Project 4_Attachment 0008 Scopes_14 May 2026.pdf
PDF 688 KB Posted
- Solicitation number
- W51EW7-26-R-A007
About this file
Summary of MDC-PAC Modular SCIF Project Documentation
This document is a Statement of Work (SOW) and technical specification set for the design and construction of a modular Sensitive Compartmented Information Facility (SCIF-in-a-Box) at Joint Base Lewis-McChord, Washington, located between Buildings 4290 and 4291. The project encompasses approximately 1,000 square feet of facility space with interior partitioning that includes one conference room, four offices, one secure vestibule/man-trap, and one communications/electrical room. The contractor is responsible for all site work, structural assembly, electrical systems, communications infrastructure, security systems, HVAC installation, and construction of an exterior brick perimeter wall with vehicle access gates and personnel doors.
The facility must achieve minimum 60dB Radio Frequency (RF) shielding across the entire six-sided perimeter and interior conference room partition, with all interior and exterior walls meeting a minimum Sound Transmission Class (STC) rating of 50. Site work includes excavation and installation of a 6-inch, 4,000 psi concrete pad with thickened edge extending 12 inches below grade and reinforced with #4 rebar. Electrical requirements include a 200-ampere main distribution panel with sub-panels, copper conductor runs, grounding systems, and arc flash study documentation. Communications infrastructure requires installation of a concrete-encased duct bank system with single-mode fiber optic and multi-pair copper cabling from Building 4290, fiber patch panels (LIUs), telecommunications equipment cabinets, and comprehensive pre- and post-installation testing using Optical Time Domain Reflectometry (OTDR) and attenuation testing. Additional systems include fire alarm control panels per applicable life safety codes, a multi-zone HVAC climate control system with external condenser units, intrusion detection and access control systems compliant with JBLM standards, and perimeter security featuring brick construction with concertina wire topping. Standard work hours are 0700 to 1600 Monday through Friday, and all work must comply with current National Electrical Code (NFPA 70), Unified Facilities Criteria (UFC), local codes, environmental regulations including stormwater pollution prevention plans, and waste management requirements. Utility outages require minimum 14 calendar days advance coordination with the government Project Manager.
View the file
Other files
Show 40 more
Latest 50 of 66 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Title: MDC-PAC Modular SCIF
1.0 DESCRIPTION OF WORK
Provide all plant, labor, tools, equipment, and materials to perform all work in strict accordance with the specifications and plans required for the project. The Contractor shall accomplish all items of work needed to provide a complete and usable SCIF-in-a-Box (SIAB) system. All work must adhere to the applicable drawings, specifications, and relevant national, state, and local codes and standards.
2.0 AREA DESCRIPTION
The work will occur at the designated project site at Joint Base Lewis-McChord – between Building 4290 & Building 4291. The Contractor is responsible for verifying all site conditions, including the availability of electrical and communication services at the designated tie-in points.
3.0 PRINCIPAL ITEMS TO BE ACCOMPLISHED
3.1 Site Work and Foundation
• Concrete Pad Installation:
• Excavate and prepare the site for a new concrete pad at the location of the new SCIF in a box.
• Prepare the subgrade and install a crushed aggregate base course, compacted to 95% standard density. The contractor shall provide a compaction test as a submittal.
• Pour a new 6” thick, 4,000 psi Portland cement concrete pad. The pad shall have a 1” chamfer on all edges and extend 4” above the surrounding grade. Concrete pad requirements may change based on requirements of the SCIF in a box.
• The concrete pad shall have a thickened edge extending 12” below grade. Both the pad and thickened edge shall be reinforced with #4 rebar at 12” O.C. in each direction.
• The contractor shall provide a concrete mix design submittal and the 28-day compressive strength test results.
• SIAB Structure & Layout:
• Dimensions: The facility shall have a combined footprint of approximately 1000 Square Feet.
• Layout: The interior shall be partitioned to include a minimum of:
• One (1) Conference Room
• Four (4) Offices
• One (1) Secure Vestibule / Man-Trap
• One (1) Communications/Electrical Room
• Mount and secure the SCIF in a box onto the newly installed concrete pad per the manufacturer's anchoring requirements.
• The contractor is responsible for procuring the machinery necessary to lift and place the SIAB.
• Provide stub-out locations in the concrete pad for electrical and communications services.
3.2 Security and Acoustic Performance
• RF Shielding: The entire six-sided perimeter of the facility (floor, walls, and ceiling) must provide a minimum of 60dB of Radio Frequency (RF) shielding. The interior wall separating the conference room from the office spaces must also meet this 60dB RF shielding requirement.
• Acoustic Protection: All walls, both exterior and interior, must provide a minimum Sound Transmission Class (STC) rating of 50.
• Secure Vestibule: A man-trap shall be constructed at the primary entrance to control access into the facility. This shall include two doors, interlocked to prevent both from being open simultaneously.
• IDS/ACS: Contractor required to provide an intrusion detection and access control system which complies with the latest specifications, regulations, and JBLM design standards.
3.3 Electrical Service
• Conduit and Wiring:
• The SCIF in a box must include a Main Distribution Panel (MDP) and all necessary sub-panels to support lighting, outlets, HVAC, and communications equipment.
• All electrical penetrations must be properly treated to maintain the SCIF's security envelope.
• Trench and install conduit from the Main Distribution Panel in Building 4290 to the SIAB's electrical panel stub-out location.
• All conductors used shall be copper and must be continuous runs without splices.
All exterior fittings shall be weatherproof.
• Connections and Testing:
• Provide electrical grounding to the SIAB mounted bonding plate per the project specifications.
• Connect the electrical service to the SIAB and coordinate with the government Project Manager (PM) for a full systems check.
• Perform an arc flash study for the affected electrical equipment and provide warning labels. Provide the study results as a submittal.
3.3 Communications Infrastructure
• Duct Bank Installation:
• Install a duct bank system from the communications tie-in point to the SIAB’s communications panel stub-out.
• The duct system shall be concrete-encased schedule-40 conduit. The contractor is responsible for field-verifying all measurements.
• Cable and Service Installation:
• Engineer-Furnish-Install-and-Test (EFI&T) a complete and usable telecommunications fiber optic and copper cable system.
