This is a technical specification document for the Route 54 Sanitary Sewer Extension Project, Contract No. WB-1, issued by the West Branch Regional Authority in Pennsylvania. The project encompasses the construction of approximately 1,520 linear feet of gravity sanitary sewer, 11 manholes, 13 lateral connections, one duplex sewage pumping station, 404 linear feet of force main, and one stream crossing located within easements on private property and Snaurytown Road right-of-way in Clinton Township, Lycoming County, Pennsylvania. The specification details all conduit requirements including rigid metal conduit, intermediate metal conduit (IMC), electrical metallic tubing (EMT), flexible metal conduit, liquid-tight flexible conduit, aluminum conduit, non-metallic plastic conduit, and associated fittings and supports. Sealed bids were to be received online at http://pennbid.net/ until 1:00 PM on Monday, February 16, 2026. The document specifies installation standards, support spacing requirements (maximum 5 feet on centers), clearance requirements (minimum 6 inches from piping, 12 inches from heat sources), and conduit routing protocols to maintain safety and operational integrity.
The specification establishes comprehensive product standards requiring all conduit and fittings to be UL listed and compliant with the National Fire Protection Association (NFPA) National Electric Code (NEC), with minimum conduit size of 3/4-inch unless otherwise specified on drawings. Each bid must be accompanied by a certified check or bid bond equal to ten percent (10%) of the total bid amount as security for proper execution. The project is subject to Pennsylvania prevailing minimum wage rates as established by the Pennsylvania Department of Labor and Industry and the provisions of the Pennsylvania Steel Products Procurement Act of 1978, P.L. 6, as amended. Contractors must register as plan holders with PennBid to receive periodic updates on addenda and project information, with bid documents only available through this designated platform.
View the file
Other files
Show 40 more
Latest 50 of 75 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SECTION 16111
CONDUIT DIVISION 16
West Branch Regional Authority 16111-1 January 2026 Route 54 Sanitary Sewer Extension Project Conduit Contract No. WB-1
PART 1 - GENERAL
1.01 WORK INCLUDED
A. Rigid metal conduit and fittings.
B. Intermediate metal conduit and fittings.
C. Electrical metallic tubing and fittings.
D. Flexible metal conduit and fittings.
E. Liquid tight flexible metal conduit and fittings.
F. Aluminum conduit and fittings.
G. Non-metallic conduit and fittings.
H. Conduit supports.
I. Underground duct non-metallic conduit and fittings.
J. Conduit supports.
1.02 RELATED WORK
A. Section 02205: Earthwork for Pipelines: Excavation and backfill for conduit and utilities on site.
B. Section 03300: Cast-In-Place Concrete: Protective envelope for underground conduit installations.
C. Section 16120: Wires And Cables.
1.03 REFERENCE STANDARDS
A. National Fire Protection Association (NFPA):
1. NFPA-70 - National Electric Code (NEC)
B. Underwriters Laboratories, Inc. (UL):
1. UL-1 - Conduit, Electric, Flexible Metal
2. UL-6 - Rigid Metal Conduit
C. American National Standards Institute (ANSI)/National Electrical Manufacturer's
Association (NEMA):
1. ANSI/NEMA FB 1 - Fittings and Supports for Conduit and Cable Assemblies
D. National Electrical Manufacturer's Association (NEMA):
1. NEMA TC 2 - Electrical Plastic Tubing (EPT) and Conduit (EPC-40 and EPC-80)
2. NEMA TC 3 - PVC Fittings for Use with Rigid PVC Conduit and Tubing
West Branch Regional Authority 16111-2 January 2026
PART 2 - PRODUCTS
2.01 GENERAL
A. All conduit and fittings shall be UL listed, in accordance with the NFPA (NEC), and as hereinafter specified.
B. Size: Minimum size of conduit shall be: 3/4-inch. Size shall be in accordance with the
NEC, but not less than shown on the Drawings.
2.02 RIGID METAL CONDUIT AND FITTINGS
A. Rigid Steel Conduit: Comply with ANSI C80.1 or FS WW-C-581, threaded galvanized steel conduit.
B. Fittings and Conduit Bodies: ANSI/NEMA FB 1; threaded type, material to match conduit.
2.03 INTERMEDIATE METAL CONDUIT (IMC) AND FITTINGS
A. Conduit: Comply with ANSI C80.1 or FS WW-C-581, threaded galvanized steel conduit.
B. Fittings and Conduit Bodies: ANSI/NEMA FB 1; use fittings and conduit bodies specified above for rigid steel conduit.
2.04 ELECTRICAL METALLIC TUBING (EMT) AND FITTINGS
A. EMT: Comply with ANSI C80.1 or FS WW-C-581 non-threaded galvanized steel tubing.
B. Fittings and Conduit Bodies: ANSI/NEMA FB 1; steel or malleable iron, compression type.
SET SCREW TYPE WILL NOT BE PERMITTED.
2.05 FLEXIBLE METAL CONDUIT AND FITTINGS
A. Conduit: FS WW-C-566; steel.
B. Fittings and Conduit Bodies: ANSI/NEMA FB 1.
2.06 LIQUID TIGHT FLEXIBLE CONDUIT AND FITTINGS
A. Conduit: Flexible galvanized steel conduit with extruded liquid tight polyvinyl chloride (PVC) jacket.
1. Provide with a continuous copper bonding conductor wound spirally between convolutions.
West Branch Regional Authority 16111-3 January 2026
B. Fittings and Conduit Bodies: All fittings and conduit bodies connecting to liquid tight flexible conduit shall be PVC.
