About this file

This is a Statement of Work (SOW) for a construction and facility conversion project at Joint Base Lewis-McChord (JBLM) involving three primary work components.

The first major component requires construction of a security fence around the JDOC (Joint Doctrine Operations Center) footprint, including approximately 1,250 linear feet of 7-foot-high fencing with three-strand barbed wire. The fence must feature black ornamental sections visible from the parade field and Building 2025 to meet historical requirements, with remaining sections in black powder-coated chain link. All sections must comply with FE-7 specifications. The project includes installation of two 12-foot vehicle swing gates (24 feet total) and 4-foot personnel gates with 90-degree vertical three-strand outriggers, plus 10-inch diameter concrete-filled pipe bollards positioned in front of vehicle gate terminal posts.

The second major component involves converting Buildings 2084 and 2090 into Operational Support Facilities. For Building 2084, the contractor must install underground telecommunications infrastructure with fiber and copper connections, construct a new telecommunications room with specific environmental controls (static dissipative tile, sheet metal shielding, LED lighting, grounding busbar, fire safety systems), provide communication drops throughout the building on cable trays, and perform comprehensive renovations including tile and carpet replacement, fixture upgrades, lighting conversion to energy-efficient LED, door and window treatments, and force protection modifications (vault doors meeting Federal specification FF-L-2740B, security screens on HVAC openings, window coverings with bars, and intrusion detection systems compatible with ICIDS IV). Building 2090 requires similar telecommunications and renovation work with modifications for office space creation (two 10-foot by 12-foot office spaces) and no bathroom work. Both buildings require installation of a 175 kW emergency backup generator with 48-hour fuel capacity, dual automatic transfer switches with isolation bypass, seismic ratings per ASCE 7-10 Zone D, and comprehensive arc fault studies with labeling upon completion. All finishes must meet JBLM Design Standards, and electrical work must comply with NEC requirements and include overhead conduit routing along building exteriors.

View the file

Other files

File Type Posted
Project 4_Attachment 0008 Scopes_14 May 2026.pdf PDF
QA_JBLM FORGE_20260518.pdf PDF
JBLM_FORGE_RPP_Amendment 3.pdf PDF
Project 14_Attachment 0018 Scopes_11 May 2026.pdf PDF
ATTACH0003 MICC_CONSTRUCTION_OTA_TC_FORGE ver05122026.pdf PDF
Project 15_Attachment 0019 Scopes_11 May 2026.pdf PDF
Project 1_Attachment 0005 D Scopes_11 May 2026.pdf PDF
Project 9_Attachment 0013 Scopes_11 May 2026.pdf PDF
Project 2_Attachment 0006 Scopes_10 May 2026.pdf PDF
Project 3_Attachment 0007 Scopes_10 May 2026.pdf PDF
JBLM_FORGE_RPP_Amendment 2.pdf PDF
Project 6_Attachment 0010 Scopes_11 May 2026.pdf PDF
JBLM_FORGE_RPP_Amendment_1.pdf PDF
QA_JBLM FORGE_20260428.pdf PDF
Project 1_Attachment 0005 A Scopes_07 Apr 2026.pdf PDF
FORGE Site Visits.pdf PDF
Special Notice JBLM Site Visit.pdf PDF
JBLM FORGE Site Visit Registration 20260422.xlsx XLSX spreadsheet
Project 1_Attachment 0005 B Scopes_07 Apr 2026.pdf PDF
Project 1_Attachment 0005 C Scopes_07 Apr 2026.pdf PDF
Project 4_Attachment 0008 Scopes_07 Apr 2026.pdf PDF
Project 17_Attachment 0021 Scopes_07 Apr 2026.pdf PDF
Project 10_Attachment 0014 Scopes_07 Apr 2026.pdf PDF
JBLM_FORGE_RPP_04172026.pdf PDF
Project 12_ Attachment 0016 Scopes_07 Apr 2026.pdf PDF
ATTACH0004 JBLM FORGE CLIN STRUCTURE.xlsx XLSX spreadsheet
Project 13_ Attachment 0017 Scopes_07 Apr 2026.pdf PDF
Project 1_Attachment 0005 A Scopes_07 Apr 2026.pdf PDF
Project 3_ Attachment 0007 Scopes_07 Apr 2026.pdf PDF
Project 8_ Attachment 0012 Scopes_07 Apr 2026.pdf PDF
Project 5_Attachment 0009 Scopes_07 Apr 2026.pdf PDF
Project 16_ Attachment 0020 Scopes_07 Apr 2026.pdf PDF
Project 18_Attachment 0022 Scopes_07 Apr 2026.pdf PDF
Project 15_Attachment 0019 Scopes_07 Apr 2026.pdf PDF
Project 1_Attachment 0005 B Scopes_07 Apr 2026.pdf PDF
Project 19_Attachment 0023 Scopes_07 Apr 2026.pdf PDF
Project 1_Attachment 0005 C Scopes_07 Apr 2026.pdf PDF
Project 6_ Attachment 0010 Scopes_07 Apr 2026.pdf PDF
ATTACH0003 MICC_CONSTRUCTION_OTA_TC_FORGE ver04082026.pdf PDF
Project 2_ Attachment 0006 Scopes_07 Apr 2026.pdf PDF
ATTACH0002_Contract 01 Specifications_JBLMFORGE_RPP.pdf PDF
Project 7_ Attachment 0011 Scopes_07 Apr 2026.pdf PDF
Project 11_ Attachment 0015 Scopes_07 Apr 2026.pdf PDF
ATTACH0001_FY26 JBLM FORGE - Project List 20260414.xlsx XLSX spreadsheet
Project 9_ Attachment 0013 Scopes_07 Apr 2026.pdf PDF
Project 14_Attachment 0018 Scopes_07 Apr 2026.pdf PDF
MICC_JBLM_FORGE_INDUSTRYDAY_SAM.GOV NONCUI.pdf PDF
Pages 601-700 from Attachment 004 Project Scopes.pdf PDF
Pages 1-500 from Attachment 004 Project Scopes.pdf PDF
Pages 701-900 from Attachment 004 Project Scopes.pdf PDF
Show 40 more