• Install new single-mode (SM) fiber optic and multi-pair copper cabling from the source at Building 4290 to the SIAB, using the new duct bank infrastructure.
• Fusion splice new fiber cables as required and install new splice cases.
• Install new fiber patch panels (Lightguide Interconnection Units or LIUs) and a telecommunications equipment cabinet inside the SIAB.
• All newly installed cables shall be tested "on the reel" before installation and after final termination. The contractor shall perform Optical Time Domain Reflectometry (OTDR) and Attenuation tests on all fiber strands.
• Label all new cables and patch panels in accordance with ANSI/TIA-606 and Joint Base Lewis-McChord labeling standards.
• Provide a detailed communications installation plan and test reports as submittals.
3.4. Fire Protection: A fire alarm control panel (FACP) and associated annunciation/detection devices shall be installed in accordance with all applicable life safety codes.
3.5. HVAC System:
• The facility shall be equipped with a multi-zone climate control system (e.g., ductless mini-split system) capable of independent temperature control for the conference room and office areas.
• All HVAC penetrations through the SCIF boundary must be protected in accordance with SCIF construction standards to maintain acoustic and RF integrity.
• Condenser units shall be located externally.
3.5. Secure Perimeter and Exterior Boundary
• 3.4.1. Perimeter Wall: The Contractor shall design and construct a secure exterior perimeter wall enclosing the SCIF-in-a-box facility, establishing a defined security boundary. Dimensions shall provide for at least 10 feet on 3 sides with one side with at least 25 feet of space for possible parking of vehicles. Wall shall be tall enough to screen visibility of the SCIF in a box from view.
• 3.4.2. Aesthetic Requirements: The perimeter wall shall be constructed of brick. The Contractor must ensure the brick type, color, and coursing match the architectural aesthetic of the surrounding adjacent buildings.
• 3.4.3. Access Control Points: The perimeter shall incorporate physical access points to include a minimum of two (2) secure personnel doors and one (1) vehicle gate. All access points must be equipped with appropriate heavy-duty hardware and locking mechanisms compliant with base physical security standards.
• 3.4.4. Security Topping: To provide an anti-climb physical deterrent, the top of the entire perimeter brick wall and gates must be outfitted with concertina wire.
4.0 CONSTRUCTION REQUIREMENTS
• Work Hours: Normal work hours are 0700 to 1600, Monday through Friday, excluding Federal holidays. Exceptions may be authorized with prior approval from the government PM.
• Permits: The Contractor shall obtain all required permits before starting work, including but not limited to digging permits.
• Codes and Specifications: The Contractor shall comply with the most recent editions of all pertinent Local, State, and Federal codes, including the National Electrical Code (NFPA 70), Unified Facilities Criteria (UFC), and applicable installation design standards.
• Environmental: The Contractor shall comply with all environmental regulations, including the submission of an Environmental Protection Plan (EPP) and a Stormwater Pollution Prevention Plan (SWPPP) if applicable.
• Waste Management: The contractor shall create and follow a waste management plan to meet or exceed installation-specific construction and demolition waste diversion goals.
• Utility Outages: Any required utility outages must be coordinated with the government PM a minimum of 14 calendar days in advance.
Project Location – MDC PAC SCIF
FRONT ISOMETRIC
GROUNDING LUG
(SEE SHEET 8)
4' X 5' AWNING
HIGH SECURITY SINGLE DOOR
WITH NAPEC HASP
ANCHOR BRACKET
45'
10'
15'
1:64
DESCRIPTION
SHEET
DRAWN BY
DATE DRAWN
APPROVED BY
SCALE
SHEET SIZE
DRAWING NO.
APPROX. SHIPPING WT. IN LBS.
C O R P O R A T I O N LINING
SERIAL #
UNIT LENGTH
CUSTOMER
UNIT SPEC
UNIT TYPE
LOCATION
REVISION
300 ARMAG AVE. • BARDSTOWN, KY 40004 • PHONE: (800) 443-9994 •
FAX: (502) 348-4801 • EMAIL: info@armagcorp.com
Manufacturers of Arms Vaults and Explosive Storage magazines since 1969
B
1 OF
LEGEND:
KILL SWITCH
DURESS
ELECTRIC RECEPTACLE
DOUBLE STACKED
SINGLE STACKED
EMERGENCY LIGHT
TELEPHONE JACK
LAN CONNECTION
SEISMIC SENSOR
SMOKE DETECTION
PIR
BULLET TRAP
DS
EMR
P L
SS
SE
SM
PIR
BT
LEGEND CONTINUED:
THERMOSTAT
GROUND
THIS DRAWING IS THE PROPERTY OF ARMAG
CORPORATION WHO CLAIMS PROPRIETARY RIGHTS
IN THE MATERIAL DISCLOSED. IT IS ISSUED IN
CONFIDENCE FOR ENGINEERING INFORMATION
ONLY AND MAY NOT BE COPIED OR USED FOR
MANUFACTURE OF ANYTHING SHOWN WITHOUT
SPECIFIC PERMISSION FROM ARMAG CORPORATION
UNLESS OTHERWISE NOTED, TOLERANCES ARE:
FRACTIONS: ±1/16 ANGLES: ±1°
MACHINED SURFACES: 125 MICRO-INCHES
THESE TOLERANCES DO NOT APPLY TO BASIC DIMS.
DRAWN TO SCALE UNLESS OTHERWISE NOTED
TK
D
UNIT WIDTH UNIT HEIGHT
QUOTE #
EXT. FINISH
S3944
01CTD
02/07/2024
12070-01 41541
45' 15' 10'
ARC VAULT
ICD 705
80,000
ADS
JOINT BASE LEWIS-MCCHORD, WA
ARC VAULT WITH RF SHIELDING, DIVIDER WALLS, ALUMINUM AWNING,
ACOUSTIC/RF COMBO DOOR, AND NETWORK CABINETS,
STC 50 "HAZE GRAY" - DEVTHANE 349QC
1384940044.CIV
Text Box Example SCIF in a Box Design:
*Contractor must confirm all requirements of scope for final SCIF design.
*Contractor not required to use this manufacturer. This is for information only.
