68-REV 1.19.26 16160 Panelboards.pdf

PDF 97 KB Posted

Attached to
Route 54 Sanitary Sewer Extension Project
Solicitation number
Not on record
Issued by
Lycoming County, Pennsylvania

About this file

This is a technical specification document for panelboards required for the Route 54 Sanitary Sewer Extension Project, Contract No. WB-1, issued by the West Branch Regional Authority in Clinton Township, Lycoming County, Pennsylvania. The project involves the construction of approximately 1,520 linear feet of gravity sanitary sewer, 11 manholes, 13 lateral connections, one duplex sewage pumping station, 404 linear feet of force main, and one stream crossing. Sealed bids for this project will be received online at http://pennbid.net/ until 1:00 PM local prevailing time on Monday, February 16, 2026. The specification details requirements for branch circuit panelboards manufactured by acceptable vendors including Square D, Eaton, or GE, which must comply with UL 67 standards and NFPA 70 National Electrical Code requirements. Panelboards shall include copper buses, thermal magnetic circuit breakers with minimum 22,000 ampere RMS ratings at 240 volts, concealed hinges, locking doors, and separate grounding terminal buses. Outdoor panelboards must be housed in NEMA 4X stainless steel enclosures. Installation requirements specify that panelboards be mounted no higher than 78 inches above finished grade to the top breaker handle and include typed circuit directory labels on the inside cover.

All work performed on this contract is subject to prevailing minimum project wage rates as established by the Pennsylvania Department of Labor and Industry. Each bid must be accompanied by a certified check, bank check, or bid bond equal to ten percent of the total bid amount. The contractor is subject to the provisions of the Pennsylvania Steel Products Procurement Act of 1978. Prospective bidders are urged to register with PennBid as plan holders to receive periodic updates regarding addenda, plan holder lists, and other bidding information. Bid documents are available exclusively through the PennBid website, and neither the owner nor the engineer will be responsible for documents obtained from other sources.

View the file

Other files

File Type Posted
63-REV 1.19.26 16000 Elect Gen Prov.pdf PDF
17-00700 Gen Cond.pdf PDF
31-01600 Mat and Equp.pdf PDF
4-00250 Experience Equipmt and Finan Stmt.pdf PDF
52-05900 Miscelanous Metals.pdf PDF
47-02820 Topsoil Seeding.pdf PDF
14-00660 Form Change Order No 1.pdf PDF
1-1 CD COVER.pdf PDF
36-02000 Site Wrk.pdf PDF
42-02310 Horizontal DD.pdf PDF
7-00630 Public Verification Form.pdf PDF
26-01340 Shop Draw.pdf PDF
70-REV 1.19.26 16402 Underground Construction.pdf PDF
27-01380 Construct Photos.pdf PDF
50-03200 Concrete Reinforcement.pdf PDF
11-00610 Release of Lien.pdf PDF
32-01700 Cont Close.pdf PDF
24-01090 Ref Stand.pdf PDF
8-00350 Non-Discrimination.pdf PDF
66-REV 1.19.26 16130 Boxes.pdf PDF
56-15015 NonPress PVC.pdf PDF
30-01570 Traffic Reg.pdf PDF
38-02110 Demolition.pdf PDF
69-REV 1.19.26 16161 Grounding.pdf PDF
60-15100 Basic Req Plumb Wrk.pdf PDF
10-00600 Bonding Forms.pdf PDF
34-01720 Proj Rec Doc.pdf PDF
67-REV 1.19.26 16140 Wiring Devices.pdf PDF
64-REV 1.19.26 16111 Conduit.pdf PDF
44-02600 Paving Surface.pdf PDF
53-09900 Painting.pdf PDF
48-02900 Landscaping.pdf PDF
46-02710 Chain Link Fence.pdf PDF
62-15136 Basic Pip Mat and Meth.pdf PDF
5-00300 Bid Form.pdf PDF
61-15115 Supp and Anchors.pdf PDF
35-01740 Warranty and Bonds.pdf PDF
3-00200 Instructions to Bidders.pdf PDF
51-03300 Cast in Place.pdf PDF
37-02102 Clear Grub.pdf PDF
58-2 TOC.pdf PDF
21-01000 Summ of Work.pdf PDF
18-00800 Supp Cond.pdf PDF
45-02607 Manholes.pdf PDF
55-11930 Pump Equp.pdf PDF
71-REV 1.19.26 16511 Led Exterior Lighting.pdf PDF
19-Wage Rates.pdf PDF
41-02300 HDPE Pipe.pdf PDF
15-00670 Payment Application.pdf PDF
49-03100 Concrete Formwork.pdf PDF
Show 40 more

