This is a Performance Work Statement (PWS) specification section for the removal and disposal of PCB-containing lighting ballasts and mercury-containing lamps at Portsmouth Naval Shipyard in Kittery, Maine, under contract SIOP 1740579. The specification outlines comprehensive requirements for handling hazardous materials in compliance with federal regulations including 40 CFR 761 (PCBs), 40 CFR 273 (Universal Waste), and applicable OSHA standards.
The contractor must furnish all labor, materials, services, and equipment necessary to remove PCB-containing lighting ballasts and associated mercury-containing fluorescent lamps in accordance with local, state, and federal regulations. A Certified Industrial Hygienist (CIH) must oversee all work, including developing and approving a job-specific removal work plan (due within 20 calendar days of contract award) and a disposal plan (due within 45 calendar days). Key submittals requiring government approval include CIH qualifications, training certifications, both work plans, and closeout documentation including transporter certifications and disposal certificates. Storage containers must comply with DOT specifications (49 CFR 178), and all PCB waste containers must be labeled with appropriate caution notices per 40 CFR 761. The contractor must handle spill cleanup within 24 hours of discovery and maintain inspection and inventory records. Ballasts without "No PCB" labels must be assumed to contain PCBs and properly containerized. Mercury-containing lamps must remain unbroken during removal and storage. Disposal must occur at permitted facilities off government property, with coordination through Defense Logistics Agency Disposition Services when appropriate, and completed with DD Form 1348-1 documentation.
View the file
Other files
Show 40 more
Latest 50 of 157 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
B60: PRODUCTION FACILITY REPAIRS - SIOP 1740579
PORTSMOUTH NAVAL SHIPYARD, KITTERY, MAINE
SECTION 02 84 16.00 22
HANDLING OF LIGHTING BALLASTS AND LAMPS CONTAINING PCBs AND MERCURY (PWD ME) 11/22
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
29 CFR 1910.1000 Air Contaminants
40 CFR 260 Hazardous Waste Management System: General
40 CFR 261 Identification and Listing of Hazardous Waste
40 CFR 262 Standards Applicable to Generators of Hazardous Waste
40 CFR 263 Standards Applicable to Transporters of Hazardous Waste
40 CFR 264 Standards for Owners and Operators of Hazardous Waste Treatment, Storage, and Disposal Facilities
40 CFR 265 Interim Status Standards for Owners and Operators of Hazardous Waste Treatment, Storage, and Disposal Facilities
40 CFR 268 Land Disposal Restrictions
40 CFR 270 EPA Administered Permit Programs: The Hazardous Waste Permit Program
40 CFR 273 Standards for Universal Waste Management
40 CFR 761 Polychlorinated Biphenyls (PCBs) Manufacturing, Processing, Distribution in Commerce, and Use Prohibitions
49 CFR 178 Specifications for Packagings
1.2 REQUIREMENTS
Removal and disposal of PCB containing lighting ballasts and associated mercury-containing lamps. Contractor may encounter leaking PCB ballasts.
SECTION 02 84 16.00 22 Page 1 llangley Typewritten Text
AMENDMENT 008, 03-10-2026
1.3 DEFINITIONS
1.3.1 Certified Industrial Hygienist (CIH)
A industrial hygienist hired by the contractor must be certified by the American Board of Industrial Hygiene.
1.3.2 Leak
Leak or leaking means any instance in which a PCB article, PCB container, or PCB equipment has any PCBs on any portion of its external surface.
1.3.3 Lamps
Lamp is defined as the bulb or tube portion of an electric lighting device. A lamp is specifically designed to produce radiant energy, most often in the ultraviolet, visible, and infra-red regions of the electromagnetic spectrum. Examples of common electric lamps include, but are not limited to, fluorescent, high intensity discharge, neon, mercury vapor, high pressure sodium, and metal halide lamps.
1.3.4 Polychlorinated Biphenyls (PCBs)
PCBs as used in this specification mean the same as PCBs, and all related items, as defined in 40 CFR 761 , Section 3, Definitions.
1.3.5 Spill
Spill means both intentional and unintentional spills, leaks, and other uncontrolled discharges when the release results in any quantity of PCBs running off or about to run off the external surface of the equipment or other PCB source, as well as the contamination resulting from those releases.
1.3.6 Universal Waste
Universal Waste means any of the following hazardous wastes that are managed under the universal waste requirements 40 CFR 273 :
(1) Batteries as described in Sec. 273.2 of this chapter;
(2) Pesticides as described in Sec. 273.3 of this chapter;
(3) Mercury containing equipment as described in Sec. 273.4 of this chapter; and
(4) Lamps as described in Sec. 273.5 of this chapter.
1.4 QUALITY ASSURANCE
1.4.1 Regulatory Requirements
Perform PCB related work in accordance with 40 CFR 761 . Perform mercury-containing lamps storage and transport in accordance with
40 CFR 261 , 40 CFR 264 , 40 CFR 265 , 40 CFR 273 .
1.4.2 Training
Instruction and certification of training of all persons involved in the
SECTION 02 84 16.00 22 Page 2 removal of PCB containing lighting ballasts and mercury-containing lamps is the responsibility of the Certified Industrial Hygienist (CIH).
