56-15015 NonPress PVC.pdf
PDF 106 KB Posted
- Attached to
- Route 54 Sanitary Sewer Extension Project
- Solicitation number
- Not on record
- Issued by
- Lycoming County, Pennsylvania
About this file
This is a technical specification document for non-pressure PVC pipe materials and installation requirements for the Route 54 Sanitary Sewer Extension Project, Contract No. WB-1, administered by the West Branch Regional Authority in Clinton Township, Lycoming County, Pennsylvania. The project involves approximately 1,520 linear feet of gravity sanitary sewer installation, 11 manholes, 13 lateral connections, one duplex sewage pumping station, 404 linear feet of force main, and one stream crossing, all with required surface restoration and appurtenances. The contractor must furnish, install, test, and place in operation polyvinyl chloride (PVC) non-pressure piping in diameters ranging from 4 inches to 36 inches, with standard laying lengths of 20 feet and 12.5 feet, subject to ASTM specifications D3034 and F794. Sealed bids were to be received online at http://pennbid.net/ by 1:00 PM local prevailing time on Monday, February 16, 2026. All buried PVC pipe must be marked with underground utility marking tape placed 9 to 12 inches below finished grade.
All PVC pipe and fittings must meet specified ASTM standards and undergo rigorous testing including drop impact tests, joint tightness tests per ASTM D3212, flattening tests, and pipe stiffness evaluations. Gaskets shall be Nitrate or Vitron O-ring material, and pipe assembly must accommodate contraction and expansion at each joint. Installation must comply with ASTM D2321 and the West Branch Regional Authority's Standard Specifications for Extensions of and Connections to the Sanitary Sewer System (April 2014). Each bid must be accompanied by a certified check or bid bond equal to ten percent (10%) of the total bid amount. The Contractor is subject to the Pennsylvania Steel Products Procurement Act of 1978 and prevailing wage requirements established by the Pennsylvania Department of Labor and Industry.
View the file
Other files
Show 40 more
Latest 50 of 75 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SECTION 15015
NON-PRESSURE PVC PIPE DIVISION 15
West Branch Regional Authority 15015-1 January 2026 Route 54 Sanitary Sewer Extension Project Non-Pressure PVC Pipe Contract No. WB-1
PART 1 - GENERAL
1.01 DESCRIPTION OF WORK
A. Scope
1. The Contractor shall provide all plant, labor, and material required to furnish, install, test, and place in operation the polyvinyl chloride (PVC) nonpressure piping required for the Project, as set forth on the Drawings and in accordance with this section of the Specifications.
2. The provisions of this section shall apply to all PVC nonpressure pipe and piping systems specified in this Division or presented on the Drawings.
3. All buried service non-pressure PVC pipe shall be marked using underground utility marking tape.
B. Related Work Specified Elsewhere in Contract Documents
1. Trench excavation, bedding, backfill, and related pipe installation work are described in Section 02205: Earthwork for Pipelines.
2. Section 15070: Piping System Appurtenances.
3. Appendix No. 1 - Standard Specifications for Extensions of and Connections to the West Branch Regional Authority Sanitary Sewer System, April 2014.
1.02 QUALITY ASSURANCE
A. Refer to requirements in Appendix No. 1 - Standard Specifications for Extensions of and Connections to the West Branch Regional Authority Sanitary Sewer System, April 2014.
1.03 SUBMITTALS
PART 2 - PRODUCTS
2.01 GENERAL
West Branch Regional Authority 15015-2 January 2026
2.02 PVC NONPRESSURE PIPE, 4"-15" IN DIAMETER
A. Scope - This specification designates general requirements for unplasticized polyvinyl chloride (PVC) Plastic Gravity Sewer Pipe with integral wall bell and spigot joints for the conveyance of domestic sewage and storm water.
B. Materials - Pipe and fittings shall meet the requirements of ASTM Specification D3034 for
4"-15" SDR 35 and F794 for 18"-36".
C. Pipe - Pipe shall be suitable for use as a gravity sewer/drain conduit. Provisions must be made for contraction and expansion at each joint with O-ring. The bell shall consist of an integral wall section with a solid cross-section O-ring, factory assembled, securely locked in place to prevent displacement during assembly. Sizes and dimensions shall be as shown in this specification. Standard laying lengths shall be 20 ft. and 12.5 ft. 1 inch. At manufacturers option, random lengths of not more than 15% of total footage of each size may be shipped in lieu of standard lengths.
D. Gasket Material: Pipe and pipe fittings shall be provided with Nitrate or Vitron O-ring gaskets.
E. Drop Impact Test - Pipe (6" long section) shall be subjected to impact from a free-falling tup (20-lb. Tup A.) in accordance with ASTM Method of Test D2444. No shattering or splitting (denting is not a failure) shall be evident when the following energy is impacted:
Nominal Size
Inches Ft.-Lbs.
4 150 6 210 8 210 10 220 12 220 15 220 18 220 21 220 24 220 27 220
F. Fittings - All fittings and accessories shall be as manufactured and furnished by the pipe supplier or approved equal and have bell and/or spigot configurations compatible with that of the pipe.
G. Temperature for Testing - Pipe shall be designed to pass all tests at 73oF.
West Branch Regional Authority 15015-3 January 2026
H. Pipe Stiffness - Minimum Pipe Stiffness f’cy at 5% deflection shall be tested in accordance with ASTM Method of Test D24-12, External Loading Properties of Plastic Pipe by Parallel- Plate Loading.
I. Joint Tightness - Two sections of pipe shall be assembled in accordance with the manufacturer’s recommendation. Joint shall be tested in accordance with ASTM D3212, Joints for Drain and Sewer Plastic Pipe Using Flexible Elastomeric Seals.
J. Flattening - There shall be no evidence of splitting, cracking, or breaking when the pipe is tested as follows:
Flatten specimen of pipe, six inches long between parallel plates in a suitable press until the distance between the plates is forty percent of the outside diameter of the pipe. The rate of loading shall be uniform and such that the compression is completed within two to five minutes.
PART 3 - EXECUTION
3.01 STORAGE AND HANDLING
Connections to the West Branch Regional Authority Sanitary Sewer System, April 2014
3.02 INSTALLATION OF PIPE
A. All PVC nonpressure pipe shall be installed in accordance with ASTM D2321, and the requirements set forth in Appendix No. 1 - Standard Specifications for Extensions of and Connections to the West Branch Regional Authority Sanitary Sewer System, April 2014 and on the Drawings.
B. All buried PVC pipe shall be marked using underground utility marking tape. Tape shall be 3 inches wide, placed 9" to 12" below finished grade and be 5.0 mil polypropylene film printed with “Caution Buried Sewer Line Below”.