HEF GENERATOR
(TYP)
HEF GENERATOR
(TYP)
1 2 3 4 5 6 7
J
H
G
F
E
D
C
B
A'
B'
C'
14' 15'12'10'
D'
E'
F'
G'
9'
8'7'5'3'2' 6'4'
11' 13'
EXPECTED HEF FOAM
COVERAGE AT 1 MINUTE
MEN'S LOCKER
ROOM
MEN'S
RESTROOM
16A
WOMEN'S
RESTROOM/LOCKER
ROOM
WOMEN'S ABA
RESTROOM
AMXS READY
ROOM
AMXS
SUPERVISION
FLIGHT CHIEF
11B
FLIGHT CHIEF
11C
FLIGHT CHIEF
11D
FLIGHT CHIEF
11E
AMXS READY
ROOM
11A
AMXS TRAINING
ROOM
11F
CTK
CTK
42B
HANGAR
AMXS
COMMANDER
1A
DEPUTY MXG
COMMANDER
1B
MXG
COMMANDER
1C
MXG
CONFERENCE
ROOM
1 MXS COMMANDER
COMMAND
SUPPORT STAFF
FIRST
SERGEANTS
MAINTENANCE
SUPERVISION
MECHANICAL
MOF
COMMANDER &
SUPERINTENDENT
5A
MAINTENANCE
OPERATIONS
CENTER
5B
QUALITY
ASSURANCE
SUPERINTENDENT
PLANS &
SCHEDULING
TRAINING
7A
TRAINING
SECTION
7B
QUALITY
ASSURANCE/
TECHNICAL
ORDER OFFICE
CORRIDOR
C
CORRIDOR
D
MXG CLASSROOM
24A
BREAK ROOM
ACCESSORIES
SUPERVISOR
ELECTRO
ENVIRONMENTAL
SHOP
BOTTLE SHOP
23B
ELECTRO
ENVIRONMENTAL
SHOP
BATTERY SHOP
23A
ACCESSORY
STORAGE
27C
BUILD UP ROOM
27B
HYDRAULICS / IFR
CLEANING ROOM
27A
KC-46 TECHNICAL
REPS
MUNITIONS
AMXS
SUPERINTENDENT
PROPULSION,
REPAIR, AND
RECLAMATION
SECTION
STORAGE
42D
ELEC
INVERTER ROOM
43A
SPRINKLER ZONE #3
SPRINKLER
ZONE #1
SPRINKLER
ZONE #2
SPRINKLER ZONE #2
SPRINKLER ZONE #3
EXISTING DRAFT
CURTAIN
NEW DRAFT
CURTAIN
EXISTING DOOR HEADER
PROVIDES REQUIREMENT FOR
DRAFT CURTAIN
EXISTING DOOR HEADER
PROVIDES REQUIREMENT FOR
DRAFT CURTAIN
FIRE SUPPRESSION NOTES
POSITION HEF GENERATORS AT LOCATION SHOWN DRAWING. SEE STRUCTURAL
DRAWINGS FOR MOUNTING DETAIL. IN SOME CASES HEF GENERATOR
DISCHARGE WILL BE DIRECTLY ABOVE BOTTOM CHORD MEMBERS, WHICH IS
ACCEPTABLE.
THE CONTRACTOR SHALL DESIGN AND INSTALL NEW HEF GENERATOR
SUPPORT FRAMING AND CONNECTION, NOT CALLED OUT, IN ACCORDANCE WITH
THE MANUFACTURES RECOMMENDATIONS. THE CONTRACTOR SHALL PERFORM
A SEISMIC ANALYSIS AND PROVIDE LATERAL BRACING IF REQUIRED.
MODIFY THE EXISTING HIGH EXPANSION FOAM SYSTEM TO PROTECT ALL AREAS
OF THE HANGAR BAY AS INDICATED ON THE DRAWINGS AND IN THE
SPECIFICATIONS.
SEE SHEET FP-102 FOR ADDITIONAL ZONING INFORMATION.
SEE PROJECT SPECIFICATIONS FOR ADDITIONAL INFORMATION NOT SHOWN ON
THE DRAWINGS.
PROVIDE SEPARATE CONTROL VALVE, WATERFLOW SWITCH, TEST AND DRAIN
ASSEMBLY FOR EACH PAINT BOOTH OR MEDIA BOOTH. LOCATE THESE ITEMS
OUTSIDE AND NEAR THE BOOTH THEY SERVE.
TWO OF THE JET-X-15A HEF GENERATORS REQUIRED FOR THE HEF SYSTEM
ARE CURRENTLY INSTALLED IN BUILDING 251, AND SHALL BE SALVAGED BY THE
CONTRACTOR FOR RE-USE. CONTRACTOR SHALL UNINSTALL TWO HEF
GENERATORS FROM BUILDING 251 AND USE THEM IN THE HANGAR 254 SYSTEM.
1.
2.
3.
4.
5.
6.
7.
PEASE AIR BASE
NEW HAMPSHIRE
NATIONAL GUARD Project
Client
Drawing
NEW HAMPSHIRE AIR NATIONAL GUARD
REVISIONS
Description
Drawn by
Designed by
Scale
Date
Project No.
Approved by
Checked by No. Date
SheetAS SHOWN
Stamp
B-2 SUBMITTAL1 08/15/14
B-3 SUBMITTAL2 11/21/14
B-3 RESUBMITTAL3 12/31/14
ADDENDUM 24 02/25/15
FP-101
FIRE SUPPRESSION PLAN
25 FEBRUARY 2015
M. AARON
S. BLOCK
M. MEADE
M. AARON
SZCQ139904
KC-46A ADAL MAINTENANCE HANGAR, BUILDING 254
PEASE AIR NATIONAL GUARD BASE, NEW HAMPSHIRE
PLAN
NORTH
SCALE: 1" = 20'-0"
FIRE SUPPRESSION PLAN
0' 3' 10' 20' 40'
4 4