Latest 50 of 66 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1.1. Principal Items to Be Accomplished

1.1.1. Contractor shall construct a security fence around the perimeter of the JDOC footprint.

1.1.1.1. Provide and install an FE-7 spec fence around the JDOC complex. All fencing visible from the parade field (to the west of the complex) and from Building 2025 (to the north of the complex) must be black ornamental to adhere to the historical requirements of the area.

Other fence secƟons can be black powder coated chain link. All secƟons of the fence shall meet the FE-7 specificaƟons

1.1.1.2. Provide and install personnel and vehicle gates as shown. The vehicle gates shall be comprised of two 12-foot swing arm gates (24 feet in total), and the personnel gates shall be 4-foot-wide single swing arm gates. Both shall have 90 deg verƟcal three strand outriggers atop the gates that shall match the height of the newly installed outriggers atop the new fence line.

1.1.1.3. Provide and install 10 inch diameter concrete filled pipe bollards. Each bollard shall be posiƟoned directly in front of the vehicle gate terminal posts, spaced between one and two feet away.

1.1.1.4. Along the plan-East side where the newly installed fence line meets up with the exisƟng four-foot tall black fence, remove that secƟon of exisƟng fence that overlaps the new fence line, and replace it with the new. All remaining fence shall be made to splice into the new fence seamlessly.

1.1.2. Contractor shall Convert Building 2084 into an Opera onal Support Facility.

1.1.2.1. Contractor shall provide and install communica ons fiber and copper to building 2084.

a. Install new underground telecommunicaƟons infrastructure pathway to building

2084. Paths are approximate, contractor shall field verify and may deviate if condiƟons dictate aŌer discussing with the Government representaƟve. All work shall be completed in accordance with the Technical Criteria for the InstallaƟon of

InformaƟon Infrastructure Architecture (I3A, dated February 2017) and UFC 3-580-

01. Contractor shall submit TIA-606 compliant telecommunicaƟons installaƟon drawings (to include drawings and lists of materials) and a cable test plan prior to start of construcƟon. Prior to construcƟon start, Contractor, DPW PM, and NEC

Personnel shall aƩend a kick-off meeƟng to review all plans, rouƟng, exisƟng and future work, and any other necessary items related to this project.

1. Provide and install new 4” concrete-encased SCH40 duct with 9 cell (3x3) 3” texƟle duct from MPHH-0033 through new entrance (approx. 100 lf) into TR SW corner of B2084.

