38546 PEASE BLDG 253 PANELBOARD HP-3 (TWO SECTIONS)
FEED FROM RDP-1 MOUNTING SURFACE
CKT. CKT. BKR. LOAD CKT. BKR. CKT.
NO. TRIP/POLE KVA A B C KVA TRIP/POLE NO.
1 15 3 AC-3 1.3 3.0 1.6 CF-1/CF-2 15 3 2
3 " 1.3 3.0 1.6 " 4 5 " 1.3 3.0 1.6 " 6
7 15 3 EF-1/EF-4 1.5 2.9 1.5 EF-7/EF-9 15 3 8
9 " 1.5 2.9 1.5 " 10 11 " 1.5 2.9 1.5 " 12
13 15 3 EF-2/EF-3 1.5 2.6 1.2 EF-11/EF-12 15 3 14
15 " 1.5 2.6 1.2 " 16 17 " 1.5 2.6 1.2 " 18
19 15 3 EF-5/EF-10 1.5 2.4 0.9 EF-19 15 3 20
21 " 1.5 2.4 0.9 " 22 23 " 1.5 2.4 0.9 " 24
25 15 3 EF-6/EF-8 1.5 5.9 4.4 ACCU-253-4 20 3 26
27 " 1.5 5.9 4.4 " 28 29 " 1.5 5.9 4.4 " 30
31 100 3 CLASS L RECEPTACLE 22.2 44.3 22.2 CLASS L RECEPTACLE 100 3 32
33 " 22.2 44.3 22.2 " 34 35 " 22.2 44.3 22.2 " 36
37 100 3 CLASS L RECEPTACLE 22.2 25.3 3.2 LIGHTS: COMPOSITE SHOP 20 1 38
39 " 22.2 23.6 1.5 LIGHTS: PREP RM/SANDING RM 20 1 40
41 " 22.2 24.5 2.3 LIGHTS: LOCKER ROOM AREA 20 1 42
43 15 3 EF-20/EF-21 1.9 3.5 1.6 * EXTERIOR WALL PACKS 20 1 44
45 " 1.9 3.5 1.6 * BID - PARKING LOT LIGHTING 20 1 46
47 " 1.9 2.9 1.0 SPARE 20 1 48
49 15 3 AC-4 1.3 9.7 8.3 AC-3 HUMIDIFIER 40 3 50
51 " 1.3 9.7 8.3 " 52 53 " 1.3 9.7 8.3 " 54
49 3 SPARE 5.0 13.3 8.3 AC-4 HUMIDIFER 40 3 56
51 " 5.0 13.3 8.3 " 58 53 " 5.0 13.3 8.3 " 60
49 3 SPARE 2.0 4.0 2.0 SPARE 3 62
51 " 2.0 4.0 2.0 64 53 " 2.0 4.0 2.0 66 49 0.0 68 51 0.0 70 53 0.0 72 49 0.0 74 51 0.0 76 53 0.0 78 49 0.0 80 51 0.0 82 53 0.0 84
117.0 115.3 115.5 TOTAL PANELBOARD KVA : 348
277/ 480 VOLTAGE
419 AVG. AMPS 300 MAIN CKT. BKR. MINIMUM INTERRUPTING CAPCITY
3 PHASE MAIN LUG MAIN BREAKER 18 KAIC
4 WIRE FULL GROUND BRANCH BREAKER 18 KAIC
PANEL SHALL BE TWO SECTION WITH SUB-FEED LUGS TO POWER SECOND SECTION
* ROUTE CIRCUIT THRU EXTERIOR LIGHTING RELAY PANEL
38546 PEASE BLDG 253 PANELBOARD RDP-1
FEED FROM SERVICE MOUNTING SURFACE
CKT. CKT. BKR. LOAD CKT. BKR. CKT.
NO. TRIP/POLE KVA A B C KVA TRIP/POLE NO.
1 200 3 PNL HP-2 62.2 179.2 117.0 PNL HP-3 300 3 2
3 " 62.2 177.4 115.3 " 4 5 " 55.2 170.7 115.5 " 6
7 150 3 PNL HP-4 26.0 35.3 9.3 PNL RDP-2 (EXISTING LOADS) 200 3 8
9 " 26.0 35.3 9.3 " 10 11 " 26.0 35.3 9.3 " 12
13 100 3 AC-1 (50 HP) 18.0 32.1 14.1 HVU-1 90 3 14
15 " 18.0 32.1 14.1 " 16 17 " 18.0 32.1 14.1 " 18
19 90 3 HVU-2 14.1 28.2 14.1 HVU-3 90 3 20
21 " 14.1 28.2 14.1 " 22 23 " 14.1 28.2 14.1 " 24
25 70 3 BLAST BOOTH VENT (25 HP) 9.4 18.8 9.4 AC-2 (25 HP) 70 3 26
27 " 9.4 18.8 9.4 " 28 29 " 9.4 18.8 9.4 " 30 31 60 3 PAINT BOOTH MUA UNIT (20 HP) 7.5 15.0 7.5 PAINT BOOTH EX FAN (20HP) 60 3 32 33 " 7.5 15.0 7.5 " 34 35 " 7.5 15.0 7.5 " 36
37 225 3 PAINT BOOTH COMP (125 HP) 43.2 43.2 38
39 " 43.2 43.2 40 41 " 43.2 43.2 42 43 0.0 44 45 0.0 46 47 0.0 48 49 0.0 50 51 0.0 52 53 0.0 54
351.7 350.0 343.3 TOTAL PANELBOARD KVA : 1045
277/ 480 VOLTAGE
1,258 AVG. AMPS 800 MAIN CKT. BKR. MINIMUM INTERRUPTING CAPCITY
3 PHASE MAIN LUG MAIN BREAKER 18 KAIC
4 WIRE FULL GROUND BRANCH BREAKER 18 KAIC
38546 PEASE BLDG 253 PANELBOARD HP-2
FEED FROM RDP-1 MOUNTING SURFACE
CKT. CKT. BKR. LOAD CKT. BKR. CKT.
