This pre-solicitation notice announces a forthcoming solicitation for base operations support (BOS) services at naval installations in Jefferson, Kitsap, and Pierce counties in Washington state. The solicitation will be for a single-award IDIQ fixed-price contract with award fee provisions comprising recurring and non-recurring work items. Services include general information, management and administration, fire and emergency services, facilities support including facility management, investment, and pavement clearance, wastewater, transportation, and environmental services. The contract term will be a base period of up to 12 months with seven 12-month option periods not exceeding 96 months total. The incumbent contractor is Chugach Federal Solutions, which has performed these services under contract N44255-14-D-9000 since March 2014. The anticipated RFP release date is 4 January 2019 with proposals due 18 February 2019. The tradeoff source selection process will consider corporate experience, technical approach, management approach, safety, and past performance with price. The NAICS code is 561210 for facilities support services.
1501000_J_Facility_Management_Amendment_0014.pdf
View the file
Other files
Show all 39
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1501000 FACILITY MANAGEMENT
TABLE OF CONTENTS
ATTACHMENT NUMBER ATTACHMENT TITLE
J-1501000-01 Control System Facilities J-1501000-02 Historical Workload Quantity J-1501000-03 ICAP Direct Condition Rating Guidance J-1501000-04 Uniformat Table J-1501000-05 Non-Dynamic Roof Assets J-1501000-06 Technical Library Inventory
J-1501000-01
CONTROL SYSTEM FACILITIES
Primary ICS Sub- System
Base Bldg Building Name
If Controllers are Remote
Building Level Controllers
System Protocols include
Notes ICS Wired
Ethernet
BLC in Bldg #
Sensor Ctrler in Bldg #
Type #1
Type #2
Qty #1 #2 #3
AMI NAVMAG II 1 Fuse-Detonator Mag-Bulk
AMI Meter using Wi-Fi with Switch, radio, and Firewall
No
AMI NAVMAG
II
62 Public Work Shop
No
AMI NAVMAG
II
64 Weapons Shop
No
SCADA NAVMAG
II
69 Admin Building
Yes
AMI NAVMAG
70 Ordnance Ops
No
AMI NAVMAG
II
77 General Warehouse
No
AMI NAVMAG
II
84 Public Work
No
AMI NAVMAG
89 Armory
No
AMI NAVMAG
II
90 Small Craft Maint Shop
No
AMI NAVMAG
II
100 High Explosive Magazine-Bulk
No
SCADA NAVMAG
108 Lift Station 9
JACE-
NXS
1 Lon
II
132 Heating Plant Boat Mnt Shop
No
AMI NAVMAG
II
151 Recreation Bldg
No
AMI NAVMAG
184 Gate House
No
AMI NAVMAG
II
187 Inert Operating
No
AMI NAVMAG
II
189 Explosive Operating Bldg
No
Primary ICS Sub- System
Base Bldg Building Name
If Controllers are Remote
Building Level Controllers
System Protocols include
Notes ICS Wired
Ethernet
BLC in Bldg #
Sensor Ctrler in Bldg #
Type #1
Type #2
Qty #1 #2 #3
AMI NAVMAG
II
825 Ordnance Transfer Facility
No
AMI NAVMAG
II
833 Waterfront Operations
No
AMI NAVMAG
II
834 Blockers & Bracers Shop
No
SCADA NAVMAG
835 Lift Station
1 Modbus
II
836 Ordnance Field Office
No
AMI NAVMAG
837 SEG/RENOV.
No
AMI NAVMAG
II
848 Reserve Training Center Ph 1
No
AMI NAVMAG
II
849 Administrative
No
SCADA NAVMAG
856 Lift Station 7
924 Storage Bldg.
No
AMI NAVMAG
II
1018 Type M Missle Magazine
No
AMI NAVMAG
II
1019 Type M Missile
No
AMI NAVMAG
II
1020 Type M Missle
No
AMI NAVMAG
II
1021 High Explosive
Primary ICS Sub- System
Base Bldg Building Name
If Controllers are Remote
Building Level Controllers
System Protocols include
Notes ICS Wired
Ethernet
BLC in Bldg #
Sensor Ctrler in Bldg #
Type #1
Type #2
Qty #1 #2 #3
AMI NAVMAG
II
1022 High Explosive
No
AMI NAVMAG
II
1023 High Explosive
No
AMI NAVMAG
II
1024 High Explosive
No
AMI NAVMAG
II
1025 High Explosive
No
AMI NAVMAG
II
1030 Explosives
No
AMI NAVMAG
1031 Lunchroom
No
AMI NAVMAG
II
1040 Gate/Sentry House
No
AMI NAVMAG
II
1041 Truck Inspection Station
No
AMI NAVMAG
II
1042 Gate/Sentry House
No
Substation 1
No
DDC Jackson Park 779 Child Development Ctr
Metasys
1 Metasys
Stand-Alone Yes
DDC Jackson Park 780 Comm. Sup.
