

Electrical data Battery 3.65 VDC lithium

Battery lifetime: up to 16 years at tBAT < 30 °C depending on selected data package up to 8 years at tBAT < 55 °C

EMC data Fulfils MID class:

- E1 and E2

Mechanical data Metrological class 2

Ambient class Fulfils OIML R49 class B and O (building/outdoor)

Ambient temperature 2…55 °C

Protection class IP68

Storage temp. empty sensor -25…60 °C

Pressure stage PN16

5Kamstrup A/S • 58101922_A1_EN_08.2022

Pressure loss

Meter sizes flowIQ® 2200 is available in different combinations of length and nominal flow Q3.

Nom. flow Q3

[m³/h]

Min. flow Q1

[l/h]

Max. flow Q4

[m³/h]

Min. cutoff

[l/h]

Max. cutoff

[m³/h]

Pressure loss ∆p at Q3

[bar]

Connection on meter

1.6 10 2.0 2 4.6 0.17 G¾B

2.5 10 3.1 2 4.6 0.4 G¾B

2.5 10 3.1 2 4.6 0.4 G1B

4.0 16 5.0 3.2 8.5 0.4 G1B

See section ‘Ordering details’ for combination possibilities

Customer logo

Trykfald for MC21 Dp MC21 Datablad

0,01

0,1

0,1 1 10 p

[b ar

Flow [m³/h]

∆∆p MULTICAL®21

A B1.6 & 2.5 4.0 flowIQ® 2200

The meter can be customized with a laser engraved logo of the customer. Contact Kamstrup for further details.

For further information about the details on the top label, please see the technical description.

Optional customer label, e.g. water company logo (14x38 mm)

6 Kamstrup A/S • 58101922_A1_EN_08.2022

Display and info codes

The large display with totalized volume, flow rate and intuitive info codes on flowIQ® 2200 makes it easy for end users to understand their own consumption data.

flowIQ® 2200 includes a large number of intelligent info codes and alarms. An info code indicates a special condition in the meter. If the info code is available in the display, the related symbol is on when it has been activated. If the ‘condition’ is not active, the sign is OFF. The info codes provide you with the exact knowledge you need to target your efforts within operations optimisation, customer information, water loss and tampering. The info codes in the display have the following meaning and function:

Info code Meaning

Water in the meter has not been stagnant for one continuous hour during the latest 24 hours.

This can be a sign of a leaky faucet or toilet cistern or indicate a leakage after the meter.

The water consumption has been consistently high for half an hour, which indicates a pipe burst.

Attempt of fraud. The meter is no longer valid for billing.

The meter is dry. In this case nothing will be measured.

The water flows through the meter in the wrong direction.

RADIO OFF flashes. The meter is still in transport mode with the built-in radio transmitter turned off. The transmitter turns on automatically when the first liter of water has run through the meter.

RADIO OFF lights permanently. The radio is switched off permanently. Can be activated via METERTOOL or DataTool.

The symbol appears when the expected capacity left is 6 months (or when the voltage drops below 2.9V).

Info codes , , and switch off automatically, when the conditions that activated them no longer exist. In other words, disappears when the water has been stagnant for one hour, disappears when the consumption falls to normal level, disappears when the water no longer flows in the wrong direction, and disappears when the meter is filled with water.

7Kamstrup A/S • 58101922_A1_EN_08.2022

Sensor information

Water meters placed throughout the network make it possible to gather information that can be of vital importance for an effective water supply, asset management and improved customer service.

Acoustic leakage detection flowIQ® 2200 water meter introduces integrated acoustic leak detection that allows you to monitor your service connections for possible leaks. Like a fine-meshed network of noise-loggers, all your meters monitor the noise in the distribution lines and service connections to detect possible leaks – 24/7.

Water flowing through a leaking pipe creates a different sound pattern than water flowing through an intact pipe.

And changes to the size of a leakage or burst will also cause the sound pattern to change. flowIQ® 2200 detects these sounds and changes while filtering out background noises such as the traffic aboveground or the normal daily water consumption within the house.

In other words, you can let your meters work for you instead of installing separate noise-loggers around your supply area.