2. Provide, install, terminate (SC), label new OSP 24SM F736, 49-72) from splice in MP-0078 to new LIU in TR SW corner of B2084. Test F736, (49-72) from B2084 LIU to Hut 3727.

3. Install, label exisƟng OSP 25 pr coiled in MPHH-0033 to new BET in TR SW corner of B2084. Test C205, 1326-1350 from B2084 to DCO 6071.

1.1.2.2. Construct new telecommunica ons room within the within Building 2084. Room shall adhere to the following specifica ons, and come equipped with the following services/fixtures.

a. Room shall be sized appropriately for the amount of telecommunicaƟons service being installed.

b. Room shall be Ɵled as appropriate for a telecom room. ExpectaƟon is for staƟc dissipaƟve Ɵle.

c. Walls of the newly enclosed room shall extend up to the same height as the rest of the buildings studded walls.

d. Walls and ceiling shall be equipped with sheet metal shielding.

e. Install overhead LED strip lighƟng within the room, switch to be located at the entrance of the new rooms exterior wall.

f. Walls and ceiling must uƟlize ¾” Type A/C fire rated plywood along the walls.

g. Install two dedicated quadruplex (double duplex) outlets with the new room, locaƟon shown on AƩachment X.

h. Install grounding busbar within the room where feasible. Busbar shall meet NEC standards. Contractor shall submit this to the government for approval.

i. Contractor shall provide a new fire alarm pull staƟon, heat detector and fire sprinkler head in this new communicaƟon room.

j. Ceiling shall be studded and built in the same manner as the walls, fully enclosed.

New ceiling shall provide three six inch wide penetraƟons and conduit sleeves for telecommunicaƟons fiber to run through. PenetraƟons shall have bag type fire stop material installed.

1.1.2.3. Provide and install new communica on drops, service, and other devices throughout building 2084.

a. Provide and install new communicaƟons drops throughout Building 2084.

CommunicaƟon drop requirements are detailed on the aƩached conceptual layout.

b. Provide and install cable trays for each of the communicaƟons requirements. Cable trays shall run centrally down the hallway stopping at each room being fed. All cable trays shall be grounded.

c. The contractor is responsible for providing and installing all necessary components of equipment to provide the service for these requirements, to include but is not limited to connecƟons, boxes, conduit, faceplates, and cabling.

d. Contractor shall submit to the government for approval shop drawings showing rouƟng of all new cable trays providing new communicaƟon requirements throughout the building. Shop drawings shall specify size of cable tray and show separaƟon requirements between different classificaƟons of cabling.

1.1.2.4. Contractor shall perform renova ons and repairs to building 2084.

a. All finishes, cove base, wall plates, shall meet JBLM Design Standards.

b. Remove and dispose of all wall Ɵle and remediate the exposed surface. The substrate shall be brought to a quality that is suitable for texturing and painƟng.

c. Remove and dispose of all restroom fixtures, to include sinks, toilets, restroom parƟƟons, mirrors, towel dispensers, soap dispensers, and urinals up to the plumbing connecƟons within the restroom area. All fixtures shall be replaced in-kind with new fixtures. All new flushometers and sink faucets shall have manual valves – no automaƟc valves or faucets are to be installed.

d. Remove and replace all floor Ɵle, up to and including the bull nose Ɵle acƟng as the base trim, and any other trim affixed to the wall. Contractor shall prepare the substrate to a quality where no imperfecƟons are visible through the newly installed Ɵle.. If seƩling has occurred which prohibits the ability to lay down Ɵles flat, the contractor shall apply a self-leveling compound to allow for a level surface. Bull nose Ɵle base trim is not to be replaced. Finishes shall meet JBLM Design Standards

e. Refinish wall from floor to ceiling, to include where the wall Ɵle was affixed to. If possible, the contractor may use the exisƟng gypsum/cement board currently exisƟng, if the exisƟng material is in such a state that can be brought to a level four finish. Wall shall be patched where needed, and be retextured and repainted.

f. Install cove base along the floors. Cove shall be four inches in height.

g. Remove and replace in-kind all wall receptacles and light switches with new devices.

