50-03200 Concrete Reinforcement.pdf

PDF 113 KB Posted

Attached to
Route 54 Sanitary Sewer Extension Project
Solicitation number
Not on record
Issued by
Lycoming County, Pennsylvania

About this file

This is a Concrete Reinforcement specification document for the Route 54 Sanitary Sewer Extension Project (Contract No. WB-1) under the West Branch Regional Authority in Pennsylvania. The specification details materials and installation requirements for reinforcing steel bars, welded steel wire fabric, support chairs, bolsters, bar supports, and spacers for cast-in-place concrete. Key material specifications include ASTM A615 60 ksi yield grade billet-steel deformed bars in uncoated finish, ASTM A185 plain type welded steel wire fabric in galvanized finish, and ASTM A82 stirrup steel. The specification requires compliance with industry standards including ACI 315, ACI 318, AWS D1.4, and CRSI Manual of Standard Practice. Contractors must submit shop drawings indicating reinforcement sizes, spacings, locations, quantities, bending schedules, splicing details, and supporting devices, along with mill test certificates for all supplied reinforcing materials. Installation requirements mandate cleaning of reinforcement before concrete placement, proper support and security against displacement, maintenance of specified concrete coverage clearances, and directional wire ties into concrete rather than toward surfaces.

The specification addresses critical installation and splicing procedures, including lap splices in accordance with ACI 318 Class B unless otherwise shown on drawings, weld splices conforming to AWS D1.4 for bars #14 and larger, and welded wire fabric lapped minimum twelve inches plus end-extension. The grouting of reinforcing bars is detailed with specific requirements for hole drilling at one-quarter inch larger than rebar diameter, minimum embedment depth of fifteen times rebar diameter, white-metal finish cleaning, and use of Sika Sikadur 32 Hi-Mod epoxy grout with minimum ambient temperature of 40 degrees Fahrenheit. No rebar-flange couplers or similar devices are permitted without prior written Engineer approval. The specification prohibits heat treatment, rebending, or straightening of reinforcing bars except as specifically approved by the Engineer.

View the file

Other files

File Type Posted
63-REV 1.19.26 16000 Elect Gen Prov.pdf PDF
17-00700 Gen Cond.pdf PDF
31-01600 Mat and Equp.pdf PDF
4-00250 Experience Equipmt and Finan Stmt.pdf PDF
52-05900 Miscelanous Metals.pdf PDF
47-02820 Topsoil Seeding.pdf PDF
14-00660 Form Change Order No 1.pdf PDF
1-1 CD COVER.pdf PDF
36-02000 Site Wrk.pdf PDF
42-02310 Horizontal DD.pdf PDF
7-00630 Public Verification Form.pdf PDF
26-01340 Shop Draw.pdf PDF
70-REV 1.19.26 16402 Underground Construction.pdf PDF
27-01380 Construct Photos.pdf PDF
11-00610 Release of Lien.pdf PDF
32-01700 Cont Close.pdf PDF
24-01090 Ref Stand.pdf PDF
8-00350 Non-Discrimination.pdf PDF
66-REV 1.19.26 16130 Boxes.pdf PDF
56-15015 NonPress PVC.pdf PDF
30-01570 Traffic Reg.pdf PDF
38-02110 Demolition.pdf PDF
69-REV 1.19.26 16161 Grounding.pdf PDF
60-15100 Basic Req Plumb Wrk.pdf PDF
10-00600 Bonding Forms.pdf PDF
34-01720 Proj Rec Doc.pdf PDF
67-REV 1.19.26 16140 Wiring Devices.pdf PDF
64-REV 1.19.26 16111 Conduit.pdf PDF
44-02600 Paving Surface.pdf PDF
53-09900 Painting.pdf PDF
48-02900 Landscaping.pdf PDF
46-02710 Chain Link Fence.pdf PDF
62-15136 Basic Pip Mat and Meth.pdf PDF
5-00300 Bid Form.pdf PDF
61-15115 Supp and Anchors.pdf PDF
35-01740 Warranty and Bonds.pdf PDF
3-00200 Instructions to Bidders.pdf PDF
51-03300 Cast in Place.pdf PDF
37-02102 Clear Grub.pdf PDF
58-2 TOC.pdf PDF
21-01000 Summ of Work.pdf PDF
18-00800 Supp Cond.pdf PDF
45-02607 Manholes.pdf PDF
55-11930 Pump Equp.pdf PDF
71-REV 1.19.26 16511 Led Exterior Lighting.pdf PDF
19-Wage Rates.pdf PDF
68-REV 1.19.26 16160 Panelboards.pdf PDF
41-02300 HDPE Pipe.pdf PDF
15-00670 Payment Application.pdf PDF
49-03100 Concrete Formwork.pdf PDF
Show 40 more

Latest 50 of 75 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SECTION 03200

CONCRETE REINFORCEMENT DIVISION 3

West Branch Regional Authority 03200-1 January 2026 Route 54 Sanitary Sewer Extension Project Concrete Reinforcement Contract No. WB-1

