Summary of MDC-PAC Modular SCIF Project Documentation

This document is a Statement of Work (SOW) and technical specification set for the design and construction of a modular Sensitive Compartmented Information Facility (SCIF-in-a-Box) at Joint Base Lewis-McChord, Washington, located between Buildings 4290 and 4291. The project encompasses approximately 1,000 square feet of facility space with interior partitioning that includes one conference room, four offices, one secure vestibule/man-trap, and one communications/electrical room. The contractor is responsible for all site work, structural assembly, electrical systems, communications infrastructure, security systems, HVAC installation, and construction of an exterior brick perimeter wall with vehicle access gates and personnel doors.

The facility must achieve minimum 60dB Radio Frequency (RF) shielding across the entire six-sided perimeter and interior conference room partition, with all interior and exterior walls meeting a minimum Sound Transmission Class (STC) rating of 50. Site work includes excavation and installation of a 6-inch, 4,000 psi concrete pad with thickened edge extending 12 inches below grade and reinforced with #4 rebar. Electrical requirements include a 200-ampere main distribution panel with sub-panels, copper conductor runs, grounding systems, and arc flash study documentation. Communications infrastructure requires installation of a concrete-encased duct bank system with single-mode fiber optic and multi-pair copper cabling from Building 4290, fiber patch panels (LIUs), telecommunications equipment cabinets, and comprehensive pre- and post-installation testing using Optical Time Domain Reflectometry (OTDR) and attenuation testing. Additional systems include fire alarm control panels per applicable life safety codes, a multi-zone HVAC climate control system with external condenser units, intrusion detection and access control systems compliant with JBLM standards, and perimeter security featuring brick construction with concertina wire topping. Standard work hours are 0700 to 1600 Monday through Friday, and all work must comply with current National Electrical Code (NFPA 70), Unified Facilities Criteria (UFC), local codes, environmental regulations including stormwater pollution prevention plans, and waste management requirements. Utility outages require minimum 14 calendar days advance coordination with the government Project Manager.

View the file

Other files

File Type Posted
QA_JBLM FORGE_20260518.pdf PDF
Project 17_Attachment 0021 Scopes_15 May 2026.pdf PDF
JBLM_FORGE_RPP_Amendment 3.pdf PDF
Project 14_Attachment 0018 Scopes_11 May 2026.pdf PDF
ATTACH0003 MICC_CONSTRUCTION_OTA_TC_FORGE ver05122026.pdf PDF
Project 15_Attachment 0019 Scopes_11 May 2026.pdf PDF
Project 1_Attachment 0005 D Scopes_11 May 2026.pdf PDF
Project 9_Attachment 0013 Scopes_11 May 2026.pdf PDF
Project 2_Attachment 0006 Scopes_10 May 2026.pdf PDF
Project 3_Attachment 0007 Scopes_10 May 2026.pdf PDF
JBLM_FORGE_RPP_Amendment 2.pdf PDF
Project 6_Attachment 0010 Scopes_11 May 2026.pdf PDF
JBLM_FORGE_RPP_Amendment_1.pdf PDF
QA_JBLM FORGE_20260428.pdf PDF
Project 1_Attachment 0005 A Scopes_07 Apr 2026.pdf PDF
FORGE Site Visits.pdf PDF
Special Notice JBLM Site Visit.pdf PDF
JBLM FORGE Site Visit Registration 20260422.xlsx XLSX spreadsheet
Project 1_Attachment 0005 B Scopes_07 Apr 2026.pdf PDF
Project 1_Attachment 0005 C Scopes_07 Apr 2026.pdf PDF
Project 4_Attachment 0008 Scopes_07 Apr 2026.pdf PDF
Project 17_Attachment 0021 Scopes_07 Apr 2026.pdf PDF
Project 10_Attachment 0014 Scopes_07 Apr 2026.pdf PDF
JBLM_FORGE_RPP_04172026.pdf PDF
Project 12_ Attachment 0016 Scopes_07 Apr 2026.pdf PDF
ATTACH0004 JBLM FORGE CLIN STRUCTURE.xlsx XLSX spreadsheet
Project 13_ Attachment 0017 Scopes_07 Apr 2026.pdf PDF
Project 1_Attachment 0005 A Scopes_07 Apr 2026.pdf PDF
Project 3_ Attachment 0007 Scopes_07 Apr 2026.pdf PDF
Project 8_ Attachment 0012 Scopes_07 Apr 2026.pdf PDF
Project 5_Attachment 0009 Scopes_07 Apr 2026.pdf PDF
Project 16_ Attachment 0020 Scopes_07 Apr 2026.pdf PDF
Project 18_Attachment 0022 Scopes_07 Apr 2026.pdf PDF
Project 15_Attachment 0019 Scopes_07 Apr 2026.pdf PDF
Project 1_Attachment 0005 B Scopes_07 Apr 2026.pdf PDF
Project 19_Attachment 0023 Scopes_07 Apr 2026.pdf PDF
Project 1_Attachment 0005 C Scopes_07 Apr 2026.pdf PDF
Project 6_ Attachment 0010 Scopes_07 Apr 2026.pdf PDF
ATTACH0003 MICC_CONSTRUCTION_OTA_TC_FORGE ver04082026.pdf PDF
Project 2_ Attachment 0006 Scopes_07 Apr 2026.pdf PDF
ATTACH0002_Contract 01 Specifications_JBLMFORGE_RPP.pdf PDF
Project 7_ Attachment 0011 Scopes_07 Apr 2026.pdf PDF
Project 11_ Attachment 0015 Scopes_07 Apr 2026.pdf PDF
ATTACH0001_FY26 JBLM FORGE - Project List 20260414.xlsx XLSX spreadsheet
Project 9_ Attachment 0013 Scopes_07 Apr 2026.pdf PDF
Project 14_Attachment 0018 Scopes_07 Apr 2026.pdf PDF
MICC_JBLM_FORGE_INDUSTRYDAY_SAM.GOV NONCUI.pdf PDF
Pages 601-700 from Attachment 004 Project Scopes.pdf PDF
Pages 1-500 from Attachment 004 Project Scopes.pdf PDF
Pages 701-900 from Attachment 004 Project Scopes.pdf PDF
Show 40 more

Latest 50 of 66 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Project Title: MDC-PAC Modular SCIF

1.0 DESCRIPTION OF WORK

Provide all plant, labor, tools, equipment, and materials to perform all work in strict accordance with the specifications and plans required for the project. The Contractor shall accomplish all items of work needed to provide a complete and usable SCIF-in-a-Box (SIAB) system. All work must adhere to the applicable drawings, specifications, and relevant national, state, and local codes and standards.