Temperature monitoring flowIQ® 2200 measures water and ambient temperatures respectively.

Information on temperatures above or below configurable in the meter will warn the utility on potentiel frost damages or quality issues.

The measurements can be used to monitor the installation and to give an indication of the quality of the water.

Consumption above legal flow range The meter logs information on consumption above the legal flow range. This information can be used to indicate if the meter size for a given installation is correct.

Consumption profile The meter tracks consumptions in different flow intervals for further analysis of the consumption patterns for the specific installation.

No consumption If no consumption has been measured for 15 days the meter will indicate this, in order to inform the utility that the consumption at a specific customer might be unusual.

8 Kamstrup A/S • 58101922_A1_EN_08.2022

Data registers

The water meter has a permanent memory, in which the values of various data loggers are saved.

The loggers can be read via the meter’s optical eye.

The following registers are logged:

Description Yearly logger Monthly logger. Daily logger Hourly logger

Logger depth 20 years 36 months 460 days 1440 hours Operating hours Info codes incl. hour counter Volume Volume reverse Volume net Acoustic Noise Value Day Flow max year incl. Date Flow min year incl. Date Flow max month incl. Date Flow min month incl. Date Flow max day incl. Timestamp Flow min day incl. Timestamp Water temp. Max. Year Water temp. Min. Year Water temp. Avg. Year Ambient temp. Max. Year Ambient temp. Min. Year Ambient temp. Avg. Year Water temp. Max. Month Water temp. Min. Month Water temp. Avg. Month Ambient temp. Max. Month Ambient temp. Min. Month Ambient temp. Avg. Month Water temp. Max. Day Water temp. Min. Day Water temp. Avg. Day Ambient temp. Max. Day Ambient temp. Min. Day Ambient temp. Avg. Day

Every time the information code changes, date and info codes are logged. Thus, it is possible to data read the latest 50 changes of the information code as well as the date the change was made. Reading is only possible via the optical eye.

9Kamstrup A/S • 58101922_A1_EN_08.2022

Integrated communication

The meter is delivered with integrated radio communication and supports both Wireless M-Bus and Kamstrup linkIQ®.

For both linkIQ® and Wireless M-Bus, you can select different transmission properties and data packages. Wireless M-Bus is available with the C1 or T1 protocol and various reading intervals. The lifetime for C1 is up to 16 years. The lifetime for T1 and T1 BSI is up to 12 years. You MUST choose one data package.

Wireless M-Bus A Wireless M-Bus data package is transmitted every 16 seconds (‘drive-by’) or 96 seconds (‘fixed network’).

When sending a data package every 16 seconds the package is kept short and compressed to achieve a long battery life.

At 96 second intervals, a longer and intelligent radio package with built-in ‘repair coding‘ is sent – the long battery life is still guaranteed since the transmission interval is increased.

16 or 96 second intervals need to be chosen when ordering, and can be re-programmed by METERTOOL or DataTool.

If needed, it is also possible to disable the radio permanently.

linkIQ® communication* linkIQ® is a Wireless M-Bus protocol which contains hourly data and is designed for a very high data performance in a fixed network by using turbo coding supported by Kamstrups READy Concentrator 1M.

This increases the range for the data collection devices, meaning that only a few sites are needed.

With Kamstrups new READy Concentrator 1M, linkIQ® can be used in an existing Wireless M-Bus network and will perform with a higher range.

linkIQ® transmits on the 868 MHz band at 25 mW.

On flowIQ® 2200, it is not possible to change the choice of communication module XX, see ”Communication” under ”Ordering details”.

However, protocol and data package (YY-ZZZ) can be changed subsequently with METERTOOL.

For communication options see document 5512-2521 at kamstrup.com.