Lon
1 Lon Network
DDC Jackson Park 1 Medical
JACE-
JACE-
JACE-
JACE-
10 Lon Modbus
1 Unit is a spare held by NHB Operations Manager
AMI Jackson Park 2 Maintenance
Primary ICS Sub- System
Base Bldg Building Name
If Controllers are Remote
Building Level Controllers
System Protocols include
Notes ICS Wired
Ethernet
BLC in Bldg #
Sensor Ctrler in Bldg #
Type #1
Type #2
Qty #1 #2 #3
Shop AMI Jackson Park 3 Bachelor
Enlisted Quarters - North
No
AMI Jackson Park 12 Indoor Physical Fitness Center
No
AMI Jackson Park 14 Admin.
(NHB)
DDC Jackson Park 17 Clinic
DDC Jackson Park 87 Medical
DDC Jackson Park 88 Storage
DDC NBK-Bangor 1001 Navy Legal Service Bldg
Steam-Eye Trap No
DDC NBK-Bangor 1003 Family Housing-Pub Qtrs-Cdr
FullBA C
2 BACnet
DDC NBK-Bangor 1004 Vet Clinic
VLX
3 BACnet
DDC NBK-Bangor 1006 Drillhall
DDC NBK-Bangor 1013 CNRNW Environmental Admin
1305 1305
Sensor
DDC NBK-Bangor 1014 RR Equip iLon 600
DDC NBK-Bangor 1016 General Warehouse-R I
DDC NBK-Bangor 1021 CBU/PW RDS
& GRNDS
Primary ICS Sub- System
Base Bldg Building Name
If Controllers are Remote
Building Level Controllers
System Protocols include
Notes ICS Wired
Ethernet
BLC in Bldg #
Sensor Ctrler in Bldg #
Type #1
Type #2
Qty #1 #2 #3
DDC NBK-Bangor 1026 Maintenance Shops-Pw
BCM-
ETH
1 BACnet
DDC NBK-Bangor 1034 Civil Servc
DDC NBK-Bangor 1035 Visitor/Pass and I.D. Center
DDC NBK-Bangor 1038 Supply Support
DDC NBK-Bangor 1042 United Telephone
AMI NBK-Bangor 1044 Filling Station
No
DDC NBK-Bangor 1048 Small Engine Storage Shed
DDC NBK-Bangor 1050 Reserve
DDC NBK-Bangor 1099 Family Hsg Welcome Center
DDC NBK-Bangor 1100 Administrative
DDC NBK-Bangor 1101 Engineering Admin Bldg.
NAVFAC CIO ICS servers, workstations, firewalls, routers, and related equipment are managed by NAVFAC
CIO
Yes
DDC NBK-Bangor 1103 COMNAVRE G NW Admin
DDC NBK-Bangor 1200 Police Station
Primary ICS Sub- System
Base Bldg Building Name
If Controllers are Remote
Building Level Controllers
System Protocols include
Notes ICS Wired
Ethernet
BLC in Bldg #
Sensor Ctrler in Bldg #
Type #1
Type #2
Qty #1 #2 #3
DDC NBK-Bangor 1201 Dry Provisions S & R Whse
DDC NBK-Bangor 1202 P W Vehicle Maint Bldg
AMI NBK-Bangor 1203 Steam Cleaning
No
DDC NBK-Bangor 1205 P W Refueler Repair Bldg
DDC NBK-Bangor 1207 Storage
DDC NBK-Bangor 1247 EOD was Oak-
Adec
NBK-Bangor 1248 EOD Garage
DDC NBK-Bangor 1268 PW Storage
DDC NBK-Bangor 1300 Fire Station #1
DDC NBK-Bangor 1460 Community
Recycling
DDC NBK-Bangor 2000 Trident
LGRM
2 Automat ed Logic
DDC NBK-Bangor 2008 Kitsap Federal Credit Union
2501 2500
DDC NBK-Bangor 2011 NUWC Newport Det
DDC NBK-Bangor 2012 NUWC Newport Storage Bldg
2011 2011 / 2012
DDC NBK-Bangor 2013 Fire Fighter Trng Class Room
Primary ICS Sub- System
Base Bldg Building Name
If Controllers are Remote
Building Level Controllers
System Protocols include
Notes ICS Wired
Ethernet
BLC in Bldg #
Sensor Ctrler in Bldg #
Type #1
Type #2
Qty #1 #2 #3
DDC NBK-Bangor 2014 Fire Fighter Trng Bldg
Staefa
DDC NBK-Bangor 2016
DDC NBK-Bangor 2017 Fire Fighter
Trnr Pump
DDC NBK-Bangor 2019 Transient Personnel Unit
DDC NBK-Bangor 2020 Correctional Custody Unit
DDC NBK-Bangor 2025 Pallet Storage
DDC NBK-Bangor 2050 Dispensary / Dental Clinic
DDC NBK-Bangor 2100 Off Crew Administration
DDC NBK-Bangor 2101 Enlisted Dining Facility