All new finishes shall be white or eggshell in color.

h. Remove and replace the exisƟng troffer lights, replacing with energy efficient LED to match the size of the opening. Consolidate the electrical breaker requirements based on the new amperage required by the LED’s.

i. Remove and replace fan covers within restrooms with ones that are white in color, sized to cover the vent opening.

j. Remove and replace two interior restroom doors within the foyer area. Both doors shall be freely swinging, with a push plate and handle. Doors shall be solid-core wood.

k. Remove and replace three storage room doors within the foyer area. Door shall be equipped with kickstands, closers, and lockable hardware. All hardware shall be saƟn chrome or brushed nickel in color, all of which shall be matching whichever color is chosen.

l. Install door trim along all doors that were replaced. Door trim shall be 2 inches wide, MDF board, painted to match the new cove base.

1.1.2.5. Perform addi onal renova ons and upgrades.

a. Remove and dispose of all cabinets, and countertops within each room, to include the plumbing, which shall be capped off where it terminates at the wall. Remove and dispose of all items currently affixed to the wall.

b. Remove and replace all carpet Ɵle, up to and including the cove base. Contractor shall prepare the substrate to a quality where no imperfecƟons are visible through the newly installed Ɵle. New Ɵle shall meet JBLM Design Standards. If seƩling has occurred which prohibits the ability to lay down carpet Ɵles flat, the contractor shall apply a self-leveling compound to allow for a level surface. Bull nose Ɵle base trim is not to be replaced.

c. Refinish wall from floor to ceiling. If possible, the contractor may use the exisƟng gypsum/cement board currently exisƟng, if the exisƟng material is in such a state that can be brought to a level four finish. Wall shall be patched where needed, and be retextured and repainted.

d. Install cove base along the floors. Cove shall be four inches in height.

e. Remove and replace in-kind all wall receptacles and light switches with new devices.

All new finishes shall be white or eggshell in color.

f. Remove and replace the exisƟng troffer lights, replacing with energy efficient LED to match the size of the opening. Consolidate the electrical breaker requirements based on the new amperage required by the LED’s.

g. Install quadruplex receptacles as needed. Conduit shall be routed above the ceiling grid back to the panel. Provide and install breakers to the panel, one 20A for each of the eight rooms. All receptacle plates shall be marked with a typewriƩen sƟck-on label on the outside cover plate. Label must display the panel name and circuit breaker number. Contractor shall provide a new type-wriƩen panel schedule.

1.1.2.6. Contractor shall provide and install force protec on modifica ons in Building 2084.

a. Remove and replace exterior doors leading to each room and leading out of the space (not the Open Storage entrance). New doors shall be metal clad and shall be exit only. New doors shall be made of 20-gauge hollow-core steel.

b. Provide and install a new Solid Core Door at the entrance to the open storage area in accordance with the following specificaƟons.

1. New vault door shall meet Federal specificaƟon FF-L-2740B.

2. New doors shall swing inward, with the hinge pins facing the secure side of the frames.

3. Doors shall not have any sight glass.

4. Install door trim along the door frame. Door trim shall be 2 inches wide, MDF board, painted to match the new cove base.

5. All accessories shall be heavy duty and tamper resistant.

6. Provide and install Electronic Access Control (EAC) via a combinaƟon lock, single moƟon egress RIM device, and controlled remote keypad with a card reader compaƟble with the new ICIDS IB system as shown in AƩachment X. CombinaƟon lock shall be self-powered, meeƟng the specificaƟons in Federal specificaƟon FF-L- 2740B.

c. Install security screens on all HVAC openings over 96 square inches that penetrate the secure perimeter of the open storage area. Screens shall be made of ¾ inch (#9) mesh, case hardened, expanded steel. Screens shall be securely fastened to the brick surface uƟlizing tamper-proof screws.

d. Cover all exterior windows in a translucent one-way window film, which blocks sight into the building. In addiƟon, provide security bars over the windows to stop physical entrance. Security bars must be mounted from the interior.

e. Provide and install an Intrusion DetecƟon System (IDS) and Access Control System (ACS). Both systems shall have the following capabiliƟes.

1. Passive Infrared Sensors (PIRS)

2. Remote Area Data Collector (RADC)

3. Balance MagneƟc Switches (BMS)

4. All equipment shall be compaƟble with the bases exisƟng ICIDS IV system on

JBLM.

5. All IDS equipment shall meet UL 2050 and comply with an Extent 3 installaƟon as referenced in that same specificaƟon.

6. All ICIDS IV equipment and programming must be installed, completed, and commissioned by an ICIDS cerƟfied integrator.

f. Provide and install lockboxes. Lockboxes shall have the following characterisƟcs.