NO. TRIP/POLE KVA A B C KVA TRIP/POLE NO.
1 45 3 ACCU-253-1 10.3 17.7 7.5 ACCU-253-2 35 3 2
3 " 10.3 17.7 7.5 " 4 5 " 10.3 17.7 7.5 " 6
7 40 3 HWP-1 5.8 7.6 1.8 B-1 15 3 8
9 " 5.8 7.6 1.8 " 10 11 " 5.8 7.6 1.8 " 12
13 40 3 HWP-2 5.8 7.6 1.8 B-2 15 3 14
15 " 5.8 7.6 1.8 " 16 17 " 5.8 7.6 1.8 " 18
19 40 3 HWP-3 5.8 7.6 1.8 B-3 15 3 20
21 " 5.8 7.6 1.8 " 22 23 " 5.8 7.6 1.8 " 24
25 15 3 DOAU-1 (SUPPLY FAN 5 HP) 2.1 3.4 1.3 DOAU-1 (RETURN FAN 3HP) 15 3 26
27 " 2.1 3.4 1.3 " 28 29 " 2.1 3.4 1.3 " 30 31 15 3 BLAST BOOTH CLAIM SYS (3 HP) 1.3 2.3 0.9 BLAST BOOTH DRY HONER (2 HP) 15 3 32 33 " 1.3 2.3 0.9 " 34 35 " 1.3 2.3 0.9 " 36
37 40 1 IWH-3 (CKT 1) 8.0 11.9 3.9 PWP-1 (105 HP) 25 3 38
39 40 1 IWH-3 (CKT 2) 8.0 11.9 3.9 " 40
41 1 SPARE 1.0 4.9 3.9 " 42
43 3 SPARE 2.0 4.0 2.0 SPARE 3 44
45 " 2.0 4.0 2.0 " 46 47 " 2.0 4.0 2.0 " 48 49 0.0 50 51 0.0 52 53 0.0 54
62.2 62.2 55.2 TOTAL PANELBOARD KVA : 180
277/ 480 VOLTAGE
216 AVG. AMPS 200 MAIN CKT. BKR. MINIMUM INTERRUPTING CAPCITY
3 PHASE MAIN LUG MAIN BREAKER 18 KAIC
4 WIRE FULL GROUND BRANCH BREAKER 18 KAIC
38546 PEASE BLDG 253 PANELBOARD HP-4
FEED FROM RDP-1 MOUNTING SURFACE
CKT. CKT. BKR. LOAD CKT. BKR. CKT.
NO. TRIP/POLE KVA A B C KVA TRIP/POLE NO.
1 50 3 PREP RM 121 FUTURE EQUIP 1.8 3.6 1.8 PREP RM 121 FUTURE EQUIP 50 3 2
3 " 1.8 3.6 1.8 " 4 5 " 1.8 3.6 1.8 " 6
7 50 3 SANDING 122 FUTURE EQUIP 1.8 3.6 1.8 SANDING 122 FUTURE EQUIP 50 3 8
9 " 1.8 3.6 1.8 " 10 11 " 1.8 3.6 1.8 " 12
13 60 3 DESPATCH OVEN 129 8.3 11.5 3.2 ACCU-253-6 (CKT 1) 25 3 14
15 " 8.3 11.5 3.2 " 16 17 " 8.3 11.5 3.2 " 18
19 15 3 CABLE HOISTS 1.6 4.8 3.2 ACCU-253-6 (CKT 2) 25 3 20
21 " 1.6 4.8 3.2 " 22 23 " 1.6 4.8 3.2 " 24
25 SPACE 0.5 1.0 0.5 SPACE 26
27 " 0.5 1.0 0.5 " 28 29 " 0.5 1.0 0.5 " 30 31 " 0.5 1.0 0.5 " 32 33 " 0.5 1.0 0.5 " 34 35 " 0.5 1.0 0.5 " 36 37 " 0.5 1.0 0.5 " 38 39 " 0.5 1.0 0.5 " 40 41 " 0.5 1.0 0.5 " 42
26.6 26.6 26.6 TOTAL PANELBOARD KVA : 80
277/ 480 VOLTAGE
96 AVG. AMPS MAIN CKT. BKR. MINIMUM INTERRUPTING CAPCITY
3 PHASE 150 MAIN LUG MAIN BREAKER 18 KAIC
4 WIRE FULL GROUND BRANCH BREAKER 18 KAIC
Project
Client
Drawing
NEW HAMPSHIRE AIR NATIONAL GUARD
REVISIONS
Description
Drawn by
Designed by
Scale
Date
Project No.
Approved by
Checked by Date
SheetAS SHOWN
Stamp
PEASE AIR BASE
NEW HAMPSHIRE
NATIONAL GUARD
09 JANUARY 2015
KC-46A ADAL FUEL CELL HANGAR, BUILDING 253
PEASE AIR NATIONAL GUARD BASE, NEW HAMPSHIRE
SZCQ139901
MGD
MGD
WAP
LDC
B-3 Submittal
B-2 Submittal
01/09/15
08/15/14 E-602
PANEL SCHEDULES
1 REVISION 1 02/17/15