Include in the instruction: The dangers of PCB and mercury exposure, decontamination, safe work practices, and applicable OSHA and EPA regulations. The CIH must review and approve the PCB and Mercury-Containing Lamp Removal Work Plans.
1.4.3 Regulation Documents
Maintain at all times one copy each at the office and one copy each in view at the job site of 29 CFR 1910.1000 , 40 CFR 260 , 40 CFR 261 , 40 CFR 262 , 40 CFR 263 , 40 CFR 265 , 40 CFR 268 , 40 CFR 270 , 40 CFR 273 and of the Contractor removal work plan and disposal plan for PCB and for associated mercury-containing lamps.
1.5 SUBMITTALS
Government approval is required for submittals with a "G" classification.
Submittals not having a "G" classification are for Contractor Quality Control approval. Submit the following in accordance with Section
01 33 00.00 22 SUBMITTAL PROCEDURES (PWD ME):
SD-07 Certificates
Qualifications of CIH ; G
Training Certification ; G
PCB and Lamp Removal Work Plan ; G
PCB and Lamp Disposal Plan ; G
SD-11 Closeout Submittals
Transporter Certification of notification to EPA of their PCB waste activities and EPA ID numbers; G
Certification of Decontamination
Certificate of Disposal and/or recycling . Submit to the Government before application for payment within 30 days of the date that the disposal of the PCB and mercury-containing lamp waste identified on the manifest was completed.
DD Form 1348-1
1.6 ENVIRONMENTAL REQUIREMENTS
Use special clothing:
a. Disposable gloves (polyethylene)
b. Eye protection
c. PPE as required by CIH
1.7 SCHEDULING
Notify the Contracting Officer 20 days prior to the start of PCB and
SECTION 02 84 16.00 22 Page 3 mercury-containing lamp removal work.
1.8 QUALITY ASSURANCE
1.8.1 Qualifications of CIH
Submit the name, address, and telephone number of the Industrial Hygienist selected to perform the duties in paragraph CERTIFIED INDUSTRIAL HYGIENIST. Submit training certification that the Industrial Hygienist is certified, including certification number and date of certification or re certification.
1.8.2 PCB and Lamp Removal Work Plan
Submit a job-specific plan within 20 calendar days after award of contract of the work procedures to be used in the removal, packaging, and storage of PCB-containing lighting ballasts and associated mercury-containing lamps. Include in the plan: Requirements for Personal Protective Equipment (PPE), spill cleanup procedures and equipment, eating, smoking and restroom procedures. The plan must be approved and signed by the Certified Industrial Hygienist. Obtain approval of the plan by the Contracting Officer prior to the start of PCB and/or lamp removal work.
1.8.3 PCB and Lamp Disposal Plan
Submit a PCB and lamp Disposal Plan within 45 calendar days after award of contract, complying with the applicable requirements of federal, state, and local PCB and Universal waste regulations and address:
a. Estimated quantities of wastes to be generated, disposed of, and recycled.
b. Names and qualifications of each Contractor that will be transporting, storing, treating, and disposing of the wastes. Include the facility location. Furnish two copies of EPA and state PCB and mercury-containing lamp waste permit applications and EPA identification numbers, as required.
c. Names and qualifications (experience and training) of personnel who will be working on-site with PCB and mercury-containing lamp wastes.
d. Spill prevention, containment, and cleanup contingency measures to be implemented.
e. Work plan and schedule for PCB and mercury-containing lamp waste removal, containment, storage, transportation, disposal and or recycling. Clean up and containerize wastes daily.
PART 2 PRODUCTS
Not used.
PART 3 EXECUTION
3.1 WORK PROCEDURE
Furnish labor, materials, services, and equipment necessary for the removal of PCB containing lighting ballasts, and associated mercury-containing fluorescent lamps in accordance with local, state, or
SECTION 02 84 16.00 22 Page 4 federal regulations. Do not expose PCBs to open flames or other high temperature sources since toxic decomposition by-products may be produced. Do not break mercury containing fluorescent lamps or high intensity discharge lamps.
3.1.1 Work Operations
Ensure that work operations or processes involving PCB or PCB-contaminated materials are conducted in accordance with 40 CFR 761 , 40 CFR 262 40 CFR 263 , and the applicable requirements of this section, including but not limited to:
a. Obtaining suitable PCB and mercury-containing lamp storage sites.
b. Notifying Contracting Officer prior to commencing the operation.
c. Reporting leaks and spills to the Contracting Officer.
d. Cleaning up spills.
e. Inspecting PCB and PCB-contaminated items and waste containers for leaks and forwarding copies of inspection reports to the Contracting Officer.
f. Maintaining inspection, inventory and spill records.