RIGHT SIDE ELEVATION
12'21'12'
50'-8 1/2"
45'
48'-0 1/4"
1:49.7485
DESCRIPTION
SHEET
DRAWN BY
DATE DRAWN
APPROVED BY
SCALE
SHEET SIZE
DRAWING NO.
APPROX. SHIPPING WT. IN LBS.
C O R P O R A T I O N LINING
SERIAL #
UNIT LENGTH
CUSTOMER
UNIT SPEC
UNIT TYPE
LOCATION
REVISION
300 ARMAG AVE. • BARDSTOWN, KY 40004 • PHONE: (800) 443-9994 •
FAX: (502) 348-4801 • EMAIL: info@armagcorp.com
Manufacturers of Arms Vaults and Explosive Storage magazines since 1969
B
2 OF
LEGEND:
KILL SWITCH
DURESS
ELECTRIC RECEPTACLE
DOUBLE STACKED
SINGLE STACKED
EMERGENCY LIGHT
TELEPHONE JACK
LAN CONNECTION
SEISMIC SENSOR
SMOKE DETECTION
PIR
BULLET TRAP
DS
EMR
P L
SS
SE
SM
PIR
BT
LEGEND CONTINUED:
THERMOSTAT
GROUND
THIS DRAWING IS THE PROPERTY OF ARMAG
CORPORATION WHO CLAIMS PROPRIETARY RIGHTS
IN THE MATERIAL DISCLOSED. IT IS ISSUED IN
CONFIDENCE FOR ENGINEERING INFORMATION
ONLY AND MAY NOT BE COPIED OR USED FOR
MANUFACTURE OF ANYTHING SHOWN WITHOUT
SPECIFIC PERMISSION FROM ARMAG CORPORATION
UNLESS OTHERWISE NOTED, TOLERANCES ARE:
FRACTIONS: ±1/16 ANGLES: ±1°
MACHINED SURFACES: 125 MICRO-INCHES
THESE TOLERANCES DO NOT APPLY TO BASIC DIMS.
DRAWN TO SCALE UNLESS OTHERWISE NOTED
TK
D
UNIT WIDTH UNIT HEIGHT
QUOTE #
EXT. FINISH
S3944
01CTD
02/07/2024
12070-01 41541
45' 15' 10'
ARC VAULT
ICD 705
80,000
ADS
JOINT BASE LEWIS-MCCHORD, WA
ARC VAULT WITH RF SHIELDING, DIVIDER WALLS, ALUMINUM AWNING,
ACOUSTIC/RF COMBO DOOR, AND NETWORK CABINETS,
STC 50 "HAZE GRAY" - DEVTHANE 349QC
REAR ELEVATIONFRONT ELEVATION
4'
10'-11 3/8"
200AMP 120/208V 3PH 60HZ
MAIN BREAKER
EXTERIOR ELECTRICAL PANEL
SIGNAL J-BOX
(THERMOSTAT AND TAMPERS)
24" X 24" NETWORK ENTRANCE
W/ TWO WGF12 FIBER WAVEGUIDES
2'-10"
8'-2"
4'
SECURITY
LED LIGHT
VESTIBULE
AIR VENT
6"
9'-11 7/8"
15'-1 1/2"
GROUNDING LUG
(SEE SHEET 8)
D-RING
ANCHOR BRACKET
WALL MOUNTED
HVAC
4' X 5' ALUMINUM AWNING
2'-2"
SIGNAL J-BOX
(THERMOSTAT AND TAMPERS)
1:48
DESCRIPTION
SHEET
DRAWN BY
DATE DRAWN
APPROVED BY
SCALE
SHEET SIZE
DRAWING NO.
APPROX. SHIPPING WT. IN LBS.
C O R P O R A T I O N LINING
SERIAL #
UNIT LENGTH
CUSTOMER
UNIT SPEC
UNIT TYPE
LOCATION
REVISION
300 ARMAG AVE. • BARDSTOWN, KY 40004 • PHONE: (800) 443-9994 •
FAX: (502) 348-4801 • EMAIL: info@armagcorp.com
Manufacturers of Arms Vaults and Explosive Storage magazines since 1969
B
3 OF
LEGEND:
KILL SWITCH
DURESS
ELECTRIC RECEPTACLE
DOUBLE STACKED
SINGLE STACKED
EMERGENCY LIGHT
TELEPHONE JACK
LAN CONNECTION
SEISMIC SENSOR
SMOKE DETECTION
PIR
BULLET TRAP
DS
EMR
P L
SS
SE
SM
PIR
BT
LEGEND CONTINUED:
THERMOSTAT
GROUND
THIS DRAWING IS THE PROPERTY OF ARMAG
CORPORATION WHO CLAIMS PROPRIETARY RIGHTS
IN THE MATERIAL DISCLOSED. IT IS ISSUED IN
CONFIDENCE FOR ENGINEERING INFORMATION
ONLY AND MAY NOT BE COPIED OR USED FOR
MANUFACTURE OF ANYTHING SHOWN WITHOUT
SPECIFIC PERMISSION FROM ARMAG CORPORATION
UNLESS OTHERWISE NOTED, TOLERANCES ARE:
FRACTIONS: ±1/16 ANGLES: ±1°
MACHINED SURFACES: 125 MICRO-INCHES
THESE TOLERANCES DO NOT APPLY TO BASIC DIMS.
DRAWN TO SCALE UNLESS OTHERWISE NOTED
TK
D
UNIT WIDTH UNIT HEIGHT
QUOTE #
EXT. FINISH
S3944
01CTD
02/07/2024
12070-01 41541
45' 15' 10'
ARC VAULT
ICD 705
80,000
ADS
JOINT BASE LEWIS-MCCHORD, WA
ARC VAULT WITH RF SHIELDING, DIVIDER WALLS, ALUMINUM AWNING,
ACOUSTIC/RF COMBO DOOR, AND NETWORK CABINETS,
'-9
/2
W
ID
TH
O F
BA
SE
F R
AM
E
44'-10" WIDTH OF BASE FRAME2 1/2"
45'-3" TO BOLT CENTERS
'-5
/2
TO
B O
LT
C
EN
TE
R S
1'-2"
11"
1'-2"
11"
45'-0 1/2"
15'
BASE FRAMING PLAN
1:48
DESCRIPTION
SHEET
DRAWN BY
DATE DRAWN
APPROVED BY
SCALE
SHEET SIZE
DRAWING NO.