1. Be wall mounted somewhere at the entrance to the open storage area

2. Shall provide approximately 60 individual lockboxes.

3. Each individual box shall be approximately 6”x6”x9”.

4. Each individual box must be separately lockable with a key.

1.1.3. Contractor shall Convert Building 2090 into an Opera onal Support Facility.

1.1.3.1. Contractor shall provide and install communica ons fiber and copper to building

2090.

a. Clear exisƟng OSP 12SM F717, (7-12+6DD) from splice in MP-1080 back to MP-0078.

Splice recovered 12 strands into F736, (37-48). Terminate (SC) all 12 strands on new fiber adapter panels in exisƟng LIU in B2090. Test F736, (37-48) from B2090 LIU to

Hut 3727. Relabel LIU and cable from MP-0078 to B2090.

b. Construct new telecommunicaƟons room within Building 2090. Room shall adhere to the following specificaƟons, and come equipped with the following services/fixtures.

c. Room shall be sized appropriately for telecommunicaƟons service being installed.

d. Room shall be Ɵled as appropriate for a telecom room. ExpectaƟon is for staƟc dissipaƟve Ɵle.

e. Walls of the newly enclosed room shall extend up to the same height as the rest of the buildings studded walls.

f. Walls and ceiling shall be equipped with sheet metal shielding.

g. Install overhead LED strip lighƟng within the room, switch to be located at the entrance of the new rooms exterior wall.

h. Walls and ceiling must uƟlize ¾” Type A/C fire rated plywood along the walls.

i. Install two dedicated quadruplex (double duplex) outlets with the new room, locaƟon shown on AƩachment X.

j. Install grounding busbar within the room where feasible. Busbar shall meet NEC standards. Contractor shall submit this to the government for approval.

k. Contractor shall provide a new fire alarm pull staƟon, heat detector and fire sprinkler head in this new communicaƟon room.

l. Ceiling shall be studded and built in the same manner as the walls, fully enclosed.

New ceiling shall provide three six inch wide penetraƟons and conduit sleeves for telecommunicaƟons fiber to run through. PenetraƟons shall have bag type fire stop material installed.

1.1.3.2. Provide and install new communica on drops, service, and other devices throughout building 2090.

a. Provide and install new communicaƟons drops throughout Building 2090.

CommunicaƟon drop requirements are detailed on the aƩached conceptual layout.

b. Provide and install cable trays for each of the communicaƟons requirements. Cable trays shall run centrally down the hallway stopping at each room being fed. All cable trays shall be grounded.

c. The contractor is responsible for providing and installing all necessary components of equipment to provide the service for these requirements, to include but is not limited to connecƟons, boxes, conduit, faceplates, and cabling.

d. Contractor shall submit to the government for approval shop drawings showing rouƟng of all new cable trays providing new communicaƟon requirements throughout the building. Shop drawings shall specify size of cable tray and show separaƟon requirements between different classificaƟons of cabling.

1.1.3.3. Contractor shall perform renova ons and repairs to building 2090.

a. Contractor shall repair Building 2090 in the same way that Building 2084 was repaired for all classroom and finish work

1. No bathroom work is required within Building 2090

b. Contractor shall provide new 10’ x 12’ office spaces as shown on the JDOC Floorplans

– Building 2090 Space Design.

1.1.3.4. Contractor shall provide and install force protec on modifica ons in Building 2084.

a. Contractor shall provide the same force protecƟon modificaƟons in Building 2084 for the open storage designated areas within Building 2090.

1.1.4. Contractor shall provide and install back-up generator for buildings 2084 and 2090.

1.1.4.1. Provide and install a new emergency generator providing stand-by power supporƟng the MDP within buildings 2084 and 2090, and complete all electrical work, connecƟons, grounding and bonding, and terminaƟons for a complete and usable system. The generator shall have minimum set raƟngs of 175 kW, 120/208V, 3 PH, 600A. AddiƟonally, the generator shall be equipped with the following.

a. The generator shall have weather-proof sound enclosure and integrated UL-Listed

(double-wall) integrated sub-base fuel tank conforming to NFPA 30, NFPA 30A and

UL42.

b. Provide and install a minimum 4” raised concrete pad for the generator even though it’s on spring mounted bumpers. The concrete pad shall be 2,500 psi compression strength concrete reinforced with #6 rebar on 12 inch centers. This pad should be seated on a solid subsurface. The pad should be flat and level to within ½ inch.

c. The generator shall have an integrated sub-base fuel tank incorporaƟng double-wall Washington State environmentally compliant construcƟon. The fuel capacity for the sub-base fuel tank shall provide a minimum ‘run-Ɵme’ of 48-conƟnuous hours and incorporaƟng ‘Energy Efficient’ Block Heaters and site gauge as sub-base fuel tank.