*) For selected markets only.

https://www.kamstrup.com/en-en/water-solutions/meters-devices/meters/flowiq-2200/documents http://kamstrup.com

10 Kamstrup A/S • 58101922_A1_EN_08.2022

Ordering details flowIQ® 2200 KWM2210-

Meter generation

Second generation 02

Mechanical design 1-part PPS body K

Communication

Wireless M-Bus 868 MHz 13 linkIQ®, Wireless M-Bus C1/T1 (for selected markets only) 59

Power supply

C-Cell C

Dynamic range

100 A

250 C

Meter size

¾” 110mm, 1.6 m³/h 1A

¾” 110mm, 2.5 m³/h 1B

¾” 170mm, 1.6 m³/h 1E

¾” 170mm, 2.5 m³/h 1D

1” 105mm, 2.5 m³/h 2A

1” 130mm, 2.5 m³/h 2B

1” 130mm, 4.0 m³/h 2C

1” 190mm, 2.5 m³/h 2D

1” 190mm, 4.0 m³/h 2E

Meter type Cold water meter 8

Country code XX

The country code is used for:

•Language and approval on type label
•Temperature class of water meter, cold water (T30 and T50)

An order is initiated by stating the type number of the selected model of flowIQ® 2200.

The type number includes information on meter type - meter size, meter length, battery supply, country code etc.

Subsequently, the meter configuration, which determines customer specific requirements, is selected.

Finally, required accessories, if any, in the form of gaskets, different extension pipes, non-return valve and standard couplings are selected.

Accessories are enclosed separately to be mounted by the installer.

11Kamstrup A/S • 58101922_A1_EN_08.2022

Configuration

DDD JJ KK LLL MMMM N P S U RR CCC V T YY ZZZ

Display views

Default 803

GMT offset – time zone

(GMT+1) 52

(GMT+2) 56

Target date

1st of the month 01

Max values – average over time (1...120 min.)

2 minutes 002

Customer label

2060-MMMM MMMM

Leakage message limit

Flow continuously...

> 0.1 % of Q3/max flow (US) 1

> 0.25 % of Q3/max flow 2

> 0.5 % of Q3/max flow 3

> 1.0 % of Q3/max flow 4

> 2.0 % of Q3/max flow 5

OFF 0

Pipe burst limit

OFF 0

Flow > 5 % of Q3 1

Flow > 10 % of Q3 2

Flow > 20 % of Q3 3

...of max flow for 30 minutes

Ambient temperature low limit

Ambient temp. < 3 °C 3

Ambient temp. < 6 °C 6

OFF 0

Ambient temperature high limit

Ambient temp. > 35 °C 3

Ambient temp. > 45 °C 6

OFF 0

Data logger profile

Standard & Accoustic Leak Detection 03

Display resolution (alphanumeric) – decimal markings

000000,001 m³ – 0000 l/h 010

0000000,01 m³ – 0000 l/h 020

00000000,1 m³ – 0000 l/h 030

000000001 m³ – 0000 l/h 040

To be continued on the next page...

12 Kamstrup A/S • 58101922_A1_EN_08.2022

Configuration

DDD JJ KK LLL MMMM N P S U RR CCC V T YY ZZZ

Continued from previous page

Temperature units of measure Celcius 0

Encryption level Encryption with separately forwarded key 3

Encryption with separately key, with encrypted access to logs 4

Transmission behaviour See note below 1) YY

RADIO OFF 90

Data packages See below 2) ZZZ

DDD JJ KK LLL MMMM N P S U RR CCC V T YY ZZZ

Unless otherwise stated in the order, Kamstrup supplies this configuration: 803 JJ 01 002 0000 3 3 3 3 03 CCC 1 3 YY ZZZ

NOTE! 1) JJ (timezone), CCC (unit, display resolution and billing units) and YYZZZ (datagram) are not pre-defined and has to be chosen in the ordering system.

2) Overview of datagrams, see ‘Communicaton Modules and Data Packages Overview’ here: 5512-2521.

Accessories

All of the below mentioned documents can be found on kamstrup.com.

See Accessories list for Water Meters: 58101270-GB.

For further information about READy, USB Meter Reader and Wireless M-Bus please see the technical description and the installation guide.

For information about Kamstrups hygiene concept see 5518-319-GB Hygiene Concept Kamstrup.

For more datagram options see document 5512-2521 Communication Modules and Data Packages Overview.