2.0 AREA DESCRIPTION

The work will occur at the designated project site at Joint Base Lewis-McChord – between Building 4290 & Building 4291. The Contractor is responsible for verifying all site conditions, including the availability of electrical and communication services at the designated tie-in points.

3.0 PRINCIPAL ITEMS TO BE ACCOMPLISHED

3.1 Site Work and Foundation

• Concrete Pad Installation:

• Excavate and prepare the site for a new concrete pad at the location of the new SCIF in a box.

• Prepare the subgrade and install a crushed aggregate base course, compacted to 95% standard density. The contractor shall provide a compaction test as a submittal.

• Pour a new 6” thick, 4,000 psi Portland cement concrete pad. The pad shall have a 1” chamfer on all edges and extend 4” above the surrounding grade. Concrete pad requirements may change based on requirements of the SCIF in a box.

• The concrete pad shall have a thickened edge extending 12” below grade. Both the pad and thickened edge shall be reinforced with #4 rebar at 12” O.C. in each direction.

• The contractor shall provide a concrete mix design submittal and the 28-day compressive strength test results.

• SIAB Structure & Layout:

• Dimensions: The facility shall have a combined footprint of approximately 1000 Square Feet.

• Layout: The interior shall be partitioned to include a minimum of:

• One (1) Conference Room

• Four (4) Offices

• One (1) Secure Vestibule / Man-Trap

• One (1) Communications/Electrical Room

• Mount and secure the SCIF in a box onto the newly installed concrete pad per the manufacturer's anchoring requirements.

• The contractor is responsible for procuring the machinery necessary to lift and place the SIAB.

• Provide stub-out locations in the concrete pad for electrical and communications services.

3.2 Security and Acoustic Performance

• RF Shielding: The entire six-sided perimeter of the facility (floor, walls, and ceiling) must provide a minimum of 60dB of Radio Frequency (RF) shielding. The interior wall separating the conference room from the office spaces must also meet this 60dB RF shielding requirement.

• Acoustic Protection: All walls, both exterior and interior, must provide a minimum Sound Transmission Class (STC) rating of 50.

• Secure Vestibule: A man-trap shall be constructed at the primary entrance to control access into the facility. This shall include two doors, interlocked to prevent both from being open simultaneously.

• IDS/ACS: Contractor required to provide an intrusion detection and access control system which complies with the latest specifications, regulations, and JBLM design standards.

3.3 Electrical Service

• Conduit and Wiring:

• The SCIF in a box must include a Main Distribution Panel (MDP) and all necessary sub-panels to support lighting, outlets, HVAC, and communications equipment.

• All electrical penetrations must be properly treated to maintain the SCIF's security envelope.

• Trench and install conduit from the Main Distribution Panel in Building 4290 to the SIAB's electrical panel stub-out location.

• All conductors used shall be copper and must be continuous runs without splices.

All exterior fittings shall be weatherproof.

• Connections and Testing:

• Provide electrical grounding to the SIAB mounted bonding plate per the project specifications.

• Connect the electrical service to the SIAB and coordinate with the government Project Manager (PM) for a full systems check.

• Perform an arc flash study for the affected electrical equipment and provide warning labels. Provide the study results as a submittal.

3.3 Communications Infrastructure

• Duct Bank Installation:

• Install a duct bank system from the communications tie-in point to the SIAB’s communications panel stub-out.

• The duct system shall be concrete-encased schedule-40 conduit. The contractor is responsible for field-verifying all measurements.

• Cable and Service Installation:

• Engineer-Furnish-Install-and-Test (EFI&T) a complete and usable telecommunications fiber optic and copper cable system.

• Install new single-mode (SM) fiber optic and multi-pair copper cabling from the source at Building 4290 to the SIAB, using the new duct bank infrastructure.

• Fusion splice new fiber cables as required and install new splice cases.

• Install new fiber patch panels (Lightguide Interconnection Units or LIUs) and a telecommunications equipment cabinet inside the SIAB.

• All newly installed cables shall be tested "on the reel" before installation and after final termination. The contractor shall perform Optical Time Domain Reflectometry (OTDR) and Attenuation tests on all fiber strands.

• Label all new cables and patch panels in accordance with ANSI/TIA-606 and Joint Base Lewis-McChord labeling standards.

• Provide a detailed communications installation plan and test reports as submittals.

3.4. Fire Protection: A fire alarm control panel (FACP) and associated annunciation/detection devices shall be installed in accordance with all applicable life safety codes.

3.5. HVAC System:

• The facility shall be equipped with a multi-zone climate control system (e.g., ductless mini-split system) capable of independent temperature control for the conference room and office areas.

• All HVAC penetrations through the SCIF boundary must be protected in accordance with SCIF construction standards to maintain acoustic and RF integrity.

• Condenser units shall be located externally.

3.5. Secure Perimeter and Exterior Boundary

• 3.4.1. Perimeter Wall: The Contractor shall design and construct a secure exterior perimeter wall enclosing the SCIF-in-a-box facility, establishing a defined security boundary. Dimensions shall provide for at least 10 feet on 3 sides with one side with at least 25 feet of space for possible parking of vehicles. Wall shall be tall enough to screen visibility of the SCIF in a box from view.

• 3.4.2. Aesthetic Requirements: The perimeter wall shall be constructed of brick. The Contractor must ensure the brick type, color, and coursing match the architectural aesthetic of the surrounding adjacent buildings.

• 3.4.3. Access Control Points: The perimeter shall incorporate physical access points to include a minimum of two (2) secure personnel doors and one (1) vehicle gate. All access points must be equipped with appropriate heavy-duty hardware and locking mechanisms compliant with base physical security standards.

• 3.4.4. Security Topping: To provide an anti-climb physical deterrent, the top of the entire perimeter brick wall and gates must be outfitted with concertina wire.

4.0 CONSTRUCTION REQUIREMENTS

• Work Hours: Normal work hours are 0700 to 1600, Monday through Friday, excluding Federal holidays. Exceptions may be authorized with prior approval from the government PM.

• Permits: The Contractor shall obtain all required permits before starting work, including but not limited to digging permits.

• Codes and Specifications: The Contractor shall comply with the most recent editions of all pertinent Local, State, and Federal codes, including the National Electrical Code (NFPA 70), Unified Facilities Criteria (UFC), and applicable installation design standards.

• Environmental: The Contractor shall comply with all environmental regulations, including the submission of an Environmental Protection Plan (EPP) and a Stormwater Pollution Prevention Plan (SWPPP) if applicable.

• Waste Management: The contractor shall create and follow a waste management plan to meet or exceed installation-specific construction and demolition waste diversion goals.

• Utility Outages: Any required utility outages must be coordinated with the government PM a minimum of 14 calendar days in advance.