Block Heaters shall have isolaƟon valves. Block Heaters shall be installed with ‘Hot Start’ heaƟng systems sized according to engine displacement.

d. The generator, enclosure, tank and electrical switches shall be seismically-rated, and anchored in accordance with ASCE 7-10 for Zone D (Is=1.5).

e. The generator controller shall be capable to interface the generator set to other power system equipment and network management systems using standard industry network communicaƟons.

f. Provide and install a sound enclosure that offers an average of 75 dB(A) sound level at 23 feet uƟlizing 2 inches of acousƟc-lined air discharge hood. AcousƟc insulaƟon to meet UL 94 HF1 flammability classificaƟon. ClassificaƟon as ‘weather-proof’ shall prevent the accumulaƟon of rainwater at base of generator within enclosure.

g. Provide and install a 3-way manual transfer switch to allow safe isolated load banking tesƟng and connecƟon of a portable backup generator Ɵed in at the same Ɵme, and complete all electrical work, connecƟons, grounding and bonding. 3-Way MTS to have interlocked breakers to prevent cross-connecƟng power sources, female camlock receptacles for load bank secƟon and male camlock receptacles for portable generator secƟon. MTS shall be cerƟfied to cULus standards and NEC 700.3F compliant. If the generator is large enough, the 3-way manual transfer switch maybe installed within the generator enclosure by the generator manufacturer, otherwise it will need to be protected from elements and readily accessible.

h. Provide and install a new 600A ATS and complete all electrical work, connecƟons, grounding and bonding, and terminaƟons for a complete, useable system. The new ATS shall have isolaƟon bypass. ATS does not need to be service rated. ATS and the 3-way MTS shall all be the compaƟble and have NEMA 3R Enclosures.

i. Provide and install conductors, conduit, connecƟon and supporƟng hardware to connect electrical service with new ATS, new generator to new MTS, new MTS to new ATS, and new ATS to the MDP. ExisƟng conductor and conduit that the insulaƟon isn’t fraying, have any hotspots or corrosion built-up can be reused when determined adequate for new generator installaƟon. The Contractor shall provide grounding system connecƟons for all new equipment and verify all grounding system connecƟons are properly completed as required per DPW Electrical Inspector. All the conduit and wire size shall meet the NEC requirements that is currently exisƟng. Due to exisƟng uƟliƟes underground, Contractor shall route generator connecƟons overhead along the exterior of the building. All conduits shall be covered with a cover/guƩer like system and shall be painted to blend into the exisƟng building exterior.

j. Provide an enclosure around the generator to include a gate and privacy slats.

Enclosure shall be sized to provide adequate spacing around the generator for maintenance. Enclosure shall be approximately 10 feet tall but shall be sized to completely hide the new generators. The sides of the enclosure shall be brick or brick facade matching the exisƟng building brick as close as feasible. New gate shall be sized as necessary and shall swing out from the generator. Privacy slates shall match the slats used on the nearby gas meter fencing.

k. Upon conclusion of work, contractor shall supply a comprehensive arc fault study and report for the newly installed generator and supporƟng equipment that includes:

1. Report summary with analysis methodology, findings and recommendaƟons

2. Summary of input data for uƟlity source, equipment and cables

3. Available fault current at each equipment locaƟon with comparison to equipment raƟng

4. Overcurrent device seƫngs (e.g. pick-up, Ɵme delay, curve), “as found” and

“as recommended”

5. Incident energy level (calories/cm2 ) for each equipment locaƟon and recommended PPE

6. Overcurrent device coordinaƟon curves including related secƟon of the single-line diagram

7. Complete system single-line diagram for the system analyzed

8. Install ARC Flash warning labels based upon study results on all equipment evaluated as a part of this study

Building 2084 Space Design Requirements:

-Open Storage Entire Building to allow NIPR, SIPR, TAC SIPR, CXJ networks

5 x Classroom Style Rooms(JDOC) -19 x workstations w/ N,S,TAC-

S,CXJ

-2 x Screens fed from single workstation -Wall mounted whiteboards -Table area at rear of room for supplies, etc.