APPROX. SHIPPING WT. IN LBS.
C O R P O R A T I O N LINING
SERIAL #
UNIT LENGTH
CUSTOMER
UNIT SPEC
UNIT TYPE
LOCATION
REVISION
300 ARMAG AVE. • BARDSTOWN, KY 40004 • PHONE: (800) 443-9994 •
FAX: (502) 348-4801 • EMAIL: info@armagcorp.com
Manufacturers of Arms Vaults and Explosive Storage magazines since 1969
B
4 OF
LEGEND:
KILL SWITCH
DURESS
ELECTRIC RECEPTACLE
DOUBLE STACKED
SINGLE STACKED
EMERGENCY LIGHT
TELEPHONE JACK
LAN CONNECTION
SEISMIC SENSOR
SMOKE DETECTION
PIR
BULLET TRAP
DS
EMR
P L
SS
SE
SM
PIR
BT
LEGEND CONTINUED:
THERMOSTAT
GROUND
THIS DRAWING IS THE PROPERTY OF ARMAG
CORPORATION WHO CLAIMS PROPRIETARY RIGHTS
IN THE MATERIAL DISCLOSED. IT IS ISSUED IN
CONFIDENCE FOR ENGINEERING INFORMATION
ONLY AND MAY NOT BE COPIED OR USED FOR
MANUFACTURE OF ANYTHING SHOWN WITHOUT
SPECIFIC PERMISSION FROM ARMAG CORPORATION
UNLESS OTHERWISE NOTED, TOLERANCES ARE:
FRACTIONS: ±1/16 ANGLES: ±1°
MACHINED SURFACES: 125 MICRO-INCHES
THESE TOLERANCES DO NOT APPLY TO BASIC DIMS.
DRAWN TO SCALE UNLESS OTHERWISE NOTED
TK
D
UNIT WIDTH UNIT HEIGHT
QUOTE #
EXT. FINISH
S3944
01CTD
02/07/2024
12070-01 41541
45' 15' 10'
ARC VAULT
ICD 705
80,000
ADS
JOINT BASE LEWIS-MCCHORD, WA
ARC VAULT WITH RF SHIELDING, DIVIDER WALLS, ALUMINUM AWNING,
ACOUSTIC/RF COMBO DOOR, AND NETWORK CABINETS,
5'-7 1/4"
8'
15'
13'-10 3/4"
CONFERENCE / CER
WORK AREA
6'
SHREDDER(BY
OTHERS)
PRIN
TER(BY
OTHERS)
2 DRAWER
GSA SAFE
(BY OTHERS)
2'-6"
TYP. 4' TYP.
FURNITURE
(BY OTHERS)
27'-8" 16'
45'
FLOOR PLAN
1 3
VESTIBULE
8'
3'-6"
1:48
DESCRIPTION
SHEET
DRAWN BY
DATE DRAWN
APPROVED BY
SCALE
SHEET SIZE
DRAWING NO.
APPROX. SHIPPING WT. IN LBS.
C O R P O R A T I O N LINING
SERIAL #
UNIT LENGTH
CUSTOMER
UNIT SPEC
UNIT TYPE
LOCATION
REVISION
300 ARMAG AVE. • BARDSTOWN, KY 40004 • PHONE: (800) 443-9994 •
FAX: (502) 348-4801 • EMAIL: info@armagcorp.com
Manufacturers of Arms Vaults and Explosive Storage magazines since 1969
B
5 OF
LEGEND:
KILL SWITCH
DURESS
ELECTRIC RECEPTACLE
DOUBLE STACKED
SINGLE STACKED
EMERGENCY LIGHT
TELEPHONE JACK
LAN CONNECTION
SEISMIC SENSOR
SMOKE DETECTION
PIR
BULLET TRAP
DS
EMR
P L
SS
SE
SM
PIR
BT
LEGEND CONTINUED:
THERMOSTAT
GROUND
THIS DRAWING IS THE PROPERTY OF ARMAG
CORPORATION WHO CLAIMS PROPRIETARY RIGHTS
IN THE MATERIAL DISCLOSED. IT IS ISSUED IN
CONFIDENCE FOR ENGINEERING INFORMATION
ONLY AND MAY NOT BE COPIED OR USED FOR
MANUFACTURE OF ANYTHING SHOWN WITHOUT
SPECIFIC PERMISSION FROM ARMAG CORPORATION
UNLESS OTHERWISE NOTED, TOLERANCES ARE:
FRACTIONS: ±1/16 ANGLES: ±1°
MACHINED SURFACES: 125 MICRO-INCHES
THESE TOLERANCES DO NOT APPLY TO BASIC DIMS.