3.2 PCB SPILL CLEANUP REQUIREMENTS
3.2.1 PCB Spills
Immediately report to the Contracting Officer any PCB spills.
3.2.2 PCB Spill Control Area
Rope off an area around the edges of a PCB leak or spill and post a "PCB Spill Authorized Personnel Only" caution sign. Immediately transfer leaking items to a drip pan or other container.
3.2.3 PCB Spill Cleanup
40 CFR 761 , subpart G. Initiate cleanup of spills as soon as possible, but no later than 24 hours of its discovery. Mop up the liquid with rags or other conventional absorbent. Properly contain and dispose of spent absorbent as solid PCB waste.
3.2.4 Records and Certification
Document the cleanup with records of decontamination in accordance with 40 CFR 761 , Section 125, Requirements for PCB Spill Cleanup. Provide test results of cleanup and certification of decontamination .
3.3 REMOVAL
3.3.1 Ballasts
As ballast are removed from the lighting fixture, inspect label on ballast. Ballasts without a "No PCB" label must be assumed to contain PCBs and containerized and disposed of as required under paragraphs STORAGE FOR DISPOSAL and DISPOSAL. If there are less than 1600 "No PCB"
SECTION 02 84 16.00 22 Page 5 labeled lighting ballasts, dispose of them as normal demolition debris.
3.3.2 Lighting Lamps
Remove lighting tubes/lamps from the lighting fixture and carefully place (unbroken) into appropriate containers (original transport boxes or equivalent). In the event of a lighting tube/lamp breaking, sweep and place waste in double plastic taped bags and dispose of as universal waste as specified herein.
3.4 STORAGE FOR DISPOSAL
3.4.1 Storage Containers for PCBs
49 CFR 178 . Store PCB in containers approved by DOT for PCB.
3.4.2 Storage Containers for lamps
Store mercury containing lamps in appropriate DOT containers. Store and label boxes for transport in accordance with 40 CFR 273 .
3.4.3 Labeling of Waste Containers
Label with the following:
a. Date the item was placed in storage and the name of the cognizant activity/building.
b. "Caution Contains PCB," conforming to 40 CFR 761 , CFR Subpart C.
Affix labels to PCB waste containers.
c. Label mercury-containing lamp waste in accordance with 40 CFR 273 .
Affix labels to all lighting waste containers.
3.5 DISPOSAL
Dispose of off Government property in accordance with EPA, DOT, and local regulations at a permitted site.
3.5.1 Identification Number
Federal regulations 40 CFR 761 , and 40 CFR 263 require that generators, transporters, commercial storers, and disposers of PCB waste posses U.S.
EPA identification numbers. Verify that the activity has a U.S. EPA generator identification number for use on the Uniform Hazardous Waste manifest. If not, advise the activity that it must file and obtain an I.D. number with EPA prior to commencement of removal work. For mercury containing lamp removal, Federal regulations 40 CFR 273 require that large quantity handlers of Universal waste (LQHUW) must provide notification of universal waste management to the appropriate EPA Region (or state director in authorized states), obtain an EPA identification number, and retain for three years records of off-site shipments of universal waste.
Verify that the activity has a U.S. EPA generator identification number for use on the Universal Waste manifest. If not, advise the activity that it must file and obtain an I.D. number with EPA prior to commencement of removal work.
SECTION 02 84 16.00 22 Page 6
3.5.2 Transporter Certification
Comply with disposal and transportation requirements outlined in 40 CFR 761 and 40 CFR 263 . Before transporting the PCB waste, sign and date the manifest acknowledging acceptance of the PCB waste from the Government.
Return a signed copy to the Government before leaving the job site.
Ensure that the manifest accompanies the PCB waste at all times. Submit transporter certification of notification to EPA of their PCB waste activities (EPA Form 7710-53).
3.5.2.1 Certificate of Disposal and/or Recycling
40 CFR 761 . Include in the certificate for the PCBs and PCB items disposed:
a. The identity of the disposal and or recycling facility, by name, address, and EPA identification number.
b. The identity of the PCB waste affected by the Certificate of Disposal including reference to the manifest number for the shipment.
c. A statement certifying the fact of disposal and or recycling of the identified PCB waste, including the date(s) of disposal, and identifying the disposal process used.
d. A certification as defined in 40 CFR 761 .
3.5.3 Disposal by the Government
Comply with disposal and transportation requirements outlined in 40 CFR 761 and 40 CFR 263 . Coordinate delivery of PCBs on-site with local Environmental for subsequent disposal on Defense Logistics Agency Disposition Services (DLA DS) contracts. If the primary site is filled to capacity, contact the Contracting Officer. The transport distance to any storage site will not exceed the distance between the project site and the DLA DS storage site.
3.5.3.1 DD Form 1348-1
Prepare DD Form 1348-1 Turn-in Document (TID), which will accompany the PCB to the storage site. Ensure that a responsible person from the activity that owns the PCB signs the DD Form 1348-1.
-- End of Section --