PART 1 - GENERAL

1.01 SECTION INCLUDES

A. Reinforcing steel bars and welded steel wire fabric for cast-in-place concrete.

B. Support chairs, bolsters, bar supports, and spacers for supporting reinforcement.

1.02 RELATED SECTIONS

A. Section 03300: Cast-in-Place Concrete.

1.03 REFERENCES

A. American Concrete Institute (ACI)

1. ACI 315 - Details and Detailing of Concrete Reinforcement.

2. ACI 318 - Building Code Requirements for Reinforced Concrete.

B. American Society for Testing and Materials (ASTM)

1. ASTM A82 - Cold Drawn Steel Wire for Concrete Reinforcement.

2. ASTM A185 - Welded Steel Wire Fabric for Concrete Reinforcement.

3. ASTM A615 - Deformed and Plain Billet-Steel Bars for Concrete Reinforcement.

C. American Welding Society (AWS)

1. AWS D1.4 - Structural Welding Code Reinforcing Steel.

D. Concrete Reinforcing Steel Institute (CRSI)

1. CRSI - Manual of Practice.

2. CRSI 63 - Recommended Practice for Placing Reinforcing Bars.

3. CRSI 65 - Recommended Practice for Placing Bar Supports, Specifications and

Nomenclature.

1.04 QUALITY ASSURANCE

A. Perform concrete reinforcement work in accordance with CRSI Manual of Standard

Practice, and CRSI Documents 63 and 65.

B. Conform to ACI 315 and 318.

West Branch Regional Authority 03200-2 January 2026

1.05 SHOP DRAWINGS

A. Submit Shop Drawings under provisions of Section 01340: Shop Drawings, Product Data and Samples.

B. Indicate sizes, spacings, locations and quantities of reinforcing steel, wire fabric, bending and cutting schedules, splicing, stirrup spacing, and supporting and spacing devices.

1.06 CERTIFICATES

A. Submit mill test certificates of supplied concrete reinforcing, indicating physical and chemical analysis.

PART 2 - PRODUCTS

2.01 MATERIALS

A. Reinforcing Steel: ASTM A615, 60 ksi yield grade billet-steel deformed bars, uncoated finish.

B. Welded Steel Wire Fabric: ASTM A185 plain type; in flat sheets; galvanized finish.

C. Stirrup Steel: ASTM A82.

2.02 ACCESSORY MATERIALS

A. Tie Wire: Minimum 16-gauge annealed type.

B. Chairs, Bolsters, Bar Supports, Spacers: Sized and shaped for strength and support of reinforcement during installation and placement of concrete, including load bearing pad on bottom to prevent base material penetration or vapor barrier puncture.

C. Chairs, Bolsters, Bar Supports, Spacers Adjacent to Architectural Concrete Surfaces:

Plastic coated, plastic tipped, or stainless-steel type; sized and shaped as required.

2.03 FABRICATION

A. Fabricate in accordance with ACI 315.

B. Locate reinforcing splices not indicated on Drawings at points of minimum stress. Indicate location of splices on Shop Drawings.

C. Weld reinforcing bars in accordance with AWS D1.4.

D. Bend reinforcing bars cold using pin sizes in accordance with ACI 318. Do not heat, rebend, or straighten reinforcing bars, unless approved by Engineer for each specific case.

West Branch Regional Authority 03200-3 January 2026

PART 3 - EXECUTION

3.01 INSTALLATION

A. Before placing concrete, clean reinforcement of foreign particles or coatings.

B. Place, support, and secure reinforcement against displacement. Do not deviate from alignment or measurement.

C. Place reinforcement to obtain concrete coverage (clearance from surface) as shown on the

Drawings.

D. Make wire ties so that ends are directed into concrete, rather than toward concrete surfaces.

E. Install welded wire fabric as flat sheets, rather than rolls.

F. The use of rebar-flange couplers, or other similar devices, will not be permitted without prior written approval for each specific joint. Where permitted, use of flange couplers will require either additional bars or an increase in bar size adjacent to the joint.

G. See Drawing notes for other reinforcing requirements.

3.02 SPLICING

A. Lap Splice: Make lap splices in accordance with ACI 318, Chapter 12, Class B, unless shown otherwise on the Drawings.

B. Weld Splice: Make weld splices in accordance with AWS D1.4 for #14 and larger bars, or only if shown on Drawings for other size bars.

C. Welded Wire Fabric: Lap welded wire fabric at least twelve (12) inches plus the end-extension of wires.

3.03 GROUTING REINFORCING BARS

A. Drill hole to one-quarter (1/4) inch larger than the rebar diameter.

B. Use carbide tip bit or star bit. Core drilling is not acceptable unless sides of hole are sandblasted after drilling is complete.

C. Depth of Embedment: Minimum fifteen (15) times rebar diameter.

D. Use compressed air to clean holes of drilling residue.

E. Thoroughly wet all surfaces of the hole with water. Remove any standing water.

West Branch Regional Authority 03200-4 January 2026

F. Clean rebar to white-metal finish.

G. Use Sika Sikadur 32 Hi-Mod epoxy grout, in accordance with the grout manufacturer's instructions to secure rebar in hole.

H. Do not grout rebar when ambient temperature is less than 40°F.

I. Cure grout in accordance with manufacturer's instructions.