Project Location – MDC PAC SCIF

FRONT ISOMETRIC

GROUNDING LUG

(SEE SHEET 8)

4' X 5' AWNING

HIGH SECURITY SINGLE DOOR

WITH NAPEC HASP

ANCHOR BRACKET

45'

10'

15'

1:64

DESCRIPTION

SHEET

DRAWN BY

DATE DRAWN

APPROVED BY

SCALE

SHEET SIZE

DRAWING NO.

APPROX. SHIPPING WT. IN LBS.

C O R P O R A T I O N LINING

SERIAL #

UNIT LENGTH

CUSTOMER

UNIT SPEC

UNIT TYPE

LOCATION

REVISION

300 ARMAG AVE. • BARDSTOWN, KY 40004 • PHONE: (800) 443-9994 •

FAX: (502) 348-4801 • EMAIL: info@armagcorp.com

Manufacturers of Arms Vaults and Explosive Storage magazines since 1969

B

1 OF

LEGEND:

KILL SWITCH

DURESS

ELECTRIC RECEPTACLE

DOUBLE STACKED

SINGLE STACKED

EMERGENCY LIGHT

TELEPHONE JACK

LAN CONNECTION

SEISMIC SENSOR

SMOKE DETECTION

PIR

BULLET TRAP

DS

EMR

P L

SS

SE

SM

PIR

BT

LEGEND CONTINUED:

THERMOSTAT

GROUND

THIS DRAWING IS THE PROPERTY OF ARMAG

CORPORATION WHO CLAIMS PROPRIETARY RIGHTS

IN THE MATERIAL DISCLOSED. IT IS ISSUED IN

CONFIDENCE FOR ENGINEERING INFORMATION

ONLY AND MAY NOT BE COPIED OR USED FOR

MANUFACTURE OF ANYTHING SHOWN WITHOUT

SPECIFIC PERMISSION FROM ARMAG CORPORATION

UNLESS OTHERWISE NOTED, TOLERANCES ARE:

FRACTIONS: ±1/16 ANGLES: ±1°

MACHINED SURFACES: 125 MICRO-INCHES

THESE TOLERANCES DO NOT APPLY TO BASIC DIMS.

DRAWN TO SCALE UNLESS OTHERWISE NOTED

TK

D

UNIT WIDTH UNIT HEIGHT

QUOTE #

EXT. FINISH

S3944

01CTD

02/07/2024

12070-01 41541

45' 15' 10'

ARC VAULT

ICD 705

80,000

ADS

JOINT BASE LEWIS-MCCHORD, WA

ARC VAULT WITH RF SHIELDING, DIVIDER WALLS, ALUMINUM AWNING,

ACOUSTIC/RF COMBO DOOR, AND NETWORK CABINETS,

STC 50 "HAZE GRAY" - DEVTHANE 349QC

1384940044.CIV

Text Box Example SCIF in a Box Design:

*Contractor must confirm all requirements of scope for final SCIF design.

*Contractor not required to use this manufacturer. This is for information only.

RIGHT SIDE ELEVATION

12'21'12'

50'-8 1/2"

45'

48'-0 1/4"

1:49.7485

DESCRIPTION

SHEET

DRAWN BY

DATE DRAWN

APPROVED BY

SCALE

SHEET SIZE

DRAWING NO.

APPROX. SHIPPING WT. IN LBS.

C O R P O R A T I O N LINING

SERIAL #

UNIT LENGTH

CUSTOMER

UNIT SPEC

UNIT TYPE

LOCATION

REVISION

300 ARMAG AVE. • BARDSTOWN, KY 40004 • PHONE: (800) 443-9994 •

FAX: (502) 348-4801 • EMAIL: info@armagcorp.com

Manufacturers of Arms Vaults and Explosive Storage magazines since 1969

B

2 OF

LEGEND:

KILL SWITCH

DURESS

ELECTRIC RECEPTACLE

DOUBLE STACKED

SINGLE STACKED

EMERGENCY LIGHT

TELEPHONE JACK

LAN CONNECTION

SEISMIC SENSOR

SMOKE DETECTION

PIR

BULLET TRAP

DS

EMR

P L

SS

SE

SM

PIR

BT

LEGEND CONTINUED:

THERMOSTAT

GROUND

THIS DRAWING IS THE PROPERTY OF ARMAG

CORPORATION WHO CLAIMS PROPRIETARY RIGHTS

IN THE MATERIAL DISCLOSED. IT IS ISSUED IN

CONFIDENCE FOR ENGINEERING INFORMATION

ONLY AND MAY NOT BE COPIED OR USED FOR

MANUFACTURE OF ANYTHING SHOWN WITHOUT

SPECIFIC PERMISSION FROM ARMAG CORPORATION

UNLESS OTHERWISE NOTED, TOLERANCES ARE:

FRACTIONS: ±1/16 ANGLES: ±1°

MACHINED SURFACES: 125 MICRO-INCHES

THESE TOLERANCES DO NOT APPLY TO BASIC DIMS.

DRAWN TO SCALE UNLESS OTHERWISE NOTED

TK

D

UNIT WIDTH UNIT HEIGHT

QUOTE #

EXT. FINISH

S3944

01CTD

02/07/2024

12070-01 41541

45' 15' 10'

ARC VAULT

ICD 705

80,000

ADS

JOINT BASE LEWIS-MCCHORD, WA

ARC VAULT WITH RF SHIELDING, DIVIDER WALLS, ALUMINUM AWNING,

ACOUSTIC/RF COMBO DOOR, AND NETWORK CABINETS,

STC 50 "HAZE GRAY" - DEVTHANE 349QC

REAR ELEVATIONFRONT ELEVATION

4'

10'-11 3/8"

200AMP 120/208V 3PH 60HZ

MAIN BREAKER

EXTERIOR ELECTRICAL PANEL

SIGNAL J-BOX

(THERMOSTAT AND TAMPERS)

24" X 24" NETWORK ENTRANCE

W/ TWO WGF12 FIBER WAVEGUIDES

2'-10"

8'-2"

4'

SECURITY

LED LIGHT

VESTIBULE

AIR VENT

6"

9'-11 7/8"

15'-1 1/2"

GROUNDING LUG

(SEE SHEET 8)

D-RING

ANCHOR BRACKET

WALL MOUNTED

HVAC

4' X 5' ALUMINUM AWNING

2'-2"

SIGNAL J-BOX

(THERMOSTAT AND TAMPERS)

1:48

DESCRIPTION

SHEET

DRAWN BY

DATE DRAWN

APPROVED BY

SCALE

SHEET SIZE

DRAWING NO.

APPROX. SHIPPING WT. IN LBS.