DRAWN TO SCALE UNLESS OTHERWISE NOTED
TK
D
UNIT WIDTH UNIT HEIGHT
QUOTE #
EXT. FINISH
S3944
01CTD
02/07/2024
12070-01 41541
45' 15' 10'
ARC VAULT
ICD 705
80,000
ADS
JOINT BASE LEWIS-MCCHORD, WA
ARC VAULT WITH RF SHIELDING, DIVIDER WALLS, ALUMINUM AWNING,
ACOUSTIC/RF COMBO DOOR, AND NETWORK CABINETS,
STC 50 "HAZE GRAY" - DEVTHANE 349QC
DOOR SCHEDULE
DOOR QTY SIZE / SWING DESCRIPTION HARDWARE
1 1 3070 / LHR ARMAG HIGH SECURITY DOOR, A-36 STEEL W/ 2" HARDWOOD MIL-DTL-29181 HIGH SECURITY HASP / PANIC BAR EXIT DEVICE 2 1 3070 / RH 18 GA COMMERCIAL METAL DOOR W/ 16 GA FRAME COMMERCIAL LEVER LOCKSET / CLOSER / WEATHER STRIPPING
3 1 3070 / LHR RF SHIELDED ACOUSTIC COMBO DOOR W/ FRAME, MEETING ICS 705 SOUND
GROUP 4 LKM10K - X10 W/ KEY OVERRIDE / CLOSER
4 1 3070 / RHR 18 GA COMMERCIAL METAL DOOR W/ 16 GA FRAME COMMERCIAL LEVER LOCKSET / CLOSER
FINISH SCHEDULE
SURFACE MATERIAL COLOR
EXTERIOR PAINT DEVOE DEVATHANE 349QC HAZE GRAY
INTERIOR PRIMER DEVOE DEVATHANE 349QC GRAY
INTERIOR WALLS WHITE TEXTURED FRP .090" WHITE
CEILING WHITE TEXTURED FRP .090" WHITE
DOORS + FRAMES DEVOE DEVTHANE 349QC GREY
BASE MOULDING FLEXCO 2000 TPR WALL BASE, 4" COVE BLACK
FLOOR SQUARE CARPET TILES GREY
ICS 705 SOUND GROUP 4
STC 50 SECURITY PERIMETER
DYNASOUND DS2400
SOUND MASKER ON
RETURN DUCT
PIRCCTV CAMERA
DYNASOUND DS2400
SOUND MASKER ON
RETURN DUCT
SM
PIR
SECURITY PLAN
IDS PREP
(EQUIPMENT
BY OTHERS)
ACS PREP
(EQUIPMENT
BY OTHERS)
BOX ONLY
(BMS BY OTHERS)
BM
S
BOX ONLY
(BMS BY OTHERS)
BOX ONLY
(PIR BY OTHERS)
CCTV MONITOR
BOX ONLY
(PIR BY OTHERS)
WALL BOX FOR
IDS KEYPAD
(BY OTHERS)
WALL BOX FOR
ACS KEYPAD /
CARD READER
(BY OTHERS)
BM
S
1:48
DESCRIPTION
SHEET
DRAWN BY
DATE DRAWN
APPROVED BY
SCALE
SHEET SIZE
DRAWING NO.
APPROX. SHIPPING WT. IN LBS.
C O R P O R A T I O N LINING
SERIAL #
UNIT LENGTH
CUSTOMER
UNIT SPEC
UNIT TYPE
LOCATION
REVISION
300 ARMAG AVE. • BARDSTOWN, KY 40004 • PHONE: (800) 443-9994 •
FAX: (502) 348-4801 • EMAIL: info@armagcorp.com
Manufacturers of Arms Vaults and Explosive Storage magazines since 1969
B
6 OF
LEGEND:
KILL SWITCH
DURESS
ELECTRIC RECEPTACLE
DOUBLE STACKED
SINGLE STACKED
EMERGENCY LIGHT
TELEPHONE JACK
LAN CONNECTION
SEISMIC SENSOR
SMOKE DETECTION
PIR
BULLET TRAP
DS
EMR
P L
SS
SE
SM
PIR
BT
LEGEND CONTINUED:
THERMOSTAT
GROUND
THIS DRAWING IS THE PROPERTY OF ARMAG
CORPORATION WHO CLAIMS PROPRIETARY RIGHTS
IN THE MATERIAL DISCLOSED. IT IS ISSUED IN
CONFIDENCE FOR ENGINEERING INFORMATION
ONLY AND MAY NOT BE COPIED OR USED FOR
MANUFACTURE OF ANYTHING SHOWN WITHOUT
SPECIFIC PERMISSION FROM ARMAG CORPORATION
UNLESS OTHERWISE NOTED, TOLERANCES ARE:
FRACTIONS: ±1/16 ANGLES: ±1°
MACHINED SURFACES: 125 MICRO-INCHES
THESE TOLERANCES DO NOT APPLY TO BASIC DIMS.
DRAWN TO SCALE UNLESS OTHERWISE NOTED
TK
D
UNIT WIDTH UNIT HEIGHT
QUOTE #
EXT. FINISH
S3944
01CTD
02/07/2024
12070-01 41541
45' 15' 10'
ARC VAULT
ICD 705
80,000
ADS
JOINT BASE LEWIS-MCCHORD, WA
ARC VAULT WITH RF SHIELDING, DIVIDER WALLS, ALUMINUM AWNING,
ACOUSTIC/RF COMBO DOOR, AND NETWORK CABINETS,
2 TON WALL-MOUNT
HVAC W/ ACOUSTIC
Z-DUCT FOR SUPPLY
AND RETURN
W24HYDB05MXXXXE
3 TON WALL-MOUNT
HVAC W/ ACOUSTIC
Z-DUCT FOR SUPPLY
AND RETURN
W36HYDB05MXXXXE
A
B
EM
R
A
A
A A
C
A
C
C
EM
R
A
A
A
T T
LIGHTING / HVAC PLAN
EM
R
A
1:48
DESCRIPTION
SHEET
DRAWN BY
DATE DRAWN
APPROVED BY
SCALE
SHEET SIZE
DRAWING NO.
APPROX. SHIPPING WT. IN LBS.
C O R P O R A T I O N LINING
SERIAL #
UNIT LENGTH
CUSTOMER
UNIT SPEC
UNIT TYPE
LOCATION
REVISION
300 ARMAG AVE. • BARDSTOWN, KY 40004 • PHONE: (800) 443-9994 •
FAX: (502) 348-4801 • EMAIL: info@armagcorp.com
Manufacturers of Arms Vaults and Explosive Storage magazines since 1969
B
7 OF
LEGEND:
KILL SWITCH
DURESS
ELECTRIC RECEPTACLE
DOUBLE STACKED
SINGLE STACKED
EMERGENCY LIGHT
TELEPHONE JACK
LAN CONNECTION
SEISMIC SENSOR
SMOKE DETECTION
PIR
BULLET TRAP
DS
EMR
P L
SS
SE
SM
PIR
BT
LEGEND CONTINUED:
THERMOSTAT
GROUND
THIS DRAWING IS THE PROPERTY OF ARMAG
CORPORATION WHO CLAIMS PROPRIETARY RIGHTS
IN THE MATERIAL DISCLOSED. IT IS ISSUED IN
CONFIDENCE FOR ENGINEERING INFORMATION
ONLY AND MAY NOT BE COPIED OR USED FOR
MANUFACTURE OF ANYTHING SHOWN WITHOUT
SPECIFIC PERMISSION FROM ARMAG CORPORATION
UNLESS OTHERWISE NOTED, TOLERANCES ARE:
FRACTIONS: ±1/16 ANGLES: ±1°
MACHINED SURFACES: 125 MICRO-INCHES
THESE TOLERANCES DO NOT APPLY TO BASIC DIMS.