DDC NBK-Bangor 2102 Marine Bq Strategic Sec Spt
1 ASI Lon
DDC NBK-Bangor 2150 COMSUBGRP 9 Facility
VLX iLon
DDC NBK-Bangor 2200 Core Bldg/East 2501 2207
DDC NBK-Bangor 2201 BEQ BLDG 1
1 Sensor
DDC NBK-Bangor 2202 BEQ BLDG II
DDC NBK-Bangor 2203 BEQ BLDG III
DDC NBK-Bangor 2204 BEQ, IX 2501
DDC NBK-Bangor 2205 BEQ BLDG 2501 2204
Primary ICS Sub- System
Base Bldg Building Name
If Controllers are Remote
Building Level Controllers
System Protocols include
Notes ICS Wired
Ethernet
BLC in Bldg #
Sensor Ctrler in Bldg #
Type #1
Type #2
Qty #1 #2 #3
IV
DDC NBK-Bangor 2206 BEQ, V 2501 2207
DDC NBK-Bangor 2207 BEQ, VI 2501
DDC NBK-Bangor 2208 BEQ, VII 2501 2207
DDC NBK-Bangor 2209 BEQ, VIII 2501
DDC NBK-Bangor 2300 Core
Building/West
AMI NBK-Bangor 2301 BEQ, BLDG 1
AMI NBK-Bangor 2302 BEQ, BLDG 2
AMI NBK-Bangor 2303 BEQ, BLDG 3
DDC NBK-Bangor 2304 BEQ UNIT 1
Stand-Alone No DDC NBK-Bangor 2305 BEQ UNIT 2
DDC NBK-Bangor 2306 BEQ UNIT 4
DDC NBK-Bangor 2500 NEX Uniform
DDC NBK-Bangor 2501 Base Theater
DDC NBK-Bangor 2600 Navy Exchange Retail Store
AMI NBK-Bangor 2604 Commissary
DDC NBK-Bangor 2650 Post Office
DDC NBK-Bangor 2700 Recreation Complex / Swimming Pool
DDC NBK-Bangor 2701 BOWLING
LANES
Primary ICS Sub- System
Base Bldg Building Name
If Controllers are Remote
Building Level Controllers
System Protocols include
Notes ICS Wired
Ethernet
BLC in Bldg #
Sensor Ctrler in Bldg #
Type #1
Type #2
Qty #1 #2 #3
DDC NBK-Bangor 2705 IN PHYS FIT
CTR
DDC NBK-Bangor 2720 BANGOR
PLAZA
VLX iLon
1 BACnet Lon
DDC NBK-Bangor 2750 Bachelor Officers Quarters
DDC NBK-Bangor 2850 DVECC Administration
DDC NBK-Bangor 2851 DVECC
DDC NBK-Bangor 2900 Chapel Complex
DDC NBK-Bangor 2901 Family Service
DDC NBK-Bangor 2902 Child Care
DDC NBK-Bangor 2903 Youth Center
AMI NBK-Bangor 2904 McDonalds
No
DDC NBK-Bangor 2905 NEX Mini Mart/Package Store
2950 2950
DDC NBK-Bangor 2906 Navy Lodge 2950 2950
DDC NBK-Bangor 2907 Family Serv
Center Annex
DDC NBK-Bangor 2908 FSC Classroom
2950 2950 VLX
DDC NBK-Bangor 2949 Gas Pump Island
2950 2950
DDC NBK-Bangor 2950 Exchange Svc
Primary ICS Sub- System
Base Bldg Building Name
If Controllers are Remote
Building Level Controllers
System Protocols include
Notes ICS Wired
Ethernet
BLC in Bldg #
Sensor Ctrler in Bldg #
Type #1
Type #2
Qty #1 #2 #3
Station NXS DDC NBK-Bangor 2951 Auto Hobby
1034 2950 / 2951 iLon 600
DDC NBK-Bangor 2956 Car Wash
AMI NBK-Bangor 3650 Small Arms Training Range
NBK-Bangor 4042 Sewage Lift Station/Site 3
DDC NBK-Bangor 4070 C.B.Unit
DDC NBK-Bangor 4071 Dog Kennel 1034
AMI NBK-Bangor 4620 Training
No
DDC NBK-Bangor 5000 Explosive Test Facility/Wqec
DDC NBK-Bangor 5090 Tactical Data Sys Res Fac
5093 5091
DDC NBK-Bangor 5091 Magazine Field Office/Ad&C
DDC NBK-Bangor 5092 In-Service Engrg.
DDC NBK-Bangor 5093 Inert Storage
DDC NBK-Bangor 5094 Container Refurbishment
5093 5093
AMI NBK-Bangor 5095 Container Refurbishment
No
AMI NBK-Bangor 5096 Inert Storehouse- Bulk
No
AMI NBK-Bangor 5097 Inert
Primary ICS Sub- System
Base Bldg Building Name
If Controllers are Remote
Building Level Controllers
System Protocols include
Notes ICS Wired
Ethernet
BLC in Bldg #
Sensor Ctrler in Bldg #
Type #1
Type #2
Qty #1 #2 #3
Bulk
AMI NBK-Bangor 5098 Inert
Bulk
No
AMI NBK-Bangor 5436 RFI Break
No
AMI NBK-Bangor 5736 In-Service Engineering
No
DDC NBK-Bangor 5936 Compressor Bldg.