C O R P O R A T I O N LINING

SERIAL #

UNIT LENGTH

CUSTOMER

UNIT SPEC

UNIT TYPE

LOCATION

REVISION

300 ARMAG AVE. • BARDSTOWN, KY 40004 • PHONE: (800) 443-9994 •

FAX: (502) 348-4801 • EMAIL: info@armagcorp.com

Manufacturers of Arms Vaults and Explosive Storage magazines since 1969

B

3 OF

LEGEND:

KILL SWITCH

DURESS

ELECTRIC RECEPTACLE

DOUBLE STACKED

SINGLE STACKED

EMERGENCY LIGHT

TELEPHONE JACK

LAN CONNECTION

SEISMIC SENSOR

SMOKE DETECTION

PIR

BULLET TRAP

DS

EMR

P L

SS

SE

SM

PIR

BT

LEGEND CONTINUED:

THERMOSTAT

GROUND

THIS DRAWING IS THE PROPERTY OF ARMAG

CORPORATION WHO CLAIMS PROPRIETARY RIGHTS

IN THE MATERIAL DISCLOSED. IT IS ISSUED IN

CONFIDENCE FOR ENGINEERING INFORMATION

ONLY AND MAY NOT BE COPIED OR USED FOR

MANUFACTURE OF ANYTHING SHOWN WITHOUT

SPECIFIC PERMISSION FROM ARMAG CORPORATION

UNLESS OTHERWISE NOTED, TOLERANCES ARE:

FRACTIONS: ±1/16 ANGLES: ±1°

MACHINED SURFACES: 125 MICRO-INCHES

THESE TOLERANCES DO NOT APPLY TO BASIC DIMS.

DRAWN TO SCALE UNLESS OTHERWISE NOTED

TK

D

UNIT WIDTH UNIT HEIGHT

QUOTE #

EXT. FINISH

S3944

01CTD

02/07/2024

12070-01 41541

45' 15' 10'

ARC VAULT

ICD 705

80,000

ADS

JOINT BASE LEWIS-MCCHORD, WA

ARC VAULT WITH RF SHIELDING, DIVIDER WALLS, ALUMINUM AWNING,

ACOUSTIC/RF COMBO DOOR, AND NETWORK CABINETS,

'-9

/2

W

ID

TH

O F

BA

SE

F R

AM

E

44'-10" WIDTH OF BASE FRAME2 1/2"

45'-3" TO BOLT CENTERS

'-5

/2

TO

B O

LT

C

EN

TE

R S

1'-2"

11"

1'-2"

11"

45'-0 1/2"

15'

BASE FRAMING PLAN

1:48

DESCRIPTION

SHEET

DRAWN BY

DATE DRAWN

APPROVED BY

SCALE

SHEET SIZE

DRAWING NO.

APPROX. SHIPPING WT. IN LBS.

C O R P O R A T I O N LINING

SERIAL #

UNIT LENGTH

CUSTOMER

UNIT SPEC

UNIT TYPE

LOCATION

REVISION

300 ARMAG AVE. • BARDSTOWN, KY 40004 • PHONE: (800) 443-9994 •

FAX: (502) 348-4801 • EMAIL: info@armagcorp.com

Manufacturers of Arms Vaults and Explosive Storage magazines since 1969

B

4 OF

LEGEND:

KILL SWITCH

DURESS

ELECTRIC RECEPTACLE

DOUBLE STACKED

SINGLE STACKED

EMERGENCY LIGHT

TELEPHONE JACK

LAN CONNECTION

SEISMIC SENSOR

SMOKE DETECTION

PIR

BULLET TRAP

DS

EMR

P L

SS

SE

SM

PIR

BT

LEGEND CONTINUED:

THERMOSTAT

GROUND

THIS DRAWING IS THE PROPERTY OF ARMAG

CORPORATION WHO CLAIMS PROPRIETARY RIGHTS

IN THE MATERIAL DISCLOSED. IT IS ISSUED IN

CONFIDENCE FOR ENGINEERING INFORMATION

ONLY AND MAY NOT BE COPIED OR USED FOR

MANUFACTURE OF ANYTHING SHOWN WITHOUT

SPECIFIC PERMISSION FROM ARMAG CORPORATION

UNLESS OTHERWISE NOTED, TOLERANCES ARE:

FRACTIONS: ±1/16 ANGLES: ±1°

MACHINED SURFACES: 125 MICRO-INCHES

THESE TOLERANCES DO NOT APPLY TO BASIC DIMS.

DRAWN TO SCALE UNLESS OTHERWISE NOTED

TK

D

UNIT WIDTH UNIT HEIGHT

QUOTE #

EXT. FINISH

S3944

01CTD

02/07/2024

12070-01 41541

45' 15' 10'

ARC VAULT

ICD 705

80,000

ADS

JOINT BASE LEWIS-MCCHORD, WA

ARC VAULT WITH RF SHIELDING, DIVIDER WALLS, ALUMINUM AWNING,

ACOUSTIC/RF COMBO DOOR, AND NETWORK CABINETS,

5'-7 1/4"

8'

15'

13'-10 3/4"

CONFERENCE / CER

WORK AREA

6'

SHREDDER(BY

OTHERS)

PRIN

TER(BY

OTHERS)

2 DRAWER

GSA SAFE

(BY OTHERS)

2'-6"

TYP. 4' TYP.

FURNITURE

(BY OTHERS)

27'-8" 16'

45'

FLOOR PLAN

1 3

VESTIBULE

8'

3'-6"

1:48

DESCRIPTION

SHEET

DRAWN BY

DATE DRAWN

APPROVED BY

SCALE

SHEET SIZE

DRAWING NO.

APPROX. SHIPPING WT. IN LBS.

C O R P O R A T I O N LINING

SERIAL #

UNIT LENGTH

CUSTOMER

UNIT SPEC

UNIT TYPE

LOCATION

REVISION

300 ARMAG AVE. • BARDSTOWN, KY 40004 • PHONE: (800) 443-9994 •

FAX: (502) 348-4801 • EMAIL: info@armagcorp.com

Manufacturers of Arms Vaults and Explosive Storage magazines since 1969

B

5 OF

LEGEND:

KILL SWITCH

DURESS

ELECTRIC RECEPTACLE

DOUBLE STACKED

SINGLE STACKED

EMERGENCY LIGHT

TELEPHONE JACK

LAN CONNECTION

SEISMIC SENSOR

SMOKE DETECTION

PIR

BULLET TRAP

DS

EMR

P L

SS

SE

SM

PIR

BT

LEGEND CONTINUED:

THERMOSTAT

GROUND

THIS DRAWING IS THE PROPERTY OF ARMAG

CORPORATION WHO CLAIMS PROPRIETARY RIGHTS

IN THE MATERIAL DISCLOSED. IT IS ISSUED IN

CONFIDENCE FOR ENGINEERING INFORMATION

ONLY AND MAY NOT BE COPIED OR USED FOR

MANUFACTURE OF ANYTHING SHOWN WITHOUT

SPECIFIC PERMISSION FROM ARMAG CORPORATION

UNLESS OTHERWISE NOTED, TOLERANCES ARE:

FRACTIONS: ±1/16 ANGLES: ±1°

MACHINED SURFACES: 125 MICRO-INCHES

THESE TOLERANCES DO NOT APPLY TO BASIC DIMS.