Kamstrup A/S Industrivej 28, Stilling DK-8660 Skanderborg T: +45 89 93 10 00 info@kamstrup.com kamstrup.com

K am st ru p A

/S

A 1_

EN

8.

https://www.kamstrup.com/en-en/water-solutions/meters-devices/meters/flowiq-2200/documents http://kamstrup.com https://www.kamstrup.com/en-en/water-solutions/meters-devices/meters/flowiq-2200/documents

Kamstrup kamstrup.com · info-us@kamstrup.com flowIQ® 2200 & 3200 Installation quick guide KWMx220

Quick installation guide steps

Installation 2

RF antenna mounting 4

Lid Mounting 5

Important information before installation 1

Check the installation 3

ICES/ISED cautions 7

FCC cautions 6

Important information before installation 1.1

Only installers are appro-ved to perform installation

Further information on kamstrup.com

Important information before installation 1.2

Maximum operating pressure

Fixed installation with min. vibration. Electromagnetic environmental class: Residential and commercial

Permitted water temperature

33 °F...120 °F

250 PSI

Important information before installation 1.3

Condensing humidity permitted. (Indoors installed in utility rooms and outdoors in meter pits). Installation in direct sun and freezing conditions must be avoided

35 °F...130 °F

IP68-rated (waterproof-submersible)

Important information before installation 1.4

The meter can be installed indoors, in a pit or under water, but direct sun should be avoided. Increased ambient temperature can adversely affect battery life (tBAT < 95 °F)

2.1Ensure correct piping during installation

Correct meter placement in installation

Connect the correct pipes parallel to the meter!

Ensure correct pressure during operation 2.2

The meter is filled with water during operation

Water pressure too low

Avoid entrained air in the water flow

≥ 5 PSI

< 5 PSI

Air

Replace gaskets when installing new meter 2.3

1 2

3 4

2.4

ExtensionFlowpart

Gasket (right size)

Flowpart Extension

Gasket (wrong size)

Ensure correct gasket size

Important! Be aware of maximum torque 2.5

22 ft-lb

11 ft-lb

¾" NPSM

Maximum torque for ¾” NPSM PPS meters: 11 ft-lb”

Maximum torque for 1” NPSM PPS meters: 22 ft-lb

1" NPSM

Install meter in the correct direction of flow 2.6

Opposite water and meter direction

Same water and meter direction

2.7Correct valve installation

Check the installation 3.1

Installation is complete

Make sure the meter displays DRY and the desired unit of mea-surement

Open the water supply

Check the installation 3.2

Check that the display switches to FLOW and that the counter is in movement

...shortly afterCurrent display status...

The flow indicator in the display will update frequently, permitting the installer to confirm that the meter is properly operating.

RF antenna mounting 4

Note: For pit antennas use clamps 30-26-1211 and for top mounted antennas use clamps

30-26-1214.

1 2

1 2

Lid mounting 5

For meters subjected to any kind of mechanical impact, Kamstrup recommends installing a convenient lid on the meter. This protects the meter display from direct sunlight and/or the glass from moderate mechanical impact.

For both flowIQ® 2200 and flowIQ® 3200 meters, it is possible to install a lid.

Note: Installing a lid is mandatory for Reclaimed Water meters.

Cautions 6.1

Caution: Changes or modifications not expressly ap-proved by the party responsible for compliance could void the users authority to operate the equipment.

RF Exposure compliance statement: This device must be installed to provide a separation distance of at least 20 cm from all persons.

This device complies with Part 15 of the FCC Rules.

Operation is subject to the following two conditions:

1This device may not cause harmful interference, and
2This device must accept any interference recieved,

including interference that may cause undesired operation.

This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications.

www.kamstrup.com

FCC cautions 6.2

However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:

- Reorient or relocate the receiving antenna.

- Increase the separation between the equipment and receiver.

- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.

- Consult the dealer or an experienced radio/TV technician for help.

ICES/ISED cautions 7.1

English:

This device complies with Industry Canada license-exempt RSS standard(s). Operation is subject to the following two conditions:

(1) This device may not cause interference, and

(2) This device must accept any interference, including interference that may cause undesired operation of the device.