DDC NBK-Bangor 5945 Environmental Test Facility
DDC NBK-Bangor 5946 Environmental Test Cells
DDC NBK-Bangor 6002 Equipment Maintenance
SWFPAC No
DDC NBK-Bangor 6006 Radiographic Inspection
DDC NBK-Bangor 6007 Reentry Body Bldg #2
AMI NBK-Bangor 6015 Recharge Bldg R-2
No
DDC NBK-Bangor 6034 Warehouse Storage
DDC NBK-Bangor 6035 Warehouse
DDC NBK-Bangor 6036 Warehouse
DDC NBK-Bangor 6038 High Explosive
SWFPAC Yes
Primary ICS Sub- System
Base Bldg Building Name
If Controllers are Remote
Building Level Controllers
System Protocols include
Notes ICS Wired
Ethernet
BLC in Bldg #
Sensor Ctrler in Bldg #
Type #1
Type #2
Qty #1 #2 #3
DDC NBK-Bangor 6039 High Explosive
DDC NBK-Bangor 6040 High Explosive
DDC NBK-Bangor 6041 High Explosive
DDC NBK-Bangor 6042 High Explosive
DDC NBK-Bangor 6043 High Explosive
DDC NBK-Bangor 6044 High Explosive
DDC NBK-Bangor 6045 High Explosive
DDC NBK-Bangor 6046 High Explosive
DDC NBK-Bangor 6047 High Explosive
DDC NBK-Bangor 6048 High Explosive
DDC NBK-Bangor 6049 High Explosive
6303 6048
DDC NBK-Bangor 6052 Special Weapons
6303 6303
DDC NBK-Bangor 6053 Special Weapons
6300 6302
DDC NBK-Bangor 6054 Guided Missile
6301 6301
DDC NBK-Bangor 6055 Guided Missile
6301 6301
Primary ICS Sub- System
Base Bldg Building Name
If Controllers are Remote
Building Level Controllers
System Protocols include
Notes ICS Wired
Ethernet
BLC in Bldg #
Sensor Ctrler in Bldg #
Type #1
Type #2
Qty #1 #2 #3
AMI NBK-Bangor 6065 EOD Magazine
No
DDC NBK-Bangor 6069 Launcher Equip Process.Bldg.
DDC NBK-Bangor 6079 Hazardous Waste Facility
DDC NBK-Bangor 6200 Guided Missile
6201 6201
DDC NBK-Bangor 6201 Guided Missile
DDC NBK-Bangor 6202 Guided Missile
DDC NBK-Bangor 6203 Guided Missile
DDC NBK-Bangor 6204 Guided Missile
6201 6866
DDC NBK-Bangor 6205 Guided Missile
DDC NBK-Bangor 6206 Guided Missile
DDC NBK-Bangor 6207 Guided Missile
DDC NBK-Bangor 6208 Guided Missile
DDC NBK-Bangor 6209 Guided Missile
DDC NBK-Bangor 6210 Guided Missile
DDC NBK-Bangor 6211 Guided Missile
DDC NBK-Bangor 6212 Guide Missile
6220 6211
Primary ICS Sub- System
Base Bldg Building Name
If Controllers are Remote
Building Level Controllers
System Protocols include
Notes ICS Wired
Ethernet
BLC in Bldg #
Sensor Ctrler in Bldg #
Type #1
Type #2
Qty #1 #2 #3
DDC NBK-Bangor 6213 Guided Missile
6220 6211
DDC NBK-Bangor 6214 Special Weapons
DDC NBK-Bangor 6215 Special Weapons
DDC NBK-Bangor 6216 Special Weapons
DDC NBK-Bangor 6217 Special Weapons
DDC NBK-Bangor 6218 High Explosive
DDC NBK-Bangor 6219 High Explosive
6220 6218
DDC NBK-Bangor 6220 High Explosive
DDC NBK-Bangor 6222 Ordnance
DDC NBK-Bangor 6223 Guided Missile
DDC NBK-Bangor 6224 Guided Missile
DDC NBK-Bangor 6225 Guided Missile
DDC NBK-Bangor 6226 Guided Missile
DDC NBK-Bangor 6227 Guided Missile
DDC NBK-Bangor 6228 Guided Missile 6222
Primary ICS Sub- System
Base Bldg Building Name
If Controllers are Remote
Building Level Controllers
System Protocols include
Notes ICS Wired
Ethernet
BLC in Bldg #
Sensor Ctrler in Bldg #
Type #1
Type #2
Qty #1 #2 #3
Magazine DDC NBK-Bangor 6229 Guided Missile
DDC NBK-Bangor 6233 Motor
DDC NBK-Bangor 6234 Motor
DDC NBK-Bangor 6235 Guided Missile
DDC NBK-Bangor 6236 Guided Missile
DDC NBK-Bangor 6237 Guided Missile
DDC NBK-Bangor 6238 Guided Missile
DDC NBK-Bangor 6239 Guided Missile
DDC NBK-Bangor 6300 Limited Area Guardhouse
DDC NBK-Bangor 6302 Vert Msl Pkging Bldg 2
DDC NBK-Bangor 6303 Vert Msl Pkging Bldg 3
DDC NBK-Bangor 6304 Reaction Force
7701 6222
DDC NBK-Bangor 6350 Maintenance Support Bldg
DDC NBK-Bangor 6401 Engineering Services Bldg
DDC NBK-Bangor 6402 Technical Support Bldg
DDC NBK-Bangor 6403 Sws Supply
Primary ICS Sub- System
Base Bldg Building Name
If Controllers are Remote
Building Level Controllers
System Protocols include
Notes ICS Wired
Ethernet
BLC in Bldg #
Sensor Ctrler in Bldg #
Type #1
Type #2
DDC NBK-Bangor 6575 MSSB
DDC NBK-Bangor 6588 Missile Assy Control Bldg
DDC NBK-Bangor 6589 Inert Comp Processing
DDC NBK-Bangor 6590 LA Eqmt Storage Bldg