DRAWN TO SCALE UNLESS OTHERWISE NOTED

TK

D

UNIT WIDTH UNIT HEIGHT

QUOTE #

EXT. FINISH

S3944

01CTD

02/07/2024

12070-01 41541

45' 15' 10'

ARC VAULT

ICD 705

80,000

ADS

JOINT BASE LEWIS-MCCHORD, WA

ARC VAULT WITH RF SHIELDING, DIVIDER WALLS, ALUMINUM AWNING,

ACOUSTIC/RF COMBO DOOR, AND NETWORK CABINETS,

STC 50 "HAZE GRAY" - DEVTHANE 349QC

DOOR SCHEDULE

DOOR QTY SIZE / SWING DESCRIPTION HARDWARE

1 1 3070 / LHR ARMAG HIGH SECURITY DOOR, A-36 STEEL W/ 2" HARDWOOD MIL-DTL-29181 HIGH SECURITY HASP / PANIC BAR EXIT DEVICE 2 1 3070 / RH 18 GA COMMERCIAL METAL DOOR W/ 16 GA FRAME COMMERCIAL LEVER LOCKSET / CLOSER / WEATHER STRIPPING

3 1 3070 / LHR RF SHIELDED ACOUSTIC COMBO DOOR W/ FRAME, MEETING ICS 705 SOUND

GROUP 4 LKM10K - X10 W/ KEY OVERRIDE / CLOSER

4 1 3070 / RHR 18 GA COMMERCIAL METAL DOOR W/ 16 GA FRAME COMMERCIAL LEVER LOCKSET / CLOSER

FINISH SCHEDULE

SURFACE MATERIAL COLOR

EXTERIOR PAINT DEVOE DEVATHANE 349QC HAZE GRAY

INTERIOR PRIMER DEVOE DEVATHANE 349QC GRAY

INTERIOR WALLS WHITE TEXTURED FRP .090" WHITE

CEILING WHITE TEXTURED FRP .090" WHITE

DOORS + FRAMES DEVOE DEVTHANE 349QC GREY

BASE MOULDING FLEXCO 2000 TPR WALL BASE, 4" COVE BLACK

FLOOR SQUARE CARPET TILES GREY

ICS 705 SOUND GROUP 4

STC 50 SECURITY PERIMETER

DYNASOUND DS2400

SOUND MASKER ON

RETURN DUCT

PIRCCTV CAMERA

DYNASOUND DS2400

SOUND MASKER ON

RETURN DUCT

SM

PIR

SECURITY PLAN

IDS PREP

(EQUIPMENT

BY OTHERS)

ACS PREP

(EQUIPMENT

BY OTHERS)

BOX ONLY

(BMS BY OTHERS)

BM

S

BOX ONLY

(BMS BY OTHERS)

BOX ONLY

(PIR BY OTHERS)

CCTV MONITOR

BOX ONLY

(PIR BY OTHERS)

WALL BOX FOR

IDS KEYPAD

(BY OTHERS)

WALL BOX FOR

ACS KEYPAD /

CARD READER

(BY OTHERS)

BM

S

1:48

DESCRIPTION

SHEET

DRAWN BY

DATE DRAWN

APPROVED BY

SCALE

SHEET SIZE

DRAWING NO.

APPROX. SHIPPING WT. IN LBS.

C O R P O R A T I O N LINING

SERIAL #

UNIT LENGTH

CUSTOMER

UNIT SPEC

UNIT TYPE

LOCATION

REVISION

300 ARMAG AVE. • BARDSTOWN, KY 40004 • PHONE: (800) 443-9994 •

FAX: (502) 348-4801 • EMAIL: info@armagcorp.com

Manufacturers of Arms Vaults and Explosive Storage magazines since 1969

B

6 OF

LEGEND:

KILL SWITCH

DURESS

ELECTRIC RECEPTACLE

DOUBLE STACKED

SINGLE STACKED

EMERGENCY LIGHT

TELEPHONE JACK

LAN CONNECTION

SEISMIC SENSOR

SMOKE DETECTION

PIR

BULLET TRAP

DS

EMR

P L

SS

SE

SM

PIR

BT

LEGEND CONTINUED:

THERMOSTAT

GROUND

THIS DRAWING IS THE PROPERTY OF ARMAG

CORPORATION WHO CLAIMS PROPRIETARY RIGHTS

IN THE MATERIAL DISCLOSED. IT IS ISSUED IN

CONFIDENCE FOR ENGINEERING INFORMATION

ONLY AND MAY NOT BE COPIED OR USED FOR

MANUFACTURE OF ANYTHING SHOWN WITHOUT

SPECIFIC PERMISSION FROM ARMAG CORPORATION

UNLESS OTHERWISE NOTED, TOLERANCES ARE:

FRACTIONS: ±1/16 ANGLES: ±1°

MACHINED SURFACES: 125 MICRO-INCHES

THESE TOLERANCES DO NOT APPLY TO BASIC DIMS.

DRAWN TO SCALE UNLESS OTHERWISE NOTED

TK

D

UNIT WIDTH UNIT HEIGHT

QUOTE #

EXT. FINISH

S3944

01CTD

02/07/2024

12070-01 41541

45' 15' 10'

ARC VAULT

ICD 705

80,000

ADS

JOINT BASE LEWIS-MCCHORD, WA

ARC VAULT WITH RF SHIELDING, DIVIDER WALLS, ALUMINUM AWNING,

ACOUSTIC/RF COMBO DOOR, AND NETWORK CABINETS,

2 TON WALL-MOUNT

HVAC W/ ACOUSTIC

Z-DUCT FOR SUPPLY

AND RETURN

W24HYDB05MXXXXE

3 TON WALL-MOUNT

HVAC W/ ACOUSTIC

Z-DUCT FOR SUPPLY

AND RETURN

W36HYDB05MXXXXE

A

B

EM

R

A

A

A A

C

A

C

C

EM

R

A

A

A

T T

LIGHTING / HVAC PLAN

EM

R

A

1:48

DESCRIPTION

SHEET

DRAWN BY

DATE DRAWN

APPROVED BY

SCALE

SHEET SIZE

DRAWING NO.

APPROX. SHIPPING WT. IN LBS.