DRAWN TO SCALE UNLESS OTHERWISE NOTED
TK
D
UNIT WIDTH UNIT HEIGHT
QUOTE #
EXT. FINISH
S3944
01CTD
02/07/2024
12070-01 41541
45' 15' 10'
ARC VAULT
ICD 705
80,000
ADS
JOINT BASE LEWIS-MCCHORD, WA
ARC VAULT WITH RF SHIELDING, DIVIDER WALLS, ALUMINUM AWNING,
ACOUSTIC/RF COMBO DOOR, AND NETWORK CABINETS,
STC 50 "HAZE GRAY" - DEVTHANE 349QC
LIGHTING SCHEDULE
ITEM # QTY DESCRIPTION MFG / PART NUMBER
A 10 4' - LED LIGHT FIXTURE RAB LIGHTING / SEAL 4-50/D10
B 1 EXTERIOR 18W LED WALL PACK LIGHT RAB LIGHTING / SLIM18
C 3 LED EXIT / EMERGENCY LIGHT HUBBLE LIGHTING / EVCURW
NETWORK ENTRANCE
WITH TWO WGF12
FIBER WAVEGUIDES
200A 120/208V 3PH 60HZ
MAIN BREAKER PANEL
(2) 24" CABINETS FOR
SECURE NETWORKS
W/ QUAD RECEPTACLES
(1) 48" CABINET FOR
NON-SECURE NETWORKS
W/ QUAD RECEPTACLE
5'-7 1/4"
8'
15'
6'
3'-6"4' TYP. C-C
7' 4'
27'-8" 16'
45'
ELECTRICAL / NETWORKING PLAN
CONFERENCE / CERWORK AREA
6'
WALL PENETRATION
FOR RACEWAY, QTY 2
DUPLEX NEMA 5-20
RECEPTACLE FOR CCTV
WALL MOUNTED
QUAD NEMA 5-20
RECEPTACLE, QTY 10
36" AFF
WALL MOUNTED BOX FOR
NETWORK DROP, QTY 10
36" AFF
5'-10"
4'
DUPLEX NEMA 5-20
RECEPTACLE FOR SHREDDER
DEDICATED BREAKER
18" AFF
VESTIBULE
4X100A
POWER FILTER
100A 120/208V 3PH 60HZ
PANELBOARD
1:48
DESCRIPTION
SHEET
DRAWN BY
DATE DRAWN
APPROVED BY
SCALE
SHEET SIZE
DRAWING NO.
APPROX. SHIPPING WT. IN LBS.
C O R P O R A T I O N LINING
SERIAL #
UNIT LENGTH
CUSTOMER
UNIT SPEC
UNIT TYPE
LOCATION
REVISION
300 ARMAG AVE. • BARDSTOWN, KY 40004 • PHONE: (800) 443-9994 •
FAX: (502) 348-4801 • EMAIL: info@armagcorp.com
Manufacturers of Arms Vaults and Explosive Storage magazines since 1969
B
8 OF
LEGEND:
KILL SWITCH
DURESS
ELECTRIC RECEPTACLE
DOUBLE STACKED
SINGLE STACKED
EMERGENCY LIGHT
TELEPHONE JACK
LAN CONNECTION
SEISMIC SENSOR
SMOKE DETECTION
PIR
BULLET TRAP
DS
EMR
P L
SS
SE
SM
PIR
BT
LEGEND CONTINUED:
THERMOSTAT
GROUND
THIS DRAWING IS THE PROPERTY OF ARMAG
CORPORATION WHO CLAIMS PROPRIETARY RIGHTS
IN THE MATERIAL DISCLOSED. IT IS ISSUED IN
CONFIDENCE FOR ENGINEERING INFORMATION
ONLY AND MAY NOT BE COPIED OR USED FOR
MANUFACTURE OF ANYTHING SHOWN WITHOUT
SPECIFIC PERMISSION FROM ARMAG CORPORATION
UNLESS OTHERWISE NOTED, TOLERANCES ARE:
FRACTIONS: ±1/16 ANGLES: ±1°
MACHINED SURFACES: 125 MICRO-INCHES
THESE TOLERANCES DO NOT APPLY TO BASIC DIMS.
DRAWN TO SCALE UNLESS OTHERWISE NOTED
TK
D
UNIT WIDTH UNIT HEIGHT
QUOTE #
EXT. FINISH
S3944
01CTD
02/07/2024
12070-01 41541
45' 15' 10'
ARC VAULT
ICD 705
80,000
ADS
JOINT BASE LEWIS-MCCHORD, WA
ARC VAULT WITH RF SHIELDING, DIVIDER WALLS, ALUMINUM AWNING,
ACOUSTIC/RF COMBO DOOR, AND NETWORK CABINETS,
NETWORK CABINET DETAIL NETWORK DROP DETAIL
(11) 62.5 UM LC FIBER
CONNECTORS IN COLOR
CODED PATCH PANEL, QTY 2
QUAD NEMA 5-20
RECEPTACLE FOR
CABINETS (X3)
24" TALL WALL-MOUNTED
NETWORKING CABINET FOR (RED)
SECURE NETWORK
(11) 62.5 UM LC FIBER
CONNECTORS IN COLOR
CODED PATCH PANEL
24" TALL WALL-MOUNTED
NETWORKING CABINET FOR
(YELLOW) SECURE NETWORK
(11) 62.5 UM LC FIBER
CONNECTORS IN COLOR
CODED PATCH PANEL
WALL PENETRATION TO
EXTERIOR JUNCTION BOX
48" TALL WALL-MOUNTED
NETWORKING CABINET FOR
(GREEN AND WHITE)
NON-SECURE NETWORKS
4" RACEWAY
TYP WALL MOUNTED NETWORK DROP
FACEPLATE - (4) LC CONNECTORS
COLOR CODED TO NETWORK
1:20
DESCRIPTION
SHEET
DRAWN BY
DATE DRAWN
APPROVED BY
SCALE
SHEET SIZE
DRAWING NO.
APPROX. SHIPPING WT. IN LBS.