DDC NBK-Bangor 6591 Missile Assy Bldg No 1
DDC NBK-Bangor 6592 Missile Assy Bldg No 2
DDC NBK-Bangor 6593 Non-Dest Test/Insp Bldg
DDC NBK-Bangor 6594 Transfer
DDC NBK-Bangor 6595 Re-Entry Body
DDC NBK-Bangor 6596 Ex Components Checkout Bldg
DDC NBK-Bangor 6597 Service
AMI NBK-Bangor 6599 Training
No
DDC NBK-Bangor 6600 Missile Assembly Building 3
AMI NBK-Bangor 6607 Water Supply Pumphouse
No
DDC NBK-Bangor 6810 Missile Motor
6594 6813
Primary ICS Sub- System
Base Bldg Building Name
If Controllers are Remote
Building Level Controllers
System Protocols include
Notes ICS Wired
Ethernet
BLC in Bldg #
Sensor Ctrler in Bldg #
Type #1
Type #2
Qty #1 #2 #3
DDC NBK-Bangor 6811 Missile Motor
DDC NBK-Bangor 6812 Missile Motor
DDC NBK-Bangor 6813 Missile Motor
DDC NBK-Bangor 6814 Missile Motor
DDC NBK-Bangor 6815 Missilemotor
DDC NBK-Bangor 6816 Missile Motor
6594 6820
DDC NBK-Bangor 6817 Missile Motor
DDC NBK-Bangor 6818 Missile Motor
DDC NBK-Bangor 6819 Missile Motor
DDC NBK-Bangor 6820 Missile Motor
DDC NBK-Bangor 6821 Missile Motor
DDC NBK-Bangor 6822 Missile Notor
DDC NBK-Bangor 6823 Missile Motor
DDC NBK-Bangor 6824 Missile Motor
DDC NBK-Bangor 6825 Missile Motor
DDC NBK-Bangor 6826 Missile Motor
6594 6828
DDC NBK-Bangor 6827 Missile Motor 6594 6828
Primary ICS Sub- System
Base Bldg Building Name
If Controllers are Remote
Building Level Controllers
System Protocols include
Notes ICS Wired
Ethernet
BLC in Bldg #
Sensor Ctrler in Bldg #
Type #1
Type #2
Qty #1 #2 #3
Magazine DDC NBK-Bangor 6828 Missile Motor
DDC NBK-Bangor 6829 Missile Motor
DDC NBK-Bangor 6830 Missile Motor
DDC NBK-Bangor 6831 Missile Motor
DDC NBK-Bangor 6832 Missile Motor
6594 6831
DDC NBK-Bangor 6833 Missile Motor
6594 6831
DDC NBK-Bangor 6834 Missile Motor
DDC NBK-Bangor 6835 Missile Motor
6594 6834
DDC NBK-Bangor 6836 Missile Motor
6594 6834
DDC NBK-Bangor 6837 Missile Motor
6594 6839
DDC NBK-Bangor 6838 Missile Motor
DDC NBK-Bangor 6839 Missile Motor
DDC NBK-Bangor 6840 Missile Motor
DDC NBK-Bangor 6841 Missile Motor
DDC NBK-Bangor 6842 Missile Motor
DDC NBK-Bangor 6843 Missile Motor
Primary ICS Sub- System
Base Bldg Building Name
If Controllers are Remote
Building Level Controllers
System Protocols include
Notes ICS Wired
Ethernet
BLC in Bldg #
Sensor Ctrler in Bldg #
Type #1
Type #2
Qty #1 #2 #3
DDC NBK-Bangor 6844 Missile Motor
DDC NBK-Bangor 6845 Missile Motor
DDC NBK-Bangor 6846 Missile Motor
DDC NBK-Bangor 6847 Missile Motor
DDC NBK-Bangor 6848 Missile Motor
DDC NBK-Bangor 6849 Missile Motor
DDC NBK-Bangor 6850 Missile Motor
DDC NBK-Bangor 6851 Missile Motor
DDC NBK-Bangor 6852 Missile Motormagazin e
DDC NBK-Bangor 6853 Missile Motor
DDC NBK-Bangor 6854 Missile Motor
DDC NBK-Bangor 6855 Missile Motor
DDC NBK-Bangor 6856 Missile Motor
DDC NBK-Bangor 6857 Missile Motor
DDC NBK-Bangor 6858 Missile Motor
DDC NBK-Bangor 6859 Missile Motor
Primary ICS Sub- System
Base Bldg Building Name
If Controllers are Remote
Building Level Controllers
System Protocols include
Notes ICS Wired
Ethernet
BLC in Bldg #
Sensor Ctrler in Bldg #
Type #1
Type #2
Qty #1 #2 #3
DDC NBK-Bangor 6860 Missile Motor
DDC NBK-Bangor 6861 Missile Motor
DDC NBK-Bangor 6862 Missile Motor
DDC NBK-Bangor 6863 Missile Motor
DDC NBK-Bangor 6864 Missile Motor
DDC NBK-Bangor 6865 Missile Motor
DDC NBK-Bangor 6866 Missile Motor
DDC NBK-Bangor 6867 Missile Motor
DDC NBK-Bangor 6868 Missile Motor
DDC NBK-Bangor 6869 Missile Motor
DDC NBK-Bangor 6870 Missile Motor
DDC NBK-Bangor 6871 Missile Motor
DDC NBK-Bangor 6872 Missile Motor
DDC NBK-Bangor 7000 Smoking Shelter/B7000/ T32
DDC NBK-Bangor 7001 Sws Maintenance
DDC NBK-Bangor 7003 SUBMART
Primary ICS Sub- System
Base Bldg Building Name
If Controllers are Remote
Building Level Controllers
System Protocols include
Notes ICS Wired
Ethernet
BLC in Bldg #
Sensor Ctrler in Bldg #
Type #1
Type #2
Qty #1 #2 #3
NXS
DDC NBK-Bangor 7029 Transportation
7600 7600
AMI NBK-Bangor 7036 E H W Transfer Switch Bldg
AMI NBK-Bangor 7041 Pump Sta No 1
No
AMI NBK-Bangor 7050 Pump Sta No.