C O R P O R A T I O N LINING

SERIAL #

UNIT LENGTH

CUSTOMER

UNIT SPEC

UNIT TYPE

LOCATION

REVISION

300 ARMAG AVE. • BARDSTOWN, KY 40004 • PHONE: (800) 443-9994 •

FAX: (502) 348-4801 • EMAIL: info@armagcorp.com

Manufacturers of Arms Vaults and Explosive Storage magazines since 1969

B

7 OF

LEGEND:

KILL SWITCH

DURESS

ELECTRIC RECEPTACLE

DOUBLE STACKED

SINGLE STACKED

EMERGENCY LIGHT

TELEPHONE JACK

LAN CONNECTION

SEISMIC SENSOR

SMOKE DETECTION

PIR

BULLET TRAP

DS

EMR

P L

SS

SE

SM

PIR

BT

LEGEND CONTINUED:

THERMOSTAT

GROUND

THIS DRAWING IS THE PROPERTY OF ARMAG

CORPORATION WHO CLAIMS PROPRIETARY RIGHTS

IN THE MATERIAL DISCLOSED. IT IS ISSUED IN

CONFIDENCE FOR ENGINEERING INFORMATION

ONLY AND MAY NOT BE COPIED OR USED FOR

MANUFACTURE OF ANYTHING SHOWN WITHOUT

SPECIFIC PERMISSION FROM ARMAG CORPORATION

UNLESS OTHERWISE NOTED, TOLERANCES ARE:

FRACTIONS: ±1/16 ANGLES: ±1°

MACHINED SURFACES: 125 MICRO-INCHES

THESE TOLERANCES DO NOT APPLY TO BASIC DIMS.

DRAWN TO SCALE UNLESS OTHERWISE NOTED

TK

D

UNIT WIDTH UNIT HEIGHT

QUOTE #

EXT. FINISH

S3944

01CTD

02/07/2024

12070-01 41541

45' 15' 10'

ARC VAULT

ICD 705

80,000

ADS

JOINT BASE LEWIS-MCCHORD, WA

ARC VAULT WITH RF SHIELDING, DIVIDER WALLS, ALUMINUM AWNING,

ACOUSTIC/RF COMBO DOOR, AND NETWORK CABINETS,

STC 50 "HAZE GRAY" - DEVTHANE 349QC

LIGHTING SCHEDULE

ITEM # QTY DESCRIPTION MFG / PART NUMBER

A 10 4' - LED LIGHT FIXTURE RAB LIGHTING / SEAL 4-50/D10

B 1 EXTERIOR 18W LED WALL PACK LIGHT RAB LIGHTING / SLIM18

C 3 LED EXIT / EMERGENCY LIGHT HUBBLE LIGHTING / EVCURW

NETWORK ENTRANCE

WITH TWO WGF12

FIBER WAVEGUIDES

200A 120/208V 3PH 60HZ

MAIN BREAKER PANEL

(2) 24" CABINETS FOR

SECURE NETWORKS

W/ QUAD RECEPTACLES

(1) 48" CABINET FOR

NON-SECURE NETWORKS

W/ QUAD RECEPTACLE

5'-7 1/4"

8'

15'

6'

3'-6"4' TYP. C-C

7' 4'

27'-8" 16'

45'

ELECTRICAL / NETWORKING PLAN

CONFERENCE / CERWORK AREA

6'

WALL PENETRATION

FOR RACEWAY, QTY 2

DUPLEX NEMA 5-20

RECEPTACLE FOR CCTV

WALL MOUNTED

QUAD NEMA 5-20

RECEPTACLE, QTY 10

36" AFF

WALL MOUNTED BOX FOR

NETWORK DROP, QTY 10

36" AFF

5'-10"

4'

DUPLEX NEMA 5-20

RECEPTACLE FOR SHREDDER

DEDICATED BREAKER

18" AFF

VESTIBULE

4X100A

POWER FILTER

100A 120/208V 3PH 60HZ

PANELBOARD

1:48

DESCRIPTION

SHEET

DRAWN BY

DATE DRAWN

APPROVED BY

SCALE

SHEET SIZE

DRAWING NO.

APPROX. SHIPPING WT. IN LBS.

C O R P O R A T I O N LINING

SERIAL #

UNIT LENGTH

CUSTOMER

UNIT SPEC

UNIT TYPE

LOCATION

REVISION

300 ARMAG AVE. • BARDSTOWN, KY 40004 • PHONE: (800) 443-9994 •

FAX: (502) 348-4801 • EMAIL: info@armagcorp.com

Manufacturers of Arms Vaults and Explosive Storage magazines since 1969

B

8 OF

LEGEND:

KILL SWITCH

DURESS

ELECTRIC RECEPTACLE

DOUBLE STACKED

SINGLE STACKED

EMERGENCY LIGHT

TELEPHONE JACK

LAN CONNECTION

SEISMIC SENSOR

SMOKE DETECTION

PIR

BULLET TRAP

DS

EMR

P L

SS

SE

SM

PIR

BT

LEGEND CONTINUED:

THERMOSTAT

GROUND

THIS DRAWING IS THE PROPERTY OF ARMAG

CORPORATION WHO CLAIMS PROPRIETARY RIGHTS

IN THE MATERIAL DISCLOSED. IT IS ISSUED IN

CONFIDENCE FOR ENGINEERING INFORMATION

ONLY AND MAY NOT BE COPIED OR USED FOR

MANUFACTURE OF ANYTHING SHOWN WITHOUT

SPECIFIC PERMISSION FROM ARMAG CORPORATION

UNLESS OTHERWISE NOTED, TOLERANCES ARE:

FRACTIONS: ±1/16 ANGLES: ±1°

MACHINED SURFACES: 125 MICRO-INCHES

THESE TOLERANCES DO NOT APPLY TO BASIC DIMS.

