SZCQ139904_FP-102_addendum2.pdf
PDF 358 KB Posted
- Solicitation number
- W912TF15R0500
About this file
SZCQ139904_FP-102_addendum2
View the file
Other files
Show 40 more
Latest 50 of 79 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1A
1B
1C
5A 5B
8A C
7B 7A
12 14
A
24A
27C 23A
27B 27A
D
23B
15 17
3940A
40B
39A 39B
40D
40C
B
32D 32C
43B
43C
1 2 3 4 5 6 7
J
H
G
F
E
D
C
B
A'
B'
C'
14' 15'12'10'
D'
E'
F'
G'
9'
8'7'5'3'2' 6'4'
11' 13'
PROVIDE NEW SPRINKLER
SYSTEM FOR ENTIRE NEW
TAIL DOCK SEE NOTE 5.
MODIFY EXISTING
SPRINKLERS IN
RENOVATED AREA
CUT AND CAP BRANCH LINES FROM
EXISTING AIRCRAFT BAY SPRINKLER
SYSTEM. DEMOLISH EXISTING
SPRINKLERS AND PIPING
SPRINKLER ZONE #3
SPRINKLER
ZONE #1
SPRINKLER
ZONE #2
SPRINKLER ZONE #2
SPRINKLER ZONE #3
EXISTING
SPRINKLER
SYSTEM TO
REMAIN.
NEW DRAFT
CURTAIN
STORAGE
42D
ELEC
INVERTER ROOM
43A
PROPULSION,
REPAIR, AND
RECLAMATION
SECTION
CTK
CTK
42B
AMXS READY
ROOM
11A
AMXS TRAINING
ROOM
11F
AMXS READY
ROOM
AMXS
SUPERVISION
FLIGHT CHIEF
11B
FLIGHT CHIEF
11C
FLIGHT CHIEF
11D
FLIGHT CHIEF
11E
MODIFY
EXISTING
SPRINKLERS IN
RENOVATED
AREA
EXISTING DRAFT
CURTAIN
EXISTING DOOR HEADER
PROVIDES REQUIREMENT FOR
DRAFT CURTAIN
EXISTING DOOR HEADER
PROVIDES REQUIREMENT FOR
DRAFT CURTAIN
FIRE SUPPRESSION NOTES
EXPAND AND MODIFY THE EXISTING SPRINKLER SYSTEMS OF THE HANGAR
BAY AS SHOWN ON THE DRAWINGS AND IN THE SPECIFICATIONS.
MODIFY THE EXISTING WET PIPE SPRINKLER SYSTEMS FOR THE SHOPS AND
OFFICES AS INDICATED ON THE DRAWINGS AND IN THE SPECIFICATIONS.
PROVIDE SPRINKLER GUARDS FOR SPRINKLERS WHERE THEY ARE
INSTALLED IN AREAS SUBJECT TO PHYSICAL DAMAGE, INCLUDING BUT NOT
LIMITED, MECHANICAL ROOMS, STORAGE, AND MAINTENANCE AREAS.
SEE PROJECT SPECIFICATIONS FOR ADDITIONAL INFORMATION NOT SHOWN
ON THE DRAWINGS.
PROVIDE DESIGN DENSITY OF 0.20 GPM/SQFT OVER DESIGN AREA OF 5,000
SQUARE FEET FOR EXISTING SYSTEM IN MAIN PORTION OF HANGAR.
1.
2.
3.
4.
5.
HANGAR AREA: SYSTEM PROVIDING A
DENSITY OF 0.20 GPM/SQFT. OVER DESIGN
AREA OF 5,000 SQUARE FEET
HC-2: SYSTEM PROVIDING A DENSITY OF
0.20 GPM/SQFT. OVER DESIGN AREA OF
2,500 SQUARE FEET
SPRINKLER DESIGN HATCH LEGEND
PEASE AIR BASE
NEW HAMPSHIRE
NATIONAL GUARD Project
Client
Drawing
NEW HAMPSHIRE AIR NATIONAL GUARD
REVISIONS
Description
Drawn by
Designed by
Scale
Date
Project No.
Approved by
Checked by No. Date
SheetAS SHOWN
Stamp
B-2 SUBMITTAL1 08/15/14
B-3 SUBMITTAL2 11/21/14
B-3 RESUBMITTAL3 12/31/14
ADDENDUM 24 02/25/15
FP-102
FIRE SUPPRESSION ZONING PLAN
25 FEBRUARY 2015
S. MILLER
S. BLOCK
M. MEADE
M. AARON
SZCQ139904
KC-46A ADAL MAINTENANCE HANGAR, BUILDING 254
PEASE AIR NATIONAL GUARD BASE, NEW HAMPSHIRE
0' 3' 10' 20' 40'
PLAN
NORTH
SCALE: 1" = 20'-0"
FIRE SUPPRESSION ZONING PLAN
4 4