No
AMI NBK-Bangor 7057 Swbsta/ Marg Wharf/ Shore Power
No
AMI NBK-Bangor 7063 Document Shredder
No
DDC NBK-Bangor 7074 Data Processing
AMI NBK-Bangor 7077 Triper Bulk
No
DDC NBK-Bangor 7085 Lower Base Fitness Center
DDC NBK-Bangor 7086 Repair Shop
DDC NBK-Bangor 7089 Hazardous Matl Storage Whse
AMI NBK-Bangor 7100 Service Pier
ICS Network in Bldg 7114.
Switch, radio, and Firewall
Yes
DDC NBK-Bangor 7101 Servc Craft Oper Bldg
Primary ICS Sub- System
Base Bldg Building Name
If Controllers are Remote
Building Level Controllers
System Protocols include
Notes ICS Wired
Ethernet
BLC in Bldg #
Sensor Ctrler in Bldg #
Type #1
Type #2
Qty #1 #2 #3
AMI NBK-Bangor 7109 Covered Boat Mtce Facility
No
AMI NBK-Bangor 7110 Small Engine Repair Shop
No
DDC NBK-Bangor 7111 Parche Building (Detachment Support)
Winder ware
AMI NBK-Bangor 7115 DEVRON FIVE Storage
No
DDC NBK-Bangor 7176 Ammunition Wharf
7702 7177
DDC NBK-Bangor 7177 Waterfront Operations
DDC NBK-Bangor 7191 Carpenter Shop 7702 7177
DDC NBK-Bangor 7203 Subsat
DDC NBK-Bangor 7204 Sub Crew Refit Mess
NBK-Bangor 7427 Sw Pmpg
Station Bldg
DDC NBK-Bangor 7445 Waterfront Security
Metasys 1 Lon Modbus
Metasys is Stand-Alone Yes
AMI NBK-Bangor 7604 Pure Water
No
AMI NBK-Bangor 7659 Sewage Lift Station No. 2
No
AMI NBK-Bangor 7660 Sewage Lift Station No. 1
DDC NBK-Bangor 7717 Engineering
Primary ICS Sub- System
Base Bldg Building Name
If Controllers are Remote
Building Level Controllers
System Protocols include
Notes ICS Wired
Ethernet
BLC in Bldg #
Sensor Ctrler in Bldg #
Type #1
Type #2
Qty #1 #2 #3
Building NXS DDC NBK-Bangor 7801 Deperming
DDC NBK-Bangor 6594 A
Transfer
AMI NBK-Bangor
Service Pier Unit Substation #7
No
AMI NBK-
Bremerton
51 Officers Quarters-51
No
DDC NBK-
Bremerton
59 Chemical/Meta llurgical Fac
1 Network
Firmware upgrade on JACE only.
Yes
DDC NBK-
Bremerton
78 Prod Skls/RADCON
TR &
NESCOM
2 Network
Firmware upgrade on JACE only.