DRAWN TO SCALE UNLESS OTHERWISE NOTED

TK

D

UNIT WIDTH UNIT HEIGHT

QUOTE #

EXT. FINISH

S3944

01CTD

02/07/2024

12070-01 41541

45' 15' 10'

ARC VAULT

ICD 705

80,000

ADS

JOINT BASE LEWIS-MCCHORD, WA

ARC VAULT WITH RF SHIELDING, DIVIDER WALLS, ALUMINUM AWNING,

ACOUSTIC/RF COMBO DOOR, AND NETWORK CABINETS,

NETWORK CABINET DETAIL NETWORK DROP DETAIL

(11) 62.5 UM LC FIBER

CONNECTORS IN COLOR

CODED PATCH PANEL, QTY 2

QUAD NEMA 5-20

RECEPTACLE FOR

CABINETS (X3)

24" TALL WALL-MOUNTED

NETWORKING CABINET FOR (RED)

SECURE NETWORK

(11) 62.5 UM LC FIBER

CONNECTORS IN COLOR

CODED PATCH PANEL

24" TALL WALL-MOUNTED

NETWORKING CABINET FOR

(YELLOW) SECURE NETWORK

(11) 62.5 UM LC FIBER

CONNECTORS IN COLOR

CODED PATCH PANEL

WALL PENETRATION TO

EXTERIOR JUNCTION BOX

48" TALL WALL-MOUNTED

NETWORKING CABINET FOR

(GREEN AND WHITE)

NON-SECURE NETWORKS

4" RACEWAY

TYP WALL MOUNTED NETWORK DROP

FACEPLATE - (4) LC CONNECTORS

COLOR CODED TO NETWORK

1:20

DESCRIPTION

SHEET

DRAWN BY

DATE DRAWN

APPROVED BY

SCALE

SHEET SIZE

DRAWING NO.

APPROX. SHIPPING WT. IN LBS.

C O R P O R A T I O N LINING

SERIAL #

UNIT LENGTH

CUSTOMER

UNIT SPEC

UNIT TYPE

LOCATION

REVISION

300 ARMAG AVE. • BARDSTOWN, KY 40004 • PHONE: (800) 443-9994 •

FAX: (502) 348-4801 • EMAIL: info@armagcorp.com

Manufacturers of Arms Vaults and Explosive Storage magazines since 1969

B

9 OF

LEGEND:

KILL SWITCH

DURESS

ELECTRIC RECEPTACLE

DOUBLE STACKED

SINGLE STACKED

EMERGENCY LIGHT

TELEPHONE JACK

LAN CONNECTION

SEISMIC SENSOR

SMOKE DETECTION

PIR

BULLET TRAP

DS

EMR

P L

SS

SE

SM

PIR

BT

LEGEND CONTINUED:

THERMOSTAT

GROUND

THIS DRAWING IS THE PROPERTY OF ARMAG

CORPORATION WHO CLAIMS PROPRIETARY RIGHTS

IN THE MATERIAL DISCLOSED. IT IS ISSUED IN

CONFIDENCE FOR ENGINEERING INFORMATION

ONLY AND MAY NOT BE COPIED OR USED FOR

MANUFACTURE OF ANYTHING SHOWN WITHOUT

SPECIFIC PERMISSION FROM ARMAG CORPORATION

UNLESS OTHERWISE NOTED, TOLERANCES ARE:

FRACTIONS: ±1/16 ANGLES: ±1°

MACHINED SURFACES: 125 MICRO-INCHES

THESE TOLERANCES DO NOT APPLY TO BASIC DIMS.

DRAWN TO SCALE UNLESS OTHERWISE NOTED

TK

D

UNIT WIDTH UNIT HEIGHT

QUOTE #

EXT. FINISH

S3944

01CTD

02/07/2024

12070-01 41541

45' 15' 10'

ARC VAULT

ICD 705

80,000

ADS

JOINT BASE LEWIS-MCCHORD, WA

ARC VAULT WITH RF SHIELDING, DIVIDER WALLS, ALUMINUM AWNING,

ACOUSTIC/RF COMBO DOOR, AND NETWORK CABINETS,

1:25.7466

DESCRIPTION

SHEET

DRAWN BY

DATE DRAWN

APPROVED BY

SCALE

SHEET SIZE

DRAWING NO.

APPROX. SHIPPING WT. IN LBS.

C O R P O R A T I O N LINING

SERIAL #

UNIT LENGTH

CUSTOMER

UNIT SPEC

UNIT TYPE

LOCATION

REVISION

300 ARMAG AVE. • BARDSTOWN, KY 40004 • PHONE: (800) 443-9994 •

FAX: (502) 348-4801 • EMAIL: info@armagcorp.com

Manufacturers of Arms Vaults and Explosive Storage magazines since 1969

B

10 OF

LEGEND:

KILL SWITCH

DURESS

ELECTRIC RECEPTACLE

DOUBLE STACKED

SINGLE STACKED

EMERGENCY LIGHT

TELEPHONE JACK

LAN CONNECTION

SEISMIC SENSOR

SMOKE DETECTION

PIR

BULLET TRAP

DS

EMR

P L

SS

SE

SM

PIR

BT

LEGEND CONTINUED:

THERMOSTAT

GROUND

THIS DRAWING IS THE PROPERTY OF ARMAG

CORPORATION WHO CLAIMS PROPRIETARY RIGHTS

IN THE MATERIAL DISCLOSED. IT IS ISSUED IN

CONFIDENCE FOR ENGINEERING INFORMATION

ONLY AND MAY NOT BE COPIED OR USED FOR

MANUFACTURE OF ANYTHING SHOWN WITHOUT

SPECIFIC PERMISSION FROM ARMAG CORPORATION

UNLESS OTHERWISE NOTED, TOLERANCES ARE:

FRACTIONS: ±1/16 ANGLES: ±1°

MACHINED SURFACES: 125 MICRO-INCHES

THESE TOLERANCES DO NOT APPLY TO BASIC DIMS.

DRAWN TO SCALE UNLESS OTHERWISE NOTED

TK

D

UNIT WIDTH UNIT HEIGHT

QUOTE #

EXT. FINISH

S3944

01CTD

02/07/2024

12070-01 41541

45' 15' 10'

ARC VAULT

ICD 705

80,000

ADS

JOINT BASE LEWIS-MCCHORD, WA

ARC VAULT WITH RF SHIELDING, DIVIDER WALLS, ALUMINUM AWNING,

ACOUSTIC/RF COMBO DOOR, AND NETWORK CABINETS,

STC 50 "HAZE GRAY" - DEVTHANE 349QC

120/208V 3Ø 60 Hz

MAIN PANEL

NEMA 3R ENCLOSURE

POWER FILTER

4 LINE 100A

RF SHIELDED

PERIMETER

200A MAIN

BREAKER

100A BREAKER TO

INTERIOR PANEL

INTERIOR PANEL

NEMA 1 ENCLOSURE

POWER DISTRIBUTION

13 14

15 16

17 18

19 20

21 22

23 24

INTERIOR SUB PANEL SCHEDULE - 100A 120/208V 3Ø RATED PANEL - MAIN LUG ONLY SURFACE MOUNT - NEMA 1

BRK. VOLTS AMPS /

POLES DESCRIPTION

LOAD (VA)

DESCRIPTION AMPS /

POLES VOLTS BRK.