2.07 NON-METALLIC PLASTIC CONDUIT AND FITTINGS
A. Conduit: NEMA TC 2; Schedule 40 or 80 PVC.
B. Fittings and Conduit Bodies: NEMA TC 3.
2.08 CONDUIT CLAMPS & STRAPS AND SUPPORTS
A. Conduit Clamps and Straps: Shall be made of same general material as conduit. All bolts, nuts, screws and fasteners in general shall be stainless steel.
B. Supports: See Specification Section 16000: Electrical General Provisions.
PART 3 - EXECUTION
3.01 INSTALLATION - CONDUIT SYSTEMS
A. Coordinate installation of conduit in masonry work. Conduit shall be concealed above vinyl or ACT ceilings and exposed on walls.
B. All conduits terminating at floor mounted equipment shall be installed in or beneath the floor slab. Coordinate with the suppliers of all floor mounted equipment and the installing Contractor so as to stub up all conduits at the equipment's electrical enclosure or device.
Provide flexible liquid tight conduit from the stub up to the equipment enclosures or device.
C. Arrange conduit to maintain headroom and present a neat appearance.
D. Route exposed conduit and conduit above accessible ceilings parallel and perpendicular to walls and adjacent piping.
E. Maintain minimum 6-inch clearance between conduit and piping. Maintain minimum 12-inch clearance between conduit and heat sources such as flues, steam pipes, and heating appliances.
F. Support conduit at a maximum of 5 feet on centers.
G. Arrange conduit supports to prevent distortion of alignment by wire pulling operations.
Fasten conduit using straps, lay-in adjustable hangers, clevis hangers, or bolted split stamped fiberglass hangers.
West Branch Regional Authority 16111-4 January 2026
H. Group conduit in parallel runs where practical and use conduit rack constructed of steel or fiberglass channel with conduit straps or clamps. Provide space for twenty-five (25%) percent additional conduit.
I. For exposed single runs, attach surface mounted conduit with clamps. Use of perforated iron straps will not be permitted.
J. Cut conduit square using a saw or pipe cutter; de-burr cut ends.
K. Bring conduit to the shoulder of fittings and couplings and fasten securely.
L. Use conduit hubs for fastening conduit to cast boxes.
M. Install no more than the equivalent of three 90-degree bends between boxes.
N. Alter conduit routing to avoid structural obstructions, minimizing crossovers. Use conduit bodies to make sharp changes in direction, as around beams.
O. Use hydraulic one-shot conduit bender or factory elbows for bends in conduit larger than 2-inch size.
P. Do not install conduit in concrete slabs, less than 4 inches thick. Conduit in floor slabs shall be covered with not less than 2 inches of concrete.
Q. Install conduit free from dents and bruises. Use suitable conduit caps to protect installed conduit against entrance of dirt and moisture.
R. Clean out conduit before installation of conductor.
S. Route conduit through roof openings for piping and ductwork where possible; otherwise, route through roof jack with pitch pocket.
T. Where conduit penetrates fire-rated walls and floors, seal opening around conduit with UL listed foamed silicone elastomer compound or other fire resistive compound with a rating equal to the rating of wall or floor being penetrated.
U. Install UL approved expansion fittings complete with grounding jumpers where conduits cross building expansion joints. Provide bends or offsets in conduit adjacent to building expansion joints where conduit is installed above suspended ceilings.
V. Seal conduit entering or leaving chemical areas with proper fittings.
W. All empty conduits shall be provided with No. 14 gauge galvanized fish wire.
X. Horizontal runs of conduit are not permitted in walls or partitions.
West Branch Regional Authority 16111-5 January 2026
Y. All conduits shall be watertight. Any conduit with water within it shall be corrected by the electrical contractor.
Z. Provide a detectable electrical warning ribbon above the top of all direct buried conduits.
AA. Conduits stubbing up through floors and walls (below grade) shall be provided with sleeved link seals. See link seal details on Drawings.
3.02 CONDUIT TYPE AND USE SCHEDULE
A. Utilize rigid Schedule 40 PVC conduit in outdoor concrete pads, slabs, ductbanks, in or below concrete floors and in direct buried applications unless otherwise noted on the Drawings or in the specifications. Install top of direct buried conduits a minimum of 24” below finished grade unless otherwise noted. Utilize Schedule 80 PVC for all exterior exposed raceways.
B. Utilize Schedule 40 PVC conduit for all raceways installed in all vaults and well pump houses. Flexible raceways in these areas shall be liquid-tight flexible non-metallic.
C. Utilize intermediate metallic conduit (IMC) in concrete filled block walls.
D. Utilize electrical metallic tubing in metal stud cavity walls and above finished ceilings. EMT shall be utilized in the Municipal Building for all interior raceways with compression type fittings.
E. Make connections to motors and equipment subject to vibration with PVC jacketed flexible liquid tight conduit. Utilize PVC liquid tight connectors as manufactured by Carlon or approved equal. Connectors containing malleable iron and steel components are not acceptable. PVC jacketed flexible liquid tight conduit shall not be utilized for any other type of connection or installation. The minimum size for motor connections shall be 1/2- inch.
F. Flexible metal conduit shall be used for final connections to lighting fixtures. Connections shall not exceed 6'-0" for light fixtures.
G. Make connections to motors and equipment subject to vibration and located in hazardous areas with stainless steel-braided flex couplings rated for the area in which they are being installed.
3.03 UNDERGROUND INSTALLATION
A. Install top of conduit, minimum 24 inches below finished grade, unless otherwise indicated.
B. Install conduit with minimum grade of 4 inches per 100 feet.
C. Install warning marker tape 12”BFG directly above all raceways.