Yes
DDC NBK-
Bremerton
433 Admin/Barrack s
VLX FullBA
DDC NBK-
Bremerton
434 Admin/Sam Adams
AMI NBK-
Bremerton
443 Administrative
No
AMI NBK-
Bremerton
467 General Warehouse/Off ice
No
AMI NBK-
Bremerton
491 Admin Facility
- Old Nhb
No
DDC NBK-
Bremerton
502 Gym/MWR
FullBAC
503 Fire Station
506 Dental/Admin
Primary ICS Sub- System
Base Bldg Building Name
If Controllers are Remote
Building Level Controllers
System Protocols include
Notes ICS Wired
Ethernet
BLC in Bldg #
Sensor Ctrler in Bldg #
Type #1
Type #2
Qty #1 #2 #3
DDC NBK-
Bremerton
515 Port Ops Maint. Bldg.
Bremerton
550 NISMF
No
DDC NBK-
844 Office
846 Exchange
Bremerton
847 Berkmier Hall
(BEQ)
Bremerton
853 FSC/Navy Campus
863 Exchange
864 FFIC
Bremerton
865 Underwood Hall (BEQ)
Bremerton
866 Enlisted Dining
Bremerton
885 Keppler Hall
Bremerton
922 NMCI Server
No
DDC NBK-
Bremerton
942 Nibbe Hall
Bremerton
954 Wycoff Transit Storage Shed
No
DDC NBK-
Bremerton
985 Training
Bremerton
995 Facilities Support
Primary ICS Sub- System
Base Bldg Building Name
If Controllers are Remote
Building Level Controllers
System Protocols include
Notes ICS Wired
Ethernet
BLC in Bldg #
Sensor Ctrler in Bldg #
Type #1
Type #2
Qty #1 #2 #3
DDC NBK-
Bremerton
1000 Shields Hall
Bremerton
1001 Ross Hall
Bremerton
1005 Exch./Bev.
Store
1012 Parking Garage
No
DDC NBK-
Bremerton
1013 Fleet Support
Bremerton
1015 Olympic Lodge
Bremerton
1017 Swimming Pool & Gym
Bremerton
1027 Fleet Recreational Fac
1044 BEQ
JACE-
NSX
2 Network
Bremerton
1105 Park Ave Parking Garage
No
AMI NBK-
1107 Parking Garage
No
DDC NBK-
Bremerton
1108 Fleet Recreational Fac
Firmware upgrade on KMC FullBAC only
AMI NBK-Keyport 1 Torpedo Shop
No
AMI NBK-Keyport 6 Diving Gear Locker
Primary ICS Sub- System
Base Bldg Building Name
If Controllers are Remote
Building Level Controllers
System Protocols include
Notes ICS Wired
Ethernet
BLC in Bldg #
Sensor Ctrler in Bldg #
Type #1
Type #2
DDC NBK-Keyport 12 Admin/Retail
ESPC Yes
AMI NBK-Keyport 15 Quality Evaluation Lab
DDC NBK-Keyport 17 Admin/Rec
JACE
AMI NBK-Keyport 33 Boat Repair
DDC NBK-Keyport 35 Miscellaneous
DDC NBK-Keyport 38 Welding Shop
DDC NBK-Keyport 40 Security Offices
AMI NBK-Keyport 73 Weapons
DDC NBK-Keyport 74 Medical
Apogee
1 Apogee
DDC NBK-Keyport 76 Fire Station
DDC NBK-Keyport 80 ATTC Center
DDC NBK-Keyport 81 Industrial-Lt
1 Lon Modbus
DDC NBK-Keyport 82 Ind-Lt/Admin
Lutron 1 Lon Modbus Lutron ESPC.
Lutron is Stand Alone
DDC NBK-Keyport 84 Industrial-Lt
DDC NBK-Keyport 85 Battery Shop, Torpedo
AMI NBK-Keyport 91 In Process Storehouse
DDC NBK-Keyport 94 Administration
DDC NBK-Keyport 95 Torpedo
Primary ICS Sub- System
Base Bldg Building Name
If Controllers are Remote
Building Level Controllers
System Protocols include
Notes ICS Wired
Ethernet
BLC in Bldg #
Sensor Ctrler in Bldg #
Type #1
Type #2
Qty #1 #2 #3
Support Shop 610 DDC NBK-Keyport 97 Administration
(MWR)
DDC NBK-Keyport 98 Ind-Lt/Lab
Apogee 1 Modbus Apogee Modbus
AMI NBK-Keyport 101 Pumphouse Sewage
No
AMI NBK-Keyport 102 Pumphouse
No
AMI NBK-Keyport 103 Pump House
No
DDC NBK-Keyport 105 MK 48 Torpedo Shop
DDC NBK-Keyport 134 Photo Lab
AMI NBK-Keyport 136 Pumphouse, Fresh Water
No
AMI NBK-Keyport 144 Shipping/Recei ving Facility
No
AMI NBK-Keyport 185 Special Projects Lab
DDC NBK-Keyport 198 Recreation
DDC NBK-Keyport 206 Laboratory
DDC NBK-Keyport 207 Laboratory
AMI NBK-Keyport 221 New Pier 1
DDC NBK-Keyport 233 Machine Shop 38
ESPC No DDC NBK-Keyport 478 Torpedo
Support Fac.
DDC NBK-Keyport 489 Ind-Lt/Food
Primary ICS Sub- System
Base Bldg Building Name
If Controllers are Remote
Building Level Controllers
System Protocols include
Notes ICS Wired
Ethernet
BLC in Bldg #
Sensor Ctrler in Bldg #
Type #1
Type #2
Qty #1 #2 #3
Svcs DDC NBK-Keyport 514 Ind-Lt/Admin
AMI NBK-Keyport 515 Bachelor Enlisted Quarters
No
AMI NBK-Keyport 735 Weapons System
No
DDC NBK-Keyport 811 Engineering Office
AMI NBK-Keyport 820 Special R & D Projects Fac.
No
AMI NBK-Keyport 824 Torpedo
No
DDC NBK-Keyport 825 Ind.Waste Trmt
AMI NBK-Keyport 877 Main Substation
DDC NBK-Keyport 893 Warehouse
DDC NBK-Keyport 894 Industrial-Lt
AMI NBK-Keyport 895 Telephone Terminal Bldg.