Latest 50 of 75 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SECTION 16160

PANELBOARDS DIVISION 16

West Branch Regional Authority 16160-1 January 2026 Route 54 Sanitary Sewer Extension Project Panelboards Contract No. WB-1

PART 1 - GENERAL

1.01 WORK INCLUDED

A. Branch circuit panelboards.

1.02 REFERENCE STANDARDS

A. National Fire Protection Association (NFPA)

1. NFPA 70: National Electrical Code (NEC)

B. Underwriters' Laboratories, Inc. (UL)

1. UL 67: Panelboards, Electric

1.03 REQUIREMENTS OF REGULATORY AGENCIES

A. Construct panelboards to UL 67 standards and provide UL labels.

B. Panelboards shall comply with all requirements of the NFPA 70.

1.04 SUBMITTALS

A. Product Data: Submit under provisions of Section 01340: Shop Drawings, Product Data and Samples.

PART 2 - PRODUCTS

2.01 ACCEPTABLE MANUFACTURERS

A. Square D, Eaton, GE.

2.02 PANELBOARDS

A. Panels shall be mounted as indicated on the Drawings, complete with panel trim having concealed hinges and trim mounted screws. Provide locking door with flush catch.

Panelboards shall include service label where used as service entrance equipment.

B. Keys: Provide two keys for each panel. Make keys interchangeable for panels of same voltage.

C. Buses in all single compartment panels shall be sized in strict accordance with the requirements of Underwriters' Laboratories and shall be copper.

D. Circuit breakers in panelboards shall be balanced over the two phases. Circuit numbers

West Branch Regional Authority 16160-2 January 2026 shown on the Drawings do not necessarily indicate the circuit breaker number in the panelboard. Branch circuits shall be connected to circuit breakers in panels as necessary to balance the system, and as required by the National Electrical Code.

E. Spare circuits are provided in the panelboards. In all cases, circuit breakers shall be provided for the spare circuits. Spaces indicated shall have all bus provisions, etc., so that future circuit breakers can be readily installed.

F. All Distribution and Branch Circuit panels shall contain a separate grounding terminal bus.

The grounding bus shall be uninsulated brazed or bolted to the cabinet.

2.03 CIRCUIT BREAKERS

A. Circuit breakers in panels shall be as described hereinafter and as indicated on the panelboard schedule.

B. Circuit breakers shall have minimum A.I.C. ratings of 22,000 ampere RMS for 240 volt, or as indicated on the Drawings.

C. Circuit breakers shall be thermal magnetic and shall be of the bolt-on type.

D. The circuit breakers shall have inverse-time-element characteristics so that tripping will be prevented on momentary overloads but will occur before dangerous values are reached.

E. The breakers shall be operable in any position and removable from the front of the panelboard without disturbing adjacent units. Units shall be bolt-on type.

F. Each branch circuit shall be distinctly numbered. The mechanism shall trip free from the handle so that contacts cannot be held closed against short circuit or abnormal overloads.

G. Automatic tripping of all breakers shall be by means of a common trip. Tie-handles will not be permitted for multiple pole breakers.

2.04 PANELBOARD CABINETS

A. Panel fronts shall be of code gauge sheet steel, and have flush, brushed stainless steel cylinder tumbler-type locks. Fronts shall have adjustable-indicating trim clamps which shall be completely concealed when doors are closed. Doors shall be mounted completely by concealed steel hinges. Fronts shall not be removable with door in locked position.

B. Where panels are required to be constructed in two or more separate sections, the boxes shall be of the same height. Boxes shall be arranged for mounting side-by-side, with conduit between. Panelboard fronts shall each overlap channel and shall butt together at center.

C. Panelboards located outdoors and not housed in a separate cabinet shall include a Nema

West Branch Regional Authority 16160-3 January 2026

4X stainless enclosure.

D. The panelboards and cabinets shall conform to the requirements of the Underwriters'

Laboratories and shall bear their label.

PART 3 - EXECUTION

3.01 INSTALLATIONS

A. Provide mounting brackets, busbar drillings, and filler pieces for unused spaces.

B. Prepare and affix typed directory to inside cover of panelboard indicating loads controlled by each circuit. Handwritten directories are not acceptable.

C. Balance the load of each panel as required.

D. Install panelboards in enclosures or as otherwise indicated on Drawings. Panelboards shall be mounted no higher than 78”AFF/AFG to the top breaker handle in panelboard.