A B C

1 120 20/1 NETWORK CABINET #1 1000 / 800 RECEPTACLES #1-2 20/1 120 2

3 120 20/1 NETWORK CABINET #2 1000 / 800 RECEPTACLES #3-4 20/1 120 4

5 120 20/1 NETWORK CABINET #3 1000 / 800 RECEPTACLES #5-6 20/1 120 6

7 120 20/1 CCTV RECEPTACLE 180 /800 RECEPTACLES #7-8 20/1 120 8

9 120 20/1 SHREDDER 400 / 800 RECEPTACLES #9-10 20/1 120 10

11 120 20/1 PRINTER 400 / 200 CER LIGHTING 20/1 120 12

13 120 20/1 SPARE - / 360 IDS / ACS 20/1 120 14

15 120 20/1 SPARE - / 250 WORK AREA LIGHTING 20/1 120 16

17 120 20/1 SPARE - / - SPARE 20/1 120 18

19 120 20/1 SPARE - / - SPARE 20/1 120 20

21 120 20/1 SPARE - / - SPARE 20/1 120 22

23 120 20/1 SPARE - / - SPARE 20/1 120 24

CONNECTED LOAD PER PHASE 3140 3250 2400

TOTAL CONNECTED LOAD (KVA) 8.79

EXTERIOR MAIN PANEL SCHEDULE - 120/208V 3Ø RATED PANEL W/ 200A MAIN BREAKER SURFACE MOUNT - NEMA 3R

BRK. VOLTS AMPS /

POLES DESCRIPTION

LOAD (VA)

DESCRIPTION AMPS /

POLES VOLTS BRK.

A B C

208 30/3 HVAC

3600 / 4200

HVAC 35/3 208

3 3600 / 4200 4

5 3600 / 4200 6

7 120 20/1 EXTERIOR LIGHTING 18 / 230 VESTIBULE 20/1 120 8

9 120 20/1 SPARE - / 3250

INTERIOR POWER 100/3 208

11 120 20/1 SPARE - / 2400 12

13 120 20/1 SPARE - / 3140 14

15 120 20/1 SPARE - / - SPARE 20/1 120 16

17 120 20/1 SPARE - / - SPARE 20/1 120 18

CONNECTED LOAD PER PHASE 9388 11050 10200

TOTAL CONNECTED LOAD (KVA) 30.64

120/208V 3Ø 60 Hz

TYPICAL GROUNDING KIT

TYPICAL WALL / ROOF CONSTRUCTION

6 5/8"

7 3/8"

10 1/8"

TYPICAL FLOOR CONSTRUCTION

COPPER BONDING

PLATE IS BRAZED TO

1/4" MILD STEEL PLATE

COPPER CONDUCTOR

-28 STRANDS OF #14 AWG

COPPER WIRE IN ROPE LAY

-121,900 CIRCULAR MIL

CROSS SECTION

GROUND CLAMP

FOR Ø3/4" ROD

COPPER CLAD GROUND ROD

Ø3/4" X 10FT. BURIED IN EARTH BY

OTHERS PER NEC REQUIREMENTS

3/8" A-36 STEEL 2" X 2 5/8"

PINE BOARD HSS 6" X 6" X 1/4"

BASE FRAME

HSS 2 1/2" X 2 1/2" X 3/16"

WALL SUPPORT 48" O.C.

2 1/2" R10 BATT

MINERAL WOOL

2 1/2" R10 BATT

MINERAL WOOL

3/4" ADVANTECH

PLYWOOD 1/4" UNDERLAYMENTFLOOR

COVERING

RSIC-1 SOUND ISOLATION CLIPS

MOUNTED TO 2X4 ON 24" X 48" PATTERN

7/8" 20 GA FURRING CHANNELS

MOUNTED IN RSIC-1 CLIPS

5/8" AC PLYWOOD

HSS 6" X 2" X 1/8" + 1/8" X 6" PL

ROOF TEE 24" O.C.(2) LAYERS

1" HARDWOOD

5/8" R4 RIGID

INSULATION

5/8" R4 RIGID

INSULATION1/4" A-36 STEEL SHELL

2 1/2" R10 BATT

MINERAL WOOL

(2) LAYERS

1" HARDWOOD1/4" A-36 STEEL SHELL

5/8" AC PLYWOOD

1:16

DESCRIPTION

SHEET

DRAWN BY

DATE DRAWN

APPROVED BY

SCALE

SHEET SIZE

DRAWING NO.

APPROX. SHIPPING WT. IN LBS.

C O R P O R A T I O N LINING

SERIAL #

UNIT LENGTH

CUSTOMER

UNIT SPEC

UNIT TYPE

LOCATION

REVISION

300 ARMAG AVE. • BARDSTOWN, KY 40004 • PHONE: (800) 443-9994 •

FAX: (502) 348-4801 • EMAIL: info@armagcorp.com

Manufacturers of Arms Vaults and Explosive Storage magazines since 1969

B

11 OF

LEGEND:

KILL SWITCH

DURESS

ELECTRIC RECEPTACLE

DOUBLE STACKED

SINGLE STACKED

EMERGENCY LIGHT

TELEPHONE JACK

LAN CONNECTION

SEISMIC SENSOR

SMOKE DETECTION

PIR

BULLET TRAP

DS

EMR

P L

SS

SE

SM

PIR

BT

LEGEND CONTINUED:

THERMOSTAT

GROUND

THIS DRAWING IS THE PROPERTY OF ARMAG

CORPORATION WHO CLAIMS PROPRIETARY RIGHTS

IN THE MATERIAL DISCLOSED. IT IS ISSUED IN

CONFIDENCE FOR ENGINEERING INFORMATION

ONLY AND MAY NOT BE COPIED OR USED FOR

MANUFACTURE OF ANYTHING SHOWN WITHOUT

SPECIFIC PERMISSION FROM ARMAG CORPORATION

UNLESS OTHERWISE NOTED, TOLERANCES ARE:

FRACTIONS: ±1/16 ANGLES: ±1°

MACHINED SURFACES: 125 MICRO-INCHES

THESE TOLERANCES DO NOT APPLY TO BASIC DIMS.

DRAWN TO SCALE UNLESS OTHERWISE NOTED

TK

D

UNIT WIDTH UNIT HEIGHT

QUOTE #

EXT. FINISH

S3944

01CTD

02/07/2024

12070-01 41541

45' 15' 10'

ARC VAULT

ICD 705

80,000

ADS

JOINT BASE LEWIS-MCCHORD, WA

ARC VAULT WITH RF SHIELDING, DIVIDER WALLS, ALUMINUM AWNING,

ACOUSTIC/RF COMBO DOOR, AND NETWORK CABINETS,

Example SCIF Design Drawings.pdf
Sheets and Views
S3944-1
S3944-2
S3944-3
S3944-4
S3944-5
S3944-6
S3944-7
S3944-8
S3944-9
S3944-10
S3944-11

File details come from the government source that posted it. Updated .