Complies with the Canadian ICES-003 Class B specifications.

This device complies with RSS 247 of Industry Canada. This Class B device meets all the requirements of the Canadian interference-causing equipment regulations.

This radio transmitter IC ID 22376-KWMx220 has been approved by Innovation, Science and Economic Development Canada to operate with the antenna types listed below, with the maximum permissible gain indicated. Antenna types not included in this list that have a gain greater than the maximum gain indicated for any type listed are strictly prohibited for use with this device.

ICES/ISED cautions 7.2

Maximum gain

Antenna type 450-470 MHz: 902-928 MHz:

Helix -2 dBi -2 dBi

Pit, small -5 dBi 1 dBi

Wall 1 dBi -1 dBi

This equipment has been approved for fixed operation, and unless otherwise advised in separate supplemental instructions for individual wireless transmitter(s), requires minimum 20 cm spacing be provided between antenna(s) and all person’s body (excluding extremities of hands, wrist and feet) during wireless modes of operation.

Must be installed to provide a separation distance of at least 20 cm from all persons.

Hardware version identification number (HVIN):

02K02D18A8UB, 02K02D18B8UB, 02K02D18R8UB,

02K02D18C8UB, 02L02D18B8UB, 02L02D18N8UB,

02L02D18L8UB, 02L02D18D8UB, 02L02D18F8UB,

02L02D18H8UB, 02L02D18M8UB, 02L02D18K8UB,

02L02D18P8UB

ICES/ISED cautions 7.3

Français:

Cet appareil est conforme aux normes CNR exemptes de licence d’Industrie Canada. Le fonctionnement est soumis aux deux conditions suivantes:

(1) Cet appareil ne doit pas provoquer d’interférences et

(2) Cet appareil doit accepter toute interférence, y compris celles susceptibles de provoquer un fonctionnement non souhaité de l’appareil.

Cet appareil numérique de la classe B est conforme à la norme NMB-003 du Canada.

Cet appareil est conforme à la norme canadienne RSS 247. Cet appareil numérique de la Classe B respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.

Cet émetteur radio IC ID 22376-KWMx220 a été approuvé par Innovation, Sciences et Développement économique Canada pour fonctionner avec les types d’antenne énumérés cidessous, avec le gain maximal autorisé indiqué. Les types d’antenne non inclus dans cette liste et ayant un gain supérieur au gain maximum indiqué pour tout type répertorié sont strictement interdits pour l’utilisation avec cet appareil.

ICES/ISED cautions 7.4

Maximum gain

Antenna type 450-470 MHz: 902-928 MHz:

Helix -2 dBi -2 dBi

Pit, small -5 dBi 1 dBi

Wall 1 dBi -1 dBi

Cet équipement a été approuvé pour une utilisation fixe et, sauf indication contraire dans les instructions supplémentaires pour émetteurs sans fil individuels, cet équipement nécessite un espace minimum de 20 cm entre l’antenne (s) et le corps de la personne utilisant l´appareil (à l’exclusion des extrémités des mains, des poignets et des pieds) pendant les modes de fonctionnement sans fil.

Doit être installé de façon à respecter une distance de minimum 20 cm à toute personne.

Numéro d’identification de la version de material (NIVM):

02K02D18A8UB, 02K02D18B8UB, 02K02D18R8UB,

02K02D18C8UB, 02L02D18B8UB, 02L02D18N8UB,

02L02D18L8UB, 02L02D18D8UB, 02L02D18F8UB,

02L02D18H8UB, 02L02D18M8UB, 02L02D18K8UB,

02L02D18P8UB

Kamstrup Water Metering, LLC 2855 Forsyth Commerce Way, Building 200 Cumming, GA 30040, USA T: +1 (404) 835-6716 info-us@kamstrup.com

K am st ru p A

/S

F

IL

E1

A

EN

-U

S_

4.