No
AMI NBK-Keyport 896 Sewage Lift Station #1
No
AMI NBK-Keyport 897 Sewage Lift Station #2
No
AMI NBK-Keyport 898 Sewage Lift Station #3
DDC NBK-Keyport 916 Security
Primary ICS Sub- System
Base Bldg Building Name
If Controllers are Remote
Building Level Controllers
System Protocols include
Notes ICS Wired
Ethernet
BLC in Bldg #
Sensor Ctrler in Bldg #
Type #1
Type #2
AMI NBK-Keyport 944 Supply Bldg
AMI NBK-Keyport 945 Supply Bldg
No
DDC NBK-Keyport 950 Special Projects R&D
DDC NBK-Keyport 951 Laboratory
DDC NBK-Keyport 1002 Automated
Material Handing
ESPC No
DDC NBK-Keyport 1003 Offices
Lutron 2 Lon Modbus Lutron ESPC. Lutron is Stand Alone Yes
AMI NBK-Keyport 1006 Haz Flammable Matl Storehse
No
DDC NBK-Keyport 1016 Admin/Museu m/ Theater
DDC NBK-Keyport 1050 Combat Sys Facil
Lutron 2 Lon Modbus Lutron ESPC. Lutron is Stand Alone Yes
DDC NBK-Keyport 1051 Hazardous Waste Transshipment
DDC NBK-Keyport 1058 Plating Plant
AMI NBK-Keyport 1059 Travel Office
DDC NBK-Keyport 1074
AMI NBK-Keyport
Switch Station
J-1501000-02
HISTORICAL WORKLOAD QUANTITIY
Annex Spec Item Description Average Annual Quantity
1501000 3 Recurring Work 1501000 3.1 Work Control 1501000 3.1.1 Service Call Reception 25,000 work orders 1501000 3.1.2 Customer Interface Services (Meetings)/Status Requests 300 Status requests/50 meetings 1501000 3.1.3 Work Order Tracking 1,500 requests 1501000 3.12 Infrastructure Condition Assessment Program (ICAP) Services 1501000 3.12.1 Inventory Management 600 changes 1501000 3.12.2 Condition Assessment (Dynamic) 14,000 assets 1501000 3.12.3 Condition Assessment (Non-Dynamic) 747 roofs 1501000 3.23 Technical Support Services 1501000 3.23.1 Plans, Files, and Drawing Updates All associated updates of plans, files and drawings for 250 projects (range from simple single drawing updates to large projects with multiple updates)
1501000 3.23.2 Technical Library Operations 1501000 3.23.3 Technical Consulting Services 100 consults 1501000 3.23.4 Engineering Design and Study Support
Facility Activation
Equipment Activation
25 projects
15 facilities (including all associated equipment and utilities for that facility)
100 individual pieces of new equipment (separate from facility activation)
J-1501000-03
ICAP DIRECT CONDITION RATING GUIDANCE
Rating Rating Definition/Direct Condition Rating (DCR) Green (+) Brand new or like brand new, free of observable or known damage. Typically within first year of installation. Entire CIMU or CIMU sample is free of observable or known distress (like new).
Green Component fully functional without damage. One-three years from installation date.
No CIMU or sample serviceability or reliability reduction. Some, but not all, minor (non-critical) subcomponents may suffer from slight degradation OR few major (critical) subcomponents may suffer from slight degradation.
Green (-) Slight or minimal damage/degradation, but fully functional. Over three years of service life. Slight or no serviceability or reliability reduction overall to the CIMU or sample. Some, but not all, minor (non-critical) subcomponents may suffer from minor degradation OR more than one major (critical) subcomponent may suffer from slight degradation.
Amber (+) Some deterioration of minor components with few or no damage of major components but functioning properly. CIMU or sample serviceability or reliability is degraded, but adequate. A very few major (critical) subcomponents may suffer from moderate deterioration with perhaps a few minor (non-critical) subcomponents suffering from severe deterioration.
Amber Definite deterioration. Still operating but with minor repairs needed. CIMU or sample serviceability or reliability is definitely impaired. Some, but not a majority, major (critical) subcomponents may suffer from moderate deterioration with perhaps many minor (non-critical) subcomponents suffering from severe deterioration.
Amber (-) Moderate damage/degradation but still functional. CIMU or sample has significant serviceability or reliability loss. Most subcomponents may suffer from moderate degradation OR a few major (critical) subcomponents may suffer from severe degradation.
Red (+) Significant damage/degradation with service life nearing end. Project planned to replace or repair component. Significant serviceability or reliability reduction in CIMU or sample. A majority of subcomponents are severely degraded and others may have varying degrees of degradation.
Red Severe damage/degradation with cracks or holes. Almost not operational but can be serviced or repaired. Severe serviceability or reliability reduction in CIMU or sample such that it is barely able to perform. Most subcomponents are severely degraded.
Red (-) Completely broken with replacement necessary. At end of service life and unsalvageable. Safety hazard. Overall CIMU degradation is total. Few, if any, subcomponents are salvageable. Complete loss of CIMU or sample serviceability.
J-1501000-04
UNIFORMAT TABLE
See separate file.
J-1501000-05
NON-DYNAMIC ROOF ASSETS
See separete file.
J-1501000-06
TECHNICAL LIBRARY INVENTORY
See separate file.