2 x Conference Style Room(JDOC & G35)

-Rolling partitions w/ whiteboards on sides to separate room in two

-5’x22’ conference table w/ seating for 18 plus 8-10 on wall; 8 x N,S,TAC- S,CXJ ports

-5’x14’ conference table w/ seating for 12; 6 x N,S,TAC-S,CXJ ports

-Screens fed from workstation at conference tables

-Wall mounted whiteboards

1 x Planning Style Room(G35) -12 x workstations w/ N,S,TAC-

S,CXJ

-4’x8’ planning table -Rolling whiteboards -Wall mounted whiteboards

OPEN Storage Entrance/Exit

Legend NIPR Connection SIPR Connection TAC-SIPR Conn.

CX-J Conn.

Commercial Conn.

Open Storage Limit

Building 2090 Space Design

OPEN Storage Entrance/Exit

Requirements:

-Open Storage Half Building to allow NIPR, SIPR, Commercial networks

1 x Cubicle & ConferenceStyle Rooms(INNO/JIOP)

-9 x workstations w/ N,S -Conference table for 10-12 w/ N,S and

A/V for projection / screen

2 x Cubicle & Office Style Room(INNO

& JIOP)

-5-6 x workstations w/ N,S -2 x 10’x12’ office spaces with single door and 1 x workstation per office w/ N,S -Conference table for 10-12 w/ N,S and

A/V for projection / screen -Small planning table for 4-6

1 x Office Room (INNO) -1 x workstation w/ N,S -Small planning table

1 x Conference Room -1 x conference table w/ seating for 15-

20 w/ N,S and A/V for projection

1 x Team Collaboration Room(ODT) -1 x workstation w/ N,S,Comm.

-2 x large tables w/ 6 workstations each w/ N,S,Comm.

1 x Team Collaboration Room(KMO) -1 x workstation w/ N,S, -1 x large table for 12-15 w/ N,S -1 x medium table for 8-10 w/ N,S and

A/V for projection

Legend NIPR Connection SIPR Connection TAC-SIPR Conn.

CX-J Conn.

Commercial Conn.

Open Storage Limit

Building 2084 Space Design ao: 27FEB26

(TYP) Convert to exit only

Install new Solid Core door w/ ICIDS V

(TYP) Provide window coverings and bars

(TYP) Remove kids height counters and plumbing in 8 rooms

Building 2090 Space Design ao: 26FEB26

Install new Solid Core door w/ ICIDS V

(TYP) Convert to exit only

Renovate wall to extend from true floor to ceiling

(TYP) Provide window coverings and bars

Construct 2EA 10’ x 12’ Office Space

Construct 2EA 10’ x 12’ Office Space

(TYP) Remove kids height counters and plumbing in 6 rooms

JDOC PH3 OSP Solution, JDOC B2084, and B2090

03727

MP-001095

MP-001075

MP-000073

AF-000125

AF-000120

MP-000975

MP-000995

MP-000985

MP-000078

MP-001080

MP-001085

MP-001105

MP-001110

MP-001130

AF-000001

MP-000845

MP-0078 to B2084:

•Add new 12 SM OSP Fiber F736, 37-48 from splice case in MP-0078 to B2084 via NEW duct MP-HH0033 to B2084:

•Pull in existing 25-pair OSP Copper C205, 1326-1350 (coiled in MPHH-0033) via NEW duct

MPHH0033

B2090 OSP Fiber Solution: In MH# MP-0078:

Clear existing 12SM F717 (7-12+6DD) from splice case in MH# MP-1080 Splice 12 strands into F736, 49-60 in existing splice case in MP-0078

• Terminate remaining 6-strands of the existing 12SM in the LIU in B2090.

• Re-label cable & LIU w/ new F736 cable ID#.

75yrds from Helo pad.

12' Vehicle Gate

4' Personnel Gate

1250' of 7' high fencing with 3 strand b-wire

3_Fence Location & Specifications.pdf
JDOC Perimeter Fence
Attachment 4 - FE-6 Fence Specifications