Only installers are appro-ved to perform installation

Installation guide for US AMI Network for flowIQ® 2200 & 3200

Kamstrup kamstrup.com · info@kamstrup.com

Think forward

Kamstrup A/S Industrivej 28, Stilling DK-8660 Skanderborg T: +45 89 93 10 00 F: +45 89 93 10 01 info@kamstrup.com kamstrup.com

Quick Guide Installation Steps

Preconditions 2

Meter installation (Mechanical) 3

Enable radio / Configure meter for AMI 4

Configuration: Select AMI and frequency 5

Check meter readability 6

Important information before installation 1

K am st ru p A

/S

7_ A

1_ U

S_

7.

Antenna is mounted

1 2

Synchronize READy Manager with READy App

3.2Installation: Meter placement

Correct meter placements in installation

Important information before installation 1

Further information on kamstrup.com

Further information on products.kamstrup.com

Preconditions 2.1

Preconditions 2.2

Download info to READy Manager from License Frequency Service

3.3Installation: Direction of flow

Correct direction

Wrong direction

3.1Installation: External antenna

Push the antenna into the meter

Push the sealing clasps into the meter

Configuration: Select AMI and frequency Configuration: Select AMI and frequency

21 21

3 3

Enable radio / Configure meter for AMI 4.5 Enable radio / Configure meter for AMI 4.6

Check meter readability 6

Meter is readable www.kamstrup.com

Place optical eye on meter

Pair devices with READy

The devices are paired

Check display: If there is FLOW, the radio is ON

If there is NO FLOW follow the next 5 steps

Enable radio / Configure meter for AMI

Enable radio / Configure meter for AMI

4.1

4.4

Turn on all the devices

Enable radio / Configure meter for AMI 4.2 Enable radio / Configure meter for AMI 4.3

The icon “RadioOff” turns OFF. Radio is now ENABLED

Enter number Enable radio

Keep short distance: Meter is configured for AMISelect AMI configuration file

Select frequency

Wait up to 3 min.

5.1 5.2

PART 1 - GENERAL
1.1 SECTION INCLUDES
A. Owner furnished products.
1.2 PRODUCT DELIVERY REQUIREMENTS
A. Owner responsibilities:
1. Coordinate delivery of Owner procured equipment with Contractor.
B. Contractor Responsibilities:
1. Transport and handle products according to manufacturer's instructions to Work area.
2. Before removing equipment from the Owner’s storage area, the Contractor is to inspect the equipment and report any damage to the products before the equipment leaves the Owner storage area. Once the equipment leaves the Owner’s storage area, the Co...
3. Provide equipment and personnel to handle products in accordance with manufacturer recommendations; use methods to prevent soiling, disfigurement, or damage.
1.3 PRODUCT STORAGE AND HANDLING REQUIREMENTS
A. Store and protect products according to manufacturer's instructions.
B. Store products with seals and labels intact and legible.
C. Store sensitive products in weathertight, climate-controlled enclosures in an environment suitable to product.
PART 2 - PRODUCTS
2.1 OWNER FURNISHED PRODUCTS
A. The following attached documents list all of the components that will be furnished by the Owner:
1. Kamstrup flowIQ 220 Data Sheet and Installation Guides.

B. All materials and equipment not specifically listed in the above, or shown as provided by others, are to be supplied by the Contractor.

2.2 CONTRACTOR FURNISHED COMPONENTS FOR OWNER-FURNISHED PRODUCTS
A. All material and equipment required for a complete installation shall be provided and installed by the Contractor.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Section 01 73 00 - Execution Requirements: Requirements for installation examination.
B. Verify that dwelling or establishment, piping, and property owner are ready for the installation before entering the property.
3.2 INSTALLATION
A. According to manufacturer instructions:
1. Refer to attached documents.
2. Coordinate with manufacturer as necessary for additional information.
3.3 FIELD QUALITY CONTROL
A. Section 01 40 00 - Quality Requirements: Requirements for inspecting and testing.
B. Testing, Adjustment & Acceptance: In accordance with manufacturer instructions.
C. Demonstrate functionality for all Owner furnished products. Provide photographic evidence of proper installation as specified in Section 01 32 33 – Photographic Documentation.
01 64 00a - Meter Specification
01 64 00b - Installation Quick Guide
01 64 00c - Installation Graphic