C O R P O R A T I O N LINING
SERIAL #
UNIT LENGTH
CUSTOMER
UNIT SPEC
UNIT TYPE
LOCATION
REVISION
300 ARMAG AVE. • BARDSTOWN, KY 40004 • PHONE: (800) 443-9994 •
FAX: (502) 348-4801 • EMAIL: info@armagcorp.com
Manufacturers of Arms Vaults and Explosive Storage magazines since 1969
B
9 OF
LEGEND:
KILL SWITCH
DURESS
ELECTRIC RECEPTACLE
DOUBLE STACKED
SINGLE STACKED
EMERGENCY LIGHT
TELEPHONE JACK
LAN CONNECTION
SEISMIC SENSOR
SMOKE DETECTION
PIR
BULLET TRAP
DS
EMR
P L
SS
SE
SM
PIR
BT
LEGEND CONTINUED:
THERMOSTAT
GROUND
THIS DRAWING IS THE PROPERTY OF ARMAG
CORPORATION WHO CLAIMS PROPRIETARY RIGHTS
IN THE MATERIAL DISCLOSED. IT IS ISSUED IN
CONFIDENCE FOR ENGINEERING INFORMATION
ONLY AND MAY NOT BE COPIED OR USED FOR
MANUFACTURE OF ANYTHING SHOWN WITHOUT
SPECIFIC PERMISSION FROM ARMAG CORPORATION
UNLESS OTHERWISE NOTED, TOLERANCES ARE:
FRACTIONS: ±1/16 ANGLES: ±1°
MACHINED SURFACES: 125 MICRO-INCHES
THESE TOLERANCES DO NOT APPLY TO BASIC DIMS.
DRAWN TO SCALE UNLESS OTHERWISE NOTED
TK
D
UNIT WIDTH UNIT HEIGHT
QUOTE #
EXT. FINISH
S3944
01CTD
02/07/2024
12070-01 41541
45' 15' 10'
ARC VAULT
ICD 705
80,000
ADS
JOINT BASE LEWIS-MCCHORD, WA
ARC VAULT WITH RF SHIELDING, DIVIDER WALLS, ALUMINUM AWNING,
ACOUSTIC/RF COMBO DOOR, AND NETWORK CABINETS,
1:25.7466
DESCRIPTION
SHEET
DRAWN BY
DATE DRAWN
APPROVED BY
SCALE
SHEET SIZE
DRAWING NO.
APPROX. SHIPPING WT. IN LBS.
C O R P O R A T I O N LINING
SERIAL #
UNIT LENGTH
CUSTOMER
UNIT SPEC
UNIT TYPE
LOCATION
REVISION
300 ARMAG AVE. • BARDSTOWN, KY 40004 • PHONE: (800) 443-9994 •
FAX: (502) 348-4801 • EMAIL: info@armagcorp.com
Manufacturers of Arms Vaults and Explosive Storage magazines since 1969
B
10 OF
LEGEND:
KILL SWITCH
DURESS
ELECTRIC RECEPTACLE
DOUBLE STACKED
SINGLE STACKED
EMERGENCY LIGHT
TELEPHONE JACK
LAN CONNECTION
SEISMIC SENSOR
SMOKE DETECTION
PIR
BULLET TRAP
DS
EMR
P L
SS
SE
SM
PIR
BT
LEGEND CONTINUED:
THERMOSTAT
GROUND
THIS DRAWING IS THE PROPERTY OF ARMAG
CORPORATION WHO CLAIMS PROPRIETARY RIGHTS
IN THE MATERIAL DISCLOSED. IT IS ISSUED IN
CONFIDENCE FOR ENGINEERING INFORMATION
ONLY AND MAY NOT BE COPIED OR USED FOR
MANUFACTURE OF ANYTHING SHOWN WITHOUT
SPECIFIC PERMISSION FROM ARMAG CORPORATION
UNLESS OTHERWISE NOTED, TOLERANCES ARE:
FRACTIONS: ±1/16 ANGLES: ±1°
MACHINED SURFACES: 125 MICRO-INCHES
THESE TOLERANCES DO NOT APPLY TO BASIC DIMS.
DRAWN TO SCALE UNLESS OTHERWISE NOTED
TK
D
UNIT WIDTH UNIT HEIGHT
QUOTE #
EXT. FINISH
S3944
01CTD
02/07/2024
12070-01 41541
45' 15' 10'
ARC VAULT
ICD 705
80,000
ADS
JOINT BASE LEWIS-MCCHORD, WA
ARC VAULT WITH RF SHIELDING, DIVIDER WALLS, ALUMINUM AWNING,
ACOUSTIC/RF COMBO DOOR, AND NETWORK CABINETS,
STC 50 "HAZE GRAY" - DEVTHANE 349QC
120/208V 3Ø 60 Hz
MAIN PANEL
NEMA 3R ENCLOSURE
POWER FILTER
4 LINE 100A
RF SHIELDED
PERIMETER
200A MAIN
BREAKER
100A BREAKER TO
INTERIOR PANEL
INTERIOR PANEL
NEMA 1 ENCLOSURE
POWER DISTRIBUTION
13 14
15 16
17 18
19 20
21 22
23 24
INTERIOR SUB PANEL SCHEDULE - 100A 120/208V 3Ø RATED PANEL - MAIN LUG ONLY SURFACE MOUNT - NEMA 1
BRK. VOLTS AMPS /
POLES DESCRIPTION
LOAD (VA)
DESCRIPTION AMPS /
POLES VOLTS BRK.
A B C
1 120 20/1 NETWORK CABINET #1 1000 / 800 RECEPTACLES #1-2 20/1 120 2
3 120 20/1 NETWORK CABINET #2 1000 / 800 RECEPTACLES #3-4 20/1 120 4
5 120 20/1 NETWORK CABINET #3 1000 / 800 RECEPTACLES #5-6 20/1 120 6
7 120 20/1 CCTV RECEPTACLE 180 /800 RECEPTACLES #7-8 20/1 120 8
9 120 20/1 SHREDDER 400 / 800 RECEPTACLES #9-10 20/1 120 10
11 120 20/1 PRINTER 400 / 200 CER LIGHTING 20/1 120 12
13 120 20/1 SPARE - / 360 IDS / ACS 20/1 120 14
15 120 20/1 SPARE - / 250 WORK AREA LIGHTING 20/1 120 16
17 120 20/1 SPARE - / - SPARE 20/1 120 18
19 120 20/1 SPARE - / - SPARE 20/1 120 20
21 120 20/1 SPARE - / - SPARE 20/1 120 22
23 120 20/1 SPARE - / - SPARE 20/1 120 24
CONNECTED LOAD PER PHASE 3140 3250 2400
TOTAL CONNECTED LOAD (KVA) 8.79
EXTERIOR MAIN PANEL SCHEDULE - 120/208V 3Ø RATED PANEL W/ 200A MAIN BREAKER SURFACE MOUNT - NEMA 3R
BRK. VOLTS AMPS /
POLES DESCRIPTION
LOAD (VA)
DESCRIPTION AMPS /
POLES VOLTS BRK.
A B C
208 30/3 HVAC
3600 / 4200
HVAC 35/3 208
3 3600 / 4200 4
5 3600 / 4200 6
7 120 20/1 EXTERIOR LIGHTING 18 / 230 VESTIBULE 20/1 120 8
9 120 20/1 SPARE - / 3250
INTERIOR POWER 100/3 208
11 120 20/1 SPARE - / 2400 12
13 120 20/1 SPARE - / 3140 14
15 120 20/1 SPARE - / - SPARE 20/1 120 16
17 120 20/1 SPARE - / - SPARE 20/1 120 18
CONNECTED LOAD PER PHASE 9388 11050 10200
TOTAL CONNECTED LOAD (KVA) 30.64
120/208V 3Ø 60 Hz
TYPICAL GROUNDING KIT
TYPICAL WALL / ROOF CONSTRUCTION
6 5/8"
7 3/8"
10 1/8"
TYPICAL FLOOR CONSTRUCTION
COPPER BONDING
PLATE IS BRAZED TO
1/4" MILD STEEL PLATE
COPPER CONDUCTOR
-28 STRANDS OF #14 AWG
COPPER WIRE IN ROPE LAY
-121,900 CIRCULAR MIL
CROSS SECTION
GROUND CLAMP
FOR Ø3/4" ROD
COPPER CLAD GROUND ROD
Ø3/4" X 10FT. BURIED IN EARTH BY
OTHERS PER NEC REQUIREMENTS
3/8" A-36 STEEL 2" X 2 5/8"
PINE BOARD HSS 6" X 6" X 1/4"
BASE FRAME
HSS 2 1/2" X 2 1/2" X 3/16"
WALL SUPPORT 48" O.C.
2 1/2" R10 BATT
MINERAL WOOL
2 1/2" R10 BATT
MINERAL WOOL
3/4" ADVANTECH
PLYWOOD 1/4" UNDERLAYMENTFLOOR
COVERING
RSIC-1 SOUND ISOLATION CLIPS
MOUNTED TO 2X4 ON 24" X 48" PATTERN
7/8" 20 GA FURRING CHANNELS
MOUNTED IN RSIC-1 CLIPS
5/8" AC PLYWOOD
HSS 6" X 2" X 1/8" + 1/8" X 6" PL
ROOF TEE 24" O.C.(2) LAYERS
1" HARDWOOD
5/8" R4 RIGID
INSULATION
5/8" R4 RIGID
INSULATION1/4" A-36 STEEL SHELL
2 1/2" R10 BATT
MINERAL WOOL
(2) LAYERS
1" HARDWOOD1/4" A-36 STEEL SHELL
5/8" AC PLYWOOD
1:16
DESCRIPTION
SHEET
DRAWN BY
DATE DRAWN
APPROVED BY
SCALE
SHEET SIZE
DRAWING NO.
APPROX. SHIPPING WT. IN LBS.
C O R P O R A T I O N LINING
SERIAL #
UNIT LENGTH
CUSTOMER
UNIT SPEC
UNIT TYPE
LOCATION
REVISION
300 ARMAG AVE. • BARDSTOWN, KY 40004 • PHONE: (800) 443-9994 •
FAX: (502) 348-4801 • EMAIL: info@armagcorp.com
Manufacturers of Arms Vaults and Explosive Storage magazines since 1969
B
11 OF
LEGEND:
KILL SWITCH
DURESS
ELECTRIC RECEPTACLE
DOUBLE STACKED
SINGLE STACKED
EMERGENCY LIGHT
TELEPHONE JACK
LAN CONNECTION
SEISMIC SENSOR
SMOKE DETECTION
PIR
BULLET TRAP
DS
EMR
P L
SS
SE
SM
PIR
BT
LEGEND CONTINUED:
THERMOSTAT
GROUND
THIS DRAWING IS THE PROPERTY OF ARMAG
CORPORATION WHO CLAIMS PROPRIETARY RIGHTS
IN THE MATERIAL DISCLOSED. IT IS ISSUED IN
CONFIDENCE FOR ENGINEERING INFORMATION
ONLY AND MAY NOT BE COPIED OR USED FOR
MANUFACTURE OF ANYTHING SHOWN WITHOUT
SPECIFIC PERMISSION FROM ARMAG CORPORATION
UNLESS OTHERWISE NOTED, TOLERANCES ARE:
FRACTIONS: ±1/16 ANGLES: ±1°
MACHINED SURFACES: 125 MICRO-INCHES
THESE TOLERANCES DO NOT APPLY TO BASIC DIMS.
DRAWN TO SCALE UNLESS OTHERWISE NOTED
TK
D
UNIT WIDTH UNIT HEIGHT
QUOTE #
EXT. FINISH
S3944
01CTD
02/07/2024
12070-01 41541
45' 15' 10'
ARC VAULT
ICD 705
80,000
ADS
JOINT BASE LEWIS-MCCHORD, WA
ARC VAULT WITH RF SHIELDING, DIVIDER WALLS, ALUMINUM AWNING,
ACOUSTIC/RF COMBO DOOR, AND NETWORK CABINETS,
| Example SCIF Design Drawings.pdf |
| Sheets and Views |
| S3944-1 |
| S3944-2 |
| S3944-3 |
| S3944-4 |
| S3944-5 |
| S3944-6 |
| S3944-7 |
| S3944-8 |
| S3944-9 |
| S3944-10 |
| S3944-11 |
File details come from the government source that posted it. Updated .